Experimental Study on behavior of Interior RC Beam Column Joints Subjected to Cyclic Loading P.Rajaram 1 A.Murugesan 2 and G.S.

Similar documents
Investigation on Behaviour of Reinforced Concrete Beam Column Joints Retrofitted with FRP Wrapping

SEISMIC RETROFIT OF BEAM-COLUMN JOINTS WITH FRP SHEETS

High Performance and Efficiency of Joints in Precast Members

Behaviour of Reinforced Concrete Dual Structural System: Strength, Deformation Characteristics, and Failure Mechanism

SEISMIC STRENGTHENING OF PARTIALLY INFILL RC BUILDINGS USING BRICK INSERTS - EXPERIMENTAL INVESTIGATION ON 3D MODEL STRUCTURE

In-plane testing of precast concrete wall panels with grouted sleeve

EXPERIMENTAL RESULTS

RETROFITTING OF COLUMNS WITH RC JACKETTING AN EXPERIMENTAL BEHAVIOR

SEISMIC RETROFITTING OF REINFORCED CONCRETE COLUMNS USING CARBON FIBER REINFORCED POLYMER (CFRP)

Seismic Behaviour of RC Shear Walls

EXPERIMENTAL STUDY ON FLEXURAL BEHAVIOUR OF REINFORCED CONCRETE HOLLOW CORE SANDWICH BEAMS

Retrofitting of Reinforced Concrete Beam with Externally Bonded CFRP

Seismic Detailing of RC Structures (IS: )

RESPONSE OF SUBSTANDARD REINFORCING DETAILS T CONNECTIONS UPGRADED WITH CONCRETE COVERS AND CFRP

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

SEISMIC ANALYSIS OF SIX STOREYED RC FRAMED BUILDING WITH BRACING SYSTEMS

Behavior and Strength of Slab-Edge Beam-Column Connections under Shear Force and Moment

Volume 1. HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents

ANALYTICAL STUDY OF ECCENTRIC BEAM COLOUMN JOINT

Experimental Study on Wall-Frame Connection of Confined Masonry Wall

Modelling of RC moment resisting frames with precast-prestressed flooring system

SHEAR PERFORMANCE OF RC MEMBERS STRENGTHENED WITH EXTERNALLY BONDED FRP WRAPS

CYCLIC BEHAVIOR OF SLENDER R/C COLUMNS WITH INSUFFICIENT LAP SPLICE LENGTH

GFRP retrofitted RC frames with columns subjected to high axial stresses

PERFORMANCE OF RC BRIDGE COLUMNS SUBJECTED TO LATERAL LOADING

Jagannathan Saravanan et al IJCSET January 2012 Vol 2, Issue 1,

Strengthening of infilled RC frames by CFRP

1. INTRODUCTION. Fig.1 Dimension of test specimen

Cyclic behaviour of RC beams using SIFCON Sections

NON ENGINEERED REINFORCED CONCRETE BUILDINGSS

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

Sabah Shawkat Cabinet of Structural Engineering 2017

BEHAVIOR OF REINFORCED CONCRETE BEAM WITH OPENING

SEISMIC TEST OF CONCRETE BLOCK INFILLED REINFORCED CONCRETE FRAMES

STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES

INHERENT DUCTILITY OF REINFORCED CONCRETE SHEAR WALLS WITH NON-SEISMIC DETAILING

Seismic Retrofit Of RC Columns With Inadequate Lap-Splice Length By External Post-Tensioned High-Strength Strips

Hybrid Reinforced Concrete Frame Building with Pumice Brick Masonry Infill under Static Lateral Loading

SEISMIC PERFORMANCE OF FLAT-SLAB SHEAR REINFORCEMENT

EXPERIMENTAL STUDY ON RC COLUMNS RETROFITTED BY FRP AND SUBJECTED TO SEISMIC LOADING

Experimental Study of Reinforced Concrete (RC) Beams Strengthened by Carbon Fiber Reinforced Polymer (CFRP): Effect of Beam Size and Length of CFRP.

STUDY AND BEHAVIOR OF INFILLED VIERENDEEL REINFORCED CONCRETE FRAME WITH OPENINGS UNDER STATIC CYCLIC LOADING WITH P.C.C INFILLING

Interaction between ductile RC perimeter frames and floor slabs containing precast units

Comparative Study of R.C.C and Steel Concrete Composite Structures

Reinforced concrete beam-column joints with lap splices under cyclic loading

Pacific Earthquake Engineering Research Center

Experimental investigation of the use of CFRP grid for shear strengthening of RC beams

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

Effect of Near Surface Mounted (NSM) Steel Bars on Shear Strength of RC Beams

Pile to Slab Bridge Connections

Council on Tall Buildings

A STUDY ON THE BEHAVIOUR OF RC BEAMS RETROFITTED USING CFRP LAMINATES UNDER SINGLE POINT LOADING

Analytical Study on Seismic Performance of Hybrid (DUAL) Structural System Subjected To Earthquake

SHEAR BEHAVIOR OF RC DEEP BEAMS WITH SOLID CIRCULAR CROSS SECTION UNDER SIMPLY SUPPORTED CONDITION AND ANTI-SYMMETRIC MOMENT

Effect of beam dimensions on structural performance of wide beam-column joints

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING

Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

IMPROVING SHEAR CAPACITY OF RC BEAMS USING EPOXY BONDED CONTINOUS STEEL PLATES

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure

DUCTILITY REQUIREMENTS FOR BUILDINGS

STRENGTHENING WITH WING WALLS FOR SEISMICALLY SUBSTANDARD R/C BEAM-COLUMN JOINTS

A Study on Hybrid FRP Wrapped Axially Loaded RC Capsule Column

Reinforced Concrete Design. Lecture no. 1

International Journal for Research in Technological Studies Vol. 1, Issue 8, July 2014 ISSN (online):

EXPERIMENTAL STUDY ON REINFORCED CONCRETE COLUMN STRENGTHENED WITH FERROCEMENT JACKET

NONLINEAR FINITE ELEMENT ANALYSIS OF NON- SEISMICALLY DETAILED INTERIOR RC BEAM-COLUMN CONNECTION UNDER REVERSED CYCLIC LOAD

RESILIENT INFRASTRUCTURE June 1 4, 2016

Infill Precast Panels as Retrofit System of Reinforced Concrete Frames

Analytical Investigation of Seismic Performance of Exterior RC Beam-Column Joints Rehabilitated with New Scheme

EARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS. By Ir. Heng Tang Hai

Experimental Investigation of Vertical Connections in Precast Wall Panel under Shear Load

Structural Upgrade of Reinforced Concrete Column-Tie Beam Assembly using FRP Composites

SHEAR STRENGTH CAPACITY OF PRESTRESSED CONCRETE BEAM- COLUMN JOINT FOCUSING ON TENDON ANCHORAGE LOCATION

Moment curvature analysis of concrete flexural members confined with CFRP grids

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

TENSILE STRENGTH OF BRICK MASONRY. A.R. Santhakumar 1, S.Ashok 2

Upgrading the shear strength of non-ductile reinforced concrete frame connections using FRP overlay systems

Comparative Study on ECC and RCC Beam Column Connections for Enhancing Seismic Resistance

Stability Analysis of Rigid Steel Frames With and Without Bracing Systems under the Effect of Seismic and Wind Loads

Energy Absorption Characteristics of Steel, Polypropylene and Hybrid Fiber Reinforced Concrete Prisms

Performance of elevated tanks in M w 7.7 Bhuj earthquake of January 26th, 2001

FLEXURAL IMPROVEMENT OF PLAIN CONCRETE BEAMS STRENGTHENED WITH HIGH PERFORMANCE FIBRE REINFORCED CONCRETE

Performance of Buildings During the January 26, 2001 Bhuj Earthquake. Abstract

Investigation of the behavior of stiffened steel plate shear walls with Finite element method

CYCLIC BEHAVIOUR OF SANDWICH CONCRETE BEAM UNDER FLEXURAL LOADING

Nonlinear Analysis of Shear Dominant Prestressed Concrete Beams using ANSYS

LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS. Qiang SHEN Graduate Research Assistant. Yahya C. KURAMA Assistant Professor

EXPERIMENTAL STUDY ON THE SEISMIC PERFORMANCE OF EXTERNALLY CONFINED REINFORCED CONCRETE COLUMNS

Finite Element Analysis of RC Beams Strengthened with FRP Sheets under Bending

Applications of sustainable post-tensioned concrete slabs

Seismic Behavior of Beam Column Joints in Reinforced Concrete Moment Resisting Frames

The cracking behaviour of reinforced concrete beams under static and dynamic loading

RESILIENT INFRASTRUCTURE June 1 4, 2016

Strengthening of Reinforced Concrete Beams using Near-Surface Mounted FRP Mohamed Husain 1, Khaled Fawzy 2, and Mahmoud Nasr 3

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

SEISMIC PERFORMANCE AND RETROFIT OF BRIDGE FOOTINGS. David I. McLean 1

STRENGTH AND BEHAVIOUR OF GEOPOLYMER CONCRETE BEAMS

Role of Fibre in Reinforcement of Structure During Earthquake

Transcription:

Experimental Study on behavior of Interior RC Beam Column Joints Subjected to Cyclic Loading P.Rajaram 1 A.Murugesan 2 and G.S.Thirugnanam 3 1 P.G.Student, Department of Civil Engineering, Institute of Road And Transport Technology, Erode 638316, Tamil Nadu, India.. 2 Research Scholar, Department of Civil Engineering, Sona College of technology, salem 636005, Tamil Nadu, India. 3 Assistant Professor and Head of Department of Civil Engineering, Institute of Road And Transport Technology, Erode 638316, Tamil Nadu, India.. gst_irtt@yahoo.co.in ABSTRACT Beam column joint is an important component of a reinforced concrete moment resisting frame and should be designed and detailed properly, especially when the frame is subjected to earthquake loading. Failure of beam column joints during earthquake is governed by bond and shear failure mechanism which are brittle in nature. Therefore, a current international code gives high importance to provide adequate anchorage to longitudinal bars and confinement of core concrete in resisting shear. Modern codes provide for reduction of seismic forces through provision of special ductility requirements. Details for achieving ductility in reinforced concrete structures are given in IS 13920. A two bay five storey reinforcement cement concrete moment resisting frame for a general building has been analyses and designed in STAAD Pro as per IS 1893 2002 code procedures and detailed as IS 13920 1993 recommendations. A beam column joint has been modeled to a scale of 1/5 th from the prototype and the model has been subjected to cyclic loading to find its behavior during earthquake. Non linear analysis is carried out in ANSYS software. Key Words: Beam Column Joint, Earthquake resistant Structures. 1. Introduction: The behavior of reinforced concrete moment resisting frame structures in recent earthquakes all over the world has highlighted the consequences of poor performance of beam column joints. Beam column joints in a reinforced concrete moment resisting frame are crucial zones for transfer of loads effectively between the connecting elements (i.e. beams and columns) in the structure. In the analysis of reinforced concrete moment resisting frames, the joints are generally assumed as rigid. In Indian practice, the joint is usually neglected for specific design with attention being restricted to provision of sufficient anchorage for beam longitudinal reinforcement. This may be acceptable when the frame is not subjected to earthquake loads. There have been many catastrophic failures reported in the past 49

earthquakes, in particular with Turkey and Taiwan earthquakes occurred in 1999, which have been attributed to beam column joints. The poor design practice of beam column joints is compounded by the high demand imposed by the adjoining flexural members (beams and columns) in the event of mobilizing their inelastic capacities to dissipate seismic energy. Unsafe design and detailing within the joint region jeopardize the entire structure, even if other structural members conform to the design requirements. Since past three decades, extensive research has been carried out on studying the behavior of joints under seismic conditions through experimental and analytical studies. Various international codes of practices have been undergoing periodic revisions to incorporate the research findings into practice. In RC buildings, portions of columns that are common to beams at their intersections are called beam column joints. Since their constituent materials have limited strengths, the joints have limited force carrying capacity. When forces larger than these are applied during earthquakes, joints are severely damaged. Repairing damaged joints is difficult, and so damage must be avoided. Thus, beam column joints must be designed to resist earthquake effects. Under earthquake shaking, the beams adjoining a joint are subjected to moments in the same (clockwise or counterclockwise) direction. Under these moments, the top bars in the beam column joint are pulled in one direction and the bottom ones in the opposite direction. These forces are balanced by bond stress developed between concrete and steel in the joint region. If the column is not wide enough or if the strength of concrete in the joint is low, there is insufficient grip of concrete on the steel bars. In such circumstances, the bar slips inside the joint region, and beams lose their capacity to carry load. Further, under the action of the above pull push forces at top and bottom ends, joints undergo geometric distortion; one diagonal length of the joint elongates and the other compresses. If the column cross sectional size is insufficient, the concrete in the joint develops diagonal cracks. 1.1. Types of joints in frames: The joint is defined as the portion of the column within the depth of the deepest beam that frames into the column1. In a moment resisting frame, three types of joints can be identified viz. interior joint, exterior joint and corner joint (Fig.1). When four beams frame into the vertical faces of a column, the joint is called as an interior joint. When one beam frames into a vertical face of the column and two other beams frame from perpendicular directions into the joint, then the joint is called as an exterior joint. When a beam each frames into two adjacent vertical faces of a column, then the joint is called as a corner joint. The severity of forces and demands on the performance of these joints calls for greater understanding of their seismic behavior. These forces develop complex mechanisms involving bond and shear within the joint. (i) Interior joint (ii) Exterior joint (iii) Corner Joint Fig 1: Type of joints in frame 50

2. Experimental Investigation: The experimental study on interior beam column joint of a multistory reinforced concrete building in Salem Zone falling under the seismic Zone III has been analyzed using STADD.pro. The specimens were designed for seismic load according to IS 1893(Part I): 2002 & IS 13920: 1993. The structure is five storey two bay frames including 1.5 m foundation depth. The maximum moment is occurred at the ground floor roof level. We are considering that particular joint for the experimental study. Fig 2: Elevation and plan view of two bay frame (G+4) 2.1. Details of specimen: The test specimen was reduced to 1/5 th scale to suit the loading arrangement and test facilities. Prototype specimen having beam dimension of 305 X 460 including slab thickness and column dimension of 305 X 460. For testing model the dimension of beam was 120 X 170 mm without slab thickness and beam length of 450mm and that column size was 120 X 230 mm. Height of the column was 600mm. 2.2. Description of the formwork and reinforcement: Reinforcement for test specimen Fig 2: Formwork and 51

2.3. Reinforcement details: The reinforcement details of beam column joint are shown in fig.2. Main reinforcement provided in the beam was 10 mm diameter bars, 3 No s at top and 3 No s at bottom. The stirrups are 6 mm diameter bars at 30 mm c/c for a distance of 2d, i.e. 300 mm from the face of the column and at 60 mm c/c for remaining length of the beam. The longitudinal reinforcement provided in the column was 8 No s of 8 mm diameter bars equally distributed along four sides of column. The column confinements are 6 mm diameter bars at 30 mm c/c for a distance of 150 mm from the face of the column and at 60 mm c/c for remaining length of the column. 2.4. Casting and curing: The mould is arranged properly and placed over a smooth surface. The sides of the mould exposed to concrete were oiled well to prevent the side walls of the mould from absorbing water from concrete and to facilitate easy removal of the specimen. The reinforcement cages were placed in the moulds and cover between cage and form provided was 20 mm. Concrete mix designed for M30 (1:1:2.5) and water cement ratio is 0.40. Cement mortar block pieces were used as cover blocks. The concrete contents such as cement, sand, aggregate and water were weighed accurately and mixed. The mixing was done till uniform mix was obtained. The concrete was placed into the mould immediately after mixing and well compacted. Control cubes and cylinders were prepared for all the mixes along with concreting. The test specimens were remolded at the end of 24 hours of casting. They were marked identifications. They are cured in water for 28 days. After 28 days of curing the specimen was dried in air and white washed. 230 6mm dia lateral ties @ 30mm c/c 450 215 6mm dia 2 legged stirrups @ 30mm c/c 3 Nos of 10 DIA 300 120 170 215 3 Nos of 10 DIA 6mm dia 2 legged stirrups @ 60mm c/c 120 ALL DIMENSION IN mm 230 8 Nos of 8 DIA Fig 3: Ductile Detailing of Beam Column Joint as per IS 13920; 1993 52

Fig 4: Casting Stage of Beam Column Joint 2.5. Test setup and instrumentation: The specimen was tested in a reaction frame. The test setup is shown in figure 4. A hydraulic jack was used to apply the axial load for column. To record the load precisely a proving ring was used. The load is applied forward cyclic and reverse cyclic and deflection measured from every 3 KN by using LVDT. The deflection was measured at the beam free end tip. Loading is applied gradually such as 3,6,9,12,15 KN respectively for forward direction and 3, 6, 9, 12, 15 KN respectively for reverse direction. 2.6. Load sequence diagram: Fig 5: Load Vs cycle number chart 53

Fig 6: Test Setup for Forward & reverse Cyclic Load 2.7. Comparisons of experiment study and FEM analysis Experimental results are compared with FEM model analysis in ANSYS, the behavior of the interior beam column joint are similar. Maximum stresses are occurred at the junction for the ultimate loading at the beam tip. The crack patterns are formed and clearly visible in the model as shown in fig: 7&8. The maximum stress are developed in the FEM model at junction the tensile stress at top exceed the maximum tensile stress and compressive stress occurred at bottom in the forward cyclic loading. Fig 7: Failure at joints due to ultimate load (23 KN) 54

Fig 8: crack pattern of post ultimate load (backside of model) 2.8. Load Deflection curve: 55

Right side Loading Left side Loading Fig 9: Load deflection curve left and right side of beam under cyclic loading 3. Parameters have been studied: 1. Ductility, 2.Energy absorption, 3.Stiffness. 3.1. Ductility: Ductility may be broadly defined as the ability of a structure to undergo inelastic deformations beyond the initial yield deformation with no decrease in the load resistance. A quantitative measure of ductility has to be with reference to a load deformation response which is nearly horizontal. Then the ratio of ultimate deformation to the deformation at the beginning of the horizontal path (of first yield) can give a measure of ductility. Fig 10: Ductility factor Vs Load Cycles 56

Fig 11: Cumulative ductility factor for forward and reverse loading 3.2. Energy absorption: When the beam column joint is subjected to reverse cyclic loading, such as those experienced during heavy wind or earthquake, some energy is absorbed in each load cycle. It is equal to the work in straining or deforming the structure to the limit of deflection. The relative energy absorption capacities during various load cycles were calculated as the sum of the areas under the hysteric loops from the versus load deflection diagram. The relative energy absorbed during the first cycle of loading was calculated as 1.676 KN mm and during 7 th cycle 123.75 kn mm. Fig 12: cumulative energy absorption for forward and reverse cycle 3.3. Stiffness: Stiffness is defined as the load required to causing unit deflection of the beam column joint. The procedure for calculating stiffness was as follows: a) A tangent was drawn for each cycle of the hysteric curves at a load of P=0.75 Pu where Pu was the maximum load of that cycle. b) Determine the slope of the tangent drawn to each cycle, which gives the stiffness of that cycle. In general, with the increase in the load there is degradation of stiffness 57

Fig 13: Stiffness degradation for forward and reverse cycle 5. Conclusion: The structural behavior of RCC beam column joint interior type has been studied at analytically by using standard software packages STAAD Pro and ANSYS. Experimental investigation has been carried out and test results show that the structural behavior of interior beam column joint model has been similar to that of the analytically predicted one. From test results, important parameter has been worked out such as ductility, energy absorption, stiffness degradation etc., in order to access the seismic behavior of the beam column joint when earthquake comes. 6. Reference: 1. A.G.Tsonos, I.A.Tegos and G.Gr.Penelis[1992]. Seismic resistance of Type 2 Exterior Beam column joints reinforced with inclined bars The ACI structural Journal, Title No.89 S1, Jan Feb 1992. 2. A.Murugesan and Dr.G.S.Thirugnanam[2009] Ductile Behavior of Steel Fibre Reinforced Concrete beam column joints subjected to Cyclic loading, National Conference on Advances and Innovations in civil Engineering, Mepco Schlenk Engineering College,Sivakasi (2009),pp 27 33. 3. G.A.Lakshmi, Anjan Dutta and S.K.Deb[2008] Numerical studies of strengthening of beam column joint under cyclic excitation using FRP composites Journals of structural Engineering, Vol 35,No 1, Apr May 2008, pp 59 65. 4. Preeda chaimahawan & Amorn pimanmas [2008] Seismic retrofit of substandard beam column joint by planer joint expansion, Materials and structures, DOI 10, June May 2008, 5. Ramesh.S [2008] Experimental study on behavior of Exterior RC beam column joints subjected to cyclic loading M.E. thesis report, Anna University, Chennai, July 2008. 6. Thirugnanam.G.S [2001] Ductile behavior of SIFCON structural member Journals of structural engineering, April June 2001, Volume 28, No.1. 7. Yung Chih Wang and Kai Hsu[2009] Shear Strength of RC Jacketed Interior Beam Column Joints without Horizontal Shear Reinforcement The ACI structural Journal, Title No.106 S24, Mar Apr 2009. 58

59