STANDARD REQUIREMENTS FOR MORTAR USED IN MORTAR SET TILE SYSTEMS

Similar documents
ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS

PRODUCT CONTROL SECTION

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

DRAFT NOTICE OF ACCEPTANCE (NOA)

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION

PRODUCT GUIDE SPECIFICATION

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

SPECIFICATION GUIDELINE

SPECIFICATION GUIDELINE

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):

September 1, 2003 CONCRETE MANUAL SPECIAL TYPES OF CONCRETE

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

ESR-2015P* Reissued April 2014 This report is subject to renewal April 1, 2015.

DESCRIPTION: Eagle Roof Tiles

A. This Section includes resinous flooring systems with epoxy body coat(s).

Part 1 - General. Spec Component Sikadur 32 Hi-Mod. DIVISION 3 -CONCRETE Section Cast-in-Place Concrete Bonding Agents for Concrete

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

CRITERIA FOR TESTING IMPACT & NON IMPACT RESISTANT BUILDING ENVELOPE COMPONENTS USING UNIFORM STATIC AIR PRESSURE

2007 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

***************************************************************************************************************

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

SECTION UTILITY MANHOLES AND STRUCTURES

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board

A. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars

Product Guide Specification

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

Truck Mixer, Agitator and Front Discharge Concrete Carrier. Standards. TMMB Printing

CBUCK Engineering. Florida Product Approval # FL R2

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065

A. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.

Standard Practice for Molding Roller-Compacted Concrete in Cylinder Molds Using a Vibrating Hammer 1

MILITARY SPECIFICATION COATING COMPOUND, SYNTHETIC RUBBER, FOR EXPOSED STEEL SURFACES

SECTION RESINOUS FLOORING or SECTION QUARTZ FLOORING

Typical Properties Specification Writers: These values are not intended for use in preparing specifications.

A. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.

Elastomeric Protected Membrane Roofing Fluid-Applied Protected Membrane Roofing. Restoration Coating System (RCS) over Cap Sheet

TECHNICAL INFORMATION

Addendum No. 1. ITB for Emergency Management/Utilities Administration Building Renovation Addendum Release Date April 06, 2017

1. ICC ES AC51 Draft Changes, Masonry Veneer Manufacturers Association (MVMA) Comments, dated September 24, 2007, compiled by John Woestman.

SECTION PRECAST CONCRETE PAVERS AND PEDESTAL LOK DOWN SYSTEM

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

REFLECTIVE FACE CONCRETE MASONRY UNITS

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

SECTION SPLIT FACE CONCRETE MASONRY UNITS

SECTION CONCRETE PAVING SLABS SET IN MORTAR

ARCHITECTURAL TESTING, Inc. Code Compliance Research Report #0774 CCRR-0131

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: BORAL ROOFING LLC

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

CIA-GEL 7000 EPOXY. One Product For All Applications ADHESIVE ANCHORING SYSTEMS FOR CONCRETE AND MASONRY

MATERIAL SPECIFICATION FOR AGGREGATES - MISCELLANEOUS

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

STATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014

High Strength Epoxy Tested in Accordance with ICC-ES AC308

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

OTEC 2017 Spray Applied Pipe Liner Supplemental Specifications 833 Calculations for the Resin Based Liner Presented by Peter Blais, PE

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck

INDUSTRIAL ATTACK 800

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

SECTION MANUFACTURED STONE VENEER. A. Section Includes: 1. Manufactured stone veneer masonry, accessories, and related materials.

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

High Strength Epoxy Tested in Accordance with ICC-ES AC308

ESR ICC Evaluation Service, Inc. Reissued September 1, 2008 This report is subject to re-examination in one year.

MATERIAL SPECIFICATION FOR BEARINGS - ELASTOMERIC PLAIN AND STEEL LAMINATED

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

NTPEP Evaluation of Epoxy and Resin Based Adhesive Bonding Systems.

ARDEX GUIDE SPECIFICATION

***********************************************************************************

EDITORIAL REVISION March Process Industry Practices Refractory. PIP RFSM1000 Monolithic Refractory Material Specification

SECTION GROUT. A. American Society for Testing and Materials (ASTM):

PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY

High Strength Epoxy tested in accordance to ICC-ES AC308

ENVIRONMENTAL CRITERIA FOR DETERMINATION OF RECYCLED CONTENT OF MATERIALS EC101 PREFACE

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW RED HEAD 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Product Guide Specification

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

ATI Evaluation Service A Division of Architectural Testing Certification Services

MATERIAL SPECIFICATION RIGID FOAM; CLOSED CELL POLYMETHACRYLIMIDE (PMI)

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Technical Bulletin. CTIOA Technical Committee

Transcription:

TESTING APPLICATION STANDARD (TAS) 123-95 STANDARD REQUIREMENTS FOR MORTAR USED IN MORTAR SET TILE SYSTEMS 1. Scope 1.1 This Protocol covers: 1) the standard requirements of mortar for use in mortar set tile systems; 2) the procedures for testing such mortar if these standards are not initially met; and, 3) the approval process for all mortar which successfully meets either the standard requirements and/or the testing requirements. 1.2 This Protocol applies to all mortar which is intended for use in Product Control Approved mortar set tile systems within the High Velocity Hurricane Zone jurisdiction. 1.3 All testing shall be conducted by an approved testing agency and all test reports shall be signed by an authorized signer of the testing agency and/or Professional Engineer. 2. Referenced Documents 2.1 The Florida Building Code, Building. 2.2 ASTM Standards C 270 Standard Specification for Mortar for Unit Masonry C 91 Standard Specification for Masonry Cement C 144 Standard Specification for Aggregate for Masonry Mortar C 109 Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or 50-mm Cube Specimens) E 380 Excerpts from Standard Practice for Use of the International System of Units (SI) (the Modernized Metric System) 2.3 Application Standards TAS 101 Test Method for Static Uplift Test Resistance of Mortar or Adhesive Set Tile Systems 3. Terminology & Units 3.1 Definitions - For definitions of terms used in this Protocol, refer to Chapter 2 and Section 1513 of the Florida Building Code, Building; and/or the RCI Glossary of Terms. Definitions from the Florida Building Code, Building shall take precedence. 3.2 Units - For conversion of U.S. customary units to SI units, refer to ASTM E 380. 4. Significance and Use 4.1 The requirements outlined herein are intended to provide a guideline for mortar manufacturers in order to obtain a Roofing Component Product Control Approval for use of their product(s) in approved mortar set tile systems. 5. Standard Requirements for Approval 5.1 Mortars for use in mortar set tile systems shall meet the 'Proportion Requirements' and 'Property Specifications' set forth in ASTM C 270 for type 'M' masonry cement mortar which is premixed and bagged. The sand: masonry cement mixing ratio shall not be exceed 2.5:1. 5.2 Alternatively, mortars for use in mortar set tile systems shall consist of not greater than 2 1 / 2 parts ASTM C 144 uniformly graded sand or 2 V2 parts ASTM C 332 lightweight aggregate in combination with one part ASTM C 91, type 'M' masonry cement which is premixed and bagged. 5.2.1 Mortars formulated as noted in Section 5.2 using lightweight aggregate are not required to meet the minimum compressive strength of those mortars from Section 5.1; however, the compressive strength shall be not less than 350 psi, as determined in compliance with ASTM C 109. 5.3 All mortars which meet the standard requirements set forth in Sections 5.1 or 5.2 shall be approved for use with flat tile profiles only based on submission of the following: completed application for Roofing Component Product Control Approval; (TAS) 123-95.1

(TAS) No. 123-95 certification from an approved testing agency that the mortars, or components thereof, meet the requirements set forth in Sections 5.1 or 5.2, respectively; street address where periodic quality control inspections may be carried out by a representative from the Authority Having Jurisdiction; a sample of the premixed bag; and, a copy of the handling and mixing instructions. 5.4 Any mortars which deviate from the standard requirements set forth in Sections 5.1 or 5.2, either through differing proportions or a substitution of masonry cement, sand or lightweight aggregate, and any mortars intended for use with low and high profile tile shall be tested as set forth in Section 6 prior to receiving Roofing Component Product Control Approval. 5.4.1 Mortars which require testing, as noted in Section 5.2, and use lightweight aggregate as a component thereof are not required to meet the minimum compressive strength of those mortars from Section 5.1; however, the compressive strength shall be not less than 350 psi, as determined in compliance with ASTM C 109. Tlle Type High Profile Low Profile Flat Minimum Characteristic Resistance Load(lbf) 30 26 50 6.1.3 The moment calculations shall be omitted from the requirements of TAS 101. 6.2 Upon successful completion of this testing, the manufacturer shall submit the applicable items listed in Section 5.3, together with the final test report(s), from TAS 101 testing, to receive a Roofing Component Product Control Approval. 7. Mortar Set Tile System Manufacturers 7.1 Mortar set tile system manufacturers may interchange any approved, premixed, bagged mortar product into mortar set tile system(s). 6. Testing Requirements 6.1 Any mortars which deviate from the standard requirements set forth in Sections 5.1 or 5.2, either through differing proportions or a substitution of masonry cement, sand or lightweight aggregate, and any mortars intended for use with low or high profile tile shall be tested in compliance with TAS 101 with the following modifications: 6.1.1 Testing shall include five (5) samples each desired tile profile. 6.1.2 The static uplift testing shall result in the following minimum characteristic resistance loads (F'). (TAS) 123-95.2

TESTING APPLICATION STANDARD (TAS) 123-95 APPENDIX 'A' STANDARD REQUIREMENTS OF TILE ADHESIVE USED TO REPAIR OR SUPPLEMENT TILE ATTACHMENT 1. Scope 1.1 This Protocol covers the testing requirements for tile adhesive applied to Product Control Approved nail-on, mortar set or adhesive set tile systems. 1.2 All testing shall be conducted by an approved testing agency and all test reports shall be signed by an authorized signer of the testing agency and/or Professional Engineer. 2. Referenced Documents 2.1 ASTM Standards C 661 Standard Test Method for Indentation Hardness of Elastomeric-Type Sealants by Means of a Durometer C 1021 Standard Practice for Laboratories Engaged in the Testing of Building Sealants D 95 Standard Test Method for Water in Petroleum Products and Bituminous Materials by Distillation D 412 Standard Test Method for Rubber Properties in Tension D 572 Standard Test Method for Rubber Deterioration by Heat and Oxygen D 897 Standard Test Method for Tensile Properties of Adhesive Bonds D 1079 Standard Definitions of Terms Relating to Roofing, Waterproofing, and Bituminous Materials D 2565 Operating Xenon Arc-type Night Exposure Apparatus With and Without Water for Exposure of Plastics E 380 Excerpts from Standard Practice for Use of the International System of Units (SI) (the Modernized Metric System) 2.2 Application Standards TAS 101 Test Procedure for Static Uplift Resistance of Mortar or Adhesive Set Tile Systems TAS 102 Test Procedure for Static Uplift Resistance of Mechanically Attached, Rigid, Roof Systems 2.3 Roof Consultants Institute Glossary of Terms 3. Terminology and Units 3.1 Definitions - For definitions of terms used in this Protocol, refer to ASTM D 16; and/or ASTM D 1079; and/or Chapter 2 of the Florida Building Code, Building; and/or The RCI Glossary of Terms. Definitions from the Florida Building Code, Building shall take precedence. 3.2 Units - For conversion of U.S. customary units to SI units, refer to ASTM E 380. 4. Significance and Use 4.1 This Protocol Appendix applies only to tile adhesives used in tile systems as a: repair component for mortar or adhesive set tile applications; or, supplement to the attachment in a nail-on tile application. 5. Test Limitations and Precautions 5.1 The Protocol may involve hazardous materials, operations and equipment. This Protocol does not purport to address all of the safety problems associated with its use. It is the responsibility of the user to consult and establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (TAS) 123-95.3

(TAS) No. 123(A)-95 6. Materials and Manufacture 6.1 Tile adhesive used for the purposes of tile repair or supplemental attachment shall consist of a synthetic rubber and resins or such other base component material that will comply with the undernoted performance and physical characteristics. 6.2 Colors shall be tan, terra-cotta, gray or such other color which blends with tile coloring. 7. Sampling 7.1 Sampling shall be in compliance with requirements set forth in ASTM C 1021. Particular reference is made to Subsection 5.2.1 of the procedure. 8. Performance Testing & Requirements 8.1 Composition 8.1.1 Water Content - Tile adhesive shall meet the maximum water volume percentage noted in Table 1, below, when tested in compliance with Section 9 of ASTM D 95. 8.1.2 Nonvolatile Matter - Tile adhesive shall meet the minimum nonvolatile matter mass percentage noted in Table 1, below, when tested in compliance with ASTM D 2369. TABLE 1 TILE ADHESIVE COMPOSITION REQUIREMENTS Component Criteria Value Water Nonvolatile Matter Volume % Mass % Maximum 1.5 % Minimum 65% + 5% 8.2 Uniformity - A thoroughly blended sample of tile adhesive shall show no separation of material after standing for 72 hours at room temperature (73.3 ± 3.6 F) in a closed container. 8.3 Workability - The tile adhesive shall be of such a consistency that it is easily forced from a tube with a 1 / 4 in. diameter hole with a hand held caulk gun at temperatures ranging from 40 F (4 C) to 100 F (38 C). 8.4 Adhesion - Tile adhesive shall meet the minimum adhesion requirements noted in Table 2, below, when tested in compliance with ASTM D 897. TABLE 2 TILE ADHESIVE ADHESION REQUIREMENTS Bonded Component Interface 3000 hour* 72 F (22.2 C) Conditioning 3000 hours 180 F(82.2 C) Concrete to Mortar 65 psi 35 psi Concrete to Concrete 100 psi 143 psi Concrete to Wood 85 psi 70 psi Clay to Clay 128 psi 128 psi Slate to Slate 112 psi 199 psi 8.5 Tensile/Elongation - Tile adhesive shall mee the minimum requirements noted in Table 3 below, when tested in compliance with ASTM D 412. TABLE 3 TILE ADHESIVE TENSILE/ELONGATION REQUIREMENTS Physical Property 3000 hours @ 72 F (22.2 C) Conditioning 1000 hours @ 158 o F (70.0 C) Tensile Strength 1000 psi 1200 psi Elongation 400% 370% Modulus 700 psi N/A 8.6 Static Uplift Resistance - Tile adhesive shall be tested for resistance to static uplift loading in compliance with TAS 102, except as noted below. 8.6.1 Test Specimen The test specimen shall include high profile, concrete "S-shaped" tiles mechanically attached directly to the deck with a single 8d annular ring shank nail. Tile adhesive shall be applied at the 'test tile' headlap in a single 3 / 8 in. wide x l 1 / 4 in. long bead placed between 1 1 / 2 in. and 2 in. from the nose of the 'test tile'. The test specimen shall be conditioned as specified in Section 8 of TAS 101. 8.6.2 Calculations Calculations need not include those for restoring moment due to (TAS) 123-95.4

(TAS) No. 123(A)-95 8.6.3 Requirement gravity or attachment resistance expressed as a moment. The tile attachment, when installed in compliance with Section 8.6.1, shall provide a minimum characteristic resistance load (F') not less than 35 lbf. constitute grounds for rejection of the lots and suspension of the Product Control Approval. In cases of rejection the Code Compliance Officer shall request removal of the rejected lot number(s) from commercial sale. 10.2 The Code Compliance Officer may, after rejection of one or more lots, require third party quality control inspection as a provision to lifting of Approval suspension. 8.7 Shore 'A' Hardness - Tile adhesive shall meet the minimum requirements noted in Table 4, below, when tested in compliance with ASTM C 661. TABLE 4 SHORE 'A' HARDNESS REQUIREMENTS Conditioning Hardness Flexibility Unconditioned 80 ±5 flexible 4 months @ 158 F (70 C) 1000 hours of UV Exposure (ASTM D 2565) 80 + 7 80 ±7 flexible flexible 1000 hours O 2 Bomb @ 158 F (70 C) (ASTM D 572) 80 + 7 flexible 2000 hours O 2 Bomb @ 158 F (70 C) (ASTM D 172) 80 ±7 semi-flexible 9. Packaged Material 9.1 Packaged material shall be certified by the manufacturer to be in compliance with the provisions of this Protocol and shall be labeled in compliance with Section 1517 of the Florida Building Code, Building. Product Control Approval documents shall be provided to the purchaser or end user upon request. 9.2 Shipping containers shall be marked with the name of the material, stock number, lot number, year of issue and quantity therein and the name of the manufacturer or supplier. 10. Rejection and Reinspection 10.1 The Chief Code Compliance Officer may periodically purchase commercial quantities of the Approved product for testing to confirm compliance with the provisions of this Protocol. Failure to meet the minimum requirements set forth in this Protocol shall (TAS) 123-95.5

(TAS) 123-95.6