Valance Installation. For Units with Beam Style Coils

Similar documents
Liner Replacement Instructions:

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

Design & Construction Standards, Revised January

BUILD A SHOWER CUBICLE

6032 SH 3P Residential Shower Installation Instructions Gelcoat & Solid Surface Bathware

SECTION 07530CP EPDM MEMBRANE ROOFING

STEP UP SHOWER BASE INSTALLATION GUIDE FOR TIMBER AND CONCRETE FLOORS

Light-Metal Roof Edge, Raised

Installation Instructions

OmniFlex 300 Plus Installation Instructions

FreeStyle Linear Drain with Full Mortar Bed Adapter Kit

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

Chapter 7. Roof Framing

Assembly Instruction. wedi Fundo Primo Shower System

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

1 PVC or ABS drain with strainer

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu

Installation Instructions

Canopy Assembly Instructions: Post-Supported Super Lumideck (2 3/4" Interlocking deck, 6" Fascia)

Reflective Insulation Specification & Application Guide for Post Frame and Metal Building Construction

INSTRUCTIONS AND GUIDELINES

SECTION HVAC PIPING INSULATION

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

ROOF MOUNT KIT OWNERS MANUAL

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

Conergy SolarFamulus II

YCW 250 I-Beam Curtain Wall System Installation Manual

1.2 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section Submittal Procedures.

SECTION ACOUSTICAL PANEL CEILINGS

Introduction. Before You Begin

Assembly Instruction. wedi Fundo Primo Steam Shower System

SECTION ROOF SPECIALTIES

Fire Barrier Duct Wrap 615+

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

SpaVault TM Installation Guide for Bullfrog Spas (7-10 x 7-10 x 38 )

CEILING & WALL SYSTEMS

SECTION HVAC INSULATION

FIREPLACE INSERT ENCLOSURE INSTALLATION INSTRUCTIONS

Weep Valves Stucco Wire Mesh Reinforcement Weather Resistive Barrier Sheathing Insulation Framing

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

SECTION HVAC DUCTS AND CASINGS

SECTION PIPING INSULATION

SECTION (15081) - HVAC INSULATION

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD ASSEMBLIES

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PATENTS ARE PENDING. Building Dimensions. Exterior Dimensions Roof Edge to Roof Edge

SECTION I -- IRONWORK

SECTION COLD-FORMED METAL FRAMING

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

BioPrism Solid Surface

Assembly Instruction wedi Fundo Floor element

FastWrap+ 1 1 /2 Commercial Kitchen Grease Duct Air Ventilation Duct

RS32 Multi-Section Skylight System under/over seam clip double diverter

ZS880 Linear Shower Drain Installation Instructions

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

N Scale Double Track Lift Bridge v1.2

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS

aquapanel InstallatIon GuIde

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

Freedom One-Piece Barrier Free Showers Installation Instructions

SECTION OUTLET, PULL, AND JUNCTION BOXES

Vertigo Cladding Board

Kingspan Day-Lite Klick

SECTION PLUMBING PIPING SYSTEMS

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Modular Buildings. Installation Manual

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

MODULAR ACOUSTIC FENCING INSTALLATION GUIDE

TILE ROOF INSTALLATION MANUAL ADDENDUM

SECTION TURBINE VENTILATORS

1. Interior gypsum wallboard. 2. Exterior gypsum board panels for ceilings and soffits. 3. Tile backing panels.

PLYWOOD FLOATING FLOOR

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

Pittsburgh Corning ProVantage Glass Block Installation System Assembly Instructions

When I started tiling, we didn t do our own shower pans that BATHS

QuietRock 530 RF Application Notes

Se incluyen las instrucciones en español

INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems)

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

HydroCycle Commercial NFT Systems

Gas Fireplaces. P36D-10 Gas Fireplace. Unit Dimensions With Vignette Faceplate. *** Important: Framing height requires consideration of the hearth

SECTION SLUICE GATES

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD


Double Containment DESIGN & INSTALLATION GUIDE TECHNICAL INFORMATION. Visit our web site

Pre-Fabricated Roof Curbs

Examples of Installation Method

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION NON-STRUCTURAL METAL FRAMING

Air flue duct for use with ecotec boilers

Transcription:

Valance Installation For Units with Beam Style Coils 1. Before installation of valance units, determine if drapes are to be used, or if any wall construction will protrude into room. If either drapes or wall protrusion are planned, locate the wall mounting brackets away from the outside wall by the distance planned. Note that wall mounting brackets may be either surface mounting models or stud mounting models. The dimension C (Fig.1) is a minimum to insure adequate space for air movement. Do not reduce C. Figure 1 2. If no obstruction exists, locate the stud mounted wall mounting brackets flush against the wall and ceiling. Refer to Fig.2 and note that the wall brackets are left or right hand. Fasten each wall bracket securely to the building studs (BEFORE SHEETROCK OR WALLBOARD IS INSTALLED) with nails, screws, or cement block rivets. Cut out sheetrock or wallboard to expose opening for coil connections and coil support channels. NOTE: Alternate surface mounting wall brackets are required for use on walls where brackets are to be mounted on the surface.

Figure 2 A. Surface mounted wall brackets are required for use on walls where bracket will be mounted on the surface. These brackets should be mounted flush against the ceiling line and meet the distance listed below from the finished wall, drapes or nearest obstruction depending upon the rows of coil. This distance is as follows: 2 Row 4-1/2" 5 Row 8-5/16" 3 Row 6-7/16" 6 Row 10-11/16" 4 Row 7-1/2" 8 Row 14-3/8" Drawings for bracket installation are available from the factory upon request.

3. Coil lengths over 13 feet {For 8 - row coil, use 10 feet) require an intermediate ceiling support (Fig. 3) in addition to the two wall brackets. Fasten the ceiling support to the ceiling with screws, hollow-wall anchors, or cement anchors along a chalk line located on the centerline (Fig. 3) of the coil supports on the two wall brackets. For junior joist construction, use clamps as required to secure the intermediate supports. Alternate "airplane" hangers also are available for special installations requiring support from a parallel wall. Figure 3 4. Locate supply and return mains under wall brackets in accordance with piping layout. At least one inch clearance should be maintained between the enclosure insulation and the supply and return mains (including pipe insulation if used). This minimum clearance is necessary to allow correct tight fitting at the wall of the turned-up edges of the enclosure insulation (Fig. 1 & 10). 5. Locate drain hole for condensate line in accordance with the piping layout or by using the fixed drain hole locator (Fig. 2} on the wall bracket, if so supplied. 6. Drill correctly sized holes thru walls for supply and return mains and drain fittings, using piping layout as a reference and table listing shown in Fig 4.

Figure 4 7. Sweat in supply and return mains. NOTE: Supply and return mains within valance enclosure are to be made of rust-proof tubing such as copper. Steel pipe should not be used. 8. Insulate the supply and return mains where they pass thru the wall with 1-2" minimum Armaflex or closed cell polyethylene (extended 6" into the room). Use half-round wall sleeves where necessary to pass thru partitions. Seal both ends of the Armaflex or polyethylene with several layers of electrician's plastic tape or other acceptable material so as to form a drip bead at the edge (Fig. 5). In this way condensate will drip off the bead rather than travel back along the insulation into the partition wall. Figure 5

9. Mount the ceiling baffle (bent lip pointing away from coil assembly) to aluminum bolts on valance coil unit assembly BEFORE mounting the coil assembly on the wall brackets. 10. Install valance coil unit assembly beam channels into the wall bracket support channels (Fig.6). Avoid damaging room walls by tilting coil assembly so that first one end is engaged into bracket supports prior to raising the other end. Inspect channel cross braces to make certain they do not interfere with the coil fins during expansion and contraction of the coil. Figure 6 11. After sweating in supply and return lines, install Edwards solid-state motorized zone valve. Part No. MV81SS; the installation may be in positions other than vertical. If Edwards mercury switch motorized zone valve. Part No. MV81, is installed, the valve should be vertical or inclined at no more than 40 from the vertical position. Edwards rotary switch zone valve (manufacturing discontinued) may be installed in positions other than vertical. All of the above zone valves should avoid positions or installation where water may leak into the electrical assembly. 12. Sweat in copper fittings and tubing for zone valve (two valves on Dual-a-matic) and connect to the SUPPLY main.

13. Adjust ceiling baffle (Fig. 6) to touch the ceiling uniformly thru the entire length by loosening and retightening the baffle holding wing nuts. Slide baffle wall trim against wall on each baffle end. Plastic foam tape is installed on top edge of the baffle to block light passage (Fig. 7). Figure 7 14. Swing rear enclosure support hooks (Fig. 6) on coil unit into vertical position and tighten wing nuts temporarily. 15. If drain hole in streamline enclosure design is not furnished by factory, drill VA" hole thru enclosure and insulation at drain end (may be either end of enclosure). If an interior drain assembly is furnished with the enclosure, the hole will not be necessary; see Fig. 7 for interior drain position. Install drain elbow fitting being careful not to strip plastic threads. Use plumbers putty or silicone construction sealant to seal between underside of drain fitting flange and enclosure lining. Enclosures 20 ft. or longer must be drained at more than one location; Chart 7A Enclosure Length No. of Drains 1-20 1 21-40 2 41-60 3 61-80 4 81-100 5 101-120 6 121-140 7

16. Lift valance condensate enclosure into position to engage upper front edge of enclosure with upper edge of coil beam (Fig. 8). 17. Lift rear edge of enclosure to engage rear support hooks (Fig. 8). Figure 8 18. Note for STREAMLINE ENCLOSURE design: Adjust rear support hooks to give sufficient pitch (1/4" per 10 feet minimum) to drain enclosure for positive condensate drainage thru drain fitting and tubing. Check pitch with a level and remove any sags or bumps to give a straight run to the drain. 19. Note for SQUARE ENCLOSURE design: Adjust rear support hooks to obtain level outer enclosure location; inner enclosure is automatically adjusted for drainage. 20. Connect one end of the rubber drain hose to the enclosure drain fitting and the other end to the drain or discharge pipe (Fig. 9). Note: If optional drain hole locator is part of wall bracket, position drain hose connection accordingly. Avoid kinks in the rubber hose. If the drain hole locator is not used, or if the drain connection is to be made at the back wall, the centerline of the drain hose passage thru the wall must be at least 1" lower than the drain fitting centerline in order to obtain positive drainage of condensate. Avoid kinks in the rubber hose.

Figure 9 21. Note that each enclosure is supplied with 4" minimum additional insulating liner at each end of the enclosure. DO NOT TRIM AND DISCARD THIS EXCESS MATERIAL. After enclosure is mounted in place, push the flap of insulation up against each wall to provide a sealed condensate liner. See instruction No. 25a for insulation splicing procedure if necessary. 22. Slide wall trim strips (Fig. 8) to each end of the enclosure and adjust for final appearance. It is not necessary to use screws to fasten wall trim. If desired, to achieve final wall trim fit to enclosure, use Double-Coat Tape, 1/32" x 1" as manufactured by (or equal) Duraco, Inc., 1025 West North Ave., Chicago, IL 60622, ph. (312) 943-2700. 23. IMPORTANT: Care must be taken not to puncture the waterproof surface of the insulating inner within the valance condensate enclosure.

24. FOR VALANCE ENCLOSURE LENGTHS LONGER THAN 16 FEET To provide continuous insulation in adjoining enclosures longer than 16 feet, insulation is supplied in roll form. At the time of installation, with the adjoining enclosures in place, unroll the insulation within the enclosures. Push the insulation tightly up into the enclosure front lip. Coat lowermost portion of the enclosure with contact glue (3M Company, No. 35 insulation adhesive or equal available through factory) and then shape the insulation to lie flat and to engage the lip at the rear edge of the enclosure. Allow excess material (approx. 4") at each end of the valance enclosure to turn up against the wall or end cap (See instruction No. 1 5 for drain fitting installation). See instruction No. 25a for insulation splicing procedure, if necessary. 25. The valance insulation (closed cell, cross-linked, polyethylene with a UL94 flame class of 94HF-1 or closed cell, type 300M Softlite ionomer foam meeting Federal Specification EMV SS-302) is self-extinguishing plastic foam (tested for flammability using standard ASTM-D 1692-68) and is heat sealable. If splicing or repairing is required, aluminum foil tape and a flameless heat gun or soldering iron is recommended for joining. An acceptable aluminum foil tape is Type P-11 manufactured by Permacel, US Hwy. No. 1, New Brunswick, N.J. 08903. An acceptable heat tool is Model HG501A manufactured by Master Appliance Corp., Racine, Wl 53403, ph. (414)-633-7791. A. To join two sections of insulation for watertight performance, cut the two butt edges straight and place both butt ends together. Place the adhesive aluminum foil tape over the seam with an equal amount of tape on each side of the joint. Press the tape firmly into place making sure that the butt ends of the insulation do not separate. If a heat tool is used, direct the hot air along the edges of the tape until the material is observed to shrink. When cooled, this taped construction will produce a watertight joint. CAUTION: Since the temperature of the heat tool is 500 to 750ºF (14 amps, 120 volts), use protective gloves. B. If a soldering iron is used, place the fiat surface of the tip of the iron on the tape edge next to the insulation, and slowly move the iron along this edge. Care must be taken to avoid touching the insulation surface directly with the hot iron tip. Repeat on the other tape edge. 26. If inside corners are to be used, note that all channel for the inside corner is pre-cut. The inside beam is shorter than the outside beam. Two L brackets are provided for each inside corner with holes pre-drilled. Mount the valance assembly following instructions No. 9 and 10. Also follow instruction No. 3 to install intermediate ceiling supports near the inside corner. Bolt the "L" brackets to the inside and outside of the aluminum beams to form a corner. A. After all piping connections are made, install the prefabricated decorative inside corner onto the channel, butting the pan to the inside corner. Install splicer pieces at each corner seam. Insulate corner, following instruction No.24. Use the same procedure for installing an inside corner.

Figure 10