Analysis of the Shell Structure under Extreme Load

Similar documents
Effective Prestress Force Considering Instantaneous Loss in Reactor Containment Building

Probabilistic Assessment of the Ultimate Pressure Capacity of the Prestressed Concrete Containment Buildings

Increased plastic strains in containment steel liners due to concrete cracking and discontinuities in the containment structure

Deflection Analysis with Shoring Load Transfer Coefficient for Post-Tensioned Slab

INELASTIC ANALYSIS OF BARC PRESTRESSED CONCRETE CONTAINMENT MODEL

1514. Structural behavior of concrete filled carbon fiber reinforced polymer sheet tube column

Modal-spectral analysis of a gas storage tank.

Case Study: Challenges of a Single-layer Reticulated Dome

Seismic Performance of Residential Buildings with Staggered Walls

FUNDAMENTAL STUDY ABOUT THE IMPACTS OF FIBER S ANGLE FOR THE STRENGTHENING OF STEEL STORAGE TANKS UNDER BENDING SHEAR LOAD

Effect of Flange Width on Flexural Behavior of Reinforced Concrete T-Beam

Pushover Analysis of Reinforced Concrete Structures with Coupled Shear Wall and Moment Frame. *Yungon Kim 1)

Girder-End Cracking in Prestressed I-Girders

STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES

Progressive Collapse Analysis of Reinforced Concrete Framed Structure

A Comparative Study on Non-Linear Analysis of Frame with and without Structural Wall System

High-Mass, Low-Velocity Impacts on Reinforced Concrete Slabs

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

Progressive Collapse Assessment of RC Structures under Instantaneous and Gradual Removal of Columns

SIMPLE INVESTIGATIONS OF TENSILE MEMBRANE ACTION IN COMPOSITE SLABS IN FIRE

EFFECTS OF INTERACTION BETWEEN JOINT SHEAR AND BOND STRENGTH ON THE ELAST-PLASTIC BEHAVIOR OF R/C BEAM-COLUMN JOINTS

Lap Splices in Tension Between Headed Reinforcing Bars And Hooked Reinforcing Bars of Reinforced Concrete Beam

A Study on the Structural Response of a PSC Inner Containment Dome with Large Openings Due to Prestress Transfer

In-plane testing of precast concrete wall panels with grouted sleeve

ANALYSIS OF THE REPLACEMENT NEED FOR THE CONTAINMENT ANCHORING BOLTS OF THE LOVIISA NPP ESTIMATED BY THE STRENGTH ASSESSMENT

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER C: DESIGN BASIS AND GENERAL LAYOUT

Effective Length of RC Column with Spandrel Wall

Explosive Testing of Open Cylinders for Verification of Composite Properties used in Computational Analysis

PSEUDO-DYNAMIC TEST AND NON-LINEAR ANALYSIS OF A 1:10 SCALE PRE-STRESSED CONCRETE CONTAIN VESSEL MODEL FOR CNP1000 NUCLEAR POWER PLANT

Punching shear resistance of reinforced concrete slabs under pneumatic loads

Earthquake Design of Flexible Soil Retaining Structures

Effect of Edge Beam and Shear Wall on the Structural Behavior of Flat Plate Multistoried Building: A Computing Modeling for lateral load Analysis

INVESTIGATION ON NONLINEAR ANALYSIS OF EXISTING BUILDING AND INTRODUCING SEISMIC RETROFITTING OUTLINES WITH CASE STUDY

Verification of the reinforced concrete beam model based on the results of a full-scale experimental study

MODELLING OF SHEAR WALLS FOR NON-LINEAR AND PUSH OVER ANALYSIS OF TALL BUILDINGS

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

Standard Specification for concrete structures-2002, Seismic Performance Verification

EXPERIMENTAL INVESTIGATION ON THE INTERACTION OF REINFORCED CONCRETE FRAMES WITH PRECAST-PRESTRESSED CONCRETE FLOOR SYSTEMS

OPTIMUM LOCATION OF RC SHEAR WALL FOR A FIVE STOREY SYMMETRICAL FRAMED STRUCTURE FOR EFFICIENT SEISMIC DESIGN USING PUSHOVER ANALYSIS

Design of an LNG Tank for Accidental Loads in Finland. 1. Introduction

STRUCTURAL APPLICATIONS OF A REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTION MODEL FOR EARTHQUAKE LOADING

Effect of Mass and Stiffness of Vertically Irregular RC Structure

Tip-Over Analysis of the HI-STORM Dry Storage Cask System

Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower

Progressive Collapse Resisting Capacity of Moment Frames with Infill Steel Panels

Basic quantities of earthquake engineering. Strength Stiffness - Ductility

Compression Test for Precast Encased Composite Columns with Corrugated Steel Tube

PRESTRESSED CONCRETE STRUCTURES. Amlan K. Sengupta, PhD PE Department of Civil Engineering, Indian Institute of Technology Madras

CHAPTER 5 FINITE ELEMENT MODELLING

EFFECT OF USER DEFINED PLASTIC HINGES ON NONLINEAR MODELLING OF REINFORCED CONCRETE FRAME FOR SEISMIC ANALYSIS

Elasto-plastic behavior of steel frame structures taking into account buckling damage

SHEAR BEHAVIOR OF MULTI-STORY RC STRUCTURAL WALLS WITH ECCENTRIC OPENINGS

EXPERIMENTAL RESPONSE OF BOUNDARY ELEMENTS OF CODE- COMPLIANT REINFORCED CONCRETE SHEAR WALLS

ON THE ULTIMATE STRENGTH OF RC SHEAR WALL UNDER MULTI-AXES SEISMIC LOADING CONDITION

9.6 Circular Prestressing

International Journal of Advance Engineering and Research Development REVISION OF IS: A REVIEW (PART 2)

Chapter 7. Finite Elements Model and Results

SC Wall Piers and Basemat Connections: Numerical Investigation of Behavior and Design

STUDIES ON LONG-SPAN CONCRETE ARCH BRIDGE FOR CONSTRUCTION AT IKARAJIMA IN JAPAN

Tensile Strength of Lap Splices in Reinforced Concrete Members

FAST NONLINEAR SEISMIC SSI ANALYSIS OF LOW-RISE CONCRETE SHEARWALL BUILDINGS FOR DESIGN-LEVEL (DBE) AND BEYOND DESIGN-LEVEL (BDBE)

REINFORCED CONCRETE WALL BOUNDARY ELEMENT LONGITUDINAL REINFORCING TERMINATION

SEISMIC PERFORMANCE EVALUATION OF A TYPICAL LOW-RISE REINFORCED CONCRETE BUILDING IN THE PHILIPPINES

Behavior of RC Beams Strengthened with Externally Post-Tensioning CFRP Strips

Structural design criteria

PERFORMANCE BASED EVALUATION OF FRAMED REINFORCED CONCRETE SHEAR WALLS BY PUSHOVER ANALYSIS

Gravity Load Collapse of Reinforced Concrete Columns with Brittle Failure Modes

Javad VASEGHI AMIRI 1, Morteza HOSSEINALIBYGIE 2

Seismic Assessment of Non-Seismically Designed Reinforced Concrete Frames with Core Walls

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING

PVP2006-ICPVT

1337. Seismic response of beam-column joints rehabilitated with FRP sheets and buckling restrained braces

LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS. Qiang SHEN Graduate Research Assistant. Yahya C. KURAMA Assistant Professor

Seismic Behavior of Column-supported and Innovative Fixed-base Cooling Towers with Ring Beam

A study of double-deck tunnel depending on types of intermediate slab with beam-spring model

USE OF INELASTIC ANALYSIS IN CASK DESIGN

ISSN: (p); (e) AXIAL FORCE-MOMENT INTERACTION DIAGRAMS TO CALCULATE SHEAR WALL REINFORCEMENT

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 1, 2011

SEISMIC FORCE RESISTING MECHANISM OF THE MULTI-STORY PRECAST CONCRETE SHEAR WALL SUPPORTED ON PILES

Prediction of Compressive Behavior of CFCT Stub Columns on the Basis of Integrated Data Analysis

Section A A: Slab & Beam Elevation

COMPARATIVE SEISMIC PERFORMANCE OF RC FRAME BUILDINGS DESIGNED FOR ASCE 7 AND IS 1893

Effect of FRP strengthening on the behavior of shear walls with opening

International Journal of Engineering Trends and Applications (IJETA) Volume 5 Issue 5, Sep-Oct 2018

Inelastic nonlinear analysis of beams with under-tension cables

ST7008 PRESTRESSED CONCRETE

Anton Andonov, Dimitar Stefanov, and Marin Kostov

Blast response simulation of Alfred Murrah building reinforced by use of HPFRCC

IMPACT ANALYSIS OF SUBMERGED FLOATING TUNNEL FOR EXTERNAL COLLISION

Study of height on response reduction factor of RC water tank in zone IV

10.5 ECCENTRICALLY LOADED COLUMNS: AXIAL LOAD AND BENDING.

Earthquake Damage Assessment of Reinforced Concrete Hotel Buildings in Hawaii

Behavior of Reinforced Concrete Walls with Mesh Reinforcement Subjected to Cyclic Loading

Preliminary Lessons Learned from the Fukushima Daiichi Accident for Advanced Nuclear Power Plant Technology Development

Analytical Study on a Longitudinal Joints of the Slab-Type Modular Bridges Sang-Yoon Lee, Jung-Mi Lee, Hyeong-Yeol Kim, Jae-Joon Song

Methodology for design of earthquake resistant steel liquid storage tanks

EUROPEAN RESEARCH INTO COMPOSITE STEEL-CONCRETE STRUCTURES

3 Dimensional Structural Modelling of Segmental Tunnel Lining Using Finite Element Software

PV Newsletter Monthly Publication from CoDesign Engineering Academy

Lehigh Preserve. Lehigh University. Sonam Srivastava Lehigh University. Theses and Dissertations

Transcription:

Analysis of the Shell Structure under Extreme Load *Joon-Ki Hong 1) and Thomas Kang 2) 1), 2) Department of Architecture & Architectural Engineering, Seoul National University, Seoul, Korea 2) tkang@snu.ac.kr ABSTRACT For containment structures, accidents caused by extreme environmental conditions should be considered even if it is highly improbable. Therefore all containment structures should observe the design code meticulously. As a role of preventing release of radiological materials, containment structures should resist beyond the design pressure. The main purpose of this study is to characterize the response of the reactor building with an analysis when a containment structure is under 0.7 MPa. The analysis is conducted using ETABS 2015. It is concluded that structural behavior of the containment structure can be analyzed using the tensile force and bending moment at various points, and that the critical point is located at 11 m in height of the modeled full-scale shell structure. 1. INTRODUCTION The three-mile island accident happened in the United States in 1979. In 1986, the Chernobyl disaster occurred. Recently, the explosion of a nuclear plant caused by the earthquake in Fukushima, Japan occurred in 2011. After these accidents, anxieties about structural safety of nuclear power plant (NPP) structures are stretched to the world. During the design of nuclear containment structures, nuclear structural engineers should consider various loading cases although it is highly improbable. For many kinds of accidents, severe accidents in the NPP structures are related to the loss of coolant accident (LOCA). In the event of a severe accident, radioactive materials are released, coinciding with increasing internal pressure level beyond the design pressure. Consequently, the NPP structure should perform a role as a radiation shield. In general, NPP structures are typically comprised of main buildings, appurtenances, and foundation. The NPP structures are designated separately as safety-related or non-safety-related components. Reactor buildings and auxiliary buildings are classified as safety-related components constructed as concrete 1) Graduate Student 2) Associate Professor

structures. The reactor buildings consist of pressure boundary parts, such as cylindrical wall, hemispherical dome-shape roof and foundation slab, and internal structures which are not belonged to the pressure boundary parts. While the structures included in pressure boundary parts are designed complying with KEPIC SNB, concrete structures which are not classified in the boundary parts should conform to KEPIC SNC (KEPIC, 2010a; KEPIC, 2010b; Moon, 2014). In the U.S., design basis and combinations are addressed in the ASME Boiler and Pressure Vessel Code (BPVC) to construct nuclear containment buildings, where loads are divided into service load and factored load categories. Particularly, severe environmental loads, extreme environmental loads, and abnormal loads are involved in the factored load category. Based on the load cases, load combinations and load factors are defined in the ASME code (ACI-ASME Joint Committee, 2015). A typical research to evaluate the structural capacity about internal pressure was the overpressurization test of a 1:4 scale containment conducted by Sandia National Laboratories. By performing the static pneumatic overpressurization test at ambient temperature, the structural response of the containment to and beyond the design pressure was observed and measured, including the failure modes (Hessheimer, 2003). Akbar and Gupta (1986) studied the reinforced concrete containment behavior under dead load, internal pressure, and earthquake. In this study, a containment shell structure subjected to 0.7 MPa of internal pressure is considered. The main purpose of this study is to characterize the behavior when the containment structure is under the extreme internal pressure. Using ETABS 2015 and LS-DYNA, finite element programs, the structural analysis is conducted (CSI, 2015). 2. ANALYSIS MODEL 2.1 Computational Model Representative types of containment buildings are summarized in Table 1 (Jeon, 2000). In particular, methods of generating nuclear energy are classified as Pressurized Water Reactor (PWR) and Pressurized Heavy Water Reactor (PHWR). The PWR method is employed on the OPR-1000 such as Kori, Hanbit, and Hanul plants. It has a hemispherical dome and cylindrical wall constructed by adopting unbonded prestressed concrete. The PWHR method was applied to the Wolsong plant, where a partially spherical dome was applied on the top of the building. The design pressure was approximately 0.41 MPa and 0.12 MPa, respectively (Kwak, 2004). In Korea, the PWR method was adopted for most of the NPP structures except for 4 units. In this respect, the OPR-1000 is established as a computational model to study a response to internal pressure in this paper.

Table 1 Types of Containment Structures (Jeon, 2000) Structure Nuclear Containment Building LNG Storage Tank OPR-1000 1) CANDU 2) Tongyeoung Incheon Shape of Dome and Ring Beam Ring X O O O Beam 1) Optimized Power Reactor 1000 MWe 2) Canada Deuterium Uranium As shown in Fig. 1, a computational containment structure in ETABS 2015 is consisted of cylindrical wall, which has a 22 m radius and 44 m elevation, and a hemispherical dome on the top of the building. The wall and dome thickness is 1.22 m. Fig. 1 Computational Shell Structure Model in ETABS 2015 Material properties for concrete are summarized in Table 2 (Lee, 2011). The

compressive strength is 38 MPa, the Poisson s ratio is 0.17, and the density is 0.0025 kg/cm 3. Equation (1) is used to determine the modulus of elasticity of concrete, E c, for normalweight concrete (ACI Committee 318, 2014). Using this equation, the value of the modulus of elasticity is taken as 29,175 MPa. (1) Table 2 Material Properties for Concrete Compressive Strength (MPa) Poisson s Ratio Density (kg/cm 3 ) Modulus of Elasticity (MPa) Concrete 38 0.17 0.0025 29175 The value of 0.7 MPa is taken to characterize the structural response under extreme internal pressure. This value is roughly 170% of 0.41 MPa, the design pressure. Therefore, the value of 0.7 MPa is sufficient to evaluate the performance for resisting internal pressure. The pressure is applied to all elements perpendicularly. The self-weight is considered as gravity load. 2.2 Assumptions and Restraints In order to simplify the analysis, the computational model is made up of only wall and dome roof as an axisymmetric structure. Components causing asymmetry such as the equipment hatch and air locking are excluded. Additionally, although the basemat foundation is a flexible bending component for containment structures, it is not established in ETABS 2015. This paper mainly focuses on the elastic behavior of cylindrical wall and dome-shaped roof without consideration of prestressing effects and yielding of the steel. 3. RESULTS OF THE ANALYSIS The elements on a vertical line are selected to examine the data because the computational model maintains the axisymmetric feature. General information about the selected elements is shown in Table 3.

Table 3 General Information of Representative Elements Height (m) Shell Object Unique Name 66.0 F153 213 65.6 F123 183 64.3 W513 153 62.3 W483 123 59.6 W453 93 56.2 W423 60 52.4 W393 33 48.3 W363 3 44.0 W567 409 38.5 W567 410 33.0 W567 411 27.5 W567 412 22.0 W567 413 16.5 W567 414 11.0 W567 415 5.5 W567 416 Figure 2 shows comparisons of the tensile forces or stresses between circumferential and longitudinal directions under design internal pressure. For the tensile force, the maximum force is obtained at 11 m elevation in the circumferential direction. Generally, the circumferential force or stress is larger than that in the longitudinal direction. (a) (b) Fig. 2 (a) Tensile Force, (b) Stress

(a) (b) Fig. 3 (a) Circumferential Stress, (b) Longitudinal Stress Fig. 4 Moment Comparison However, as shown in Figs. 3(a) and 3(b), there are differences between the internal and external stress for both directions. A variation in the longitudinal stress is substantial, while a variation in the circumferential direction is quite small. The moments are induced with increasing magnitude of external and internal stress difference. Hence, the pattern of moment is opposite to the tensile force. The moments are observed at the location where stress differences between the external and internal

surfaces are evident as shown in Fig. 4, ranging from 5 m to 11 m in height. Contrary to the circumferential moment which is almost zero, the maximum longitudinal moment is shown at the height of 8 m. The longitudinal moments are close to zero from 11 m to the top of the structure. In conclusion, the stress difference between external and internal wall surfaces is closely related with the moment, and the bending deformation of the containment structure is induced mainly by the longitudinal moment. Fig. 5 Strain Comparison Figure 5 shows the strain of elements for horizontal and longitudinal directions. Both strain values are determined by dividing each stress by the modulus of elasticity of concrete. Therefore the distribution is almost the same shape as that in Fig. 2(b). The maximum circumferential strain of the cylindrical wall is observed at the height of 11 m and shows 0.000439. For longitudinal direction, the maximum strain is 0.000397 at 5.5 m elevation. The strain values are compared with the rupture strain of concrete, where the modulus of rupture for concrete, f r, is derived from Eq. (2) of ACI 318-14, and the value of, the modification factor, is 1.0 for normalweight concrete. As a result, the value of 3.83 MPa is taken. (ACI 318 Committee, 2014), and the concrete strain at rupture is determined to be 0.00013. (2) Circumferential and longitudinal strains exceed the rupture strain of concrete; therefore, it is concluded that crack would occur in all areas of the concrete containment structure without prestressing.

Fig. 6 Deformed Shape of the Containment Structure The deformed shape of the containment is shown in Fig. 6, which is plotted using displacements in horizontal and vertical directions. Deformation values between the centers of meshes are determined by linear interpolation. A vertical displacement at apex is given by 8.66 mm and a maximum horizontal displacement shows 9.65 mm at 11 m elevation. It is speculated that the horizontal deformation governs the structural behavior of the building under the extreme internal pressure. According to Fig. 2(a) and Fig. 5, maximum values of tensile forces and strains are identified at 11 m elevation. Therefore, it is figured out that the lateral expansion is caused by the circumferential tensile force. 4. LS-DYNA MODELING Along with the ETABS 2015 analysis, an internal pressure analysis is being conducted, which is in progress using LS-DYNA. This is the finite element method analysis software specialized in and used in large deformation analysis such as the impact, crash, explosion, or collapse. Figure 7 shows the containment structure established in LS-DYNA. Essentially, dimensions of the containment are the same as those used in the ETABS 2015 model. For concrete, *MAT_CSCM_CONCRETE is used and *MAT_PLASTIC_KINEMATIC keyword is employed to establish steel reinforcing bars. The reinforcement modeling embedded in the concrete is executed using *CONSTRAINED_LAGRANGE_IN_SOLID keyword (LSTC, 2016)..

(a) (b) Fig. 7 (a) Overview of the Containment, (b) Reinforcement Modeling It is confirmed that the displacement induced by gravity load is the same as the result of ETABS 2015 analysis. In the following study, asymmetric factors, such as equipment hatch or entrance, will be considered to improve the accuracy and reliability of results. In addition, it is also planned to conduct a study on comparing structural responses caused by extreme internal pressure. 5. CONCLUSION In the design of containment structures, various load cases and combinations should be considered including implausible cases. Especially, structural safety against extreme internal pressure is important as the containment which plays a role of the radiation shield. In this study, analysis is conducted to characterize the response of the containment subjected to 0.7 MPa pressure. Several conclusions drawn from the analysis are summarized below: (1) At 11 m elevation, the maximum tensile force is noted in the circumferential direction. (2) Based on the tendency of moments, the maximum moment is obtained at approximately 8 m elevation in the longitudinal direction. Above the height of 11 m, moments in both directions are nearly zero. (3) All elements strain values in both directions are larger than the rupture strain of concrete. Therefore, without prestressing, concrete crack is expected to be observed. (4) Overall, the circumferential tensile force and strain are larger than those in the longitudinal direction. In addition, the maximum horizontal displacement is

given by 9.65 mm at 11 m elevation. The structural response of the containment under internal pressure is characterized by the horizontal deformation of the cylindrical wall. Consequently, the bending behavior is governed by the longitudinal moment, and the tensile force induces expansion. The critical location is where the maximum tensile force and maximum bending moment occur simultaneously. Based on this coupled relationship, the critical location is determined to be at the height of 11 m, although the longitudinal moment is smaller than that below this level. ACKNOWLEDGMENT This research was supported by the National Research Foundation of Korea (NRF) grant (No. 2015-001535). The conclusions in this paper are those of the authors and do not necessarily represent those of the sponsor. REFERENCES ACI Committee 318 (2014), Building Code Requirements for Structural Concrete (ACI 318-14) and Commentary (ACI 318R-14), American Concrete Institute, Farmington Hills, MI. ACI-ASME Joint Committee (2015), ASME Boiler and Pressure Vessel Code Section III-Division 2 and ACI Standard 359, The American Society of Mechanical Engineers, New York, NY. Akbar, H. and Gupta, A. (1986), Ultimate Behavior of an R.C. Nuclear Containment Subjected to Internal Pressure and Earthquake, Journal of Structural Engineering, Vol. 112(6), 1280-1295. CSI (2015), CSI Analysis Reference Manual, Computers & Structures, Inc., Berkeley, CA. Hessheimer, M. F., Klamerus, E. W., Lambert, L. D., and Rightley, G. S. (2003), Overpressurization Test of a 1:4-Scale Prestressed Concrete Containment Vessel Model. NUREG/CR-6810, SAND2003-0840P, Sandia National Laboratories, Albuquerque, NM. Jeon, S.-J. and Kim, Y.-J. (2010), An advanced design procedure for dome and ring beam of concrete containment structures, Journal of the Korea Concrete Institute, Vol. 20(6), 817-824. (in Korean) KEPIC (2010a), KEPIC-SNB Concrete Containment, Korea Electric Association, Songpa, Seoul. (in Korean) KEPIC (2010b), KEPIC-SNC Nuclear Safety-Related Concrete Structures, Korea Electric Association, Songpa, Seoul. (in Korean) Kwak, H.-G., Kim, S.-J., Kim, D.-Y., Kim, S.-H., and Chung, Y.-S. (2004), Nonlinear analysis of reactor containment structures during ultimate accident condition, Proceedings of the Korean Nuclear Society Conference, Gyeongju. (in Korean) Lee, H.-P. (2011), "Shell finite element of reinforced concrete for internal pressure analysis of nuclear containment building, Nuclear Engineering and Design, Vol.

241(2), 515-525. LSTC (2016), LS-DYNA Keyword User s Manual, Livermore Software Technology Corporation, Livermore, CA.