POWERTECH LABS INC. CONNECTABILITY TESTING OF COPPER AND ALUMINUM WIRING, PHASE 2: Current Cycling Tests Mechanical Connectors PROJECT PL-00236

Similar documents
DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015)

Factors Influencing Fretting Corrosion of Tin Plated Contacts

TECHNICAL ANALYSIS #2

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

2/2 % ) Direct Acting Subminiature Solenoid Valves. 1/8" and 1/4" NPT. Features. Construction. Electrical

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

Temperature Controllers: JC Series Digital Indicating Controllers. JC Series. High Performance Controllers...at the lowest prices anywhere!

Technical Specification for LV ABC Fuse Switch Disconnectors

MC -SEALconTACT. Multilam contacts. Multilam Technology

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION GROUNDING AND BONDING

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

SECTION CHAIN-LINK FENCES AND GATES 02821/1

ELECTRICAL RESISTIVITY AS A FUNCTION OF TEMPERATURE

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS

Thermocouple Reference Table

TEMPORARY PROTECTIVE GROUNDING EQUIPMENT

nicrom e l e c t r o n i c

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

Installation Instructions

Single Pulse Resistance Welder Instruction Pamphlet CD125SP High Accuracy CD Welder

THERMOCOUPLES and THERMORESISTANCES - Temperature measurement sensors for industrial use Figure 1: Standard Thermocouples

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

Series Sump and Sewage Systems

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

The Leader in Oilfield Coating Technology ISO 9001:2008.

Phone: Fax:

Specification Lightning Protection Systems

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics

INSTALLATION AND MAINTENANCE GUIDE SECTION 3 HANDRAIL DECK LIGHTS

RC9 Poke-Thru Series INSTALLATION INSTRUCTIONS Installation Instruction No.: R3 Updated April 2005

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60

Spring Pressure Connection Technology Vibration-Proof Fast Maintenance-Free

Surface Mount Sense Resistors

Evolution Series. 8" Poke-Thru Devices I N S T A L L A T I O N I N S T R U C T I O N S. IMPORTANT: Please read all instructions before beginning.

Galvanic and Stray Current Corrosion

U.V resistance UL Sunlight Resistance. Flame retardant IEC

THE KENYA POWER AND LIGHTING CO. LTD

For Silverback Solar

SPRING LOADED THERMOCOUPLE CONFIGURATIONS

Zoned Comfort Control

Details of technical leaflets/write-up on various pieces of equipment.

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

LV bolted straight joint connector BSLB-4/16, BSLU-4/16

SECTION INSULATED WIRE AND CABLE

Metal Transitions HIGH TEMPERATURE

Power Electronics Packaging Revolution Module without bond wires, solder and thermal paste

ELECTRICAL SAFETY Information Bulletin

Installation plan. Tumble dryer. PT 8807 EL (Electrically heated) en - US Mat. NR / 02

ELECTRICAL BULLETIN

STOCK LIST COQUITLAM, BC, CANADA SHEET PLATE COIL PIPE TUBE ROD BAR FITTINGS FLANGES EXTRUSIONS ALUMINUM BRASS BRONZE COPPER COPPER-NICKEL

Substation Bus Design: Current Methods Compared with Field Results

Circular Connectors Conforming to JIS C 5432

TEMPERATURE TESTING AND ANALYSIS OF PV MODULES PER ANSI/UL 1703 AND IEC STANDARDS

TABLE OF CONTENTS. Type HFB-P1... A-22. Type HFB-N... A-23. Types KA-U, KKA-U... A-24. Type K2A-U... A-25. Types K3A-U, KK3A-U...

Aluminum vs. Copper Conductors A Serious Alternative?

High-Strength Aluminum Wires for Low-Voltage Automotive Engine Wiring Harnesses

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Embedded Mold Temperature Sensor

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated

Dimensions in Millimeters (Inches) A Bushing Diameter. B Bushing Height

ANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers"

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A.

AP5K-C Precision AC Double-Pulse Spot Welding Machine User s Manual Shenzhen Will-Best Electronics Co., Ltd

Standard of Practice - Campus Electrical Distribution System

A. Product Data shall be provided for each type of product indicated.

SPRING LOADED THERMOCOUPLE CONFIGURATIONS THERMOWELL & REPLACEABLE INSERT II 2G/D Ex e TCRE/WE

SELECTION GUIDE Appearance Sensing distance Operation Mode Connector Shape example (M8) Outer diameter (Ferrous material only) Wiring Output Output no

MESH FLOOR HEATING SYSTEMS INSTALLATION INSTRUCTIONS

ELECTRICAL CODE TRADE REFERENCE

INTERNATIONAL STANDARD

Data Bus Connector and Terminator Requirements Document DB-1001-A. Revision C

Documentation. Transient voltage suppressor - AX2090- TS Version: Date:

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

UNDERGROUND SERVICES SECONDARY

ELECTRICAL BULLETIN

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

BPA Air Conditioner Test Results. Tests on November 22 nd and 28 th, 2016

LSA Rating Table Low Voltage Alternators - 4 pole

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

Section 5 Roller Chain Drive Components

Highly Accelerated Thermal Shock Reliability Testing

INTERNATIONAL STANDARD

Product Specification JUL 14 Rev. A1

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE

Mar11 Rev D

ROOF ICE MELT RIM SYSTEM

JBS Enterprise Limited. Rm B1, 1/F, Hing Win Industrial Bldg 110 How Ming Street, Kwun Tong Kowloon, Hong Kong Tel: Fax:

Transcription:

Management System Registered to ISO 9001/14001 12388-88 th Avenue Tel: (604)590-7500 Surrey, British Columbia Fax: (604)590-5347 Canada V3W 7R7 www.powertechlabs.com POWERTECH LABS INC. CONNECTABILITY TESTING OF COPPER AND ALUMINUM WIRING, PHASE 2: Current Cycling Tests Mechanical Connectors PROJECT PL-00236 Prepared for the: International Copper Association Ltd. Prepared by: Chris Morton, P.Eng. Senior Engineer, Power Labs Reviewed by: Logan Connaughton, P.Eng Senior Engineer, Power Labs Signature Signature Date Date Report #: PL-00236-REP1 27 June 2014 Page 1 of 63 A6163

TABLE OF CONTENTS 1. EXECUTIVE SUMMARY... 3 2. INTRODUCTION... 4 3. TEST SAMPLES... 4 3.1 WIRE... 4 3.2 CONNECTORS... 4 3.3 SAMPLE ASSEMBLIES... 5 3.4 CONNECTOR PREPARATION... 6 3.5 TEST LOOP ASSEMBLY... 6 3.6 SAMPLE LABELLING... 10 4. TEST PROCEDURE... 12 5. TEST RESULTS... 13 5.1 TEMPERATURE CYCLE... 13 5.2 SAMPLE RE-TORQUING... 13 5.3 SAMPLE FAILURES... 14 5.4 DC RESISTANCE AND PEAK TEMPERATURE RISE VALUES... 15 5.5 SAMPLES REMOVED DURING TESTING DUE TO FAILURE... 49 5.6 ANALYSIS OF THE RESULTS... 50 6. ANALYSIS BY IEC 61238-1 METHODOLOGY... 53 7. CONCLUSIONS... 61 7.1 IEC ANALYSIS... 61 7.2 OVERALL CONCLUSIONS... 61 Report #: PL-00236-REP1 27 June 2014 Page 2 of 63

1. EXECUTIVE SUMMARY The objective of this study was to compare the electrical connectability of #1 AWG copper and #2/0 AWG 8000 series aluminum wire for use in low-voltage electrical power distribution applications. This report describes the current cycling test component on mechanical screw-type connector samples. The test connectors were standard single screw lug connectors obtained from local industrial electrical suppliers. The aluminum wire test samples were prepared with and without abrasion of the conductor surface, with and without oxide inhibitor applied to the conductor, and with the set screw tightened to 70%, 100%, and 125% of the rated torque. The copper wire samples were prepared without abrasion and without oxide inhibitor, and with the set screw tightened to 70%, 100%, and 125% of the rated torque. The wire and connector samples were subjected to accelerated ageing by current cycling using the test procedures outlined in IEC 61238-1 as a guide. Test samples were subjected to 1500 current cycles in a high humidity environment with the temperature of the conductor cycling from room temperature to 100 C rise above ambient and back to room temperature in a period of 2.25 hours. Short circuit current was also applied to each sample after 200 current cycles were completed. The dc resistance and peak temperature of each sample was monitored during the test. The overall conclusions from the testing are as follows: 1. The copper mechanical connectors on copper wire had the most stable resistance and temperature readings, and performed the best during the test. 2. The aluminum (dual rated) mechanical connectors on copper wire performed relatively poorly during the test, with 1/3 of the samples failing or showing elevated resistance and temperature levels by the end of the test. 3. The aluminum (dual rated) mechanical connectors on aluminum wire performed very poorly during the test, and had a very high failure rate even before the mid-point of the test. Over 90% of the samples had either failed or showed elevated resistance and temperature levels by the end of the test. There was no clear correlation between conductor preparation method, torque level, and failure, except that the connectors that had been torqued to 125% of the rated torque level performed marginally better than the others. Report #: PL-00236-REP1 27 June 2014 Page 3 of 63

2. INTRODUCTION The objective of this study is to compare the electrical connectability of copper and aluminum wire for use in low-voltage (<1000 V) electrical power distribution applications. The wire and connector samples used in the testing were obtained from local North American suppliers. The work was done at the request of the International Copper Association Ltd. (ICA), and was carried out at Powertech Labs, Surrey, B.C, Canada from July 2013 to February 2014. This report describes the Phase 2 (current cycling test) component of the testing on mechanical screw-type connector samples. 3. TEST SAMPLES 3.1 WIRE The wire was obtained from a local industrial supplier (Texcan) by Powertech Labs. The wire was standard, stock product that was supplied in the absence of specifying the manufacturer when ordering. The wire samples used for the testing are listed below in Table 1. Table 1. Wire samples used in the testing. Manufacturer Size Type Model Rating Voltage BICC 1 AWG Copper Not marked RW90 600V Alcan 2/0 AWG Aluminum Alloy NUAL RW90 600V 3.2 CONNECTORS Connectors were obtained for the tests from local suppliers. The connectors were standard, commonly available types from standard industrial electrical suppliers, and included the following types: Single screw mechanical lug connectors, CU rated, copper or brass body (plated) Single screw mechanical lug connectors, AL/CU dual rated, aluminum body A typical sample connector is shown in Figure 1. Report #: PL-00236-REP1 27 June 2014 Page 4 of 63

Figure 1. Typical connector sample (AL/CU dual rated shown). 3.3 SAMPLE ASSEMBLIES The test sample assemblies consisted of short lengths of bare wire terminating in an electrical connector at one end, and a current equalizer at the other end. The layout of a typical sample is shown in Figure 2. Reference (control) conductor samples with no connector were also included in the testing. Two reference samples of each conductor size and type were used. weld 12" wire connector current equalizer Figure 2. Typical connector test sample. Report #: PL-00236-REP1 27 June 2014 Page 5 of 63

3.4 CONNECTOR PREPARATION The samples included an equal number of connectors that were tightened to each of the following three torque values: 70% of rated torque. 100% of rated torque. 125% of rated torque. Where used, contact lubricant (oxide inhibitor), was applied on the connection barrel and/or conductor as directed in the manufacturer s installation instructions. A commonly available product was selected. Neither oxide inhibitor nor any other lubricant was used on the screw threads. Each copper wire sample was prepared with no wire brushing or abrasion of the wire or connector, and no oxide inhibitor was used. For the aluminum wire samples, three different preparation methods were used: 1. Wire brushing/abrasion of the bare wire surface, and application of oxide inhibitor. 2. Application of oxide inhibitor only. 3. No oxide inhibitor and no abrasion. A summary of the combinations of preparation methods for each sample is given in Table 2. 3.5 TEST LOOP ASSEMBLY The test sample assemblies were elevated on wooden rails, 3 ft. from the laboratory floor, and connected together into a series loop so that the same current level could be passed through all samples simultaneously. Samples were suspended in free air so that cooling would be by natural convection. The plan view layout of the test loop is shown in Figure 3, and a circuit schematic is shown in Figure 4. A photograph of some of the samples in the test is shown in Figure 5. Report #: PL-00236-REP1 27 June 2014 Page 6 of 63

Type Table 2. Sample preparation used for the current cycle tests. Conductor Connector Rating Abrasion Inhibitor Torque Control #1 Cu --- --- --- --- 2 Control 2/0 Al --- --- --- --- 2 Mechanical #1 Cu AL/CU N N 125% 4 Mechanical #1 Cu AL/CU N N 100% 4 Mechanical #1 Cu AL/CU N N 70% 4 Mechanical #1 Cu CU N N 125% 4 Mechanical #1 Cu CU N N 100% 4 Mechanical #1 Cu CU N N 70% 4 Mechanical 2/0 Al AL/CU Y Y 125% 4 Mechanical 2/0 Al AL/CU N Y 125% 4 Mechanical 2/0 Al AL/CU N N 125% 4 Mechanical 2/0 Al AL/CU Y Y 100% 4 Mechanical 2/0 Al AL/CU N Y 100% 4 Mechanical 2/0 Al AL/CU N N 100% 4 Mechanical 2/0 Al AL/CU Y Y 70% 4 Mechanical 2/0 Al AL/CU N Y 70% 4 Mechanical 2/0 Al AL/CU N N 70% 4 Total No. Units Report #: PL-00236-REP1 27 June 2014 Page 7 of 63

test enclosure support frame AWG CU mechanical samples AWG AL mechanical samples control conductors Figure 3. Test loop sample layout, plan view (not to scale). Current jumpers between rows of samples and are not shown. Report #: PL-00236-REP1 27 June 2014 Page 8 of 63

Data Acquisition and Control System thermocouple bundles test samples 600V AC Source Current Transformer Motor Driven Variable Autotransformer High Current Transformer Figure 4. Circuit schematic for the test loop. Figure 5. Samples set up for the test. Report #: PL-00236-REP1 27 June 2014 Page 9 of 63

3.6 SAMPLE LABELLING Samples were labelled as indicated in Table 3. Sample No. Inhibitor Abrasion Table 3. Sample labelling for all samples. Torque Conductor Type Connector Rating Manufacturer CCtrl1 --- --- --- #1 Cu Control --- --- --- CCtrl2 --- --- --- #1 Cu Control --- --- --- ACtrl1 --- --- --- 2/0 Al Control --- --- --- ACtrl2 --- --- --- 2/0 Al Control --- --- --- Model CM1 N N 125% #1 Cu Mechanical AL/CU KA26U CM2 N N 125% #1 Cu Mechanical AL/CU KA26U CM3 N N 100% #1 Cu Mechanical AL/CU KA26U CM4 N N 100% #1 Cu Mechanical AL/CU KA26U CM5 N N 70% #1 Cu Mechanical AL/CU KA26U CM6 N N 70% #1 Cu Mechanical AL/CU KA26U CM7 N N 125% #1 Cu Mechanical AL/CU ADR21 CM8 N N 125% #1 Cu Mechanical AL/CU ADR21 CM9 N N 100% #1 Cu Mechanical AL/CU ADR21 CM10 N N 100% #1 Cu Mechanical AL/CU ADR21 CM11 N N 70% #1 Cu Mechanical AL/CU ADR21 CM12 N N 70% #1 Cu Mechanical AL/CU ADR21 CM13 N N 125% #1 Cu Mechanical CU KLU125 CM14 N N 125% #1 Cu Mechanical CU KLU125 CM15 N N 100% #1 Cu Mechanical CU KLU125 CM16 N N 100% #1 Cu Mechanical CU KLU125 CM17 N N 70% #1 Cu Mechanical CU KLU125 CM18 N N 70% #1 Cu Mechanical CU KLU125 CM19 N N 125% #1 Cu Mechanical CU STC1102 CM20 N N 125% #1 Cu Mechanical CU STC1102 CM21 N N 100% #1 Cu Mechanical CU STC1102 CM22 N N 100% #1 Cu Mechanical CU STC1102 CM23 N N 70% #1 Cu Mechanical CU STC1102 CM24 N N 70% #1 Cu Mechanical CU STC1102 Table Content Redacted Report #: PL-00236-REP1 27 June 2014 Page 10 of 63

Sample No. Inhibitor Abrasion Torque Conductor Type Connector Rating Manufacturer Model AM1 Y Y 125% 2/0 Al Mechanical AL/CU KA26U AM2 Y Y 125% 2/0 Al Mechanical AL/CU KA26U AM3 Y N 125% 2/0 Al Mechanical AL/CU KA26U AM4 Y N 125% 2/0 Al Mechanical AL/CU KA26U AM5 N N 125% 2/0 Al Mechanical AL/CU KA26U AM6 N N 125% 2/0 Al Mechanical AL/CU KA26U AM7 Y Y 100% 2/0 Al Mechanical AL/CU KA26U AM8 Y Y 100% 2/0 Al Mechanical AL/CU KA26U AM9 Y N 100% 2/0 Al Mechanical AL/CU KA26U AM10 Y N 100% 2/0 Al Mechanical AL/CU KA26U AM11 N N 100% 2/0 Al Mechanical AL/CU KA26U AM12 N N 100% 2/0 Al Mechanical AL/CU KA26U AM13 Y Y 70% 2/0 Al Mechanical AL/CU KA26U AM14 Y Y 70% 2/0 Al Mechanical AL/CU KA26U AM15 Y N 70% 2/0 Al Mechanical AL/CU KA26U AM16 Y N 70% 2/0 Al Mechanical AL/CU KA26U AM17 N N 70% 2/0 Al Mechanical AL/CU KA26U AM18 N N 70% 2/0 Al Mechanical AL/CU KA26U AM19 Y Y 125% 2/0 Al Mechanical AL/CU ADR21 AM20 Y Y 125% 2/0 Al Mechanical AL/CU ADR21 AM21 Y N 125% 2/0 Al Mechanical AL/CU ADR21 AM22 Y N 125% 2/0 Al Mechanical AL/CU ADR21 AM23 N N 125% 2/0 Al Mechanical AL/CU ADR21 AM24 N N 125% 2/0 Al Mechanical AL/CU ADR21 AM25 Y Y 100% 2/0 Al Mechanical AL/CU ADR21 AM26 Y Y 100% 2/0 Al Mechanical AL/CU ADR21 AM27 Y N 100% 2/0 Al Mechanical AL/CU ADR21 AM28 Y N 100% 2/0 Al Mechanical AL/CU ADR21 AM29 N N 100% 2/0 Al Mechanical AL/CU ADR21 AM30 N N 100% 2/0 Al Mechanical AL/CU ADR21 Table Content Redacted Report #: PL-00236-REP1 27 June 2014 Page 11 of 63

Sample No. Inhibitor Abrasion Torque Conductor Type Connector Rating Manufacturer Model AM31 Y Y 70% 2/0 Al Mechanical AL/CU ADR21 Table Content Redacted AM32 Y Y 70% 2/0 Al Mechanical AL/CU ADR21 AM33 Y N 70% 2/0 Al Mechanical AL/CU ADR21 AM34 Y N 70% 2/0 Al Mechanical AL/CU ADR21 AM35 N N 70% 2/0 Al Mechanical AL/CU ADR21 AM36 N N 70% 2/0 Al Mechanical AL/CU ADR21 4. TEST PROCEDURE The wire and connector samples were subjected to accelerated ageing by current cycling. The test procedure IEC 61238-1 (2003-05), Compression and mechanical connectors for power cables for rated voltages up to 30 kv (Um = 36 kv), was used as a guide, with modifications and details as listed below: 4 samples of each configuration were tested. The numbers of samples of each type used are given in Table 2. Welded equalizers were prepared and samples were connected together palm-to-palm in accordance with ANSI C119.4-2011. Samples were subjected to 1500 heating/cooling cycles, each consisting of 1 hour of heating by applying high current followed by 1.25 hours of natural cooling with no current applied. The current level was determined at the start of the test as the current required to heat the control (reference) conductor samples to a temperature rise of 100-105 C above ambient temperature. A current level of 280 A was used for the test. One application of short-circuit current was applied to each sample after the 200 th current cycle to achieve 250 C to 270 C on the reference conductor. Samples were tested in groups, by location in the test loop. Sample assemblies were tested in an enclosure with an ambient temperature of 25-30 C during the test. The test was conducted in a high humidity environment (>90% RH, non-condensing). Humidity was maintained using atomizing sprayers which operated on a 20% duty cycle. Connector DC resistance was measured approximately every 100 cycles or less, and the temperature of connectors and reference conductors was monitored during the test. Peak temperature rise values for each connector were measured using thermocouples attached to the surface of the connector body with thermally conductive epoxy. Connection performance was evaluated by the change in the corrected dc resistance and temperature rise above the control conductor temperature over the course of the test. Report #: PL-00236-REP1 27 June 2014 Page 12 of 63

5. TEST RESULTS 5.1 TEMPERATURE CYCLE The samples completed 1500 current cycles total, with a typical heat/cooling current cycle shown in Figure 6. The small oscillations in the temperature were caused by the humidification atomizers turning on and off, which temporarily cooled the ambient temperature slightly. Figure 6. Typical heating/cooling cycle. 5.2 SAMPLE RE-TORQUING The initial test plan was to apply the required torque values when setting up the connectors at the beginning of the test, and leave the connectors in this state throughout the test. However, a large number of the aluminum wire connectors were found to be very loose (practically zero residual torque) after the application of short circuit current after 200 cycles. It was decided that, in order to continue the comparative test, all connectors would be retightened to the original starting torque levels. In a normal current cycling test the connectors would not be touched after the initial torque was applied. However, the test would not have continued to completion had the samples not been retightened. Report #: PL-00236-REP1 27 June 2014 Page 13 of 63

5.3 SAMPLE FAILURES During the test a number of connectors failed by exceeding a peak temperature level that was considered unsafe to allow them to continue with the testing. Although the connectors were still intact (i.e., the conductor had not melted or separated from the connector), they were bypassed using shunt jumpers in order to allow the test to continue. Generally, the temperature level that was considered too high to safely continue was 250 C. An example of a bypassed sample is shown in Figure 7. In one case a connector actually failed completely by melting through the conductor during the short-circuit test (see Figure 8). This sample was removed from the test. Figure 7. Sample bypassed using a shunt jumper due to overheating during testing. Report #: PL-00236-REP1 27 June 2014 Page 14 of 63

Figure 8. Sample AM32 that failed during the short-circuit test. 5.4 DC RESISTANCE AND PEAK TEMPERATURE RISE VALUES DC resistance values were recorded and corrected for temperature to 20 C 1. For comparison, samples were grouped by wire type, connector type, and preparation. The resistance data for each group of connectors is plotted in Figure 9 through Figure 24. Peak temperature rise above ambient values are the maximum temperatures reached by each connector in the selected cycles, minus the ambient temperature during that cycle. The peak temperature rise above ambient data is plotted in Figure 25 through Figure 40. 1 Temperature correction is a standard calculation that uses the following formula to calculate the resistance corrected to 20 C. This compensates for minor variations in the temperature at which the connector resistance was measured. Corrected Resistance α = temperature coefficient of resistance = 0.004 C -1 θ = connector temperature at the time of measurement Report #: PL-00236-REP1 27 June 2014 Page 15 of 63

Comments on the plots: Samples that overheated and were bypassed with a shunt jumper are labelled with the prefix BP. Bypassed samples had no further resistance and temperature measurements recorded for the remainder of the test, and are considered to have failed the test. Samples that failed by melting through of the conductor are labelled with the prefix F. The measurement made before the short-circuit test is labelled as 200 in the legend. The measurement made after the short-circuit test is labelled as 200SC in the legend. There are occasional gaps in the peak temperature rise data, which are due to thermocouples that became dislodged. The fluctuations in the resistances and temperatures of the control samples give an indication of the error limits of the readings and the normal random variations due to methodology. Report #: PL-00236-REP1 27 June 2014 Page 16 of 63

Figure 9. DC resistance of control conductor samples, corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 17 of 63

Figure 10. DC resistance of copper wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 125% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 18 of 63

Figure 11. DC resistance of copper wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 100% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 19 of 63

Figure 12. DC resistance of copper wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 70% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 20 of 63

Figure 13. DC resistance of copper wire with CU connectors, no wire abrasion, no oxide inhibitor applied, at 125% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 21 of 63

Figure 14. DC resistance of copper wire with CU connectors, no wire abrasion, no oxide inhibitor applied, at 100% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 22 of 63

Figure 15. DC resistance of copper wire with CU connectors, no wire abrasion, no oxide inhibitor applied, at 70% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 23 of 63

Figure 16. DC resistance of aluminum wire with AL/CU dual-rated connectors, with wire abrasion, with oxide inhibitor applied, at 125% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 24 of 63

Figure 17. DC resistance of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, with oxide inhibitor applied, at 125% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 25 of 63

Figure 18. DC resistance of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 125% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 26 of 63

Figure 19. DC resistance of aluminum wire with AL/CU dual-rated connectors, with wire abrasion, with oxide inhibitor applied, at 100% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 27 of 63

Figure 20. DC resistance of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, with oxide inhibitor applied, at 100% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 28 of 63

Figure 21. DC resistance of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 100% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 29 of 63

Figure 22. DC resistance of aluminum wire with AL/CU dual-rated connectors, with wire abrasion, with oxide inhibitor applied, at 70% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 30 of 63

Figure 23. DC resistance of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, with oxide inhibitor applied, at 70% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 31 of 63

Figure 24. DC resistance of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 70% of rated torque at the start of the test. Resistance values are corrected to 20 C. Report #: PL-00236-REP1 27 June 2014 Page 32 of 63

Figure 25. Peak temperature rise above ambient temperature of the control conductor samples. Report #: PL-00236-REP1 27 June 2014 Page 33 of 63

Figure 26. Peak temperature rise above ambient temperature of copper wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 125% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 34 of 63

Figure 27. Peak temperature rise above ambient temperature of copper wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 100% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 35 of 63

Figure 28. Peak temperature rise above ambient temperature of copper wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 70% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 36 of 63

Figure 29. Peak temperature rise above ambient temperature of copper wire with CU connectors, no wire abrasion, no oxide inhibitor applied, at 125% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 37 of 63

Figure 30. Peak temperature rise above ambient temperature of copper wire with CU connectors, no wire abrasion, no oxide inhibitor applied, at 100% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 38 of 63

Figure 31. Peak temperature rise above ambient temperature of copper wire with CU connectors, no wire abrasion, no oxide inhibitor applied, at 70% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 39 of 63

Figure 32. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, with wire abrasion, with oxide inhibitor applied, at 125% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 40 of 63

Figure 33. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, with oxide inhibitor applied, at 125% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 41 of 63

Figure 34. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 125% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 42 of 63

Figure 35. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, with wire abrasion, with oxide inhibitor applied, at 100% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 43 of 63

Figure 36. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, with oxide inhibitor applied, at 100% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 44 of 63

Figure 37. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 100% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 45 of 63

Figure 38. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, with wire abrasion, with oxide inhibitor applied, at 70% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 46 of 63

Figure 39. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, with oxide inhibitor applied, at 70% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 47 of 63

Figure 40. Peak temperature rise above ambient temperature of aluminum wire with AL/CU dual-rated connectors, no wire abrasion, no oxide inhibitor applied, at 70% of rated torque at the start of the test. Report #: PL-00236-REP1 27 June 2014 Page 48 of 63

5.5 SAMPLES REMOVED DURING TESTING DUE TO FAILURE The list of samples that overheated or failed during testing are listed in Table 4, in order of the cycle in which they overheated or failed. Failed at cycle Table 4. Samples that were bypassed due to overheating or failure. Sample No. Abrasion Inhibitor Torque /Compression Conductor Type Connector Rating 1 AM30 N N 100% 2/0 Al Mechanical AL/CU 1 AM35 N N 70% 2/0 Al Mechanical AL/CU 3 AM3 N Y 125% 2/0 Al Mechanical AL/CU 3 AM4 N Y 125% 2/0 Al Mechanical AL/CU 25 AM7 Y Y 100% 2/0 Al Mechanical AL/CU 25 AM8 Y Y 100% 2/0 Al Mechanical AL/CU 25 AM15 N Y 70% 2/0 Al Mechanical AL/CU 25 AM16 N Y 70% 2/0 Al Mechanical AL/CU 145 AM9 N Y 100% 2/0 Al Mechanical AL/CU 153 AM33 N Y 70% 2/0 Al Mechanical AL/CU 153 AM34 N Y 70% 2/0 Al Mechanical AL/CU 200 AM32 Y Y 70% 2/0 Al Mechanical AL/CU 201 AM11 N N 100% 2/0 Al Mechanical AL/CU 201 AM12 N N 100% 2/0 Al Mechanical AL/CU 204 AM6 N N 125% 2/0 Al Mechanical AL/CU 204 AM10 N Y 100% 2/0 Al Mechanical AL/CU 204 AM31 Y Y 70% 2/0 Al Mechanical AL/CU 204 AM36 N N 70% 2/0 Al Mechanical AL/CU 217 AM27 N Y 100% 2/0 Al Mechanical AL/CU 217 AM28 N Y 100% 2/0 Al Mechanical AL/CU 222 AM29 N N 100% 2/0 Al Mechanical AL/CU 266 AM13 Y Y 70% 2/0 Al Mechanical AL/CU 266 AM14 Y Y 70% 2/0 Al Mechanical AL/CU 303 AM26 Y Y 100% 2/0 Al Mechanical AL/CU 379 AM18 N N 70% 2/0 Al Mechanical AL/CU 487 AM25 Y Y 100% 2/0 Al Mechanical AL/CU 523 CM4 N N 100% #1 Cu Mechanical AL/CU 941 CM1 N N 125% #1 Cu Mechanical AL/CU Report #: PL-00236-REP1 27 June 2014 Page 49 of 63

5.6 ANALYSIS OF THE RESULTS The results were analyzed by comparing the change in corrected resistances and peak temperature rises above ambient for each type of connector sample at the end of the test. The change in resistance was determined as the percent difference between the values after 1500 cycles compared to the values after 25 cycles. A plot of the change in resistance for each connector after 1500 current cycles is shown in Figure 41. The peak temperature rise was determined as the difference between the peak connector temperature and the peak control conductor temperature at the end of the test. A plot of the temperature rise difference between each connector and the control conductors at 1500 current cycles is shown in Figure 42. Table 5 gives a summary of the results for the connector samples by change in resistance and temperature, grouped by the type and preparation of the samples. Type Table 5. Summary of sample performance by type and preparation. Conductor Connector Rating Abrasion Inhibitor Torque Total No. Units No. Showing >10% increase in resistance No. with Connector Temp. > Control Temp. Mechanical #1 Cu AL/CU N N 125% 4 2 1 1 Mechanical #1 Cu AL/CU N N 100% 4 1 1 1 Mechanical #1 Cu AL/CU N N 70% 4 1 1 0 Mechanical #1 Cu CU N N 125% 4 0 0 0 Mechanical #1 Cu CU N N 100% 4 0 0 0 Mechanical #1 Cu CU N N 70% 4 0 0 0 Mechanical 2/0 Al AL/CU Y Y 125% 4 1 2 0 Mechanical 2/0 Al AL/CU N Y 125% 4 4 4 2 Mechanical 2/0 Al AL/CU N N 125% 4 2 4 1 Mechanical 2/0 Al AL/CU Y Y 100% 4 4 4 4 Mechanical 2/0 Al AL/CU N Y 100% 4 4 4 4 Mechanical 2/0 Al AL/CU N N 100% 4 4 4 4 Mechanical 2/0 Al AL/CU Y Y 70% 4 4 4 4 Mechanical 2/0 Al AL/CU N Y 70% 4 4 4 4 Mechanical 2/0 Al AL/CU N N 70% 4 4 4 3 No. Failed Report #: PL-00236-REP1 27 June 2014 Page 50 of 63

Figure 41. Change in corrected resistance from cycle 25 to cycle 1500 for each sample. Samples are grouped by type and preparation. Solid bars indicate samples that failed and were removed from the test. Report #: PL-00236-REP1 27 June 2014 Page 51 of 63

Figure 42. Difference between connector temperature rise and control conductor temperature rise after cycle 1500 for each sample. Samples are grouped by type and preparation. Solid bars indicate samples that failed and were removed from the test. Report #: PL-00236-REP1 27 June 2014 Page 52 of 63

6. ANALYSIS BY IEC 61238-1 METHODOLOGY The standard IEC 61238-1 (2003-05), Compression and mechanical connectors for power cables for rated voltages up to 30 kv (Um = 36 kv), was used as a guide for evaluating samples. The standard uses the following criteria to evaluate the performance: Initial scatter of resistance values for all connectors of the same type at the start of the test. Mean scatter of resistance values for all connectors of the same type throughout the test. Change in resistance factor 2 of each connector throughout the test. Resistance factor ratio of each connector, comparing the resistance factor at the end of the test to the start of the test. Maximum temperature difference between each connector compared to the control (reference) conductor temperature. Evaluation of the values up to cycle 1000. Of these values, the initial scatter and mean scatter are not applicable since there are not enough samples of each type and preparation to make these values meaningful. Due to variations in the test procedure compared to the IEC standard procedure, the change in resistance factor was not evaluated. The maximum values required by IEC 61238-1 are: Resistance factor ratio 2.0 Maximum connector temperature θ ref (θ ref = max. temperature of the control conductor) A summary of the IEC analysis is shown in Table 6. The resistance ratio values and maximum connector temperature for each type of connector are summarized in Table 7 and Table 8 respectively, and are shown in Figure 43 and Figure 44. 2 The resistance factor is a dimensionless value that is defined as the ratio of the resistance per unit length of the connector to that for the control conductor. Report #: PL-00236-REP1 27 June 2014 Page 53 of 63

Conductor Connector Rating Table 6. Summary of IEC Analysis. Abrasion Inhibitor Torque Results of IEC Analysis (see Note (1) below) Maximum Resistance Factor Ratio Temperature Difference (samplecontrol) No. Pass No. Fail No. Pass No. Fail #1 Cu AL/CU N N 125% 1 3 2 2 #1 Cu AL/CU N N 100% 2 2 2 2 #1 Cu AL/CU N N 70% 2 2 4 0 #1 Cu CU N N 125% 4 0 4 0 #1 Cu CU N N 100% 4 0 2 2 (2) #1 Cu CU N N 70% 4 0 3 1 (2) 2/0 Al AL/CU Y Y 125% 2 2 2 2 2/0 Al AL/CU N Y 125% 1 3 0 4 2/0 Al AL/CU N N 125% 1 3 0 4 2/0 Al AL/CU Y Y 100% 0 4 0 4 2/0 Al AL/CU N Y 100% 0 4 0 4 2/0 Al AL/CU N N 100% 0 4 0 4 2/0 Al AL/CU Y Y 70% 0 4 0 4 2/0 Al AL/CU N Y 70% 0 4 0 4 2/0 Al AL/CU N N 70% 0 4 0 4 Note (1): - Any resistance factor ratio > 2.0 or maximum connector temperature that exceeds the control conductor temperature at any time during the test is considered a failure by IEC. There is no method to differentiate connectors that exceeded the limit by a small amount and those that exceeded the limit by a large amount. There is also no allowance for connectors that briefly exceed the limit in the middle of the test, but then drop below the limit by the end of the test. Note (2): - The copper connectors on copper wire, with 100% and 70% torque applied, exceeded the control conductor temperature by a small amount in the middle of the test, but dropped below the control conductor temperature by the end of the test. Report #: PL-00236-REP1 27 June 2014 Page 54 of 63

Table 7. Results of evaluation of resistance factor ratio for IEC. Sample Connector Resistance factor Conductor Abrasion Inhibitor Torque No. Rating ratio Pass/Fail BP CM1 #1 Cu AL/CU N N 125% did not finish fail CM2 #1 Cu AL/CU N N 125% 3.17 fail CM7 #1 Cu AL/CU N N 125% 2.07 fail CM8 #1 Cu AL/CU N N 125% 1.72 pass CM3 #1 Cu AL/CU N N 100% 9.16 fail BP CM4 #1 Cu AL/CU N N 100% did not finish fail CM9 #1 Cu AL/CU N N 100% 1.84 pass CM10 #1 Cu AL/CU N N 100% 1.89 pass CM5 #1 Cu AL/CU N N 70% 2.81 fail CM6 #1 Cu AL/CU N N 70% 2.28 fail CM11 #1 Cu AL/CU N N 70% 1.93 pass CM12 #1 Cu AL/CU N N 70% 1.76 pass CM13 #1 Cu CU N N 125% 1.33 pass CM14 #1 Cu CU N N 125% 1.35 pass CM19 #1 Cu CU N N 125% 1.18 pass CM20 #1 Cu CU N N 125% 1.48 pass CM15 #1 Cu CU N N 100% 1.40 pass CM16 #1 Cu CU N N 100% 1.28 pass CM21 #1 Cu CU N N 100% 1.17 pass CM22 #1 Cu CU N N 100% 1.00 pass CM17 #1 Cu CU N N 70% 1.14 pass CM18 #1 Cu CU N N 70% 1.25 pass CM23 #1 Cu CU N N 70% 1.41 pass CM24 #1 Cu CU N N 70% 1.43 pass AM1 2/0 Al AL/CU Y Y 125% 1.94 pass AM2 2/0 Al AL/CU Y Y 125% 1.49 pass AM19 2/0 Al AL/CU Y Y 125% 3.25 fail AM20 2/0 Al AL/CU Y Y 125% 2.26 fail BP AM3 2/0 Al AL/CU N Y 125% did not finish fail BP AM4 2/0 Al AL/CU N Y 125% did not finish fail AM21 2/0 Al AL/CU N Y 125% 3.51 fail AM22 2/0 Al AL/CU N Y 125% 1.95 pass AM5 2/0 Al AL/CU N N 125% 5.42 fail BP AM6 2/0 Al AL/CU N N 125% did not finish fail AM23 2/0 Al AL/CU N N 125% 2.77 fail AM24 2/0 Al AL/CU N N 125% 1.58 pass Report #: PL-00236-REP1 27 June 2014 Page 55 of 63

Sample No. Table 8. Results of evaluation of resistance factor ratio for IEC cont d. Conductor Connector Rating Abrasion Inhibitor Torque Difference Between Connector and Control Temperature Pass/Fail BP AM7 2/0 Al AL/CU Y Y 100% did not finish fail BP AM8 2/0 Al AL/CU Y Y 100% did not finish fail BP AM25 2/0 Al AL/CU Y Y 100% did not finish fail BP AM26 2/0 Al AL/CU Y Y 100% did not finish fail BP AM9 2/0 Al AL/CU N Y 100% did not finish fail BP AM10 2/0 Al AL/CU N Y 100% did not finish fail BP AM27 2/0 Al AL/CU N Y 100% did not finish fail BP AM28 2/0 Al AL/CU N Y 100% did not finish fail BP AM11 2/0 Al AL/CU N N 100% did not finish fail BP AM12 2/0 Al AL/CU N N 100% did not finish fail BP AM29 2/0 Al AL/CU N N 100% did not finish fail BP AM30 2/0 Al AL/CU N N 100% did not finish fail BP AM13 2/0 Al AL/CU Y Y 70% did not finish fail BP AM14 2/0 Al AL/CU Y Y 70% did not finish fail BP AM31 2/0 Al AL/CU Y Y 70% did not finish fail F AM32 2/0 Al AL/CU Y Y 70% did not finish fail BP AM15 2/0 Al AL/CU N Y 70% did not finish fail BP AM16 2/0 Al AL/CU N Y 70% did not finish fail BP AM33 2/0 Al AL/CU N Y 70% did not finish fail BP AM34 2/0 Al AL/CU N Y 70% did not finish fail AM17 2/0 Al AL/CU N N 70% 5.27 fail BP AM18 2/0 Al AL/CU N N 70% did not finish fail BP AM35 2/0 Al AL/CU N N 70% did not finish fail BP AM36 2/0 Al AL/CU N N 70% did not finish fail Report #: PL-00236-REP1 27 June 2014 Page 56 of 63

Sample No. Table 9. Results of evaluation of maximum connector temperature for IEC. Conductor Connector Rating Abrasion Inhibitor Torque Difference Between Connector and Control Temperature Pass/Fail BP CM1 #1 Cu AL/CU N N 125% did not finish fail CM2 #1 Cu AL/CU N N 125% 28.95 fail CM7 #1 Cu AL/CU N N 125% -8.55 pass CM8 #1 Cu AL/CU N N 125% -7.95 pass CM3 #1 Cu AL/CU N N 100% 54.45 fail BP CM4 #1 Cu AL/CU N N 100% did not finish fail CM9 #1 Cu AL/CU N N 100% -7.4 pass CM10 #1 Cu AL/CU N N 100% -5.8 pass CM5 #1 Cu AL/CU N N 70% -0.65 pass CM6 #1 Cu AL/CU N N 70% -8.15 pass CM11 #1 Cu AL/CU N N 70% -2.15 pass CM12 #1 Cu AL/CU N N 70% -0.35 pass CM13 #1 Cu CU N N 125% -3.35 pass CM14 #1 Cu CU N N 125% -2.55 pass CM19 #1 Cu CU N N 125% -8.05 pass CM20 #1 Cu CU N N 125% -8.05 pass CM15 #1 Cu CU N N 100% -3.05 pass CM16 #1 Cu CU N N 100% -1.25 pass CM21 #1 Cu CU N N 100% 1.35 fail CM22 #1 Cu CU N N 100% 2.05 fail CM17 #1 Cu CU N N 70% 3.95 fail CM18 #1 Cu CU N N 70% -0.55 pass CM23 #1 Cu CU N N 70% -4.95 pass CM24 #1 Cu CU N N 70% -5.95 pass AM1 2/0 Al AL/CU Y Y 125% -7.5 pass AM2 2/0 Al AL/CU Y Y 125% -3.7 pass AM19 2/0 Al AL/CU Y Y 125% 37.9 fail AM20 2/0 Al AL/CU Y Y 125% 39.05 fail BP AM3 2/0 Al AL/CU N Y 125% did not finish fail BP AM4 2/0 Al AL/CU N Y 125% did not finish fail AM21 2/0 Al AL/CU N Y 125% 45.95 fail AM22 2/0 Al AL/CU N Y 125% 32.15 fail AM5 2/0 Al AL/CU N N 125% 52.5 fail BP AM6 2/0 Al AL/CU N N 125% did not finish fail AM23 2/0 Al AL/CU N N 125% 50.15 fail AM24 2/0 Al AL/CU N N 125% 47.35 fail Report #: PL-00236-REP1 27 June 2014 Page 57 of 63

Table 10. Results of evaluation of maximum connector temperature for IEC cont d. Sample No. Conductor Connector Rating Abrasion Inhibitor Torque Difference Between Connector and Control Temperature Pass/Fail BP AM7 2/0 Al AL/CU Y Y 100% did not finish fail BP AM8 2/0 Al AL/CU Y Y 100% did not finish fail BP AM25 2/0 Al AL/CU Y Y 100% did not finish fail BP AM26 2/0 Al AL/CU Y Y 100% did not finish fail BP AM9 2/0 Al AL/CU N Y 100% did not finish fail BP AM10 2/0 Al AL/CU N Y 100% did not finish fail BP AM27 2/0 Al AL/CU N Y 100% did not finish fail BP AM28 2/0 Al AL/CU N Y 100% did not finish fail BP AM11 2/0 Al AL/CU N N 100% did not finish fail BP AM12 2/0 Al AL/CU N N 100% did not finish fail BP AM29 2/0 Al AL/CU N N 100% did not finish fail BP AM30 2/0 Al AL/CU N N 100% did not finish fail BP AM13 2/0 Al AL/CU Y Y 70% did not finish fail BP AM14 2/0 Al AL/CU Y Y 70% did not finish fail BP AM31 2/0 Al AL/CU Y Y 70% did not finish fail F AM32 2/0 Al AL/CU Y Y 70% did not finish fail BP AM15 2/0 Al AL/CU N Y 70% did not finish fail BP AM16 2/0 Al AL/CU N Y 70% did not finish fail BP AM33 2/0 Al AL/CU N Y 70% did not finish fail BP AM34 2/0 Al AL/CU N Y 70% did not finish fail AM17 2/0 Al AL/CU N N 70% 116.6 fail BP AM18 2/0 Al AL/CU N N 70% did not finish fail BP AM35 2/0 Al AL/CU N N 70% did not finish fail BP AM36 2/0 Al AL/CU N N 70% did not finish fail Report #: PL-00236-REP1 27 June 2014 Page 58 of 63

Figure 43. IEC resistance factor ratio for each sample, with the maximum IEC limit indicated by a line at 2.0. Samples are grouped by type and preparation. Solid bars indicate samples that failed and were removed from the test. Report #: PL-00236-REP1 27 June 2014 Page 59 of 63

Figure 44. IEC maximum difference between connector temperature and control conductor for each sample. Samples are grouped by type and preparation. Solid bars indicate samples that failed and were removed from the test. Report #: PL-00236-REP1 27 June 2014 Page 60 of 63

7. CONCLUSIONS 7.1 IEC ANALYSIS The IEC analysis provides a quantified, standardized method of evaluating connectors. However, because this analysis normalizes and averages the results over the full duration of the test, it does not necessarily give a complete picture of the trends throughout the test. IEC also considers failure of any sample in any of the evaluation criteria at any point in the test to be failure of the test. In this test, no sample sets were able to achieve an overall pass rating according to IEC, so this evaluation criteria alone is not sufficient to compare the performance of the different types of connectors. Overall, a good performing connector should exhibit a trend of stability of resistance and temperature readings throughout the test, particularly during the latter half of the test. The general results of the IEC analysis were as follows: 1. Mechanical dual-rated (AL/CU) connectors on #1 AWG copper wire: Resistance factor ratio: fail Maximum connector temperature: fail 2. Mechanical copper (CU) connectors on #1 AWG copper wire: Resistance factor ratio: pass Maximum connector temperature: fail * * Although the rating is a fail by the strict interpretation of IEC analysis, the connector temperatures exceeded the control conductor temperature only a small amount and for a few cycles in the middle of the test. 3. Mechanical dual-rated (AL/CU) connectors on #2/0 AWG aluminum wire: Resistance factor ratio: Maximum connector temperature: fail fail 7.2 OVERALL CONCLUSIONS The general conclusions from the testing to 1500 cycles are: 1. Mechanical dual-rated (AL/CU) connectors on #1 AWG copper wire: 33% of the samples failed or showed a trend of significantly increasing resistance and temperature by the end of the test. There was no definite correlation between performance and the torque level applied to the connectors at the start of the test. 2. Mechanical copper (CU) connectors on #1 AWG copper wire: All samples had a relatively stable resistance and temperature over the course of the test. No samples failed, and none showed a trend of significantly increasing resistance and temperature by the end of the test. Report #: PL-00236-REP1 27 June 2014 Page 61 of 63

3. Mechanical dual-rated (AL/CU) connectors on #2/0 AWG aluminum wire: 94% of the samples failed or showed a trend of significantly increasing resistance and temperature by the end of the test. The best performance was achieved by the samples that had been prepared with the conductor wire brushed (abraded), oxide inhibitor applied, and a torque level of 125% of the rated torque. A summary plot of the connector performance in the testing is shown in Figure 45. The overall conclusions from the testing to 1500 current cycles are as follows: 1. The copper mechanical connectors on copper wire had the most stable resistance and temperature readings, and performed the best during the test. 2. The aluminum (dual rated) mechanical connectors on copper wire performed relatively poorly during the test, with 1/3 of the samples failing or showing elevated resistance and temperature levels by the end of the test. 3. The aluminum (dual rated) mechanical connectors on aluminum wire performed very poorly during the test, and had a very high failure rate even before the mid-point of the test. Over 90% of the samples had either failed or showed elevated resistance and temperature levels by the end of the test. There was no clear correlation between conductor preparation method, torque level, and failure, except that the connectors that had been torqued to 125% of the rated torque level seemed to perform slightly better than the others. Report #: PL-00236-REP1 27 June 2014 Page 62 of 63

Figure 45. Overall summary of the results. Report #: PL-00236-REP1 27 June 2014 Page 63 of 63