Demountable Shear Connectors for Sustainable Composite Construction

Similar documents
Sustainable composite beam behaviour with deconstructable bolted shear connectors

RECENT RESEARCH OF SHEAR CONNECTION IN PREFABRICATED STEEL-CONCRETE COMPOSITE BEAMS

THE STRUCTURAL BEHAVIOUR OF COMPOSITE CONNECTIONS WITH STEEL BEAMS AND PRECAST HOLLOW CORE SLABS

Comparative Study of R.C.C and Steel Concrete Composite Structures

Council on Tall Buildings

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 3, No 1, 2012

Contents. Tables. Notation xii Latin upper case letters Latin lower case letters Greek upper case letters Greek lower case letters. Foreword.

High Performance and Efficiency of Joints in Precast Members

Residual strength of Y-type perfobond rib shear connectors to cyclic load on highway bridge

Seismic Behaviour of RC Shear Walls

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress

Non Linear Analysis of Composite Beam Slab Junction with Shear Connectors using Ansys.16

Experimental study on seismic behavior of composite concrete and

Nonlinear Analysis of Shear Dominant Prestressed Concrete Beams using ANSYS

Crack detection in composite bridges with relative displacement sensors

Design of Steel-Concrete Composite Bridges

Finite Element Analysis of RC Beams Strengthened with FRP Sheets under Bending

Various Types of Shear Connectors in Composite Structures

Nonlinear Models of Reinforced and Post-tensioned Concrete Beams

SEISMIC RESPONSE OF MULTIPLE-ANCHOR CONNECTIONS TO CONCRETE

Cement grouted steel bars in glulam

UHPC Connection of Precast Bridge Deck

EXPERIMENTAL BEHAVIOUR AT ULTIMATE LIMIT STATE OF A SEMI-PREFABRICATED TIMBER-CONCRETE COMPOSITE FLOOR SYSTEM

FINAL REPORT. Prepared by

Analytical Study on a Longitudinal Joints of the Slab-Type Modular Bridges Sang-Yoon Lee, Jung-Mi Lee, Hyeong-Yeol Kim, Jae-Joon Song

Copyright By Gun Up Kwon 2008

VTU EDUSAT PROGRAMME Lecture Notes on Design of Stair cases

Effect of FRP strengthening on the behavior of shear walls with opening

Effect of bolt gauge distance on the behaviour of anchored blind bolted connection to concrete filled tubular structures

RECENT ADVANCES IN THE DESIGN AND CONSTRUCTION OF COMPOSITE FLOOR SYSTEMS

Composite Beams of Cold Formed Steel Section and Concrete Slab

Experimental investigation of the use of CFRP grid for shear strengthening of RC beams

ST7008 PRESTRESSED CONCRETE

Ultimate strength prediction for reinforced concrete slabs externally strengthened by fiber reinforced polymer (FRP)

Numerical Modelling of Shear Connections for Composite Slabs

Lysaght Bondek. Structural steel decking system Design and Construction Manual

Shear behaviour of open beam-to-tubular column angle connections

3D analysis of solid reinforced concrete beams subjected to combined load of bending, torsion and shear

Experimental Study on Shear Splitting Failure of Full-Scale Composite Concrete Encased Steel Beams

INHERENT DUCTILITY OF REINFORCED CONCRETE SHEAR WALLS WITH NON-SEISMIC DETAILING

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

Structural behaviour and failure mechanisms of concrete monoblock railway sleepers

MECHANICAL CHARACTERIZATION OF SANDWICH STRUCTURE COMPRISED OF GLASS FIBER REINFORCED CORE: PART 1

IMPROVING SHEAR CAPACITY OF RC BEAMS USING EPOXY BONDED CONTINOUS STEEL PLATES

STRENGTHENING STEEL-CONCRETE COMPOSITE BRIDGES WITH HIGH MODULUS CARBON FIBER REINFORCED POLYMER (CFRP) LAMINATES

SHEAR BEHAVIOR OF RC BEAMS USING U-SHAPED UFC PERMANENT FORMWORK WITH SHEAR KEYS OR BOLTS

Lecture Retaining Wall Week 12

FINITE ELEMENT ANALYSIS OF HOLLOW-CORE SLABS. E. Frăţilă a, *, Z. Kiss a

Heat transfer analysis of hybrid stainless-carbon steel beam-column joints

Summary. 1. Introduction. Enrique GONZÁLEZ DUEÑAS Civil Engineer LRA Infrastructures Consulting Madrid, SPAIN

Finite Element Modeling of New Composite Floors Having Cold-Formed Steel and Concrete Slab

HIGH PERFORMANCE REINFORCEMENT PRODUCTS. Product Catalogue.

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

Experimental Research of Bridges with Encased Beams

Seismic Detailing of RC Structures (IS: )

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

fischer Test Report Fixing Tests for Bison Hollow Core Slabs

FINITE ELEMENT ANALYSIS OF STEEL BEAM-CFST COLUMN JOINTS WITH BLIND BOLTS

UNIVERSITY OF BOLTON WESTERN INTERNATIONAL CENTRE FZE. BEng (HONS) CIVIL ENGINEERING SEMESTER ONE EXAMINATION 2015/2016

Effect of beam dimensions on structural performance of wide beam-column joints

4.6 Procedures for Connections

Design for earthquake-resistent reinforced concrete structural walls

Flexural Behavior of Composite Slab

Talk to us, THE SMART DECKING PEOPLE Visit or Global Roofing Solutions Bond-Dek Composite Deck

Experimental investigation on the shear capacity of RC dapped end beams and design recommendations

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

HILTI HY 150 REBAR DESIGN GUIDE

THE EXTENDED N2 METHOD IN SEISMIC DESIGN OF STEEL FRAMES CONSIDERING SEMI-RIGID JOINTS

PRECAST REINFORCED CONCRETE SANDWICH PANEL AS AN INDUSTRIALISED BUILDING SYSTEM

Shear studs in slab-column connections with rectangular column

Introduction to Earthquake Engineering Behaviour of structures under earthquakes

CHAPTER III METHODS AND MATERIALS

A new ductile approach design of joints assembled with screw connectors

SHEAR BEHAVIOR OF RC DEEP BEAMS WITH SOLID CIRCULAR CROSS SECTION UNDER SIMPLY SUPPORTED CONDITION AND ANTI-SYMMETRIC MOMENT

Studies on ductility of RC beams in flexure and size effect

ANALYTICAL STUDY OF PUNCHING SHEAR ON WAFFLE SLAB WITH DIFFERENT RIB SIZES

Deflection Assessment of an FRP-Reinforced Concrete Bridge. By Danielle K. Stone, Andrea Prota, and Antonio Nanni

Strengthening of infilled RC frames by CFRP

Flexural Behavior of RC T- Section Beams Strengthened with Different Configurations of CFRP Laminates

NEW HYBRID GLULAM BEAM REINFORCED WITH CFRP AND ULTRA-HIGH-PERFORMANCE CONCRETE

CYCLIC BEHAVIOUR OF SANDWICH CONCRETE BEAM UNDER FLEXURAL LOADING

CONCRETE FRAME CORNERS IN CIVIL DEFENCE SHELTERS SUBJECTED TO NEGATIVE MOMENT

Design for Shear for Prestressed Concrete Beam

Sabah Shawkat Cabinet of Structural Engineering 2017

Structural Design of Pergola with Airfoil Louvers

Ensuring sufficient robustness to resist

PRELOADING EFFECT ON LOAD CAPACITY AND DUCTILITY OF RC BEAMS STRENGTHENED WITH PRESTRESSED CFRP STRIPS

VERTICAL SHEAR RESISTANCE IN A SLIM FLOOR COMPOSITE SECTION

APPENDIX B ABC STRUCTURES DESIGN GUIDE

Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit

ESECMASE - SHEAR TEST METHOD FOR MASONRY WALLS WITH REALISTIC BOUNDARY CONDITIONS

Study of behaviour of reinforced concrete deep beam under two points loading and the effect of shear reinforcement

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

Investigation of the behavior of stiffened steel plate shear walls with Finite element method

ABSTRACT. KEY WORDS: Tubular piles; composite behavior; offshore structures; push-out strength; bond strength; slip.

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

Layher Aluminium Lattice Beams. Information and User Guide. Aluminium Lattice Beam 750 (Product Code 4903XXX)

The Ultimate Structural Engineering Software Package!

Design of large scale wind turbine towers in seismic areas

Modelling of RC moment resisting frames with precast-prestressed flooring system

Transcription:

Keynote Paper Demountable Shear Connectors for Sustainable Composite Construction *Dennis Lam 1) and Xianghe Dai 2) 1, 2) School of Engineering, Design & Technology, University of Bradford, Bradford, BD7 1DP, UK 1) d.lam1@bradford.ac.uk ABSTRACT The UK Government has set an ambitious and legally binding target to reduce national greenhouse gas emissions by at least 80% by 2050 with an intermediate target of a 34% reduction by 2020, therefore it is important to consider the whole life cycle in composite construction. Composite flooring system formed by connecting the concrete slabs to the supporting steel beams has been widely used for many years throughout the world. Steel and concrete composite construction is well established as a costeffective arrangement for floor systems in multi-storey steel frame building structures. Composite action between steel beams and concrete slabs through the use of shear connectors are responsible for a considerable increases in the load-bearing capacity and stiffness of the steel beams, which when utilized in design, can result in significant savings in steel weight and construction cost. However, shear connectors are welded through the steel decking and cast into the concrete; this made reuse of the steel components after deconstruction almost impossible. A demountable shear connector is developed and tested to assess its potential and suitability in term of replacing the traditional welded through headed shear studs. Test results shown that these shear connectors can be easily demounted after test and have a similar capacity and behaviour of the welded headed stud shear connectors. 1) Professor 2) Lecturer 93

1. INTRODUCTION Composite steel structures formed by connecting the concrete slabs to the supporting steel beams have been widely used for many years throughout the world. The use of composite action between steel and concrete is well established as a costeffective arrangement for floor systems in multi-storey steel frame building structures. Composite action between steel beams and concrete slabs through the use of shear connectors is responsible for a considerable increase in the load-bearing capacity and stiffness of the steel beams, which when utilized in design, can result in significant savings in steel weight and construction cost. However, shear connectors are welded through the steel decking and cast into the concrete; this made deconstruction and reuse of the steel components almost impossible. In steel concrete composite construction, longitudinal shear force is transferred across the steel flange/concrete slab interface by mean of the mechanical action of the shear connectors. The capacity of the shear connection to transfer longitudinal shear forces depend on the strength and stiffness of the shear connectors and also the resistance of the concrete slab against longitudinal cracking induced by the high concentration of the load imposed by the dowel action. Present knowledge on welded headed stud shear connector in solid slab is well illustrated by Mottram and Johnson (1990) and Menzies (1971). The shear connectors used in steel concrete composite construction have primarily been this type of connectors. These connectors can be classified as flexible connectors, because under small shear forces, there will be relative movement or slip between the concrete slab and the steel beam at the interface. The research in demountable shear connector by Lam and Saveri (2012) shown in Fig. 1 is formed from the standard 19 mm diameter T.W. Nelson headed shear connector with a 16mm threaded end; and with or without a collar, a M16 Gr 8.8 nut is used to fasten the connector to the steel beam. Since the connector is manufactured from the standard headed stud shear connector, it has the same material properties of the standard welded headed studs. Although researches on bolted connectors have been carried out previously by Dallam (1968) and Marshall et al. (1971) on bolted connectors, their main emphasis was on the pre-tension behaviour of the shear connectors using high friction-grip bolts. More recently, research by Kwon et al. (2010) on bolted connectors was focused on the post-installed capacity for strengthening existing structures rather than the sustainable issues. Research on the sustainable issue for demountable shear connectors for composite construction is limited, the only other published research to date is carried out by Mirza et al (2010) using blind bolts as shear connectors. Although they performed reasonably adequate as shear connector, some of these blind bolts have a relatively brittle behaviour. The objective of this research is to investigate the behaviour of this form of demountable shear connectors embedded in normal-weight concrete when subjected to a static shear force. The results are used to be compared with those of the welded headed stud shear connectors to help to determine the feasibility of using this form of connectors in composite construction. 94

Fig. 1 Demountable shear connector 2. EXPERIMENTAL STUDY A push off test specimen shown in Fig. 2 similar to the one described in Eurocode 4 (2004) was used. The test consisted of a short length of steel beam connected to two concrete slabs 300 300 150 mm in sizes. 2 pairs of shear connectors were used to connect the concrete slabs to the steel beam, vertical load is applied to the steel beam and slip between the steel beam and the slabs are measured against the load per connector. Both sides of the concrete slabs were cast horizontally using the same mix and poured at the same time. Once the slabs reached their required strength, the slabs were then connected to the steel beam before the test. The test program consisted of eight push off tests. The test parameters included the compressive strength of concrete and the sizes of the headed stud collar. Details of the test series and their results are shown in Table 1. Fig. 2 Push off test specimen 95

Ref. Concrete Cube Strength, f cu (MPa) Table 1: Push test program and results Stud Type Max. Load per stud (kn) Slip at Max. Load (mm) Mode of Failure POT 1 19.85 16mm 75.0 8.75 Stud fracture POT 2 21.45 17mm collar 93.5 7.94 Stud fracture POT 3 20.10 18mm collar 71.9 22.03 Concrete crushing POT 4 25.20 18mm collar 81.5 10.02 Concrete crushing POT 5 29.90 18mm collar 90.0 20.25 Concrete crushing POT 6 61.38 18mm collar 107.5 22.03 Stud fracture POT 7 20.10 19mm welded 71.6 5.2 Concrete crushing POT 8 29.90 19mm welded 92.7 9.0 Concrete crushing For specimens with demountable headed stud shear connectors, two types of failure mechanism were observed; fracture of the shear connectors near the threaded end or failure by concrete crushing and splitting. The load slip curves of the two specimens representing these two types of failure are shown in Fig. 3. It can be seen that the load slip curve associated with stud fracture, although quite ductile, end abruptly. Concrete crushing splitting type of failure provides considerable warning as the load carrying capacity decreases slowly. The fracturing of the shear connectors is shown in Fig. 4 while concrete crushing and splitting failure is illustrated in Fig. 5. For the specimen failed by concrete crushing, the slabs were demounted from the steel beam and examined carefully, there was no damage occurred to the threaded portion of the demountable stud and the slabs were easily detached from the steel beam. Fig. 3 Load slip curves of demountable stud POT2 and POT 5 96

Fig. 4 Stud fracture Fig. 5 Concrete crushing splitting A comparison of load slip curves of push test with welded headed studs and push test with demountable connectors are shown in Fig. 6, the results showed that with similar concrete strength and mode of failure, the demountable connector appears to be more ductile than the welded connector but achieving the similar capacity. However, the welded connectors showed a much higher initial stiffness when compared with the demountable studs. In addition, at 6 mm slip, the shear capacity of the demountable connector is 16% lower than the welded connector. However, although these connectors have a lower shear capacity, this might not has significance influence to the ultimate and serviceability limited state of composite beams in bending. 97

Load per connector (kn) 100 90 80 70 60 50 40 30 20 10 0 Welded Demountable 0 2 4 6 8 10 12 14 16 18 20 Slip (mm) Fig. 6 Welded vs. demountable connectors in C30 concrete 3. FINITE ELEMENT MODEL A finite element (FE) model of the steel-concrete composite beams are built using ABAQUS (2011) to investigate the load-slip behaviour of these demountable shear connectors to the ultimate and serviceability limited state of the composite beams in bending. A 12m span simply supported beam is built with solid elements with four points loading. Fig. 7 shows the 3-D FE model of composite beams with solid concrete slabs. Combination of three dimensional eight-node brick (C3D8R) and six-node wedge (C3D6R) reduced integration elements are used to model the concrete slab and the steel beam. The reduced integration approach eliminates shear locking and ensures computational efficiency of the analysis. A 457 152 52 UB S355 is used for the steel section and a 150mm thick solid concrete slab with concrete cube strength of 30 N/mm2 and shear connectors at 300 c/c is modelled. Two points loading is applied at the one-third point. The load-slip characteristic of the shear connectors obtained from the push test experiments is represented by the spring elements in the FE model. The results of the moment vs. mid-span deflection with welded shear connectors and demountable shear connectors are shown in Fig. 8. Results showed that although the shear capacity of the demountable shear connector is 16 % lower than that of the welded connector, the effect to the bending moment capacity of the 12m composite beam is less than 5%. In addition, the low initial stiffness of the demountable shear connectors to the welded 98

shear connectors did not have significant effect to the initial stiffness of the composite beams. Fig. 7 FE model of 12m span simply supported composite beam 700 600 500 Moment (knm) 400 300 200 100 0 Demountable C25/30 Welded C25/30 0 100 200 300 400 500 600 700 800 900 1000 Mid span deflection (mm) Fig.8 Moment vs. mid-span deflection of the composite beams 4. CONCLUSIONS A demountable shear connector is developed in the form of headed stud shear connectors. A series of the push off tests have been carried out to assess its potential and suitability. Test results shown that these shear connectors can be easily 99

demounted during the working load stage and after the test. They have a similar behaviour and shear capacity to the welded headed studs. In addition, test results showed that the new demountable shear connectors process high ductility in comparison with the welded shear connectors but relatively lower initial stiffness. A FE model is built to investigate the load slip behaviour of these demountable shear connectors to the moment capacity of the composite beams. Results showed that although the shear capacity of the demountable shear connector is 16 % lower than that of the welded connector, the effect to the moment capacity of the 12m composite beam is less than 5%. In addition, the lower initial stiffness of the demountable shear connectors did not affect the initial stiffness of the composite beam. Full-scale beam tests with this type of demountable shear connectors is currently being planned and further research on this form of demountable shear connectors with metal deck profile composite slabs is on-going. REFERENCES ABAQUS Standard User s Manual. (2011), Hibbitt, Karlsson and Sorensen, Inc. version 6.11, USA. Dallam, L.N. (1968) High Strength Bolt Shear Connectors Pushout Tests ACI Journal, Vol. 65(9), 767-769. EN1994-1-1. Eurocode 4, (2004) Design of Composite Steel and Concrete Structures. Part 1.1, General Rules and Rules for Buildings. British Standards Institution, London. Kwon, G., Engelhardt, M.D. and Klingner, R.E. (2010) Behavior of post-installed shear connectors under static and fatigue loading Journal of Constructional Steel Research, Vol. 66(4), 532-541. Lam, D and Saveri, E. (2012), Shear capacity of demountable shear connectors, 10th International Conference on Advances in Steel Concrete Composite and Hybrid Structures, Singapore, 767 774. Marshall, W.T., Nelson, H.M. and Banerjee, H.K. (1971), An Experimental Study of the Use of High Strength Friction Grip Bolts as Shear Connectors in Composite Beams, The Structural Engineer, Vol. 49(4), 171-178. Marza, O., Uy, B. and Patel, N. (2010) Behavior and Strength of Shear Connectors Ultilising Blind Bolting Steel & Composite Structures Proceedings of the 4th International Conference, 791 796. Menzies, J.B. (1971) CP 117 and Shear Connectors in Steel-Concrete Composite Beams made with Normal-Density or Lightweight Concrete. The Structural Engineer, Vol. 49(3), 137-153. Mottram, J.T. and Johnson, R.P., (1990) Push tests on studs welded through profile steel sheeting, The Structural Engineer, Vol. 68(10), 187-193. 100