A NEW ALGORITHM FOR SENSORS VERIFICATION AND CORRECTION IN AIR HANDLING UNITS

Similar documents
Whole Building Energy Performance Evaluation through. Similar Control Strategies

MODELING AND VALIDATION OF EXISTING VAV SYSTEM COMPONENTS

Canada Published online: 28 Feb 2011.

Building Energy Modeling Using Artificial Neural Networks

formulating the diagnostics differs fundamentally. First-principle model-based approach use a priori knowledge to specify a model that serves as the b

CASE STUDIES ON HVAC SYSTEM PERFORMANCE USING A WHOLE BUILDING SIMULATION BASED REAL-TIME ENERGY EVALUATION APPROACH WITH BEMS

A Case Study in Energy Modeling of an Energy Efficient Building with Gas Driven Absorption Heat Pump System in equest

Use of MathCad and Excel to Enhance the Study of Psychrometric Processes for Buildings in an Air Conditioning Course

BUILDING ZONE FAULT DETECTION WITH KALMAN FILTER BASED METHODS

EVALUATION OF BUILDING ENERGY CONSUMPTION BASED ON FUZZY LOGIC AND NEURAL NETWORKS APPLICATIONS

Model Based Building Chilled Water Loop Delta-T Fault Diagnosis

Validation of Numerical Modeling of Air Infiltration through Building Entrance Doors

I. Khoo, BEng(Hons), G.J. Levermore, BSc, ARCS, PhD, DIC, CEng, FCIBSE, MASHRAE, MInstE, K.M. Letherman, BSc, MSc, PhD, CEng, FIEE, FCIBSE.

Persistence Tracking in a Retro-commissioning Program

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

Energy modeling in IDA ICE according to ASHRAE , app. G

AHU Models Using Whole Building Cooling and Heating Energy Consumption Data

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Leveraging Smart Meter Data & Expanding Services BY ELLEN FRANCONI, PH.D., BEMP, MEMBER ASHRAE; DAVID JUMP, PH.D., P.E.

Ceiling Radiant Cooling Panels

Commissioning for Energy Savings

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based

Principles of Ventilation and Air Conditioning Design & Installation

Verification of Chiller Performance Promotion and Energy Saving

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader

Facilities Management System That Reduces Environmental Burden of Buildings

UNDERSTANDING MANUFACTURING ENERGY USE THROUGH STATISTICAL ANALYSIS

Pressure Independent Valve Systems. ASHRAE Seminar College of the North Atlantic, Doha, Qatar 20 th April 2013

Chilled Water System Optimization

Unitary Air Conditioner Field Performance

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Underf loor For Schools

Energy Saving Calculations for Recommissioning and Design

Reducing Operating Costs with Optimal Maintenance Scheduling

Challenges in Design and Optimization of Large Scale Energy Efficient Systems

Technical Retro-Commissioning of Existing Buildings

OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS

Universal Translator 3: A free software tool to support your data processing needs

COMPUTER MODEL OF A UNIVERSITY BUILDING USING THE ENERGYPLUS PROGRAM

COUPLING STRATEGY OF HVAC SYSTEM SIMULATION AND CFD PART 2: STUDY ON MIXING ENERGY LOSS IN AN AIR-CONDITIONED ROOM

CASE STUDIES IN USING WHOLE BUILDING INTERVAL DATA TO DETERMINE ANNUALIZED ELECTRICAL SAVINGS

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom

How LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc.

Sensitivity of energy and exergy performances of heating and cooling systems to auxiliary components

DISPLACEMENT VENTILATION

Mechanical-Electrical Technology MECHANICAL-ELECTRICAL TECHNOLOGY Sacramento City College Catalog

Optimization of Building Energy Management Systems

Building Automation Systems

Model Predictive Control of Once Through Steam Generator Steam Quality

Optimizing Buildings Using Analytics and Engineering Expertise

Asset Energy Calculator Guidance

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Development of New Self-Comparison Test Suites for EnergyPlus

RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT. Adam Renzi, PE

Air Quality Sensors in Buildings and HVAC systems

Doubling Down on Not Balancing Variable Flow Hydronic Systems BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure

Sub Wet-Bulb Evaporative Chiller

2016 ASHRAE 90.1 Summary of Important Changes

Intelligent Process Cooling Technology Saves on Water and Energy, Improves Productivity

E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings

Application of a cooling tower model for optimizing energy use

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2

Residential HVAC Field Verification and Diagnostics

Variable Frequency Drives

Recommissioning Energy Savings Persistence

A systematic approach of integrated building control for optimization of energy and cost

Study on the heat transfer characteristics of an evaporative cooling tower B

Performance Testing of Cold Climate Air Source Heat Pumps

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

CHILLED WATER SYSTEM OPTIMIZER

Measuring Up. Tools for High Performance Building Performance. RESNET 2008 San Diego, CA February 20, 2008 Bill Spohn. Bill Spohn, testo, inc.

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

Advanced Rooftop Controllers Field Validated HVAC Energy Savings & More

Energy Efficient Control of Fans in Ventilation Systems

Heat Rejection using Cooling Towers

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency

Application of Advanced Energy Technologies

Performance Efficiency Standard for Evaporative Cooling Equipment

George Bourassa, National Director, Commissioning Services Robert Bucey, Program Manager RETRO-COMMISSIONING

AN INVERSE MODEL TO PREDICT AND EVALUATE THE ENERGY PERFORMANCE OF LARGE COMMERCIAL AND INSTITUTIONAL BUILDINGS

5/7/2012. Agenda. What is High Performance? Ensuring a Successful Transition to Sustainable, High-Performance Operations

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training

Assessment of Climate Change Robustness of a Deep Energy Retrofit Design of an Existing Day Care Centre

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

HEATING LOAD PREDICTIONS USING THE STATIC NEURAL NETWORKS METHOD. S.Sholahudin 1, Hwataik Han 2*

Disaggregation and Future Prediction of Monthly Residential Building Energy Use Data Using Localized Weather Data Network

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Small Building Tune-up Pilot Program. Kevin Afflerbaugh, LEED AP Jim Zarske, PE, CEM, LEED AP Nexant, Inc.

Critical exergy analysis of counterflow reversibly used cooling towers

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING

High Technology Energy Savings Guide

Retro-Commissioning in Hospitals

Transcription:

A NEW ALGORITHM FOR SENSORS VERIFICATION AND CORRECTION IN AIR HANDLING UNITS Nunzio Cotrufo, Radu Zmeureanu Department of Building, Civil and Environmental Engineering Concordia University Montréal Quebec, Canada ABSTRACT The use of trend data from Building Automation Systems (BAS) is a cost-effective strategy for ongoing commissioning in HVAC systems. Quality of measurements, thus, is essential for the effectiveness of commissioning process. This paper presents an approach to verify, and correct if necessary, the outdoor air temperature and relative humidity measurements in an AHU economizer. The proposed iterative algorithm solves an optimization problem that maximizes the goodness of fit, in terms of coefficient of variation, CV- RMSE, between a directly measured variable, and its value derived from an air energy balance. This approach has been verified with data from an institutional building in Montréal, proving its capability to highlight errors in the measurements of outdoor air relative humidity and temperature. Corrected values have been finally validated through comparison against spot measurements with calibrated sensors. INTRODUCTION The implementation of ongoing commissioning for HVAC systems is a cost-effective strategy to overcome the rise of faults and decrease in energy performance over the entire building systems life cycle (Roth K. et al., 2008). Faults and degradation can affect both equipment and sensors, causing decrease in equipment performance, energy wastes and occupancy discomfort. This paper focuses on faulty sensors detection in Air Handling Units (AHU), and presents a new algorithm to automatically adjust the measured air temperature and humidity. Faults in sensors may be often considered as soft failures, and thus they may produce small persistent waste of energy and/or discomfort for occupant, and remaining unrevealed for a long time (Haves P., 1999). Although numerous methods and algorithms for HVAC Automatic Fault Detection and Diagnosis (AFDD) have been developed during the last decades (Breuker M. S. and J. E. Braun, 1998, Jia Y. and T. A. Reddy, 2003, Cui J. and S. Wang, 2005), the same attention has not been given to self-correction algorithms, making the human intervention in commissioning strategies still crucial (Padilla M. et al., 2015). Four different types of faults are identified in sensors: bias faults, drift faults, complete failures and precision degradation (Chen Y. and L. Lan, 2010). Adding self-correction algorithms to systems control codes allows to minimize fault effects until the human action fix the fault (Fernandez N. et al., 2009). Self-correction algorithms could consist of virtual sensor measurements which replace values from sensors detected as faulty. Several virtual sensors algorithms have been developed for HVAC equipment and components: Nassif et al. (2003), Song et al. (2012), McDonald et al. (2014). Fernandez N. et al. (2009b) presented algorithms for sensors fault detection, isolation and correction in AHU. Algorithms implement rules based on physical principles coupled with knowledge of the AHU components configuration. Brambley M. R. et al., 2011 presented a study on selfcorrection strategies for AHU: 26 algorithms have been based on models developed during commissioning in order to simulate the correct system operation. Ten of those algorithms were integrated in the code of a prototype software for automated sensors fault detection and correction. Padilla M. et al. (2015) proposed a sensor correction algorithm for supply air temperature and pressure in an AHU, developing grey box models using variables usually measured for control purpose by the Building Energy Management System (BEMS). Whether a fault in sensors is detected, faulty measurements are replaced by values derived from those models. Finally, Padilla M. and D, Choiniere (2015) developed an algorithm for sensors fault detection and isolation in an AHU. The authors developed the algorithm coupling Principal Component Analysis (PCA) and Active Functional Tests (AFT). This paper presents a new algorithm for sensor selfcorrection without need for human intervention or

additional measurements at additional cost. Results from testing the algorithm in an AHU economizer are presented as well. ALGORTHM The algorithm proposed in this paper aims for the selfcorrection of measurements of outdoor air temperature or relative humidity entering the AHU economizer. Only one of these two sensors might show abnormal measurements. Measurements from a BAS trend data are used in this study. The reference value of outdoor air temperature is predicted at each time step from the air energy balance at the mixing box of the economizer (assuming that all other sensors give accurate measurements). The measurements are corrected with a constant optimal value identified through an iterative procedure, and compared with the correspondent reference value. Short term measurements with calibrated sensors are used for validation purpose only. The algorithm could also be applied to the return or mixed air stream, assuming as correct the measurements from the other air temperature and relative humidity sensors. i) Energy Balance The energy balance of mixing of two air streams in the adiabatic mixing box of the AHU is written as presented in Equation 1 in terms of α-factor. The α-factor is intended as the ratio of the outdoor air flow rate to the supply air flow rate (Eq. 2) (ASHRAE. 2001). α = h ma hrec h oa h rec (1) α = m oa m a (2) where h ma is the mixed air enthalpy, h rec is the recirculated air enthalpy, and h oa is the outdoor air enthalpy, m oa is the outdoor air mass flow rate, and m a is the supply air mass flow rate. The outdoor air temperature entering the mixing box is predicted from the energy balance in terms of α-factor by using the sequence of Equations 3, 4 and 5 at each time step. x oa,α = α (x ma - x rec ) + x rec (3) h oa,α = α (h ma - h rec ) + h rec (4) T oa,α = h oa,α h fg x oa,α C pa + C pv x oa,α (5) where x oa,α is the outdoor air specific humidity estimated with α-factor, kg/kg; x ma is the mixed air specific humidity, kg/kg; x rec is the recirculated air specific humidity, kg/kg; h oa,α is the outdoor air enthalpy estimated with α-factor, kj/kg; T oa,α is the outdoor air temperature estimated with α-factor, C; h fg is the water vaporization heat, h fg = 2,501 kj/kg; C pv is the water vapor specific heat at constant pressure P = 101,325 Pa; C pv = 1,875 kj/(kg K), and C pa is the dry air specific heat at constant pressure P = 101,325 Pa, C pa = 1,006 kj/(kg K). Values derived from eq. 5 for each time step compose a vector of temperatures, which are compared to the outdoor air temperature measurements from the BAS. The results of comparison are reported in terms of Coefficient of Variation of the Root Mean Square Error CV-RMSE (%). If high CV-RMSE values are obtained, we conclude that the measurements of the variable of interest (in this case the outdoor air temperature) might contain abnormal values. We assume CV-RMSE values higher than 10% to be indicative of the presence of abnormal values. Investigation on the presented algorithm using laboratory data should conducted in order to identify an optimal CV-RMSE limit value for abnormal values detection. In this case, the measurements of outdoor air temperature need to be corrected and, for this purpose, a self-correction algorithm is proposed to be used. Certainly, the scope of this correction should be limited in time until the maintenance team make the physical corrections or replacement of sensors. ii) Iterative Procedure The measured value of outdoor air temperature at each time step is modified (Eq. 7). A delta vector (dt(j)) of 38 air temperature corrections, containing values from - 5.0 C up to +5.0 C, increased by 0.25 C, is used (Eq. 6). For each j-correction, a new α-factor vector of values (α cor(j)) is derived through Equations 8 and 9. dt = [-5.0, -4.75, -4.50. +4.50,+4.75, +5.0] (6) T oa,cor (j) = T oa + dt(j) (7) h oa,cor (j) = T oa,cor(j) C pa + + x oa (h gf + T oa,cor(j) C pv) (8)

α cor(j) = h ma h rec (9) h oa,cor (j) h rec where j varies from 1 to the 38, T oa,cor (j) is the j-th corrected outdoor air temperature measurement, h oa,cor (j) is the j-th corrected outdoor air enthalpy, and α cor(j) is the j-th corrected α-factor. For each j, the corrected vector of α-factor values is used with equations 3, 4 and 5 to obtain a new predicted value of T oa,α(j). For each j, the CV-RMSE between T oa, α (j) and T oa,cor(j), over the entire sample, is calculated. The dt(j) correction value that gives the minimum CV-RMSE is retained as the best correction value dt(j*) of outdoor air temperature. CASE STUDY This study uses two AHUs installed in parallel in a new university building in Montréal, QC. The outdoor air and recirculated air flows are mixed in two mixing boxes, installed in parallel, before the air is treated and supplied to the conditioned space (Figure 2). Four variable speed fans are used to supply the conditioned air to the building, and two fans for the returned air. Two heat recovery coils are installed at the outdoor air intake for pre-heating or pre-cooling. Finally all measurements of outdoor air temperature T oa recorded by the BAS are replaced with the corrected outdoor air temperature T oa * (Eq. 10). T oa = T oa + dt(j*) (10) In addition to the correction of measurements of the outdoor air temperature, this iterative procedure allows for the correction of α-factor. As a result, we obtain a better estimate of the outdoor air flow rate, if there is no air flow meter on the outdoor air intake. The effectiveness of the overall algorithm is verified by comparing the corrected outdoor air temperature measurements with short term measurements with calibrated sensors. The flow-chart of the overall algorithm implementation is showed in figure 1. Figure 2 Schematic of the Air Handling Units. Figure 1 Flow-chart of the overall algorithm process. The recirculated air temperature (T rec) and relative humidity (RH rec), are derived from the return air conditions, considering that the air specific humidity does not change through the return fan, and the outdoor air temperature increases by 1.8 C (Zibin N., 2014). Table 1 lists variables used in this study from the BAS trend data that contains measurements recorded at 15- min time step. Moreover, short term measurements with calibrated sensors have been taken from September 2 to September

19 in 2015 in order to preliminary verify the accuracy of measurements from the BAS. Short term measurements of the mixed air relative humidity have been taken, since this variable is not recorded by the BAS. Measurements from BAS trend data taken when the heat recovery coils were working have been excluded from the data set. Table 1 Variable used in this study for sensors self-correction. Variable Unit Symbol Outdoor air temperature C T oa Outdoor air relative humidity % RH oa Return air temperature C T r Return air relative humidity % RH r Mixed air temperature C T ma Mixed air relative humidity % RH ma From the comparison with short term measurements, we concluded that the BAS measurements of outdoor air relative humidity and temperature show abnormal values (Figures 3 and 4). Statistical indices from comparison confirm the occurrence of abnormal values from the BAS: Mean Absolute Error MAE = 30.8% and CV-RMSE = 45.7% for relative humidity, MAE = 1.3 C and CV-RMSE = 9.1% for air temperature. As the proposed algorithm considers the failure of only one sensor, and for the purpose of presenting the proposed algorithm, the short term measurements have been used to replace the measurements from one of the two outdoor conditions sensors. Figure 3 Outdoor air relative humidity from spot (blue) and BAS (red) measurements, from September 2 to 19, 2015. Figure 4 Outdoor air temperature from spot (blue) and BAS (red) measurements, from September 2 to 19, 2015. Hence, two data sets have been generated: (i) the T oa faulty data set, which is composed of uncorrected outdoor air temperature values from BAS trend data, and of accurate short-term measurements of outdoor air relative humidity; and (ii) the RH oa faulty data set, which is composed of uncorrected outdoor air relative humidity values from BAS trend data, and of accurate short-term measurements of outdoor air temperature. RESULTS The proposed algorithm has been applied to available measurements from September 2 to September 19, 2015. The two following sub-sections give results from those two data sets: i) T oa faulty data set; and ii) RH oa faulty data set. (i) T oa faulty data set Figure 5 highlights some differences between measured and derived (T oa), suggesting the occurrence of faulty values affecting one of the variables involved in the energy balance equation (Eq. 1). The statistical indices support also the same conclusion: MAE = 3.1 C and CV-RMSE = 34.5%. Although normally the temperature difference is not reported as percentages, for the consistence with the reporting of difference in relative humidity, we preferred to use the percentage in reporting the CV-RMSE of air temperature difference. The remarkable difference between measurements and derived values showed in figure 5, thus, comes from inaccurate evaluations of the α-factor, which derive from faulty values involved in eq. 1, and which finally

cause incorrect outdoor air temperature derived values (eq. 5). Through the iterative procedure, the best correction value of outdoor air temperature has been found to be dt * = - 2.0 C. Figure 6 shows the variation of CV- RMSE with dt. The corrected outdoor air temperature values have been thus evaluated: T oa = T oa - 2.0 C. The corrected outdoor air temperature, thus, replaced the values collected by the BAS creating a corrected data set. To evaluate the effectiveness of the propose algorithm, the derived outdoor air temperature T oa,α (Eq. 3, 4 and 5), are compared with the corrected T oa measurements. Comparison is showed in figure 7. Statistical indices show an improvement in the data set due to the correction procedure on outdoor air temperature values: MAE = 2.7 C (from 3.1 C) and CV-RMSE = 20.6% (from 34.5%). Thus figure 7, compared to figure 5, shows a slight improvement in comparison between measurements (corrected) and correspondent derived values. Statistical indices reflect this improvement. Statistical indices used for the comparison between spot and corrected measurements show improvement in CV- RMSE but a worse MAE value: MAE = 1.8 C (from 1.3 C) and CV-RMSE = 6.9% (from 9.1%). Figure 8 shows the outdoor air temperature profiles from spot measurements, corrected values and measurements from the BAS. Figure 5 Comparison between measurements collected from BAS and values derived from α. A perfect correlation reference line is plotted in red. Figure 7 - Comparison between corrected measurements from the BAS and correspondent values derived from α. A perfect correlation reference line is plotted in red. Figure 6 CV-RMSE versus dt

Figure 8 - T oa from spot measurements (blue), from adjusted measurements (black), and from the BAS (red), from September 2 to September 19, 2015. (ii) RH oa faulty data set Implementing the algorithm on the RH oa faulty data set, RH oa,α values are derived from the α-factor through Equations 11 and 12. Within the algorithm steps, this correspond to what have been done for the outdoor air temperature along Equations 3-5. Figure 9 Comparison between measured and derived outdoor air relative humidity values. A perfect correlation reference line is plotted in red. x oa,α = x ma x rec α + x rec (11) RH oa,α = Pv oa Ps oa 100 (12) where x oa,α is the outdoor air specific humidity derived from the α-factor, kg/kg; Pv oa is the outdoor air partial pressure of water vapor, Pa, function of the outdoor air specific humidity; Ps oa is the outdoor air saturated vapor pressure, Pa, function of the outdoor air dry temperature, Pa. Figure 9 highlights the significant difference between measured (RH oa) and derived (RH oa,α) outdoor air relative humidity. The statistical indices support also the conclusion of a large difference between those relative humidity values: Mean Absolute Error (MAE) = 92.4%, and CV-RMSE = 410.6%. Similarly to the previous section (T oa faulty data set), the large variation between measured and derived outdoor air relative humidity values depend on the inaccuracy of estimated α-factor, and thus, on the correctness on measurement values used in α-factor calculation. Through the iterative procedure, the best correction value of air specific humidity was obtained dx * = 0.0035 kg/kg. The corrected outdoor air relative humidity (RH oa ) values have been thus obtained from the corrected outdoor air specific humidity (x oa ). The corrected outdoor air relative humidity values replaced the values collected by the BAS, creating a corrected data set. In order to verify the effectiveness of the algorithm, the outdoor air relative humidity (RH oa,α ) have been derived from α-factor (Eq. 11 and 12), along the corrected data set, and compared to RH oa. The comparison between the corrected RH oa and derived RH oa,α values (Figure 10) shows a remarkable improvement with reference to values from before the optimization. The statistical indices show also a good agreement: MAE = 3.6% (from 92.4%) and CV-RMSE = 4.7% (from 410.6%).

Figure 11 Outdoor air relative humidity from spot measurements (blue), corrected measurements (red), and measurements from the BAS (black). Figure 10 - Comparison between corrected measurements from the BAS and correspondent values derived from α. A perfect correlation reference line is plotted in red. Statistical indices used for the comparison between spot and corrected measurements of outdoor air relative humidity confirm the effectiveness of the proposed algorithm: MAE = 5.5% (from 30.8%) and CV-RMSE = 6.0% (from 45.7%). Figure 11 shows the outdoor air relative humidity profiles from spot measurements, corrected values and measurements from the BAS. The missing values in Figure 11 corresponds to those records, removed for the analysis, when the heat recovery coils worked. Tables 2 summarizes the statistical indices from the comparison between measurements and derived values, before and after the use of correction algorithm. Table 3 summarizes statistical indices from the comparison between the spot measurements and measurements from the BAS (before the correction algorithm), and between the spot measurements and corrected measurements (after the correction algorithm). For this case study, the proposed algorithm improved significantly the estimates of outdoor air relative humidity; as the CV- RMSE was reduced from 45.7% to 6.0%. For the outdoor air temperature, the effectiveness of the algorithm is not clear; the CV-RMSE was reduced from 9.1% to 6.9%. However, both CV-RMSE values are acceptable as they are less than 10%. Table 2 Statistical indices from comparison between measurements and derived values Before the correction algorithm After the correction algorithm MAE CV- MAE CV- RMSE RMSE RH oa 92.4% 411.0% 3.6% 4.7% T oa 3.1 C 34.5% 2.7 C 20.6% Table 3 Statistical indices from comparison of the spot measurements with uncorrected measurements from the BAS (before the correction algorithm), and with the corrected measurements (after the correction algorithm). Before the correction algorithm MAE CV- RMSE After the correction algorithm MAE CV- RMSE RH oa 30.8% 45.7% 5.5% 6.0% T oa 1.3 C 9.1% 1.8 C 6.9% CONCLUSIONS The self-correction algorithm presented in this paper can be applied to measurements from the BAS trend data, when abnormal values are noticed. The algorithm

validation have been done using short term measurements. The proposed algorithm proved to be more effective, in this case study, for the correction of measurements of outdoor air relative humidity then of outdoor air temperature. The difference between spot measurements of the outdoor air temperature and BAS trend data have not constant high variation (Figure 4) due to some physical factors such as the influence of solar radiation on the sensor. As a consequence the use of a constant correction value for the entire data set does not allow for a larger reduction of the CV-RMSE value. However, the CV-RMSE values are less than 10% (Table 3), which can be accepted for practical purposes. The reduction of CV-RMSE between the spot measurements and corrected BAS trend data is larger for the outdoor air relative humidity because the difference between the spot measurements and the uncorrected BAS trend data is almost constant over the entire data set (Figure 3), due to the constant bias error of the sensor. The proposed self-correction algorithm could be integrated into AHU control strategies implemented by the BAS. If faulty measurements are detected, the proposed algorithm would produce corrected values, which would be used by the BAS instead of the directly measured faulty ones. At the same time, information on eventual detected abnormal values would be sent to building operators, supporting them in scheduling maintenance and calibration strategies and inspections. Until the human intervention would not recalibrate the faulty sensor, the proposed algorithm would supply corrected values to the BAS. In conclusion, the proposed self-correction algorithm proved to be effective in the case study for the correction of measurements of outdoor air relative humidity and temperature. Results presented in this paper concern a 17 days long data set of measurements during the fall season (September 2015). Future investigations should use larger data sets from different periods of the year. The algorithm should be tested with other case studies. Also, the effectiveness of using variable correction values instead of a constant correction values, as presented in the paper, should be tested. For instance, correction values could be evaluate independently per each hour of the day or bin of values, depending on the sensor error profile. ACKNOWLEDGEMENTS The authors acknowledge the support from the NSERC Smart Net Zero Energy Buildings Network and from the Faculty of Engineering and Computer Science, Concordia University, Montreal Canada. REFERENCES ASHRAE. 2001. Handbook, Fundamentals. American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta 111. Brambley, M. R., N. Fernandez, W. Wang, K. A. Cort, H. Cho, H. Ngo, and J. Goddard. 2011. Final project report: Self-correcting controls for VAV system faults. Pacific Northwest National Laboratory, PNNL-20452. Breuker, M. S., and J. E. Braun. 1998. Evaluating the performance of a fault detection and diagnostic system for vapor compression equipment. HVAC&R Research 4 (4): 401-25. Chen, Y. and L. Lan. 2010. Fault detection, diagnosis and data recovery for a real building heating/cooling billing system. Energy Conversion and Management 51 (5): 1015-24. Cui, J. and S. Wang. 2005. A model-based online fault detection and diagnosis strategy for centrifugal chiller systems. International Journal of Thermal Sciences 44 (10): 986-99. Fernandez, N., H. Cho, M. R. Brambley, J. Goddard, S. Katipamula, and L. Dinh. 2009. Project final report: Self-correcting HVAC controls. Pacific Northwest National Laboratory, PNNL-19074. Fernandez N., M. R. Brambley, and S. Katipamula. 2009b. Project final report: Self-correcting HVAC controls: Algorithms for sensors and dampers in air-handling units. Pacific Northwest National Laboratory, PNNL-19104. Haves, Philip. 1999. Overview of diagnostic methods. Paper presented at Proceedings of the workshop on diagnostics for commercial buildings: From research to practice.

Jia Y. and T. A. Reddy. 2003. Characteristic physical parameter approach to modeling chillers suitable for fault detection, diagnosis, and evaluation. Journal of Solar Energy Engineering 125 (3): 258-65. McDonald, E., R. Zmeureanu, and D. Giguère. 2013. Virtual flow meter for chilled water loops in existing buildings. ASHRAE Transactions; 2014, 120(2). Nassif, N., S. Kajl, and R. Sabourin. 2003. Modélisation des composants d'un système CVAC existant. In VIe Colloque Interuniversitaire Franco- Québécois, Québec, Canada. CIFQ2003 / 12-01. Padilla, M., D. Choinière, and J. A. Candanedo. 2015. A model-based strategy for self-correction of sensor faults in VAV air handling units. Science and Technology for the Built Environment. Padilla M. and D. Choinière. 2015. A combined passiveactive sensor fault detection and isolation approach for air handling units. Energy and Buildings 99: 214-9. Roth K., D. Westphalen, and J. Brodrick. 2008. Ongoing commissioning. ASHRAE Journal 50 (3): 66. Song, L., I. Joo, & G. Wang. 2012. Uncertainty analysis of a virtual water flow measurement in building energy consumption monitoring. HVAC&R Research, 15:5, 997-1010. Zibin N. 2014. A bottom-up method to calibrate building energy models using building automation system (BAS) trend data. Msc Degree., Concordia University.