XHBN.FF-D Joint Systems. Design/System/Construction/Assembly Usage Disclaimer. Joint Systems. System No. FF-D-1066

Similar documents
XHBN.FF-D Joint Systems. Joint Systems. System No. FF-D-3008

Joint Systems. System No. FF-D-0044

XHBN.HW-D Joint Systems. Design/System/Construction/Assembly Usage Disclaimer. Joint Systems. System No. HW-D-0631

BXUV.V481. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263

BXUV.U435. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263

JB ENGINEERING AND CODE CONSULTING, P.C Cardinal Drive Munster, IN Phone: Fax:

UL Online Certifications Directory

Design No. U415 BXUV.U415 Fire-resistance Ratings - ANSI/UL 263. Design No. U415

UL Design System HW-D-1012 continued

EVALUATION REPORT OF CENTRAL STATES MANUFACTURING, INC. 'CENTRAL-LOC PANEL' FLORIDA BUILDING CODE 5TH EDITION (2014) FLORIDA PRODUCT APPROVAL

BXUV.U415 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

Design No. M507. Design No. M507

Page 2 of 5 1. Flooring Systems The flooring system shall consist of one of the following: System No. 1 Subflooring Nom 23/32 in. thick wood structura

Design No. L565. Design No. L565

FIRESTOP TECHNICAL PACK TEL: (888) 721-SEAL (7325) FAX: (888) 921-SEAL (7325)

SUBMITTAL INDEX. Product Datasheets: Product Approvals:

Design No. D929 February 07, Restrained Assembly Rating 1, 1-1/2, 2, or 3 Hr. (See Items 1, 5, 9, 10, 14)

System No. HW-D-0548

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

Duct Wrap Flexible Wraps

BXUV.U411. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263

The System U.S. Patent No. 5,913,788

CAJ. Combos. C-AJ of 5. Through Penetrations Series. Concrete. 3Fire Protection Products

System No. C-AJ-8133

Design No. D923 December 10, Restrained Assembly Ratings 3/4, 1, 1-1/2, 2 or 3 Hr. (See Items 2, 7, 8, 9 and 12)

SLOTTED STUD WIND-LOAD & NON-LOAD BEARING DEFLECTION WALL SYSTEM. U.L. FIRE RATED Head-of-Wall Joint Systems

System No. HW-D-0119

Subject: NRCA MRCA Joint Technical Bulletin. Date: January 2008 NOT COMPROMISE.

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

Firestopping Submittal Package

Through-Fastener Panel UL Listing documentation

PARKING PLAZA MEXICO COVERED GAS PUMP ISLAND PARKING BUS PARKING AREA. The Evans Group COVERD AREA TACO STAND COVERD AREA AREA FREEZER EXIT EXIT

System No. C-AJ-8048

BXUV.L576 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

Design No. P922 September 26, Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 6, 7) Unrestrained Assembly Rating 0 Hr (See Item 6)

BXUV.L548 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

FIRESTOP SUBMITTAL PACKAGE

System No. C-AJ-8096

CONNECTOR B L O C K S H E A R. Design for Composite Structural Action BLOCK SHEAR CONNECTOR APPLICATION. Airspace

CEYDC.R25563 Nonmetallic Plumbing System Components Listed for Fire Resistance

Hebel Fire Walls Masonry solutions to increase speed of construction and performance.

BXUV.L521 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

Fire Protection Products. Firestop Submittal Package FIP 1-Step Firestop Foam. Electrical Trade

SUBMITTAL INDEX. Product Datasheets: Product Approvals:

VITALink 2-Hour Fire Resistive Circuit Integrity Cable with Hose Stream

Design No. P921 April 16, Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 4, 6, 7 and 9) Unrestrained Assembly Rating 0 Hr (See Item 7)

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19

BXUV.U465. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263

SECTION NON--STRUCTURAL METAL FRAMING

I-STUD Shaftwall System

LLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

RATING: Consult factory for availability Consult factory for availability

I-STUD Shaftwall System

Design No. D927 December 10, Restrained Assembly Ratings 3/4, 1, 1-1/2, 2 & 3 Hr. (See Items 1, 6, 7, 8 & 11) Unrestrained Assembly Ratings 0 Hr

ENGINEERING EVALUATION

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

Design No. P214 December 09, Restrained Assembly Rating 1 Hr. Unrestrained Assembly Rating 1 Hr. Unrestrained Beam Rating 1 Hr.

Expansion Joint Covers

NATIONAL GYPSUM COMPANY 3-Hour Area Separation Wall System

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

A. Types of lightgauge metal framing units include the following: 1. C-shaped structural steel studs Uniform Building Code.

Cavity ShAftwall System

St. Monica Food Pantry

2.5" Min. Stud or Runner. 1.5" Mineral Fiber Blanket in Cavity, If Required. Wallboard. Retaining Angle. 1" Min. Damper Sleeve on 10" centers.

Design No. D925 December 10, Restrained Assembly Ratings 3/4, 1, 1-1/2, 2 or 3 Hr. (See Items 1, 6 and 10)

SECTION CEMENTITIOUS WOOD FIBER DECKS

A. Access doors and frames are part of an access door and frame allowance.

Expansion Joint Covers (079513)

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

Installation. Resilmount A237R. Installation Instructions. Furring channel sound isolation clip

NATIONAL GYPSUM COMPANY 2-Hour Area Separation Wall System

Concrete Inserts. B Adjustable Metal Deck Ceiling Bolt

Design No. P907 October 31, Restrained Assembly Rating 1, 1-1/2 or 2 Hr. (See Items 5 and 6) Unrestrained Assembly Rating 0 Hr.

System No. W-J-4050 ANSI/UL1479 (ASTM E814) CAN/ULC S115 4F2 4E. Reproduced by HILTI, Inc. Courtesy of. Underwriters Laboratories, Inc.

ADVANCE METAL INDUSTRIES L.L.C.

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

Fig Beam Clamp Retaining Strap (B-Line B3367)

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017

Introducing NEW. Taking on joint pain, one joint cover at a time.

installation instructions Combination Fire & Smoke Damper

SECTION COMPOSITE METAL DECKING

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

SECTION TRESPA ATHLON SOLID COMPOSITE PHENOLIC TOILET PARTITIONS. A. Solid composite phenolic toilet compartments and urinal screens.

Special Applications. Dorn Equipment, Corporation 27 Upham Street Melrose, MA Phone: Fax:

Construction Details 5-37

SPECIFICATIONS Aluminum Stair Nosing - Bull Nosing

Design No. P725 December 10, Restrained Assembly Rating-1, 1-1/2 or 2 H (See Item 8) Unrestrained Assembly Rating-1, 1-1/2 or 2 H (See Item 8)

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Student Services & Classroom Addition SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

MASONRY ANCHORS AND CONNECTORS May 6, 2014

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

SECTION VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT

Union County Vocational - Technical Schools Scotch Plains, New Jersey

CONNECTOR S T U D S H E A R. Design for Composite Structural Action STUD SHEAR CONNECTOR APPLICATION

Transcription:

XHBN.FF-D-1066 - http://database.ul.com/cgi-bin/xyv/template/lisext/1frame/showpage.html?name=xhbn.ff-d-10... Page 1 of 2 9/18/2009 Page Bottom XHBN.FF-D-1066 Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Listed or Classified products, equipment, system, devices, and materials. Authorities Having Jurisdiction should be consulted before construction. Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field. When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction. Only products which bear UL's Mark are considered as Classified, Listed, or Recognized. See General Information for System No. FF-D-1066 March 20, 2006 Assembly Rating 2 Hr Nominal Joint Widths 3, 4, 5 and 6 In. (See Item 2A) Class II and III Movement Capabilities 50% Compression, Extension or Horizontal Shear 1. Floor Assembly Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m 3 ) structural concrete. 2. Joint System Max width of joint (at time of installation of joint system) is 3, 4, 5 or 6 in. (76, 102, 127 or 152 mm). The joint system is designed to accommodate a max 50 percent compression, extension or horizontal shear from its installed width. The joint system consists of the following: A. Mechanical Joint Assembly Fire barrier material encased in corrugated metal and provided with

XHBN.FF-D-1066 - http://database.ul.com/cgi-bin/xyv/template/lisext/1frame/showpage.html?name=xhbn.ff-d-10... Page 2 of 2 9/18/2009 metal flanges. Assembly to be installed in floor in accordance with the installation instructions provide with the product. The following assemblies are to be used with the different joint sizes: Nom Joint Width In. (mm) 3 (76) MFX-3F 4 (102) MFX-4F 5 (127) MFX-5F 6 (152) MFX-6F Mechanical Joint Designation CONSTRUCTION SPECIALTIES INC B. Retaining Angles Stair-stepped 20 gauge (or heavier) galvanized steel angles installed over metal flanges of joint assembly in accordance with the installation instructions provide with the product. Angles to extend entire length of joint and are to be attached to floor with min 3/16 in. (5 mm) diam by 1-1/2 in. (38 mm) long masonry anchors spaced a max of 18 in. (457 mm) on center. C. Joint Cover Min 0.034 in. (0.9 mm) thick metallic cover plates secured to top side of floor, continuous over full length of joint. Cover plate attached to floor on one side of opening only with min 1-1/2 in. (38 mm) long masonry anchors spaced a max of 18 in. (457 mm) on center. As an alternate, where the linear joint opening is enclosed within a chase wall and is non load bearing, a cover consisting of a creased sheet of min 2 mil (0.05 mm) thick stainless steel foil secured with 1 in. (25 mm) wide continuous galv steel washer strips along each side of the joint opening may be used. *Bearing the UL Classification Mark Last Updated on 2006-03-20 Questions? Notice of Disclaimer Page Top Copyright 2009 Underwriters Laboratories Inc. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright 2009 Underwriters Laboratories Inc. "

XHBN.FW-D-1062 - file://t:\ul Listings\MFX\XHBN_FW-D-1062 -.htm Page 1 of 3 6/5/2008 Page Bottom XHBN.FW-D-1062 Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Listed or Classified products, equipment, system, devices, and materials. Authorities Having Jurisdiction should be consulted before construction. Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field. When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction. Only products which bear UL's Mark are considered as Classified, Listed, or Recognized. See General Information for System No. FW-D-1062 March 20, 2006 Assembly Rating 2 Hr Nominal Joint Widths 3, 4, 5 and 6 In. (See Item 3A) Class II and III Movement Capabilities 50% Compression, Extension or Horizontal Shear

XHBN.FW-D-1062 - Page 2 of 3 1. Floor Assembly Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m 3 ) structural concrete. 2. Wall Assembly* Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m 3 ) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 3. Joint System Max width of joint (at time of installation of joint system) is 3, 4, 5 or 6 in. (76, 102, 127 or 152 mm). The joint system is designed to accommodate a max 50 percent compression, extension or horizontal shear from its installed width. The joint system consists of the following: A. Mechanical Joint Assembly Fire barrier material encased in corrugated metal and provided with metal flanges. Assembly to be installed in floor in accordance with the installation instructions provide with the product. The following assemblies are to be used with the different joint sizes: Nom Joint Width In. (mm) Mechanical Joint Designation 3 (76) MFX-3FW 4 (102) MFX-4FW 5 (127) MFX-5FW 6 (152) MFX-6FW CONSTRUCTION SPECIALTIES INC B. Retaining Angles Min 24 gauge (or heavier) galvanized steel angles installed over metal flanges of joint assembly in accordance with the installation instructions provided with the product. Angles to extend entire length of joint and are to be attached to floor with min 3/16 in. (5 mm) diam by 1-1/2 in. (38 mm) long masonry anchors spaced a max of 18 in. (457 mm) on center. C. Retaining Clips Min 24 gauge galvanized steel clips installed over metal flanges of joint assembly in accordance with installation instructions provided with the product. Clips to extend entire length of joint and are to be attached to wall with min 3/16 in. (5 mm) diam by 1-1/2 in. (38 mm) long masonry anchors spaced a max of 18 in. (457 mm) on center. D. Joint Cover Min 0.034 in. (0.9 mm) thick metallic cover plates installed on top side of floor, continuous over full length of joint. Cover plate attached only to wall with min 1-1/2 in. (38 mm) long file://t:\ul Listings\MFX\XHBN_FW-D-1062 -.htm 6/5/2008

XHBN.FW-D-1062 - file://t:\ul Listings\MFX\XHBN_FW-D-1062 -.htm Page 3 of 3 6/5/2008 masonry anchors spaced a max of 18 in. (457 mm) on center. As an alternate, where the linear joint opening is enclosed within a chase wall and is non load bearing, a cover consisting of a creased sheet of min 2 mil (0.05 mm) thick stainless steel foil secured with 1 in. (25 mm) wide continuous galv steel washer strips along each side of the joint opening may be used. *Bearing the UL Classification Mark Last Updated on 2006-03-20 Questions? Notice of Disclaimer Page Top Copyright 2008 Underwriters Laboratories Inc. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright 2008 Underwriters Laboratories Inc. "

XHBN.WW-D-1057 - http://database.ul.com/cgi-bin/xyv/template/lisext/1frame/showpage.html?name=x... Page 1 of 2 5/15/2007 XHBN.WW-D-1057 Page Bottom See General Information for System No. WW-D-1057 March 20, 2006 Assembly Rating 2 Hr Nominal Joint Width 3, 4, 5 and 6 In. (See Item 2A) Class II and III Movement Capabilities 50% Compression, Extension Or Vertical Shear 1. Wall Assembly Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m 3 ) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Joint System Max width of joint (at time of installation of joint system) is 3, 4, 5 or 6 in. (76, 102, 127 or 152 mm). The joint system is designed to accommodate a max 50 percent compression, extension or vertical shear from its installed width. The joint system consists of the

XHBN.WW-D-1057 - http://database.ul.com/cgi-bin/xyv/template/lisext/1frame/showpage.html?name=x... Page 2 of 2 5/15/2007 following: A. Mechanical Joint Assembly Fire barrier material encased in corrugated metal and provided with metal flanges. Assembly to be installed on either side of wall in accordance with the installation instructions provide with the product. The following assemblies are to be used with the different joint sizes: Nom Joint Width In. (mm) 3 (76) MFX-3W 4 (102) MFX-4W 5 (127) MFX-5W 6 (152) MFX-6W Mechanical Joint Designation CONSTRUCTION SPECIALTIES INC B. Retaining Angles Min 2-1/2 by 2-1/2 in. (64 by 64 mm) No. 20 gauge (or heavier) galvanized steel angles installed over steel flanges of joint. Angles to extend entire length of joint and are to be attached to wall assembly with min 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long masonry anchors spaced a max of 18 in. (457 mm) on center. C. Joint Cover Min 0.034 in. (0.9 mm) thick metallic cover plates secured to each side of wall, continuous over full height of joint. Cover plates attached to wall on one side of opening only with min 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long masonry anchors spaced a max of 18 in. (457 mm) on center. As an alternate, in the area from the finished ceiling to the floor above, a cover consisting of a creased sheet of min 2 mil (0.05 mm) thick stainless steel foil secured with 1 in. (25 mm) wide continuous galv steel washer strips along each side of the joint opening may be used. *Bearing the UL Classification Mark Last Updated on 2006-03-20 Questions? Notice of Disclaimer Page Top Copyright 2007 Underwriters Laboratories Inc. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright 2007 Underwriters Laboratories Inc. "