Rain tightness of wind barrier and sealing of window joints Experimental laboratory testing

Similar documents
The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide.

(Project Location) (your firm's name)

Johns Manville MinWool Water & Fire Block Mineral Wool Insulation

DuPont Tyvek Air Barrier Installation Guidelines. Canadian Version. Version 2

COMP ONENT CATA LO GUE FOR INDUSTRIAL BUILDINGS

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

SINGLE FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

ASSEMBLY INSTRUCTION TG 2002

RevealShield SA Penetrations

LUX Specifications. Section S - Preformed Steel Siding

PLATON RUGGED, DIMPLED HIGH-DENSITY POLYETHYLENE (HDPE) MEMBRANE THAT KEEPS FOUNDATIONS AND FLOORING DRY ADVANCED TECHNOLOGY EASY INSTALLATION

OSB.COMFORT INSTALLATION GUIDE * 1 RECOMMENDED USE PANEL COMPOSITION

MULTI-FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

7520 Casement Windows

ELEVATION FOR DETAIL REFERENCE ONLY

Contents: 3. Benefits of CLT with regard to airtightness. 4. Technical aspects of airtightness. 5. Configurations and specific connections. 6.

Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure

D Side lap. Side lap screw spacing < 500mm factory-installed seals on side lap. Decoupling tape > 60mm

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

Integrated Air & Water Barrier Systems

Eclipse Energy Guard. Product Information & Installation Manual General Installation Requirements

6110 Horizontal Sliding Windows

Crawl Space Moisture Control

Air and Vapor Barrier 3015

Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera

NU-WALL EXTRUDED ALUMINIUM CLADDING. Installation Specifications Vertical orientation (over cavity)

Moisture and temperature conditions in cold lofts and risk of mould growth

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

DuPont. Tyvek Sheathing Membrane Installation Guidelines. Version 2. Canadian Version

STORAGE AND TRANSPORTION

The Role of Control Layers in Building Enclosure Design

A. Source Limitations: Obtain each type of building insulation through one source.

Feature Zone IECC 2009 IECC

Smart Vapor Retarders

Brick Veneer Walls. Insulation

Awning Windows Montecito New Construction Window

Weather Resistant Barrier

Thermasheath-XP. Insulation for Exposed Use

COMP ONENT CATA LO GUE FOR B UILDING YO UR OWN HOME

NRCC Guarded Hot Box Testing (ASTM C ) for Energy Efficiency of a Total Roof Assembly

Evaluation of the long term durability of adhesive tapes and its substrates: Requirements and testing

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION

FlexClad Duct and Pipe Sealing System

ELEVATION FOR DETAIL REFERENCE ONLY

STUDY REPORT SR 299 (2013) Rigid Sheathing and Airtightness in New Zealand. GE Overton

ELEVATION FOR DETAIL REFERENCE ONLY

Pella 250 Series. Wood Frame Construction with Vinyl Siding... V250-ID-888 Wood Frame Construction with Brick Veneer...

ELEVATION FOR DETAIL REFERENCE ONLY

Advanced technologies for enhancing the building envelope. 3M Building and Construction Market

Insight. Stress Relief. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE

Tech Solutions WEATHERMATE Straight Flashing. Commercial Installation Guide

Gold Bond BRAND Gypsum Sheathing

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

Thermal Laminate Board.

Radon Vent Pipe System. Labeling Performance Indicators

Dynamic Bonding Systems B.V. A division of Dutch Bonding Group B.V.

KNIGHT WALL SYSTEMS GUIDE DETAILS:

Multi-layer Insulation Blanket for Walls

Casement Windows Montecito New Construction Window

GypLyner. GypLyner. Metal framed wall lining system. All our systems are covered by SpecSure when using genuine Gyproc and Isover products.

Trusted ICC ES DIVISION: ATLANTA, CGF PRO, ENERGYS. Look. Conformity! Evaluation. ICC-ES Evaluation

DuPont RainVent Batten Installation Guidelines

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction

NCMA TEK TEK 19-5A FLASHING DETAILS FOR CONCRETE MASONRY WALLS

ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;

MARLIN WINDOWS, INC 3500 HC SERIES 3 3 8" SLIDING WINDOW PAGE 1

INSTALLATION MANUAL. ZIP System R12 Sheathing. Contents. 07 ZIP System R12 Sheathing Window Installation 08 ZIP System R12 Sheathing Siding Guidelines

SINTEF Building and Infrastructure confirms that. Unihouse timber frame building elements

J41 Reinforced bitumen membrane roof coverings

ELEVATION FOR DETAIL REFERENCE ONLY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

AirSmart. The intelligent choice in airtight systems. Superior strength and quality. Energy saving and cost effective. Reduces condensation risk

Majrex. System Guidelines For Air Barrier and Vapor Control Installation

KNIGHT WALL SYSTEMS GUIDE DETAILS:

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

SUBSTRATES FOR WOOD FLOOR SETTING

Airtightness Measurements of Wood Frame Low Energy Row Houses Sverre B. Holøs 1 and Thor-Oskar Relander 2

How do you install yours?

BBA 001 Documents included under the scope of BBA s ISO UKAS accreditation

Building Enclosure Details and Assemblies for Wood-Frame Buildings

Published in: Proceedings Thermal Performance of the Exterior Envelopes of Whole Buildings XI, Dec 5-9, 2010, Clearwater Beach, Florida

84 Lapping & Jointing 86 Service Pipe Penetrations 87 Sealing to Cavity Wall Constructions 88 Protecting Membranes System Components.

PRODUCT SELECTION GUIDE

BDA Agrément BAW /01/C

FLASHCLAD HORIZONTAL WEATHERBOARD CAVITY CLADDING SYSTEM. Product. Scope. Appraisal No. 800 [2013] Appraisal No. 800 (2013) Amended 05 February 2016.

Leak Tightness of Jointing. 1. Basic Principles

Rev. 07 8/15 Please Read Disclaimers:

Results on Assessing the Effectiveness of Wall-Window Interface Details to Manage Rainwater

BGC STRATUM AND STRATUM DUO CAVITY CLADDING SYSTEMS. Product. Scope. Appraisal No. 847 [2013] Appraisal No. 847 (2013) Amended 14 October 2015

Background Basement Thermal Behavior

NOVABRIK MORTARLESS BRICK SYSTEM Parement extérieur Verkleidung Bedachung. Regulations

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: PROWALL BUILDING PRODUCTS, INC.

OPTIWIN MOTURA. Technical Description. Synopsis:

PLASTICS. Chapter 5. Materials of Construction-Plastics 1

CENTRIA Intercept Entyre Preformed Metal Modular Panel Wall System

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

Building blocks for your ideas

BRE Global Assessment Report

City of Republic Community Development Department. Residential Roofs REVISION DATE: JANUARY 2017

Transcription:

Rain tightness of wind barrier and sealing of window joints Experimental laboratory testing Hans Boye Skogstad, M. Sc Sivert Uvsløkk, M. Sc Ola Asphaug, B. Sc Inside the test chamber SINTEF Building and Infrastructure 1

Quantify the rain tightness to Wind barriers Sealing of window joints Background More extreme weather conditions Avoid moisture damages from rain during the building period Possibility to choose materials and sealing methods depending on the weather conditions where the building is situated More open claddings wind barrier exposed Timber frame wall SINTEF Building and Infrastructure 2

Wind barrier layer and windows mounted in timber frame wall Two step rain and air tightening Rain shield Ventilated air space Wind barrier / window sealing Timber frame with insulation Water vapor barrier Indoor cladding SINTEF Building and Infrastructure 3

Wind barrier = air barrier Moving the air tight layer to the outside of the building means fewer joints, less risk for penetration and may reduce the labor costs (Langmans 2011) An air tight wind barrier is essential to achieve a rain tight wind barrier layer The buildings air change rate can be measured early in the construction period when the wind barrier is visible from both sides easier and less costs to improve the wind barriers air tightness SINTEF Building and Infrastructure 4

Testing of water tightness, EN1027, method 1A static pressure 5 nozzles each 2 L/min 10 minutes on every pressure difference, 0- Pa Test chamber visual observation of water leakages Inside the test chamber, nozzles spraying water on the test section SINTEF Building and Infrastructure 5

Wind barriers and sealing methods tested Wind barrier materials Asphalt impregnated fiber board Gypsum board Nonwoven spun bond plastics Sealing methods Strips of nonwoven nailed down with battens Sealing compound of acrylic paste Expanding sealing tape Adhesive tape / adhesive nonwoven Adhesive bitumen membrane SINTEF Building and Infrastructure 6

Asphalt impregnated fibre board Vertikal joint Pa Horizontal joint Pa Bottom sill Pa SINTEF Building and Infrastructure 7

Asphalt impregnated fibre board Horizontal joint plastic profile 100 Pa Vertical joint Pa Bottom sill 300 Pa Horizontal joint With strips of breather membrane nailed down with battens Pa SINTEF Building and Infrastructure 8

Asphalt impregnated fibre board Vertical joint Pa Bottom sill 450 Pa Horizontal joint Pa SINTEF Building and Infrastructure 9

Asphalt impregnated fibre board SINTEF Building and Infrastructure 10

Strips of nonwoven nailed down with battens Wind barrier Rain tighness in Pa corner under above side Fibre board 0 0 0 Fibre board 50 0 100 250 Gypsum board 150 150 0 150 Nonwoven 0 0 0 SINTEF Building and Infrastructure 11

Spun-Bonded Polyethylene Flexible Sheets Test section SINTEF Building and Infrastructure 12

Polyurethane foam Sealing compound of acrylic paste Rain tighness in Pa corner under above side Polyurethane foam 200 50 200 Sealing compound 400 400 100 400 SINTEF Building and Infrastructure 13

Spun-Bonded Polyethylene Flexible Sheets Test section SINTEF Building and Infrastructure 14

Spun-Bonded Polyethylene Flexible Sheets Test section SINTEF Building and Infrastructure 15

Expanded sealing tape Expanded sealing tape With mambrane With rain shield Expanded sealing tape Without membrane With rain shield Rain tighness in Pa corner under above side 100 50 () 1) 150 1) Under the membrane SINTEF Building and Infrastructure 16

Spun-Bonded Polyethylene Flexible Sheets Test section SINTEF Building and Infrastructure 17

Adhesive tape Wind barrier Rain tighness in Pa corner under above side Fibre board 150 Gypsum board 150 250 200 Nonwoven 150 SINTEF Building and Infrastructure 18

Spun-Bonded Polyethylene Flexible Sheets Sealing of window joints SINTEF Building and Infrastructure 19

Gypsum board Test section SINTEF Building and Infrastructure 20

Asphalt impregnated fiber board Sealing of window joints SINTEF Building and Infrastructure 21

Adhesive bitumen membrane Strips of nonwoven Wind barrier Rain tighness in Pa corner under above side Nonwoven Nonwoven Nonwoven SINTEF Building and Infrastructure 22

Wind barrier, conclusion Vertical joints Battens nailed down over the joints give good tightening Unevenness under battens give leakages were vertical joints end over the window or end in horizontal joints Bad placing of nails may give early but relatively small leakages Horizontal joints Battens nailed down over the joints give good tightening Plastic profiles in joints give relatively good tightening Bad placing of nails may give early but relatively small leakages Recommendation Rain tightness of wind barrier layer minimum 300 Pa. This corresponds with details described in SINTEF design sheets SINTEF Building and Infrastructure 23

Sealing of window joints, conclusion Strips of nonwoven nailed down with battens Have been used for decades Poor tightening and not suitable when window assembled deep in wall Expanding sealing tape, polyurethane foam, sealing compound Rain tight at minimum 50 Pa Timber frame and board edges exposed for rain Timber frame underneath window has to be protected with membrane Adhesive Tape and strips of adhesive nonwoven or bitumen Rain tight at minimum 150 Pa Several test sections rain tight at minimum Pa Suitable when window assembled deep in wall SINTEF Building and Infrastructure 24

Adhesive tape and durability Adhesive tape has earlier not been recommended due to insufficient documentation of durability Several products are now tested and can document lasting adhering Adhesive tape has to document good long term adhering to the current materials used SINTEF Building and Infrastructure 25