Ed Ferrier Applications Engineer LG Electronics USA, Inc. Commercial Air Conditioning Alpharetta, Georgia

Similar documents
Tuesday September 26 th Main Program: Overview and Discussion of VRF Technology

Appendix B 2019 Commercial Unitary Air Conditioning and Heat Pumps Specification

Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)

VRF system optimization. Ryan R. Hoger, LEED AP Thank you to our Sponsors

Compact with impact. DVM S Eco

Space Conditioning Systems, Ducts, and Fans (Page 1 of 6)

Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)

Space Conditioning Systems, Ducts, and Fans (Page 1 of 6))

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

Retail Effects of ANSI/ASHRAE/IES Standard

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

Building Energy Efficiency Analysis for a High School

Energy Efficiency Programs

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment

Product Catalog. Variable Refrigerant Flow (VRF) System VRF-PRC008C-EN. Air Source Heat Pump and Heat Recovery Outdoor Units.

Trane Water-Source Variable Refrigerant Flow

Building Energy Efficiency Analysis for a High School

Residential HVAC Rebate Program Manual

2018 Smart Energy New Homes Program Manual

Sound HVAC Choices for Sustainable Design. Julian de Bullet

Dayton Chapter February 9, Bob Thomson, P.E., LEED-AP, CDT

Mechanical Technical Assignment One ASHRAE Standard Compliance Evaluation

Oklahoma University Children s Medical Office Building

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

Energy Code Analysis - Current Requirements & What is Coming International Energy Conservation Code & ASHRAE Standard 90.1

Technical Report Two: Building and Plant Energy Analysis Report

SINGLE PACKAGED VERTICAL AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM

County of Yolo Development Services Building Inspection Division

EnergyPro Building Energy Analysis. Single-story School Building

VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM

1 Project Information. 2 Building Type. 3 Trade Ally/Contractor Information. HVAC Rebate Worksheet. Retrofit New Construction

SUSTAINABLE TECHNOLOGIES FOR STATIONARY AIR CONDITIONING WORKSHOP PROCESS APPLICATIONS AND SYSTEMS APPROACH TO SELECTING REFRIGERANTS

LOGO. Trivium Level II Energy Audit

DAIKIN MXS SERIES MULTI-ZONE HEATING & COOLING SYSTEMS NEW! NOW CONNECT UP TO5 INDOOR UNITS!

Commercial HVAC. Emerging Technologies

EnergyPro Building Energy Analysis. Nine-story Office Building

DRAFT METHODOLOGY FOR CALCULATING COOLING AND HEATING ENERGY-INPUT-RATIO (EIR) FROM THE RATED SEASONAL PERFORMANCE EFFICIENCY (SEER OR HSPF)

Consumer Energy Tax Credit

Next Connecticut Energy Code

BETA OPTION 1: PERFORMANCE RATING METHOD. Section General Information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects

Refrigerant Charge Verification

BOARD OF PUBLIC WORKS 1600 O Street Auburn, NE Rebate Program

CONSTRUCTION REQUIREMENTS

Business Energy Rebates Application

ENVIRONMENTAL ASSESSMENT WORKSHEET

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality

Product Catalog. VRF Water Source Unit 6to48Tons VRF-PRC017A-EN. November 2014

Heat Pumps Community Workshop Manchester Library, Manchester

Development of Design Guidance for K-12 Schools: From 30% to 50% Energy Savings

DISPLACEMENT VENTILATION

Thermal & Fluids PE References Exam Errata

Trane Engineering News Multi-pipe unit for heating and cooling buildings

ANNUAL STAKEHOLDER MEETING

MEP's Letter of Assurance

Holistic Design Approach For Energy Efficiency ASHRAE TECHNOLOGY AWARD CASE STUDIES

2015 Vermont Commercial Building Energy Standards ISBN:

Daikin AURORA MULTI-ZONE HEATING & COOLING SYSTEMS

DAIKIN AURORA MULTI-ZONE HEATING & COOLING SYSTEMS

Title 24: Where We're Headed with the 2013 Standards. Featuring: Martyn C. Dodd EnergySoft, LLC

Reed Berinato Mechanical Option. Building and Plant Energy Analysis Report October 27, Contents

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

DAIKIN MXS SERIES MULTI-ZONE HEATING & COOLING SYSTEMS

Advanced Testing for Innovative Design

Holistic Design Approach For Energy Efficiency ASHRAE TECHNOLOGY AWARD CASE STUDIES

Evaluating Variable Air Volume (VAV) Packaged Rooftop Systems for Use in High Performance Environments

2013 Title 24, Part 6 Residential HVAC April 11, Gina Rodda Gabel Associates, LLC

DUCT SYSTEM DESIGN CONSIDERATIONS Part 2

DAIKIN AURORA MULTI-ZONE HEATING & COOLING SYSTEMS

DAIKIN AURORA MULTI-ZONE HEATING & COOLING SYSTEMS

HVAC System Design for Hazelwood Office Building

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation

LEED Energy Performance Summary Report

R e c e n t P R O J E C T S

Heating and Cooling Incentive Application for Business Customers

COPs, EERs, and SEERs

Product Catalog. Variable Refrigerant Flow (VRF) Air Source Heat Pump and Heat Recovery Outdoor Units 4TVH*/4TVR* VRF-PRC008B-EN.

DMC SERIES MULTI-ZONE INVERTER AURORA HEAT PUMP SYSTEMS. 1.5 & 2 TON, 2 & 3 ZONE SYSTEMS Up to 17.9 SEER / Up to 12.5 HSPF / Up to 12.

Gerald R. Ford Museum

Heating and Cooling Incentive Application for Business Customers

Deep Energy Retrofit Modeling and Cost Effectiveness Study: A Technical Policy Brief. January 2013

MEP's Letter of Assurance

Heating and Cooling Incentive Application for Business Customers

ORDINANCE NO. XXXX BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF LAWRENCE, KANSAS:

CONSTRUCTION DOCUMENTS NECESSARY FOR PLAN REVIEW

Heating and Cooling Incentive Application for Business Customers

ENERGY EFFICIENCY CERTIFICATION

Heating and Cooling Incentive Application for Business Customers

WaterFurnace Explains GEOTHERMAL HEATING & COOLING

Heating and Cooling Incentive Application for Business Customers


CREDIT COMPLIANCE (Please complete the color coded criteria(s) based on the option path selected)

TECHNICAL REPORT 2 STENGEL HALL ACADEMIC CENTER FOR EXCELLENCE. Linden Hall School for Girls Lititz, Pennsylvania

Variable Refrigerant Flow Systems: Technology Introduction

What s My Baseline? ASHRAE

HELPING HVAC PROFESSIONALS TAKE THE LEED ACHIEVING LEED CERTIFICATION

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics

Technical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis

Geothermal System Design Overview Course 1

Transcription:

Ed Ferrier Applications Engineer LG Electronics USA, Inc. Commercial Air Conditioning Alpharetta, Georgia Email: ed.ferrier@lge.com 1 VRF-PI-HA-003-US 012L07 AHRI Standard 1230 2 VRF-PI-HA-003-US 012L07 1

AHRI Standard 1230 AHRI = Air Conditioning Heating and Refrigeration Institute AHRI Standard 1230 was launched in 2011 Established certification standard for Variable Refrigerant Flow (VRF) equipment Before 2011, no certification standard was available for VRF equipment (DOE waiver required) Since VRF is relatively new to US market, AHRI had to create a new standard to rate this equipment 3 VRF-PI-HA-003-US 012L07 AHRI Standard 1230 Covers air source and water source VRF equipment 65,000 Btu/h thru 300,000 Btu/h VRF equipment larger than 300,000 Btu/h currently not covered by any AHRI VRF equipment smaller than 65,000 Btu/h currently covered by AHRI Standard 210/240 www.ahridirectory.org 4 VRF-PI-HA-003-US 012L07 2

AHRI Standard 1230 Performance data reported includes EER (Energy Efficiency Rating) at 95 F COP (Coefficient of Performance) at 47 F COP (Coefficient of Performance at 17 F IEER (Integrated Energy Efficiency Ratio 5 VRF-PI-HA-003-US 012L07 AHRI Standard 1230 What is IEER? Measures VRF equipment s ability to react to changing building loads IEER = (0.020*A) + (0.617*B) + (0.238*C) + (0.125*D) Where A = EER @ 100% net capacity B = EER @ 75% net capacity C = EER @ 50% net capacity D = EER at 25% net capacity 6 VRF-PI-HA-003-US 012L07 3

7 VRF-PI-HA-003-US 012L07 When designing a refrigerant pipe system for VRF, refrigerant safety must be considered The occupied spaces where the refrigerant piping and indoor units are installed may experience a discharge of refrigerant if a leak occurs in the system. Local codes and ASHRAE Standard 15 (in conjunction with ASHRAE Standard 34) provide guidelines to assist in designing safe VRF refrigerant systems 8 VRF-PI-HA-003-US 012L07 4

Determine smallest occupied space volume Spaces connected by permanent openings may be considered in volume calculations Permanent openings may include Ducts Transfer grills 9 VRF-PI-HA-003-US 012L07 ASHRAE 15/34 Establishes maximum allowable volume of R410A refrigerant concentration level (RCL) in an occupied space 26 lbs per 1000 cubic feet for commercial and residential occupancies 13 lbs per 1000 cubic feet for institutional occupancies 10 VRF-PI-HA-003-US 012L07 5

Below is an example of design process for a VRF system for a 2 story office building Need to layout VRF system in order to calculate total system refrigerant 11 VRF-PI-HA-003-US 012L07 VRF layout for first floor system 18 ton water source VRF system, total system charge 63.32 lbs Rise Up 12 VRF-PI-HA-003-US 012L07 6

ASHRAE 15 refrigerant concentration levels for offices 26 lbs/1000 ft 3 allowed for occupied areas First floor system has total of 63.32 lbs of refrigerant Smallest volume of office allowed = (63.32 * 1000 ft 3 ) /26 = 2435 ft 3 With 9 ceiling height, smallest office area allowed is 2435/9 = 270 ft 2 After reviewing office areas on first floor, Conference Room 113 area of 247 ft 2 < 270 ft 2 Rm Number Room Name Area(sq. ft) Comment 102 Showroom 820 103 Office 1102 104 Women Restroom 146 Combined w/107 105 Men Restroom 165 Combined w/107 106 Breakroom 270 107 Corridor 728 108 Practice 1400 109 Storage 160 Unoccupied 110 Elec 100 Unoccupied 113 Conference 247 115A Lecture 432 115B Lecture 432 13 VRF-PI-HA-003-US 012L07 To comply with ASHRAE 15, a transfer opening could be added to Conference 113 (check with local codes) Rise Up Wall transfer grille 14 VRF-PI-HA-003-US 012L07 7

To comply with ASHRAE 15, Conference 113 could be removed from VRF system and served by single split system. Rise Up Split system condenser 15 VRF-PI-HA-003-US 012L07 Another solution, split 18 ton system into (2) smaller 6 ton and 12 ton systems, lowering system charge Rise Up 16 VRF-PI-HA-003-US 012L07 8

VRF layout for second floor system 36 ton water source VRF system, total system charge 114.71 lbs Drop Down 17 VRF-PI-HA-003-US 012L07 ASHRAE 15 refrigerant concentration levels for offices Second floor system has total of 114.71 lbs of refrigerant Smallest volume of office allowed = (114.71 * 1000 ft 3 ) /26 = 4442 ft 3 With 10 ceiling height, smallest office area allowed is 4442/10 = 444 ft 2 After reviewing office areas on second floor, the following are too small 202, 203, 205, 206, 207, 208, 209, 210, 211, 212, 213, 214, 215, 216, 218, 220 Rm Number Room Name Area(sq. ft) Comment 201 Lobby 672 202 Break Room 352 203 Office 180 204 Office 720 205 Conference 208 206 Office 198 207 Conference 143 208 Office 121 209 Office 121 210 Office 121 211 Office 192 212 Office 120 Rm Number Room Name Area(sq. ft) Comment 213 Office 120 214 Office 120 215 Office 120 216 Office 378 218 Office 400 219 Office 930 220 Conference 396 221 Restroom 142 Combined w/ 219 222 Restroom 164 Combined w/ 219 224 Storage 90 Unoccupied 225 Storage 90 Unoccupied 226 Storage 117 Unoccupied 18 VRF-PI-HA-003-US 012L07 9

To comply with ASHRAE 15, transfer openings could be added to 202, 203, 205, 206, 207, 208, 209, 210, 211, 212, 213, 214, 215, 216, 218, 220 Drop Down Wall transfer grilles (typ) 19 VRF-PI-HA-003-US 012L07 Another solution, divide the 36 ton water source VRF system into (2) systems 24 and 12 ton with smaller refrigerant charges Drop Down 20 VRF-PI-HA-003-US 012L07 10

ASHRAE 15 refrigerant concentration levels for offices Second floor 24 ton system has total of 81.03 lbs of refrigerant Smallest volume of office allowed = (81.03 * 1000 ft 3 ) /26 = 3116 ft 3 With 10 ceiling height, smallest office area allowed is 3116/10 = 312 ft 2 After reviewing office areas on second floor 24 ton system, the following are too small 203, 212, 213, 214, 215 Rm Number Room Name Area(sq. ft) Comment 201 Lobby 672 202 Break Room 352 203 Office 180 204 Office 720 212 Office 120 213 Office 120 214 Office 120 215 Office 120 Rm Number Room Name Area(sq. ft) Comment 216 Office 378 218 Office 400 219 Office 930 221 Restroom 142 Combined w/ 219 222 Restroom 164 Combined w/ 219 224 Storage 90 Unoccupied 225 Storage 90 Unoccupied 226 Storage 117 Unoccupied 21 VRF-PI-HA-003-US 012L07 ASHRAE 15 refrigerant concentration levels for offices Second floor 12 ton system has total of 43.8 lbs of refrigerant Smallest volume of office allowed = (43.8 * 1000 ft 3 ) /26 = 1684 ft 3 With 10 ceiling height, smallest office area allowed is 1684/10 = 168 ft 2 After reviewing office areas on second floor 12 ton system, the following are too small 207, 208, 209, 210 Rm Number Room Name Area(sq. ft) Comment 205 Conference 208 206 Office 198 207 Conference 143 208 Office 121 209 Office 121 210 Office 121 211 Office 192 220 Conference 396 22 VRF-PI-HA-003-US 012L07 11

To comply with ASHRAE 15, transfer openings could be added to 203, 207, 208, 209, 210, 212, 213, 214, 215 (check with local codes) Drop Down Wall transfer grilles (typ) 23 VRF-PI-HA-003-US 012L07 Another solution to comply with ASHRAE 15 Combine rooms 207,208, 209, 210 into single ducted unit Combine rooms 212, 213, 214, 215 into single ducted unit Separate room 203 to separate split system Drop Down Split system condenser 24 VRF-PI-HA-003-US 012L07 12

ASHRAE Standard 15 requires that system with over 110 lbs of refrigerant charge have the fusible plugs vented to outdoors Check refrigerant charge of each system 12 T 12 T 12 T 12 T 6 T Pump Dry cooler boiler 25 VRF-PI-HA-003-US 012L07 Check refrigerant charge of each system First Floor 18 ton water source VRF 35.49 lbs (equipment charge) 27.83 lbs (pipe system charge) Total of 63.32 lbs < 110 lbs (venting not required) 26 VRF-PI-HA-003-US 012L07 13

Check refrigerant charge of each system Second Floor water source system 24 ton system total charge 81.03 lbs 12 ton system total charge 43.8 lbs < 110 lbs (venting not required) 27 VRF-PI-HA-003-US 012L07 Questions? 28 VRF-PI-HA-003-US 012L07 14