STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

Similar documents
Administrative Changes

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

POST FRAME BUILDING STANDARDS

2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

130 MPH EXPOSURE B WFCM GUIDE. Guide to Wood Frame Construction in High Wind Areas for One- and Two-Family Dwellings 2015 EDITION

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

R Code and Commentary for 2012 NC Residential Code final 03/06/13

SECTION PLATE CONNECTED WOOD TRUSSES

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017

2003 International Residential Building Code

Wall bracing panel requirements

BUILDING CODES Presented by CORUM ENGINEERING

FIGURE R502.2 FLOOR CONSTRUCTION

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division

CALCULATING WIND LOADS ON LOW-RISE STRUCTURES PER 2015 WFCM ENGINEERING PROVISIONS (STD342-1)

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International

CHAPTER 5 FLOORS SECTION R501

TYPICAL BEARING WALL FRAMING

MBOIA IRC Wall Bracing. Mark Halverson. Maine Building Officials and Inspectors Association. First Last

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date

Individual Truss Marking Is it a Building Code Requirement?

Residential Wood Deck Design

PRESENTATION OUTLINE MUBEC & IRC APPLICABILITY & ADMIN. 6/17/2015 RESIDENTIAL STRUCTURAL SYSTEMS. Carmen B. Bombeke, P.E.

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Building Guide. Colorado Chapter of the International Code Council

DETAIL DRAWINGS. RASTRA is a stay-in-place insulated concrete. form that is structurally strong, energy-efficient,

Modular Wood Framing Goes Vertical

RESPONSIBILITIES IN THE DESIGN PROCESS INVOLVING METAL PLATE CONNECTED WOOD TRUSSES

REINFORCING TABLES INSTALLATION MANUAL

TOWN OF SOUTH KINGSTOWN REQUIREMENTS FOR BUILDING PERMITS RESIDENTIAL SINGLE FAMILY

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

SEISMIC STRENGTHENING PROVISIONS FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS

4.6 Procedures for Connections

TECHNICAL NOTE On Cold-Formed Steel Construction

INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT

Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

Floor Truss Ribbon Board Load Path

FACT SHEET #2 DECK INFORMATION

Custom 24 x 26 Garage Plan Roy Hartmann Plan #g218 By SDS-CAD Specialized Design Systems CLIENT

APPENDIX. WOOD JOIST/RAFTER MAXIMUM SPANS ( for 16 o.c. spacing) WITH SINGLE ROW OF PV PANELS AT MIDSPAN (ft.) AND PANEL SUPPORT AT 32 o.c.

See the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals.

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

The following are details of the code requirements of the 2015 International Residential Code for single-story decks.

Considerations for Outof-Plane. Design

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity

Wood Frame Construction Manual for One- and Two-Family Dwellings 2015 EDITION WORKBOOK

BUILDING BULLETIN One and Two Family Dwellings Decks and Residential Access Ramps

Temporary Construction Loads Over I-Joist Roofs And Floors

2.2E Parallam PSL Deep Beam

CH. 9 WOOD CONSTRUCTION

LPI 56 Technical Guide

2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E.

Common Errors in Truss Design

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.

Figure 1 Shear wall segments with mono-sloped top plates

Plan Check No. Checked by: An Appointment Is Required for Verification

The Homeowner s Building Application Checklist for Constructing a Residential Addition

10/23/2011. Plan Examination. Plan ExaminationPurpose. Catch problems in advance of construction.

Proposed Modification to the Florida Building Code

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

14' x 24' Garage Plan

2.2E Parallam PSL Deep Beam

FOUNDATIONS CHAPTER 4

One and Two Family Additions

Table R (1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor. Sheathing and Combination Subfloor Underlayment

The designer shall also submit additional information required by the University as described and underlined below.

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

Nabil A. Rahman, Ph.D., P.E.

Each proposed project will be reviewed for compliance with the following codes as applicable.

Supplemental Concrete Tilt Up Retrofit Plan Check Correction Sheet (2014 LABC)

Evaluation of the High-Heel Roof-to-Wall Connection with Extended OSB Wall Sheathing

2) Open ConstructionCalc ProBeam from Microsoft Excel, then File Open. 3) Part 1 General Input.

SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series

What is Conventional Construction?

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements

City of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209)

4.2 Tier 2 Analysis General Analysis Procedures for LSP & LDP

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

Lateral Design of Mid- Rise Wood Structures

10 EXTREME BASEMENT PANELS

CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS

COFS Mission. AISI Standards Hierarchy. North American Standards for Cold-Formed Steel Framing. Member versus System Design. Specification 10/21/2016

Wood Truss Restraint and Bracing Guide

MAT109: Introduction to the Wood Frame Construction Manual

Copyright. magazine. CFS Load Bearing Construction

GARAGE MAIN FLOOR PLAN SDSCAD Specialized Design Systems

Maximum Spans Southern Pine Joists & Rafters

1 AND 2 FAMILY DWELLING REQUIREMENTS

one structural behavior, systems and design Course Description Course Description Syllabus & Student Understandings statics mechanics of materials

RESIDENTIAL WOOD DECK CONSTRUCTION GUIDE

FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION

RESIDENTIAL DETACHED STORAGE STRUCTURES (GARAGE)

Transcription:

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION Presented by: Susan L. Lasecki P.E., S.E.

Presentation Outline Gravity Design Load Paths from Roof to Foundation Roof Framing Floor Framing Wall Framing Lateral Loads Basement walls Wind Loads and Shear walls Future presentation

Gravity Design Complete load paths include the transfer of vertical loads (both downward and uplift) from the roof to the foundations Load Sources Dead load self weight Snow load Live load

Gravity Design - Roof Roof Framing Manufactured wood trusses Conventional Framing Joist and rafter tables in Appendix based on span and species and allowable deflection Loads Snow Wind Downward does not govern Uplift = 20 psf

Conventional Roof Framing Conventional roof framing consists of 2x members installed as roof rafters and ceiling joists. Code section SPS321.27 Typical spacing = 16 o.c. Roof framing members required to be anchored using engineered clips, straps or hangers. Collar ties every 48 o.c. Ceiling joists are required for providing lateral restraint. If ceiling joists are not provided an engineered system needs to be in place such as a ridge beam, wall ties, etc.

Roof Trusses Pre-manufactured roof framing system typically installed at @ 24 o.c. Issues: Connections Gable end framing Temporary bracing

Roof Truss - Connections Connections must resist loads from wind shear, wind uplift and top of wall wind reaction.

Roof Truss Gable End Framing Gable End Framing Top of wall bracing typically accomplished by attachment of drywall sheathing to truss bottom chord which is then transferred into the perpendicular walls Illustration from the Alpine Encyclopedia of Trusses

Roof Truss Gable End Framing Gable End Framing When the loads at the gable end are very high, another method may be needed to transfer the wind loads into the perpendicular walls. A horizontal truss is used in this application Illustration from the Commentary for Permanent Bracing of Metal Plate Connected Wood Trusses, John E. Meeks

Roof Truss Gable End Framing Gable End Framing Diagonal bracing used to transfer the wind reaction to the wood roof diaphragm Illustration from the Commentary for Permanent Bracing of Metal Plate Connected Wood Trusses, John E. Meeks

Roof Truss - Bracing Permanent bracing is designed by the truss supplier and illustrated on the truss shop drawings. Temporary bracing is the responsibility of the general contractor in accordance with the installation instructions provided by the truss supplier. (see next slide)

Illustration from the Alpine Encyclopedia of Trusses

Gravity Design Floor Joists Floor Framing Manufactured wood trusses TJI Conventional Framing Joist tables in Appendix based on span, species and allowable deflection Loads Dead load Live load

Joist Cantilevers WI - UDC (6) OVERHANG OF FLOORS. (a) General. Except as provided in pars. (b) and (c), a floor joist overhang shall be cantilevered beyond the outer edge of the supporting wall below it by no more than the actual depth of the joist or shall be designed through structural analysis in accordance with s. SPS 321.02 (3). (b) Joist overhangs parallel to the main floor framing system. Joist overhangs that are extensions of, and parallel to, the main floor framing system may extend beyond the depth of the joist without structural analysis provided they meet all of the following conditions: 1. The overhang is cantilevered no more than 2 feet beyond the outer edge of the supporting wall below it. 2. a. The overhang supports a uniform load limited to the weight of the bearing wall and the tributary roof area above it. b. The tributary length of the roof area, excluding the eave overhang, is no more than 2 feet greater than the actual length of the joist directly below. This section continues IRC R502.3.3 Floor cantilevers. Floor cantilever spans shall not exceed the nominal depth of the wood floor joist. Floor cantilevers constructed in accordance with Table R502.3.3(1) shall be permitted when supporting a light-frame bearing wall and roof only. Floor cantilevers supporting an exterior balcony are permitted to be constructed in accordance with Table R502.3.3(2).

Joist Cantilevers In General Cantilevers must have a backspan to cantilever ratio of 2:1 minimum. If the cantilever end is loaded with a wall, the ratio needs to be increased. If a cantilever does not fit within the prescriptive text of the code, it should be reviewed by an engineer. Solid blocking should be installed between all cantilevered joists at the bearing location.

Floor Framing Bridging/Blocking Conventional wood framing Diagonal Solid

Floor Joists Parallel to Basement Wall Wisconsin UDC

Load Bearing Wood Studs Capacity of studs is based on: Max spacing. Assumed loads. Stud grade species Fully braced studs in weak direction. Application of sheathing or drywall on one side or Blocking at 4-0 o.c. (minimum)

Gravity Design Wood walls Wisconsin Residential Code Maximum allowable unbraced height for a load bearing wall is 10-0 without additional engineering

Gravity Design Wood walls IRC Maximum allowable unbraced height for a load bearing wall is 10-0 without additional engineering a. Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where justified by analysis. b. Shall not be used in exterior walls. c. A habitable attic assembly supported by 2 4 studs is limited to a roof span of 32 feet. Where the roof span exceeds 32 feet, the wall studs shall be increased to 2 6 or the studs shall be designed in accordance with accepted engineering practice.

Tall Walls

Full Height Basement Wall Loads Loads Total horizontal load W=q*h^2/2 q can vary from 40 to 65 lbs/ft depending on the soil conditions (lower for sand and higher for clay) Top reaction = W/3 Bottom reaction = 2/3W

Partial Height Foundation Walls Observed Condition Potential failure: Rotation of the frost wall inward Excessive rotation could cause a first floor framing collapse Repair Methods for existing conditions Install wood or metal studs full height inside the wall capable of supporting full lateral load. Anchor studs to slab on grade and wood floor framing above.

Partial Height Foundation Walls Code Requirements WI-UDC SPS 321.18 Foundations. (1) GENERAL. (a) Design. Foundation walls shall be designed and constructed to support the vertical loads of the dwelling, lateral soil pressure, and other loads without exceeding the allowable stresses of the materials of which the foundations are constructed. (b) Lateral support at base. Lateral support such as floor slab or framing shall be provided at the base of foundation walls. (c) Lateral support at top. Lateral support shall be provided at the top of the foundation walls by one of the following: 2. Structural analysis. A system designed through structural analysis 3. Anchor bolts. a. Structural steel anchor bolts, at least ½inch in diameter, embedded at least 7 inches into the [concrete or] grouted masonry with a maximum spacing of 72 inches and located within 18 inches of wall corners.

Partial Height Foundation Walls Code Requirements IRC R404.1.2.2.2 Concrete foundation stem walls supporting light-frame above-grade walls. Concrete foundation stem walls that support light-frame above-grade walls shall be designed and constructed in accordance with this section. 1. Stem walls not laterally supported at top. Concrete stem walls that are not monolithic with slabs-on-ground or are not otherwise laterally supported by slabs-on-ground and retain 48 inches (1219 mm) or less of unbalanced fill, measured from the top of the wall, shall be constructed in accordance with Section R404.1.2. Foundation stem walls that retain more than 48 inches (1219 mm) of unbalanced fill, measured from the top of the wall, shall be designed in accordance with Sections R404.1.3 and R404.4. R404.1.3 Design required. Concrete or masonry foundation walls shall be designed in accordance with accepted engineering practice when either of the following conditions exists: 1. Walls are subject to hydrostatic pressure from groundwater. 2. Walls supporting more than 48 inches (1219 mm) of unbalanced backfill that do not have permanent lateral support at the top or bottom. R404.4 Retaining walls. Retaining walls that are not laterally supported at the top and that retain in excess of 24 inches (610 mm) of unbalanced fill shall be designed to ensure stability against overturning, sliding, excessive foundation pressure and water uplift. Retaining walls shall be designed for a safety factor of 1.5 against lateral sliding and overturning.

Partial Height Foundation Walls Correct Design Condition Design lower portion of wall as a retaining wall. Wall needs to be connected to footing with dowels at uniform spacing. Connection between wall and footing is considered fixed rather than hinged.

Foundation Construction: Multiple Top Plate Recently observed condition in a home where the G.C. wanted to increase clear height in basement without using taller concrete forms. The triple top plate leads to an indirect load transfer and the potential for the top of the wall to rotate inward. The plate to plate connection is not a fixed connection and the plates can separate. Not sure how the anchor bolts were installed.

Questions? Also, please feel free to ask questions via phone or email at: Slasecki@ionic-sd.com 414-540-8755