SECTION HVAC PIPING INSULATION

Similar documents
University of Delaware

Design & Construction Standards, Revised January

HVAC INSULATION. A. General Requirements for Flexible Elastomeric Insulation: 3. Use pre-molded roll on pipe sizes 3.5" and below.

SECTION HVAC INSULATION

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

BuildingName The Description of the Project P DOCUMENTS

University of Houston Master Construction Specifications Insert Project Name

SECTION PIPING INSULATION

SECTION (15081) - HVAC INSULATION

Mechanical Insulation for Refrigeration Systems

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

Insulation for VRF/VRV HVAC Systems. Variable Refrigerant Flow(VRF) and Variable Refrigerant Volume(VRV) System Insulation Needs

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

INSULATION SECTION 15250

SECTION HANGERS AND SUPPORTS FOR PLUMBING

FOAMGLAS INSULATION SPECIFICATION

SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT

Light-Metal Roof Edge, Raised

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

HVAC Piping Insulation- FIBERGLAS Insulation

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

SECTION HVAC DUCTS AND CASINGS

SECTION 07530CP EPDM MEMBRANE ROOFING

Sample Specification

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION THERMAL INSULATION GENERAL THERMAL INSULATION PART RELATED DOCUMENTS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS

PIP INSC1000 Cold Service Insulation Materials and Installation Specification

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION MANUFACTURED ROOF EXPANSION JOINTS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section

Daytona Beach Pier Building Renovation Jun 2010

Recommended Installation and Repair Guide

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

SECTION PRE-ENGINEERED BUILDING INSULATION

GUIDE SPECIFICATION: DUCT LINER

Solving Corrosion Under Insulation Utilizing FOAMGLAS Cellular Glass Insulation Systems

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe

SECTION ROOF SPECIALTIES

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

FlexClad Duct and Pipe Sealing System

EMERGENCY SERVICES CENTER AT SUGAR GROVE, WEST VIRGINIA SECTION THERMAL INSULATION FOR MECHANICAL SYSTEMS 08/10

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems.

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

INSULATION PRODUCTS. Selection Guide & Reference Chart

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

SECTION PLUMBING INSULATION

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

SECTION G RELIEF VENTS A-0

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Techna-Duc. Advantages. Features and Benefits. LEED Eligible Product

High Temperature Fabrics and Blankets for the Insulation Industry

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

PRODUCT SELECTION GUIDE

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

A. Source Limitations: Obtain each type of building insulation through one source.

(Project Location) (your firm's name)

Steel Panel Frame. Exterior Steel Sheeting. Optional Rigid Insulation. Optional Steel Insulation Liner

Daytona Beach Pier Building Renovation Jun 2010

ACOUSTICAL DUCT & PIPE LAGGING INDUSTRIAL NOISE CONTROL PRODUCTS

Metal Roof Panels

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

KS SERIES - VERTICAL INSTALLATION

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION #05-221C 2012

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

Redi-Klad 1000 Pipe Insulation

SPECIFICATION FOR COLD INSULATION

WATERPROOFING TAMKOWATERPROOFING.COM

Updated 6/4/2012. Table Of Contents SECTION PLUMBING INSULATION

SECTION EXPANSION CONTROL

Purdue e-pubs. Purdue University. Weiwei Zhu Oklahoma State University, United States of America,

OptiLiner Banded Liner System, Thermal, Metal Building

Questar ThermWise Duct Technical Specifications

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

Crawl Space Moisture Control

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

Fire Barrier Duct Wrap 615+

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D

Transcription:

SECTION 23 07 19 - HVAC PIPING INSULATION PART I - GENERAL 1.1 SECTION INCLUDES A. Piping and Valve Insulation B. Insulation Jackets C. Insulation Lagging 1.2 RELATED SECTIONS A. Section 23 05 29 Hangers and Supports for HVAC B. Section 23 07 16 HVAC Equipment Insulation C. Section 23 21 13 Hydronic Piping D. Section 23 21 16 Hydronic Specialties E. Section 23 22 13 Steam and Condensate Piping F. Section 23 22 16 Steam and Condensate Specialties 1.3 REFERENCES A. National Commercial and Industrial Insulation Standards Manual, maintained by the Midwest Insulation Contractors Association (MICA) [Note to PSC: Any experienced insulation contractor should be familiar with this manual. It provides a comprehensive guide of installation practices for the mechanical insulation industry. By referencing this standard it becomes unnecessary to identify exhaustive and detailed installation procedures. These standards are to insulation what SMACNA standards are to ductwork.] B. ASHRAE Standard 90.1 Energy Standard for Buildings C. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials D. IECC - International Energy Conservation Code E. Illinois Energy Conservation Code F. IMC - International Mechanical Code 1.4 QUALITY ASSURANCE A. Products and execution shall be in compliance with applicable codes and standards including those referenced above in paragraph entitled REFERENCES. B. Installation shall be in compliance with manufacturer s recommendations and installation instructions. PART 2 - PRODUCTS 2.1 INSULATION A. Type F: Fiberglass, Semi-Rigid Premolded, ASTM C547 Type I B. Type M1: Mineral Wool, Semi-Rigid Premolded, 1,000 deg. F maximum service temperature, ASTM C547 Type IV C. Type M2: Mineral Wool, Semi-Rigid Premolded or Rigid Board, 1,200 deg. F maximum service temperature, ASTM C547 Type II-III U OF I FACILITIES STANDARDS 23 07 19-1 HVAC PIPING INSULATION

D. Type C: Calcium Silicate, Rigid Premolded, 1200 deg. F maximum service temperature, ASTM C533 E. Type E: EPDM Cellular Flexible Elastomeric Foam Tube and Sheet, 300 deg. F maximum service temperature, ASTM C534 Grade 1 1. Not allowed: NBR/PVC blend 2. Approved Products a. Aeroflex Aerocel b. Armacell (a) AP Armaflex FS (b) UT Solaflex [Note to PSC: The University has experienced widespread failure of NBR/PVC blend insulation in recent years. This problem has been addressed by specifying EPDM elastomeric material exclusively in lieu of NBR/PVC blend. NBR/PVC blend is disallowed for all applications including piping, equipment and ductwork. Note to PSC: Aeroflex and Armacell, the primary manufacturers of elastomeric insulation, both offer complete lines of EPDM elastomeric insulation products. However, standard AP Armaflex, given that it is NBR/PVC blend, is not allowed.] F. Type P: Polyisocyanurate, Rigid Premolded, ASTM C591 G. Type PH: Phenolic, Rigid Premolded ASTM C1126 Type III H. Type CG: Cellular Glass, Rigid Premolded, ASTM C552 Type II 2.2 JACKETS, FACTORY APPLIED A. ASJ (All Service Jacket): White, kraft-paper, fiberglass-reinforced scrim with aluminum-foil vapor barrier backing B. PVDC: Polyvinylidene Chloride Film, 60 mil. Basis of design: Saran 560 2.3 JACKETS, FIELD APPLIED A. PVC: Polyvinyl Chloride, cut and curled sheet, 30 mil, solvent welded 1. For protecting or securing insulation only, not for vapor barrier B. PVDC: Polyvinylidene Chloride Film, 60 mil. Basis of design: Saran 560 C. FAC: Fiberglas Fabric with Adhesive Coating: 18 oz./sq. yd. fiberglass fabric, lagging adhesive and coating. Basis of design: Foster 81-42 D. PW: Asphaltic laminate, fiberglass reinforcement with aluminum-foil vapor barrier, 125 mil heat seal. Basis of design: Pittsburgh Corning PITTWRAP 2.4 FITTING COVERS A. PVC, standard duty, factory fabricated, 20 mil, tape secured 1. For protecting or securing insulation only, not for vapor barrier B. PVC, heavy duty, factory fabricated, 30 mil, solvent welded for use with field applied PVC jacket 2.5 LAGGING, FIELD INSTALLED ALUM: Aluminum, 016 thick, stucco embossed finish. Fasten with aluminum or stainless steel bands on 12 centers. 1. For protecting or securing insulation only, not for vapor barrier U OF I FACILITIES STANDARDS 23 07 19-2 HVAC PIPING INSULATION

B. FMAS (Flexible Metallic Adhesive System): Self-adhesive embossed multi-ply aluminum foil sheet, 6.0 mil minimum total thickness. Basis of design: VentureClad 1577CWE [Note to PSC: FMAS appears to be a proven product in the industry. The University now approves it although the jury is still out to some degree. If it proves to be problematic in any manner its approval will be revisited.] 2.6 LAGGING FITTING COVERS A. Aluminum, Factory Fabricated,.024 Thick 2.7 REMOVABLE COVERS, CUSTOM MANUFACTURED A. Standard Applications, Less than 450 Degrees F. 1. Jacket and Liner: 17oz Silicone Impregnated Fiberglass Fabric 2. Insulation: 2 Type E Glass Mat. a. 1 allowed for constructability if approved by PSC 3. Fastening: 2 Nomex Velcro and/or Lace Hooks with Stainless Steel Wire 4. Thread: Kevlar/Stainless Steel Thread B. Acoustical Applications, Less than 450 Degrees F. 1. Jacket: 17oz Silicone Impregnated Fiberglass Fabric 2. Liner: 17oz Teflon Impregnated Fiberglass Fabric 3. Insulation: 2 Type E Glass Mat. 4. Fastening: 2 Nomex Velcro or Lace Hooks with Stainless Steel Wire 5. Thread: Kevlar/Stainless Steel Thread 6. 2 lb. mass loaded vinyl C. Provide where shown on drawings or otherwise indicated. [Note to PSC: Clearly indicate location and type of custom covers on drawings and/or elsewhere within documents. Use sparingly; custom covers are costly and typically have long lead times.] 2.8 TAPES, ADHESIVES, COATINGS, FASTENERS A. Provide in accordance with insulation manufacturer s specifications and requirements. B. Sheet metal screws installed outdoors shall be stainless steel with rubber washers. Galvanized screws shall not be used outdoors. 2.9 MATERIAL PROPERTIES A. Insulation material shall satisfy material property requirements of referenced ASTM standards. For convenient summary of referenced ASTM standards see Insulation Specification Materials Guide as presented by National Commercial and Industrial Insulation Association (NIA). B. All insulation materials including jackets, tapes, adhesives and coatings shall meet ASTM E84 25/50 Flame Spread/Smoke Development requirements. C. Piping insulation located in ventilation air plenums shall be UL listed for application. PART 3 - EXECUTION 3.1 INSTALLATION A. General Requirements. 1. Install insulation after piping has been inspected and tested unless otherwise authorized by Engineer. Piping shall be clean, dry and free of rust. U OF I FACILITIES STANDARDS 23 07 19-3 HVAC PIPING INSULATION

2. Insulate all piping systems conveying fluids with temperature above 105 deg. F, below 60 deg. F or below dew point of ambient air. When fluid is below 60 deg. F or below dew point of ambient air insulation shall have uninterrupted vapor barrier. 3. Insulate all components of piping systems for both cold and hot applications. This includes fittings, unions, flanges, strainers, expansion joints and specialties. This includes valve bodies, bonnets, control valves and pressure regulating valves. The common practice of leaving valves, unions, flanges and strainers uninsulated in hot piping systems is not allowed. a. Exceptions: Steam traps, steam condensate pump bodies, coil headers, HW coil packs, control valves and balance valves at small terminal heating units (e.g. reheat coils, fin tube,) CHW components above drain pans (e.g. fan coil units), instrumentation and associated piping beyond 24 from main. Other appropriate exceptions may be presented to PSC for approval prior to proceeding with work. 4. Do not apply insulation on cold active piping systems, vulnerable to condensation. 5. Do not allow insulation to remain unsealed, vulnerable to entrance of moisture. 6. Provide continuity of insulation and vapor barrier through penetrations unless code prohibits. Ensure openings at penetrations, including roofs and exterior walls, adequate in size to accommodate such continuity. 7. Provide continuity of insulation and vapor barrier through hangers and at supports. 8. Do not use staples or screws to fasten insulation on chilled water or other cold piping. 9. Insulate valves in manner that allows full operation without damaging or compromising insulation or vapor barrier. 10. Install metal shields at all hangers and supports. Shields shall be galvanized sheet metal, half round with flared edges. Length and thickness gauge shall be as follows: Pipe Size Shield Size 2 and smaller 12" long x 20 gauge 2 ½ to 6 12" long x 18 gauge 8 to 14 18 long x 16 gauge 16 to 24" 24" long x 14 gauge [Note to PSC: The University takes exception to MSS Standards as applied to insulation shields. Such requirements are viewed to be excessive.] 11. Provide high compressive strength inserts or welded steel shoes at hangers and supports to prevent compression of insulation. Inserts shall be same thickness as insulation. Inserts shall be 180 degree minimum cylindrical segments same length as associated metal shield. Rectangular blocks, plugs, or wood material not acceptable unless approved by PSC for specific application. Inserts and associated jacketing shall be as follows: a. Chilled water applications (1) < 4 Pipe, metallic and non-metallic (a) Phenolic (2.5 lb./sf) or cellular glass (b) 6 mil PVDC jacket (e.g. Saran 560) U OF I FACILITIES STANDARDS 23 07 19-4 HVAC PIPING INSULATION

(2) > 6 Pipe, metallic and non-metallic (a) Phenolic (5.0 lb./sf) or cellular glass (b) 6 mil. PVDC jacket (e.g. Saran 560) b. Hot water applications (1) < 4 Pipe, metallic and non-metallic (a) Phenolic (2.5 lb./sf) or calcium silicate (b) ASJ or 6 mil. PVDC jacket (e.g. Saran 560) (2) > 6 Pipe, metallic (a) Welded shoe with insulation fill (See Section 23 05 29 Hangers and Supports for HVAC) (b) ASJ jacket (3) > 6 Pipe, non-metallic (e.g. polypropylene) (a) Phenolic (5.0 lb./sf) or cellular glass c. Steam applications 6 mil. PVDC jacket (e.g. Saran 560) (1) < 4 Pipe, metallic (a) Calcium silicate (b) ASJ jacket (2) > 6 Pipe, metallic (a) Welded shoe with insulation fill (See Section 23 05 29 Hangers and Supports for HVAC) (b) ASJ jacket 12. Provide high compressive strength inserts at strut-mount pipe clamps to prevent compression of insulation. Inserts shall be phenolic or calcium silicate as appropriate for application. Inserts shall be same thickness as insulation. Insert shall be 360 degree cylindrical segment extending beyond pipe clamp on each side. 180 degree cylindrical shields shall be provided. Cush-clamps (e.g. Unistrut Cush-a-Clamp) not allowed unless approved by PSC for specific application. In no case shall such be used on cold piping applications. 13. As an alternate to specified support system for strut-mount pipe clamps Aeroflex Aerofix-U polymeric inserts with integral vapor barrier may be used. Such applies to strut-mount clamps only. 14. As an alternate to specified support system, Hydra-Zorb Klo-Shure insulation coupling may be used. Insulation shall be adhered within coupling to maintain vapor barrier. 15. Ensure piping is supported by specified inserts only. Piping shall not be in direct contact with metallic hangers/supports. Exception: Welded shoe pipe supports on hot piping applications. 16. Provide heavy duty protective lagging on insulated piping extending to or through floors or curbs. Lagging shall be.032 thick aluminum sheet, mechanically secured. Extend minimum 12 above floor/curb. 17. Provide protective 30 mil solvent-welded PVC jacket on exposed interior horizontal piping below 2 AFF level and exposed vertical piping below 8 AFF level. Also provide 30 mil solvent-welded PVC jacket on any horizontal piping above 2 AFF that is U OF I FACILITIES STANDARDS 23 07 19-5 HVAC PIPING INSULATION

vulnerable to damage by climbing or stepping as determined by PSC. Example: Branch run-outs to coils. a. Exception: In cases where temperature rating of PVC jacket is deemed inadequate for high temperature application,.024 thick aluminum lagging with safety break shall be provided. B. Specific Requirements for Insulation Type 1. Type F: Fiberglass, Semi-Rigid Premolded a. Insulate fittings with field or factory cut fiberglass inserts, multiple inserts may be required. Install PVC fitting covers over insulation. Fasten fitting covers to pipe jacket with PVC tape, both ends. Tacks or staples not allowed. 2. Type M1: Mineral Wool, Semi-Rigid Premolded a. Insulate fittings with field or factory cut fiberglass inserts, multiple inserts may be required. Install 20 mil PVC fitting covers over insulation. Fasten fitting covers to pipe jacket with PVC tape, both ends. Tacks or staples not allowed. 3. Type M2: Mineral Wool, Semi-Rigid Premolded a. Insulate fittings with like material, factory or field fabricated. Flexible inserts not allowed. Install aluminum lagging. 4. Type CS: Calcium Silicate; Rigid Premolded a. Attach with 18 gage SS tie wires on 12 centers b. Use single layer for less than 3 thick. For thickness 3 and greater, use two layers, stagger jointed. Wire each layer individually. c. Install lagging as indicated in Application Schedule below. 5. Type E: EPDM Elastomeric Foam, Flexible Tube and Sheet a. Fully adhere insulation to pipe at joints and terminations to prevent moisture transfer along pipe. Adhere around entire circumference of pipe. b. Form fit and fully adhere insulation at valves, strainers, specialties, instrumentation and appurtenances. Fully adhere insulation at all points vulnerable to ingress of moisture. 6. Type P: Polyisocyanurate, Rigid Premolded a. Use fittings of like material, factory or field fabricated. b. Place vapor barrier over fitting; install finished fitting cover (i.e. tape fitting before installing cover). c. Fill any voids in insulation that result from custom fit-up. d. Seal all openings in Saran vapor barrier with approved mastic. 7. Type PH: Phenolic, Rigid Premolded. a. Use fittings of like material, factory or field fabricated. b. Place vapor barrier over fitting; install finished fitting cover (i.e. tape fitting before installing cover). c. Fill any voids in insulation that result from custom fit-up. d. Seal all openings in Saran vapor barrier with approved mastic. 8. Type CG: Cellular Glass, Rigid Premolded. a. Install above ground CG insulation with ASJ jacket and vapor barrier mastic. U OF I FACILITIES STANDARDS 23 07 19-6 HVAC PIPING INSULATION

b. Install buried CG insulation with PW jacket per manufacturer s instructions to maintain warranty. Install to adequately accommodate pipe movement. Provide joint sealant (e.g. Pittsburgh Corning PITTCOTE) at joints, changes in insulation thickness and terminations. C. Additional Requirements for Outdoor Installations 1. Ensure insulation jacket is sealed waterproof, vapor tight. 2. Provide tightly fitted metal lagging with overlapped sections properly oriented for prevailing weather. 3. Mechanically attach lagging sections with aluminum or stainless steel bands, 12 on center. Minimize use of screws. Seal all seams and penetrations watertight. 4. With approval of PSC: In lieu of metal lagging provide FMAS flexible metallic adhesive system (specification provided above) with factory fabricated aluminum fitting covers. Apply pressure to FMAS with spreading tool to ensure maximum adherence. [Note to PSC: Edit text above as required to ensure clarity of lagging requirements. If metal lagging is required delete references to FMAS or vice-versa. Or, allow FMAS as an approved option as stated/indicated. Discuss with Owner prior to finalizing design.] 3.2 APPLICATION SCHEDULE [Note to PSC: Edit Schedules as appropriate for project.] Application Insulation Thickness Ref.# (see Thickness Schedule) Jacket, Covering Lagging Steam, Condensate and Pumped Condensate in Walk-through Tunnel M2 (1) Steam (2) Cond. ASJ ALUM Insulation to Match Existing in Walk-through Tunnel CS (1) Steam (2) Cond. FAC None Steam Expansion Joint - Provide custom manufactured removable cover Steam, Condensate and Pumped Condensate in Shallow Trench Tunnel Per Spec. Integral Integral None M2 (1) Steam (2) Cond. None ALUM Steam, Condensate and Pumped Condensate in Building F or M1 (1) Steam (2) Cond. ASJ None* Steam Vent Above 8 AFF level None NA NA NA Steam Vent Below 8 AFF level (for burn protection) F or M1 1 All Pipe Sizes ASJ None* Perimeter, Preheat, Reheat Water > 140F F or M1 (3) ASJ None* U OF I FACILITIES STANDARDS 23 07 19-7 HVAC PIPING INSULATION

Perimeter, Preheat, Reheat Water < 140F F or M1 (4) ASJ None* Chilled Water E or PH (6) E: None PH: PVDC None* Chilled Beam E (6) None None* Cooling Coil Condensate Drain E (7) None None* Piping with Temperature 60F 105F (e.g. Chilled Beam, Condenser Water) None NA NA NA Piping with Temperature 0-40F (e.g. Refrigerant for Walk-In Cooler/Freezer) E or PH (8) E: None PH: PVDC None* Chilled Water, Buried (Ductile Iron) None NA NA NA Other Buried Piping, Not Preinsulated CG (1) PW None Cold Piping Outdoors, Above Ground Option 1 Cold Piping Outdoors, Above Ground Option 2 Hot Piping Outdoors, Above Ground Option 1 Hot Piping Outdoors, Above Ground Option 2 P or E (6) E: None P: PVDC CG (6) ASJ M1 (2) ASJ CG (2) ASJ * Provide lagging in areas specified for protection from physical damage. ALUM or FMAS ALUM or FMAS* ALUM or FMAS* ALUM or FMAS* [Note to PSC: Where multiple options are indicated for insulation type, thickness, jacket and/or lagging type, edit as appropriate for project. CG is preferred for outdoor piping above ground if economically viable.] [Note to PSC: Edit Schedule as required to ensure clarity of lagging requirements. If metal lagging is required delete references to FMAS or vice-versa. Or, allow FMAS as an approved option as stated/indicated.] U OF I FACILITIES STANDARDS 23 07 19-8 HVAC PIPING INSULATION

3.3 THICKNESS SCHEDULE Application Schedule Reference# Temp Reference 3/4 & Smaller Minimum Insulation Thickness for Pipe Size 1-1 ¼ 1 ½ - 2 2 1/2-3 4-6 8 & Larger (1) 250-350F 3.5 4.0 4.5 4.5 4.5 4.5 (2) 200-250F 2.5 2.5 3.0 3.0 3.0 3.0 (3) 140-200F 1.5 1.5 2.0 2.0 2.0 2.0 (4) 105-140F 1.0 1.0 1.5 1.5 1.5 1.5 (5) 60-105F NA NA NA NA NA NA (6) 40-60F 1.0 1.0 1.5 1.5 1.5 2.0 (7) 40-60F 0.5 0.5 0.5 0.5 0.5 0.5 (8) <40F 1.0 1.0 1.5 1.5 1.5 2.0 [Note to PSC: For several pipe sizes thickness schedule indicates required minimum thickness in excess of that required by ASHRAE Standard 90.1] [Note to PSC: Thicknesses indicated in schedule are minimum values. Use Manufacture s thickness calculation tool to determine required insulation thickness for project-specific temperature and humidity conditions. Increase scheduled insulation thickness as required.] [Note to PSC: ASHRAE Standard 90.1 applies to building systems only. Insulation thickness may be reduced within steam tunnels to accommodate dimensional limitations as required. Edit thickness schedule accordingly.] Notes: 1. Manufacture s thickness guide or calculation shall be used to determine required minimum insulation thickness for ambient temperature and humidity conditions. Applied insulation thickness shall meet or exceed this value. Thickness may exceed scheduled value. Discuss with PSC prior to bidding. [Note to PSC: Perform required calculations, edit schedule accordingly and delete this note. Note is provided for projects with no PSC.] 2. Insulation thickness and R value shall satisfy ASHRAE Standard 90.1 at a minimum. 3. For repairs, insulation thickness shall match existing. END OF SECTION 23 07 19 This section of the U of I Facilities Standards establishes minimum requirements only. It should not be used as a complete specification. U OF I FACILITIES STANDARDS 23 07 19-9 HVAC PIPING INSULATION