DEVELOPMENT OF FLOOR DESIGN SPECTRA FOR OPERATIONAL AND FUNCTIONAL COMPONENTS OF CONCRETE BUILDINGS IN CANADA

Similar documents
EFFECTS OF STRONG-MOTION DURATION ON THE RESPONSE OF REINFORCED CONCRETE FRAME BUILDINGS ABSTRACT

SEISMIC VULNERABILITY OF REINFORCED CONCRETE BRIDGE COLUMNS IN CANADA

Seismic Evaluation of the Historic East-Memorial Building Retrofitted with Friction Dampers, Ottawa, Canada

Inelastic Versus Elastic Displacement-Based Intensity Measures for Seismic Analysis

SEISMIC PERFORMANCE OF ECCENTRICALLY BRACED FRAMES DESIGNED FOR CANADIAN CONDITIONS

Seismic Evaluation of Steel Moment Resisting Frame Buildings with Different Hysteresis and Stiffness Models

Evaluation of Seismic Behavior for Low-Rise RC Moment Resisting Frame with Masonry Infill Walls

COMPUTER AIDED DESIGN AND ANALYSIS OF RC FRAME BUILDINGS SUBJECTED TO EARTHQUAKES

0306 SEISMIC LOADS GENERAL

UTILIZING UNIFORM HAZARD SPECTRA FOR SEISMIC PERFORMANCE EVALUATION OF HIGHWAY BRIDGES IN CANADA

Inelastic Torsional Response of Steel Concentrically Braced Frames

Effect of Standard No Rules for Moment Resisting Frames on the Elastic and Inelastic Behavior of Dual Steel Systems

ANALYSIS PROCEDURES FOR PERFORMANCED BASED DESIGN

Floor Response Spectra Generation for Seismic Design of Buildings

Seismic Evaluation of a 1930 Steel Bridge with Lightly Reinforced Concrete Piers

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

Assessment of the Vulnerability of Buildings to Progressive Collapse due to Blast Loads

SIGNIFICANCE OF SHEAR WALL IN FLAT SLAB MULTI STORIED BUILDING - A REVIEW. Vavanoor, India

Evaluation of Response Reduction Factor and Ductility Factor of RC Braced Frame

EVALUATION OF THE NEED FOR WEAK BEAM-STRONG COLUMN DESIGN IN DUAL FRAME-WALL STRUCTURES

ON DRIFT LIMITS ASSOCIATED WITH DIFFERENT DAMAGE LEVELS. Ahmed GHOBARAH 1 ABSTRACT

Concept of Earthquake Resistant Design

Conventional steel constructions for the performance-based earthquake retrofit of low-rise school buildings

This point intends to acquaint the reader with some of the basic concepts of the earthquake engineer:

HYBRID MOMENT RESISTING STEEL FRAMES

A Performance Based Evaluation of a Wall- Frame Structure Employing the Pushover Analysis Tool

PERIODS OF REINFORCED CONCRETE FRAMES DURING NONLINEAR EARTHQUAKE RESPONSE

Seismic performance assessment of reinforced concrete buildings using pushover analysis

Pushover Analysis Of RCC Building With Soft Storey At Different Levels.

NONLINEAR PERFORMANCE OF A TEN-STORY REINFORCED CONCRETE SPECIAL MOMENT RESISTING FRAME (SMRF)

Seismic Damage Prediction of Reinforced Concrete Buildings Using Pushover Analysis

Nonlinear seismic response of structural systems having vertical irregularities due to discontinuities in columns

PREDICTION OF SEISMIC TORSIONAL EFFECTS IN TALL SYMMETRIC BUILDINGS

NON LINEAR STATIC ANALYSIS OF DUAL RC FRAME STRUCTURE

Base Shear Scaling. B. J. Davidson. Compusoft Engineering Ltd.

DESIGN OF HIGH-RISE CORE-WALL BUILDINGS: A CANADIAN PERSPECTIVE

AN EXAMINATION OF DAMAGES OF REINFORCED CONCRETE CONSOLED BUILDINGS IN TURKEY DUE TO 17 AUGUST 1999 KOCAELI EARTHQUAKE

Index terms Diagrid, Nonlinear Static Analysis, SAP 2000.

PERFORMANCE BASED ANALYSIS OF R.C.C. FRAMES

Performance Improvement of Tall Reinforced Concrete Structures with Multiple Tuned Mass Dampers (MTMD)

Lecture 5 Building Irregularities

Seismic Performance Evaluation of an Existing Precast Concrete Shear Wall Building

The Influence of Change in Basement Floors Stiffness on the Earthquake Force Distribution across the Height of Concrete Moment Frames

DYNAMIC SHEAR AMPLIFICATION IN HIGH-RISE CONCRETE WALLS: EFFECT OF MULTIPLE FLEXURAL HINGES AND SHEAR CRACKING

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

TO STUDY THE PERFORMANCE OF HIGH-RISE BUILDING UNDER LATERAL LOAD WITH BARE FRAME AND SHEAR WALL WITH OPENINGS

Nonlinear Dynamic Analysis of Base Isolated Reinforced Concrete Building

Seismic Evaluation of Infilled RC Structures with Nonlinear Static Analysis Procedures

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY

SEISMIC RESPONSE OF A MID RISE RCC BUILDING WITH SOFT STOREY AT GROUND FLOOR

STRENGTH REDUCTION FACTORS FOR MULTI-DEGREE-OF-FREEDOM SYSTEMS

MODAL PUSHOVER ANALYSIS OF RC FRAME BUILDING WITH STAIRCASE AND ELEVATOR CORE

3. Analysis Procedures

SEISMIC DAMAGE CONTROL WITH PASSIVE ENERGY DEVICES: A CASE STUDY

Seismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada

SEISMIC PERFORMANCE OF REINFORCED CONCRETE FRAME BUILDING WITH AND WITHOUT URM INFILL WALLS

3.5 Tier 1 Analysis Overview Seismic Shear Forces

Comparisons of Current Seismic Assessment Methods for Non-Seismic Designed Reinforced Concrete Bridges

SEISMIC PERFORMANCE OF FLAT SLAB WITH DROP AND CONVENTIONAL SLAB STRUCTURE

OPTIMUM DAMPING IN ISOLATION SYSTEM

Evaluation of Seismic Performance Factors for RC Buildings Retrofitted by EBF with Single and Dual Vertical Links

INFLUENCE OF BNWF SOIL MODELLING ON DYNAMIC BEHAVIOUR OF PILE FOUNDATION FOR RC FRAME WITH STRUCTURAL WALL

Assessing seismic displacements and ductility demand of tall reinforced concrete shear walls located in eastern Canada

STRUCTURAL APPLICATIONS OF A REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTION MODEL FOR EARTHQUAKE LOADING

A COMPARISON BETWEEN THE REQUIREMENTS OF PRESENT AND FORMER ROMANIAN SEISMIC DESIGN CODES, BASED ON THE REQUIRED STRUCTURAL OVERSTRENGTH

Analyzing Asymmetric Reinforced Concrete Frame Structures Responsiveness to Seismic Activity on Slopes Md Zainul Abedin Mudassar 1 Vinod Kumar Gama 2

SEISMIC VULNERABILITY OF EXISTING RC BUILDINGS IN INDIA

International Journal of Intellectual Advancements and Research in Engineering Computations

Engr. Thaung Htut Aung M. Eng. Asian Institute of Technology Deputy Project Director, AIT Consulting

EVALUATION OF ANALYSIS PROCEDURES FOR PERFORMANCE-BASED SEISMIC DESIGN OF BUILDINGS

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

Available at ISSN

SEISMIC CONSIDERATIONS FOR TELECOMMUNICATION TOWERS MOUNTED ON BUILDING ROOFTOPS

STUDYING THE EFFECT OF EARTHQUAKE EXCITATION ANGLE ON THE INTERNAL FORCES OF STEEL BUILDING S ELEMENTS BY USING NONLINEAR TIME HISTORY ANALYSES

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

BEHAVIOUR OF BUILDING FRAMES WITH STEEL PLATE SHEAR WALLS

Comparison of Seismic Behavior of Multi-Storey R/C Buildings With and Without Internal Beams

International Journal of Advance Engineering and Research Development

International Journal of Scientific & Engineering Research, Volume 7, Issue 10, October ISSN Pushover Analysis of RC Building

EARTHQUAKE LOADS ON MULTISTOREY BUILDINGS AS PER IS: AND IS: : A COMPARATIVE STUDY

A Comparative Study on Non-Linear Analysis of Frame with and without Structural Wall System

4.2 Tier 2 Analysis General Analysis Procedures for LSP & LDP

Evaluation of Seismic Response Modification Factors for RCC Frames by Non Linear Analysis

IS 1893 and IS Codal Changes

Seismic Analysis of Earthquake Resistant Multi Bay Multi Storeyed 3D - RC Frame

Application of Pushover Analysis for Evaluating Seismic Performance of RC Building

Seismic safety assessment of an unreinforced masonry building in Albania

SYMMETRIC 3D R/C BUILDINGS SUBJECTED TO BI-DIRECTIONAL INPUT GROUND MOTION

Response of TBI case study buildings

PERFORMANCE BASED PUSHOVER ANALYSIS OF WOOD FRAMED BUILDINGS

Seismic Performance of Residential Buildings with Staggered Walls

Performance Based Seismic Design of Reinforced Concrete Building

International Journal of Engineering and Techniques - Volume 4 Issue 2, Mar Apr 2018

A Comparison of Basic Pushover Methods

User Elements Developed for the Nonlinear Dynamic Analysis of Reinforced Concrete Structures

FEASIBILITY STUDY ON SEISMIC RESPONSE ESTIMATION OF DAMAGED R/C BUILDINGS BASED ON OBSERVATION DATA AND NUMERICAL ANALYSIS

A CASE STUDY OF PERFORMANCE-BASED SEISMIC EVALUATION AND RETROFIT OF AN EXISTING HOSPITAL BUILDING IN CALIFORNIA, U.S.

Performance Assessment for Reinforced Concrete Buildings with Soft First Stories. Takuya NAGAE, Keiichiro SUITA, Masayoshi NAKASHIMA

DESIGN ASPECTS AFFECTING THE SEISMIC BEHAVIOUR OF STEEL MRF BUILDINGS: ANALYSIS OF THREE CASE STUDIES

Transcription:

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China DEVELOPMENT OF FLOOR DESIGN SPECTRA FOR OPERATIONAL AND FUNCTIONAL COMPONENTS OF CONCRETE BUILDINGS IN CANADA M. Saatcioglu, M. Shooshtari 2, N. Naumoski 3 and S. Foo 4 Professor and University Research Chair, Department of Civil Engineering, the University of Ottawa, Ottawa, Ontario, Canada. Email:Murat.Saatcioglu@uOttawa.ca 2 Assistance Professor, Department of Civil Engineering, Bu-Ali Sina University, Hamedan, Iran. Email:mshooshtari@alumni.uottawa.ca 3 Adjunct Professor, Department of Civil Engineering, the University of Ottawa, Ottawa, Ontario, Canada. Email:nove.naumoski@pwgsc.gc.ca 4 Risk Management Specialist, Public Works & Government Services Canada, Gatineau, PQ, KA S5, Canada, Email: simon.foo@pwgsc.gc.ca ABSTRACT : Previous earthquakes have clearly demonstrated that the damage to operational and functional components of buildings usually cause more injuries, fatalities, and property and financial loss than those inflicted by structural damage. Operational and functional components of a building include architectural components, mechanical and electrical equipment, and building contents. An important step towards ensuring the safe design of operational and functional components of buildings is to develop floor design response spectra. This constitutes the scope of the current research program described in this paper. A total of 6 buildings, consisting of 5, and 5-story frame buildings were designed and analyzed to establish floor response spectra. The buildings were designed for Ottawa and Vancouver representing Eastern and Western Canadian seismicity. Fifteen artificially generated earthquake records (accelerograms) were used for each structure, compatible with the Uniform Hazard Response Spectra specified in the 25 edition of the National Building Code of Canada. It was observed that the response amplifications relative to ground excitations varied from floor to floor, and were frequency dependent. Generally, the higher floors showed higher amplification with differences in spectra between the floors being more pronounced in low-rise buildings, as compared to medium and high-rise buildings. The acceleration floor response spectra for individual floors are presented in the paper with details of the analyses that led to their developments. Recommendations are made for design floor response spectra for reinforced concrete frame buildings in Canada. KEYWORDS: Earthquakes, floor response spectra, frames, nonlinear analysis, non-structural components, operational and functional components, response spectra.. INTRODUCTION Past earthquakes have shown that the damage to operational and functional components of buildings usually cause more injuries, fatalities, property, and financial loss than those inflicted by structural damage. There have been many incidences that a building, which sustained only minor structural damage, was deemed unsafe and unusable as a result of extensive damage to its operational and functional components. Failure of such components also poses serious problems for search and rescue operations after the earthquake, resulting in additional and unnecessary increases in casualties. Equipment failures and the debris caused by falling objects could critically affect the performance of vital facilities such as emergency

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China command centers, fire and police stations, hospitals, power stations and water supply plants. During the 994 Northridge earthquake in California, several major hospitals had to be evacuated, not because of structural damage, but because of the failure of emergency power systems, air control units, falling ceilings and light fixtures. In Canada, the 988 Saguenay earthquake, the strongest event in eastern North America recorded within the last 5 years, caused very little structural damage. It has been well documented that a great majority of the injuries, property damage, and economic loss was caused by the failure of operational and functional components (OFC) in buildings. Operational and functional components of buildings include: Architectural components parapets, claddings, partitions, stairways, lighting systems, suspended ceilings, etc. Mechanical and electrical equipment pipes and ducts, escalators, central control panels, transformers, emergency power systems, fire protection systems, machinery, etc. Building contents books and shelves, furniture, file cabinets, storage racks, etc. A rational approach to designing operational and functional components of buildings includes the use of floor design response spectra. Such design spectra, conforming to the 25 National Building Code of Canada (NBCC 25) are currently not available in Canada. The NBCC-25 reflects the most recent seismic hazard data available, based on Uniform Hazard Spectra (). The current research program is an effort towards filling this gap and meeting the needs of the design profession in terms of providing floor design spectra compatible with the current seismic hazard levels incorporated in NBCC-25. This was achieved through comprehensive dynamic analyses of selected reinforced concrete frame buildings. Accordingly, three buildings were designed for Vancouver, reflecting the western Canadian seismicity and an additional three buildings were designed for Ottawa, reflecting the eastern Canadian seismicity. The buildings had 5, and 5 stories, covering a wide range of periods of vibrations for frame building. NBCC-25 compatible earthquake records were used to conduct dynamic inelastic response history analyses. Acceleration time histories were obtained from the analyses and response spectrum was constructed for each floor under each record. Mean, and mean plus standard deviation response spectra were generated to develop floor design response spectra. The details of the procedure followed, and the floor response spectra obtained are presented in the following sections. 2. REINFORCED CONCRETE BUILDINGS SELECTED A total of six reinforced concrete buildings, designed on the basis of the seismic provisions of NBCC-25 were selected. The buildings consisted of 5, and 5 storey heights. Moment resisting frame buildings were considered in Vancouver and Ottawa for each of the three building heights. The frame buildings in Vancouver included cases where the buildings were designed without considerations for the current drift limitations, including cases that may also represent buildings built prior to the enactment of modern building codes. Figures and 2 show the floor plan and elevation views of buildings. The floor plan was selected to be symmetrical to minimize the effects of torsion. The analyses were conducted in the short direction of plan. The lateral load resisting system was considered to consist of bare building frames, without any participation from non-structural elements, such as architectural and masonry enclosures and/or partition walls. Therefore, their periods may be longer than those with significant participation of non-structural components providing unintentional stiffening effects. The fundamental period computed for 5, and 5-storey buildings were.75 sec, 3.47 sec and 5. sec, respectively. The design force levels were computed on the basis of the seismic design provisions of NBCC-25. provided for Vancouver and Ottawa were used to reflect the appropriate seismic hazard levels. The buildings in Vancouver were designed and detailed as fully ductile buildings, using the ductility related force modification factor, R d = 4.. The buildings in Ottawa, on the hand, were designed to be moderately ductile, with R d = 2.5. All buildings were assumed to be located on firm soil (Class C in NBCC-25), without the amplification effects of soft soils. The force levels were based on building periods obtained by

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China employing the empirically developed period expressions suggested by the code, incorporating field data and the possibility of additional stiffening by non-structural elements, with due allowances made by the code for relaxation up to 5%, provided the computed periods based on bare frame models showed higher values. 6. m 6. m 6. m 6. m 6. m 6. m 6. m 8 m 6. m 3 m Figure Typical floor plan for the frame buildings selected 3 @ 6=8 m 3 @ 6=8 m @ 4= 4 m 5 @ 4= 6 m 3 @ 6=8 m 5 @ 4= 2 m a)5-storey b)-storey c)5-storey Figure 2 Elevation views of buildings selected The buildings were analyzed using equivalent static loads and computer software SAP2 to establish design forces. Two-dimensional static analyses were conducted using preliminary member dimensions to determine the critical values of bending moments, axial forces and shear forces at each joint. These values

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China were then used to design the beams and columns, based on the CSA Standard A23.3 (24). The analyses were repeated with revised member sizes when necessary. 3. GROUND MOTION RECORDS EMPLOYED The current research project involves development of floor response spectra for reinforced concrete frame buildings in Canada. Therefore, the ground motion records required for dynamic analysis need to reflect the Canadian seismicity. Although a large database of California earthquakes is available, they may not be applicable to seismic analyses of buildings in Canada, because of differences in their frequency content. Therefore, the use of actual California earthquake records is not feasible. Instead, simulated records, compatible with target spectra are needed. The seismic hazard maps of Canada have been updated by the Geological Survey of Canada (GSC) recently. The GSC proposed a new seismic hazard model that includes new knowledge from recent earthquakes, new strong motion relations and better understanding of site conditions. The newly proposed hazard computation was made for 2% in 5 year probability level, instead of the % in 5 years used earlier. The seismicty is presented in the form of uniform hazard spectra (), incorporating the composite effects of earthquakes that contribute most strongly to the hazard at the specified probability level. These spectra were adopted by the National Building Code of Canada in 25, in an idealized manner. Accordingly, the spectral accelerations are specified at.2,.5,. and 2. second periods. These four spectral quantities allow the construction of approximate uniform hazard spectrum for each location. For the objectives of the current investigation, it is important to select ground motion records that are compatible with the given in the code. Atkinson and Beresnev (998) developed artificially generated records with a view that they provide realistic representations of ground motions for selected earthquake magnitudes and distances that contribute to hazard at respective locations and for selected probability levels. In their approach, more than one record is used to match the target. Four horizontal components are generated for a moderate nearby earthquake, and four horizontal components are generated for a larger distant earthquake with a total of eight records for every selected city. This was found necessary because moderate nearby earthquakes would not produce sufficiently long-period energy to match the long-period band whereas the larger distant earthquakes would have lost too much high-frequency energy to match the short-period band. The records suggested by Atkinson and Beresnev (998) were selected for use in the current investigation. The records selected correspond to the probability of occurrence of 2% in 5 years, as they were compatible with the uniform hazard spectra specified in NBCC-25. For Ottawa, 5 artificial records were selected from M (magnitude) 6. and M7.. The distance for these records varied from 25 km to 5 km for M6. and from 5 km to km for M7.. Fifteen different records were selected for Vancouver. They included 7 records from M6.5 (short event) and 8 records from M7.2 (long event). 4. DYNAMIC INELASTIC RESPONSE HISTORY ANALYSES Analysis of structures due to earthquake motions should be done in two orthogonal directions, separately and independently. Most computer software includes planar frame models. Three-dimensional structures can be modeled as a series of two-dimensional frames linked together to reflect the actual strength and stiffness in each direction. In a two-dimensional analysis, the structure is idealized as a planar assemblage of discrete elements. The buildings designed in the current investigation all have four interior and two exterior frames with three bays in the short direction. Due to the rigid slab diaphragm assumption, each frame was assumed to have the same horizontal deflection at each floor level. Hence, the frames were modeled by connecting them in series with rigid links. The links were modeled by specifying rigid beam elements having infinitely high axial rigidities and infinitely small flexural rigidities. These elements transfer lateral forces without moment connections between the frames.

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China Each of building designed was modeled having six frames connected to each other by rigid links. Identical frames with the same member sizes, strengths and stiffness parameters were lumped into one frame to reduce the number of elements and the required processing time. Thus, the structures were modeled as two frames connected by rigid links, where one of the frames represented the strength and stiffness of four interior frames and the other represented the same for two exterior frames. This is shown in Figure 3 for the -storey frame building. Computer software DRAIN-2DX (Prakash, V. et al. 993) was used to carry out nonlinear time history analysis of buildings. DRAIN-2DX is a general purpose dynamic analysis program that utilizes the stiffness method of structural analysis. Dynamic equation of motion is solved numerically through the step-by-step linear acceleration method. Three degrees of freedom were used at each node, consisting of X and Y translations and R rotation about the Z-axis. Flexural yield strengths for all structural elements are defined as part of the parameters that defined the hysteretic model. The element stiffness was defined with due considerations given to concrete cracking. The flexural rigidities were taken as 7% and 35% of those computed based on gross sectional properties for vertical and columns and beams, respectively. Takeda s hysteretic model (Takeda et al. 97) was employed to describe the element stiffness during loading, unloading and reloading under earthquake excitations. Figure 4 shows the hysteretic model used for flexure. Structural mass was assumed to be concentrated at each floor level and was specified at each node. Damping was specified as 5% of critical damping, consisting of stiffness and mass dependent components. Response time histories of floor accelerations were obtained as output. Rigid Links 6. m 6. m 6. m 6. m 6. m 6. m Force k 2 k k 3 Deformation Exterior Frames Interior Frames Figure 4 Takeda s hysteretic model Figure 3 Frame model used in analysis 5. DESIGN FLOOR RESPONSE SPECTRA Dynamic analyses of buildings under 3 earthquake records resulted in a total of 9 floor response spectra for buildings in Ottawa and Vancouver, one for each floor of each building. The mean spectral relationships were computed for each floor. Figure 5 shows the acceleration response spectra at all levels of buildings designed for Ottawa and Vancouver. The examination of response spectra indicates that there is a progressive increase in response going from

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China the first floor to upper floors. The rate of response amplification is higher in low-rise buildings as compared to companion medium and high-rise buildings. The 5-storey building showed an approximate amplification factor of 4 for roof response relative to the response of the first-storey. However this amplification factor was approximately 3 and 2 for -storey and 5-storey buildings. This may be explained by the ground motion response spectra for buildings with different fundamental periods. The amplification of response for each building was higher in the short period range relative to the medium and long period ranges, indicating the period dependence of response acceleration. The response spectra further indicated a higher amplification for buildings in Vancouver which were subjected to stronger ground motions, relative to those in Ottawa..8.6.4.2 5-Storey Building in Ottawa - Mean st Floor 2 3 4 Period (sec) 5 -Storey Building in Ottawa - Mean.8 st Floor.6 6th Floor 7th Floor 8th Floor.4 9th Floor th Floor.2 2 3 4 Period (sec) 5 a) 5-Storey building in Ottawa b) -Storey Building in Ottawa.8.6.4.2 5-Storey Building in Ottawa - Mean st Floor 6th Floor 7th Floor 8th Floor 9th Floor th Floor th Floor 2th Floor 3th Floor Period (sec) 2 3 4 5.4.8.6.4.2 5-Storey Building in Vancouver - Mean st Floor 2 3 4 Period (sec) 5 c) 5-Storey building in Ottawa d) 5-Storey Building in Vancouver.4.8.6.4.2 -Storey Building in Vancouver - Mean st Floor 6th Floor 7th Floor 8th Floor 9th Floor th Floor 2 3 4 Period (sec) 5.4 5-Storey Building in Vancouver - Mean st Floor 6th Floor 7th Floor 8th Floor.8 9th Floor th Floor th Floor 2th Floor.6 3th Floor.4.2 2 3 4 Period (sec) 5 e) -Storey building in Vancouver f) 5-Storey Building in Vancouver Figure 5 Floor response spectra Mean values Floor response spectra were also constructed for mean plus one standard deviation values. These spectra were deemed appropriate for the development of floor design spectra. This is shown in Figure 6 for all buildings. The figure also includes the for respective cities, depicting the amount of amplification observed at each floor level relative to ground. An upper bound design spectrum was derived through

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China curve fitting, while incorporating the effects of period..4.8.6.4.2 5-Storey Building in Ottawa - Mean+SD 2 3 4 Period (sec) 5.4.8.6.4.2 -Storey Building in Ottawa - Mean+SD st Floor 6th Floor 7th Floor 8th Floor 9th Floor th Floor 2 3 4 Period (sec) 5 a) 5-Storey building in Ottawa b) -Storey Building in Ottawa.4 5-Storey Building in Ottawa - Mean+SD st Floor 6th Floor.8 7th Floor 8th Floor 9th Floor th Floor.6 th Floor 2th Floor 3th Floor.4.2 2 3 4 Period (sec) 5.8.5.9.6.3 5-Storey Building in Vancouver - Mean+SD st Floor 2 3 4 Period (sec) 5 c) 5-Storey building in Ottawa d) 5-Storey Building in Vancouver.8 -Storey Building in Vancouver - Mean+SD.5 st Floor 6th Floor 7th Floor 8th Floor.9 9th Floor th Floor.6.3 2 3 Period (sec) 4 5.8.5.9.6.3 5-Storey Building in Vancouver - Mean+SD st Floor 6th Floor 7th Floor 8th Floor 9th Floor th Floor th Floor 2th Floor 3th Floor 2 3 4 Period (sec) 5 e) -Storey building in Vancouver f) 5-Storey Building in Vancouver Figure 6 Floor response spectra Mean plus one standard deviation values The following expression may be used to compute the amplification factor for floor response spectra relative to. C = 5..5T a () Where T a is the fundamental period of building housing the OFC in seconds, computed by an accepted method of mechanics; and C is the response amplification factor relative to. The floor design spectral acceleration values for a building on firm ground, S f (T) can be computed from the expression given below: S f (T) = C S(T a ).5 S(.2) for T 2. sec (2)

The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China Where, C is the floor response amplification factor defined in Eq. ; T is the vibration period of the OFC to be designed; T a is the fundamental period of the building that houses the OFC, computed using accepted methods of mechanics; S(T a ) is the value specified in NBCC-25 for firm ground (Class C soil). The floor design spectrum has a cutoff value at.5 S(.2). Beyond T = 2. sec, the use of constant, i.e., S(T > 2.) = S(2.) appears to overestimate the spectral values obtained from the use of artificially generated ground motions. Further amplifications of to obtain floor response spectra overestimates the floor acceleration values obtained from dynamic analysis. Therefore, it is suggested that the amplification introduced beyond T = 2. sec is reduced linearly as the period increases from 2. sec to 5. sec to merge with the vale at T = 5. sec. i.e., S f (5.) = S(5.), and follow the thereafter. The floor design spectra obtained by Eq. 2 are plotted in Figure 6 as the proposed spectra for design, providing upper bound values to mean plus one standard deviation floor design spectral accelerations. Figure 6 indicates that the proposed floor design spectra represent spectral values for the roof, whereas the can be used as the floor response spectra for the first floor. A linear interpolation can be made between the two sets of spectra for in between floors. 6. CONCLUSIONS The following conclusions can be derived from the analytical research project presented in this paper: Floor response spectra show amplified spectral accelerations relative to the ground spectral accelerations as described by. The amplification of floor spectral accelerations is the highest at the roof level. The amplification factors for roof is approximately 4. for 5-storey frame buildings, 3. for -storey frame buildings and 2. for 5 storey frame buildings. The amplification decreases gradually going from the roof level to the first storey level. The first storey floor response spectra approach to for the ground. Floor to floor amplification of spectral accelerations are more pronounced in low-rise buildings. The spectra for different floors tend to approach each other as buildings become taller. Eqs. and 2, developed as part of the current research project, can be used to generate floor design spectra from the specified for a given location. REFERENCES Atkinson, G.M. and Beresnev, I.A.. (998). Compatible ground-motion time histories for new national seismic hazard maps. Canadian Journal of Civil Engineering, 25: 35-38. Canadian Standards Association. (24). CSA-A23.3 Design of Reinforced Concrete Buildings. Rexdale, ON, Canada. CSI. (2). SAP 2, Integrated Software for Structural Analysis and Design, Computers and Structures Inc., Berkely, Caligornia. National Research Council. (25). National Building Code of Canada, National Research Council, Ottawa, Canada. Prakash, V., Powell, G.H., and Campbell, S. (993). DRAIN-2DX: Base Program Description and User Guide. Version.. University of California at Berkeley. Takeda, T., Sozen, M. A. and Nielsen, N. N. (97). Reinforced concrete response to simulated earthquakes. J. of the Structural Division, ASCE, 96, ST2, 2557-2573.