Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher.

Similar documents
Computational and field test analysis of thermal comfort performance of user-controlled thermal chair in an open plan office

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

Postprint.

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Designing Air-Distribution Systems To Maximize Comfort

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

CFD Simulation Studies on Integrated Approach of Solar Chimney and Earth Air Tunnel Heat Exchanger for Building Space Conditioning

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at ScienceDirect. Energy Procedia 57 (2014 )

The potential of earth-air heat exchangers for low energy cooling of buildings in South Algeria

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Research on indoor thermal environment of stilted buildings in Chongqing, China

Thermal Management of Densely-packed EV Battery Set

PROJECT COMPLETION REPORT FOR SHORT TERM GRANT A STUDY ON IMPROVING AIR CIRCULATION IN A CONFINED SPACE

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

Assessment of the natural air ventilation of buildings in urban area with the CFD tool UrbaWind. Dr Stéphane SANQUER Meteodyn

Experimental investigation of zero energy office under natural and forced ventilation

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Design, Fabrication and Experimental Study of a Novel Loopheat-pipe based Solar Thermal Facade Water Heating System

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Available online at ScienceDirect. Procedia Engineering 145 (2016 ) 18 25

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

Quenching steels with gas jet arrays

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY

A Solar Wall System Utilized in Rural Houses of Northeast China

COMPUTATIONAL ANALYSIS ON THE EFFECTS OF FAÇADE MODIFICATIONS ON WIND-DRIVEN NATURAL VENTILATION PERFORMANCE OF A SINGLE-CELL ROOM

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods

Pearl River Tower. Guangzhou, China. AEI Professional Project Awards January 2014 PHOTO CREDIT: TIM GRIFFITH

Solar Passive Techniques: Earth Air Tunnel

Comparison of RANS, URANS and LES in the Prediction of Airflow and Pollutant Dispersion

Thermal Comfort in Architecture

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS

Three-Dimensional Numerical Simulation of a Model Wind Turbine

ENERGY PERFORMANCE OF DIFFERENT TYPES OF DOUBLE SKIN FACADES IN VARIOUS CLIMATES

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

Live Transportation Research and Improvement Initiatives

Roof Mounted Wind Turbines: The influence of roof shape, building height and urban location on wind speed

MODELING A SHROUD FOR THE WIND TURBINE AND CARRYING A FLUID FLOW ANALYSIS USING CFD SOFTWARE PACKAGE

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

CFD modeling of airflows and contaminant transport in an aircraft cabin

caused by subjective factors such as oversimplified modeling for simulation, nonuniform calculation methods, casual input parameters and boundary cond

40-Ton Articulated Truck Cooling System Modelling Using STAR-CCM+

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation

DISPLACEMENT VENTILATION

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Analysis of the corrosion test process for heat exchangers in corrosion test chambers by CFD simulation

A Comparative Study of the Thermal Comfort of Different Building Materials in Sana a

681: Environmentally Responsive Architecture; Passive Design for School in Southern India

Urban Physics: towards sustainable buildings and cities

Smoke Dispersion from Stacks on Pitched-Roof Buildings: Model Calculations Using MISKAM in Comparison with Wind Tunnel Results

EFFECTIVE THRUST TRANSFORMATION INSIDE TUNNELS WITH JET FANS (BANANA JET)

PS Modeling airflow in outdoor grain pile aeration systems. Introduction

CFD Simulation Methodology for Ground-Coupled Ventilation System

CFD on Small Flow Injection of Advanced Accumulator in APWR

Design and distribution of air nozzles in the biomass boiler assembly

ScienceDirect. CFD Analysis of a Kerosene Fuel Tank to Reduce Liquid Sloshing

DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE

ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS.

Task 1 For Task 1, the outlet was set as a zero-gauge pressure outlet, which is the same outlet condition as the five smaller pipes.

Side by side tests of two SDHW systems with solar collectors with and without antireflection treatment

Bahrain World Trade Centre

Optimization of embedded Heat Exchanger in a flat plate Integrated Collector Storage Solar Water Heater (ICSSWH), with indirect heat withdrawal.

CRHT VII. Design and CFD analysis of Pico- hydro Turgo turbine. Paper no. CRHT17-11

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Introduction to basics of energy efficient building design

Prediction of Pollutant Emissions from Industrial Furnaces Using Large Eddy Simulation

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

BEYOND ARROWS: ENERGY PERFORMANCE OF A NEW, NATURALLY VENTILATED DOUBLE-SKIN FACADE CONFIGURATION FOR A HIGH-RISE OFFICE BUILDING IN CHICAGO

Numerical study of the influence of injection/production well perforation location on CO 2 -EGS system

Optimising design of secondary combustion chambers using CFD

Heat Transfer Simulation of Impinging Jet with Finned Heat Sink

VALIDATION OF A CFD MODEL IN RECTANGULAR SETTLING TANKS

Analysis of Flue Gas Flow Behavior in Economiser Duct Using Cfd

Investigations of Intelligent Solar Heating Systems for Single Family House

Liquid-Solid Phase Change Modeling Using Fluent. Anirudh and Joseph Lam 2002 Fluent Users Group Meeting

Thermally operated mobile air-conditioning system

ENERGY SAVING IN BUILDING USING PCM IN WINDOWS

Passive Cooling of Power Electronics: Heat in the Box

Transcription:

Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher. Item type Authors Citation DOI Publisher Journal Article Calautit, John Kaiser; Aquino, Angelo I.; Shahzad, Sally; Nasir, Diana S. N. M; Hughes, Ben Richard Calautit J. K. et al (2016). 'Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher.' Energy Procedia, 105:2065-2870, 8th International Conference on Applied Energy, Beijing, China. October 10.1016/j.egypro.2017.03.634 Applied Energy Energy Procedia Downloaded 11-May-2018 19:29:38 Link to item http://hdl.handle.net/10545/620568

Available online at www.sciencedirect.com ScienceDirect Energy Procedia 105 (2017 ) 2865 2870 The 8 th International Conference on Applied Energy ICAE2016 Thermal comfort and indoor air quality analysis of a lowenergy cooling windcatcher John Kaiser Calautit a, *, Angelo I. Aquino a, Sally Shahzad b, Diana SNM Nasir a, Ben Richard Hughes a a Department of Mechanical Engineering, University of Sheffield, Sheffield S10 2TN, United Kingdom b School of Engineering and Technology, University of Derby, Derby, DE22 3AW, UK Abstract The aim of this work was to investigate the performance of a roof-mounted cooling windcatcher integrated with heat pipes using Computational Fluid Dynamics (CFD) and field test analysis. The windcatcher model was incorporated to a 5m x 5m x3 m test room model. The study employed the CFD code FLUENT 15 with the standard k- model to conduct the steady-state RANS simulation. The numerical model provided detailed analysis of the airflow and temperature distribution inside the test room. The CO 2 concentration analysis showed that the system was capable of delivering fresh air inside the space and lowering the CO 2 levels. The thermal comfort was calculated using the Predicted Mean Vote (PMV) method. The PMV values ranged between +0.48 to +0.99 and the average was +0.85 (slightly warm). Field test measurements were carried out in the Ras-Al-Khaimah (RAK), UAE during the month of September. Numerical model was validated using experimental data and good agreement was observed between both methods of analysis. 2017 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license 2016 The Authors. Published by Elsevier Ltd. (http://creativecommons.org/licenses/by-nc-nd/4.0/). Selection and/or peer-review under responsibility of ICAE Peer-review under responsibility of the scientific committee of the 8th International Conference on Applied Energy. Keywords: Built Environment; Computational Fluid Dynamics (CFD); Cooling; Energy; Natural Ventilation 1. Introduction and Literature Review The windcatcher dates back to 1,500 years ago. Their usage was spread to Middle East countries such as Iran, Egypt and the UAE. Natural ventilation and passive cooling of the airflow without electrical power are the most important features of windcatchers [1]. In the UAE, windcatchers can be seen in the town of Bastakiya and signified a remarkable effort to attain comfortable living in a hot climate. Coles et al. [2] studied the effectiveness of UAE s Bastakiya windcatchers by carrying out measurement of temperatures, wind tunnel modelling and interviews with previous residents. Recently, McCabe and Roaf [3] performed dynamic thermal modelling of a Bastakiya house centered on the windcatcher ventilation system using historical climate data. The study analysed the potential of traditional windcatchers to increase the comfort by varying the height and cross-sectional area. To this end, most of the studies on windcatchers in the UAE are mainly based on the traditional systems and many of these historic buildings 1876-6102 2017 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the scientific committee of the 8th International Conference on Applied Energy. doi:10.1016/j.egypro.2017.03.634

2866 John Kaiser Calautit et al. / Energy Procedia 105 ( 2017 ) 2865 2870 have been demolished to make way for new developments [2]. The use of modern air-conditioning technology and cheap energy due to government supports have contributed to the diminishing of functional windcatchers. Nowadays, windcatchers can be seen in new developments in the UAE which are exaggerated in scale and have no functional purpose. Though the non-functional wind towers are copies of the ones in historic Bastakiya district, it still shows that there is an awareness of its heritage value. As energy becomes less affordable, energy security decreases and as people become more aware of the environmental impact, the ability to passively cool buildings becomes more important. Many researchers [1] have attempted to improve the effectiveness of windcatchers by increasing the ventilation rates and operation time. Several studies [1,4] focused on the aerodynamics design and ventilation performance of windcatchers. Recently, several works [5,6] have integrated heat pipes in windcatchers to improve its cooling performance in hot countries. The numerical analysis [5] showed that the temperature reduction of the supply air reached up to 12 C while still providing the fresh air requirements. Figure 1 shows the operation of the cooling windcatcher with heat pipes. The hot outdoor air enters the windcatcher through the louvers. The airflow is driven downwards and passed through a series of heat pipes which absorbs the heat from the airflow (evaporator) and transfers it to a parallel cool sink (condenser). Adjustable dampers are mounted at the bottom of the deviceto control the delivery rate of the outdoor air, as fluctuations in external wind speed greatly influence the air movement rate within the occupied space. The cooled air is supplied to the room beneath the channel via ceiling diffusers. The current work expands on previous research [5,6] by investigating the capabilities of the system to provide good thermal comfort and indoor air quality in buildings. 2. Research Methodology Fig. 1. Schematic of (a) windcatcher cooling system; (b) heat pipe heat transfer 2.1. Computational modelling ANSYS FLUENT 15 software was used to conduct the steady-state Reynolds averaged Navier Stokes equation (RANS simulation) which employed a control-volume-based technique for solving the flow equations. The standard k- turbulence model was used, which is a well-established method in research on windcatcher natural ventilation [1]. Second-order upwind scheme was used to discretised all the transport equations. The numerical code used the semi-implicit method for pressure-linked equations (SIMPLE) algorithm for the velocity-pressure coupling of the computation. The governing equations are not repeated here but available in the ANSYS FLUENT guide. The windcatcher (Figure 1) was created using commercial CAD modeller. The CAD solid data was imported into ANSYS DesignModeller (pre-processor) to generate a fluid domain. The domain (Figure 2a) was separated into three parts: the windcatcher, indoor and outdoor environment. The windcatcher was incorporated to the indoor domain with the dimensions of 5m x 5m and 3m, representing a small room. It was assumed that the windcatcher was supplying airflow at 100% (fully open), therefore dampers were not modeled in the system. The dimension (20 mm outer diameter) and spacing (50mm horizontal

John Kaiser Calautit et al. / Energy Procedia 105 ( 2017 ) 2865 2870 2867 and 20mm vertical) of the heat pipes located downstream of the windcatcher channel were based on earlier work [5-7]. The cool sink was not included in the modelling for simplification [5]. Figure 2a shows the computational domain used for the analysis of the room with a windcatcher. The domain was sufficiently large to prevent artificial acceleration of the flow. The length of the up-stream domain was kept short, 5 times the height of the test room, to avoid the unintended existence of stream-wise gradients while satisfying the recommendations. The length of the down-stream domain was 15 times the height of test room, sufficiently long to allow the wake region development behind test room, which was important for the simulation of exhaust flow from the leeward opening [8]. Fig. 2. (a) computational domain; (b) ABL flow profiles for wind velocity and turbulence kinetic energy [8] Due to the complex geometry of the windcatcher model, an unstructured-grid technique was employed to discretise the domain. The advanced size function in ANSYS Meshing was used to precisely capture the geometry while maintain a smooth growth rate between regions of curvature. In order to capture accurately the flow-fields near the critical areas of interest (i.e. louvers and heat pipes) in the simulation, size functions were applied in those surfaces. The total number of the grid elements was 5.6 million. The selected resolution of the grid was based on the grid sensitivity analysis and convergence analysis on several grids (4.6 to 9.2 million). The boundary conditions were set using the guidelines highlighted by [8] for the simulation of flows in the urban environment. The vertical profiles of the airflow velocity and turbulence kinetic energy were imposed on the inlet as shown in Figure 2b, based on the measurement data of [8]. The mean velocity of the approach flow obeyed a power-law with α = 0.25, which corresponds to a sub-urban terrain. The top and side boundaries were defined as symmetry and the outlet surfaces of the domain was set as zero-static pressure. All the test room surfaces were set as smooth non-slip walls. The standard wall functions were prescribed to the wall boundaries [8]. The wall functions for the ground surface were modified to reflect the effect of roughness of the ground using the equivalent sand-grain roughness height and roughness constant. The inlet temperature was set to 36 C and relative humidity was set to 50% which are typical average in Ras-Al-Khaimah (RAK) during September. The wall temperature of the heat pipes was set to 20 C [5,6]. For the CO 2 distribution simulation, the room was filled with 12 occupants (equally distributed inside the room. A simplified exhalation (constant exhalation) model [9] was used for the analysis. The model of the occupant was simplified to a 1.80m x 0.30m x 0.17m cuboid shape. The area for the mouth opening is equal to 0.13m x 0.10m [9]. Average value of 6 l/min of exhaled air was assumed for the simulation [9]. 2.2. Experimental field testing Field testing measurements were carried out in RAK, which is situated in the northern part of the United Arab Emirates (UAE), located at latitude 25.67 N and longitude 55.78 E with and elevation of 8.00 m. The climate of RAK can be characterised as a hot-desert climate with very hot summers and mild winters. High temperatures can be expected from June to August, with a mean temperature ranging between 37-40 C. The tests were carried out during the month of September (Sept. 17 18, 2014)

2868 John Kaiser Calautit et al. / Energy Procedia 105 ( 2017 ) 2865 2870 between 11AM to 4PM. The prevailing winds in RAK are from the northern direction (N-NNW-NW) and therefore, the opening of the windcatcher was positioned to face the predominant wind. The average wind speed in RAK is between 3.6 m/s-4.6 m/s but during the days of test wind speeds went up to about 5.7-6.0 m/s. A 1 m x 1 m prototype of the cooling windcatcher was manufactured (Figure 3a) and installed on top of a 3 m x 3 m x 3 m test room as displayed in Figure 3b. Similarly, the 20mm heat pipes were arranged inside the downstream of windcatcher channel as described in Section 2.1. The cool sink was fed by water at approximately 20 C. The walls and roof of the room was built using insulated studwork. A small cut-out at the back of the room serves as an outlet. The temperature was measured using type-k thermocouple: outdoor, supply air (3 equally-spaced thermocouples downstream of windcatcher channel) and heat pipe wall (1 on surface). The thermocouples were connected to a data logger to monitor and collect the data. The uncertainty associated with the measurement tool was ±0.6 C at a temperature of 50 C and ±0.5 C at 0 C. The measurement device recorded the temperature every second. Fig. 3. (a) Full scale windcatcher prototype; (b) windcatcher installation; (c) measurement of supply air 3. Numerical Results Figure 4a illustrates the contours of velocity in the vertical plane drawn from the middle of the room which is aligned with the direction of the flow and contains the centre of the windcatcher. The airflow that entered the windcatcher via the 45 louvers was deflected upwards while the lower side of the flow was in reverse which formed a small recirculation region. The flow slightly accelerated (up to 1.02 m/s) as it turns sharply inside the 90 corner. Reduction in speed was observed downstream of the heat pipes (0.9 to 0.45 m/s). A column of fast moving air enters the space, where the airstream hit the floor of the room and moves toward the opening on the right wall. Figure 4b shows the CO 2 distribution inside the room with 12 occupants (CO 2 source). As observed, fresh outdoor air (assumed to be 382ppm) ventilates the room and dilutes the CO 2. Figure 5a shows the contours of static temperature in the vertical mid-plane which is aligned with the flow direction. The numerical model predicted the indoor temperature to be around 25 C (closer to the air jet) to 29 C (closer to outlet). A greater temperature reduction was obtained at the immediate downstream of the heat pipes with a supply air temperature between 24 C- 27 C, a reduction of upto 12 C. Figure 6a displays the calculated thermal comfort for the plotted points inside the room (Figure 5b). The thermal comfort was calculated using the Predicted Mean Vote (PMV) method which refers to a thermal scale that runs from Cold (-3) to Hot (+3). The values for metabolic rate and clothing were assumed and set as 1met (sitting) and 0.4 (summer clothing). As observed, the calculated PMV values ranged between +0.48 to +0.99 and the average was +0.85 (slightly warm), which was above the recommended acceptable PMV value in the ASHRAE Standard 55-2013. The percentage of occupants that will be dissatisfied with the indoor conditions were between 10-28.2%. It should be noted that the calculation was only based on steady state conditions and a transient model (varying indoor and outdoor conditions) should be used for a more detailed analysis.

John Kaiser Calautit et al. / Energy Procedia 105 ( 2017 ) 2865 2870 2869 Wind = ABL profile Outdoor air = 382PPM 0.48m/s 0.12m/s 385PPM 500PPM 550PPM 0.42 m/s 0.12 m/s 400PPM Fig. 4. Cross-sectional contour of (a) velocity magnitude (m/s); (b) CO 2 concentration (ppm) Outdoor air = 36 C 24 C 29 C 25 C 28 C Fig. 5. Cross-sectional contour of air temperature ( C); (a) side view; (b) top view (1.1m height) PPD (%) 100 80 60 40 20 0 1 2 3 4 5 6 7 8 9 Fig.6. Calculated thermal comfort; (a) Predicted Mean Vote (PMV); (b) Predicted Percentage of Dissatisfied (PPD) 4. Experimental Results and Method Validation Figure 7a displays the measurements of outdoor air temperature, supply air temperature at the three positions downstream of the windcatcher and heat pipe surface temperature during the 5-hour testing on (09/18/14) from 11 AM to 4 PM The windcatcher began to deliver airflow into the test room at 11:30 and the temperature drop ranged between 3 C-4 C during this period. When the wind started to blow consistently within the ±40 wind angle from 1 PM to 4PM and the temperature drop ranged between 3 C 11.5 C during this period. Figure 7b shows a detailed view of the temperature measurements from 3 PM to 4 PM. The temperature measurements taken during several periods (03:05, 03:16, 03:30, 03:37, 03:48 and 03:58) were used for the validation of the steady-numerical model. It is worth noting that for this numerical model, the test room size was reduced to 3m x 3m x 3m so it will be similar to the field test. Predicted supply temperatures are added to the chart for comparison with the measured results. As observed, the numerical model in most cases under-predicted the supply temperature, however a similar trend between both methods was observed. The average error between the results was 3.15%.

2870 John Kaiser Calautit et al. / Energy Procedia 105 ( 2017 ) 2865 2870 5. Conclusions and Future Work Fig. 7. (a) field test measurements; (b) validation of numerical modelling A numerical and experimental investigation was carried out to investigate the ventilation and thermal comfort performance of a passive cooling windcatcher integrated with heat pipes. The study employed the CFD code FLUENT 14.5 to conduct the steady-state RANS simulation which employed the FVM approach. The numerical model provided detailed analysis of the airflow and temperature distribution inside the test room. For the indoor CO 2 concentration analysis, a simplified exhalation (constant exhalation) model was used and the room was filled with 12 occupants. The analysis showed that the system was capable of delivering fresh air inside the space and lowering the CO 2 levels. The thermal comfort was calculated using the Predicted Mean Vote (PMV) method and Predicted Percentage of Dissatisfied (PPD). The calculated PMV values ranged between +0.48 to +0.99 and the average was +0.85 (slightly warm). It should be noted that the calculation was only based on steady state conditions and a transient model should be used for a more detailed analysis. Field testing measurements conducted in the Ras-Al-Khaimah (RAK) during the month of September demonstrated the positive effect of the integration of heat pipes on the cooling performance References [1] Hughes BR, Calautit JK, Ghani SA, The Development of Commercial Wind Towers for Natural Ventilation: a review. Applied Energy 2012;92:606-27. [2] Coles A, Jackson P, Jones I. How wind towers work: A study of the effectiveness in Dubai's Bastakiya, International Committee of Vernacular Architecture Conference, Al Ain, 2012. [3] Ciaran M, Roaf S. The wind towers of Bastakiya: assessing the role of the towers in the whole house ventilation system using dynamic thermal modelling. Architectural Science Review 2013;56:183-194. [4] Calautit JK, Hughes BR. Wind tunnel and CFD study of the natural ventilation performance of a commercial multidirectional wind tower. Building and Environment 2014;80:71-83. [5] Calautit JK, O'Connor D, Sofotasiou P, Hughes BR. CFD Simulation and Optimisation of a Low Energy Ventilation and Cooling System. Computation 2015;3:128-149. [6] Calautit JK, Chaudhry HN, Hughes BR, Ghani SA. Comparison between evaporative cooling and heat pipe assisted thermal loop for a commercial wind tower in hot and dry climatic conditions, Applied Energy 2013; 101:740-755. [7] Calautit JK, Hughes BR, Shahzad SS.CFD and wind tunnel study of the performance of a uni-directional wind catcher with heat transfer devices. Renewable Energy 2015;83:85-99. [8] Tominaga Y, Akabayashi S, Kitahara TA, Arinami Y. Air flow around isolated gable-roof buildings with different roof pitches: Wind tunnel experiments and CFD simulations. Building and Environment 2015;84:204-213. [9] Calautit JK, O Connor D, Hughes BR. Determining the optimum spacing and arrangement for commercial wind towers for ventilation performance. Building and Enviornment 2014;82:274-287. Biography Dr Calautit is a Research Associate in the University of Sheffield. He received his Mechanical Engineering degree from Heriot-Watt University and his PhD from the University of Leeds. His PhD study focused on numerical and experimental techniques to design and investigate performance of passive cooling windcatchers.