RAPID MACROCELL TESTS OF LDX 2101 STAINLESS STEEL BARS

Similar documents
BOND STRENGTH OF REINFORCING BARS WITH DEFORMATION SPACINGS THAT EXCEED MAXIMUM SPECIFIED IN ASTM A615

CRITICAL CHOLORIDE CORROSION THRESHOLD FOR GALVANIZED REINFORCING BARS

MMFX 2 (ASTM A 1035, GRADE 100) STEEL REBAR CORROSION PERFORMANCE TESTING IN ACCORDANCE WITH AASHTO MP 18M/MP MMFX Technologies Corporation

EVALUATION OF MECHANICAL AND CORROSION PROPERTIES OF MMFX REINFORCING STEEL FOR CONCRETE

IDEA Program (Stage 1) Report for the Period June 1994 through September 1994 Contract Number NCHRP-93-ID009

Corrosion Resistance of Alternative Reinforcing Bars: An Accelerated Test

EFFECTS OF DEICERS ON CONCRETE DETERIORATION

MONITORING CORROSION ACTIVITY IN CHLORIDE CONTAMINATED CONCRETE WRAPPED WITH FIBER REINFORCED PLASTICS. Abstract. Introduction

METAL FINISHING. (As per revised VTU syllabus: )

STAINLESS STEEL SELECTION FOR FLUE GAS DESULFURIZATION EQUIPMENT

The effect of electroplating of Cr and Sn on corrosion resistance of low carbon steel (CK15)

Corrosion Properties of Enhanced Duplex Steel UNS S32304

REPRODUCIBILITY OF CRITICAL CHLORIDE THRESHOLD LEVELS FOR STAINLESS STEEL REINFORCEMENT

Bond Characteristics of ASTM A1035 Steel Reinforcing Bars

CORROSION PERFORMANCE OF EPOXY-COATED REINFORCEMENT MACROCELL TESTS

EFFECT OF CHLORIDE CONCENTRATION IN SOIL ON REINFORCEMENT CORROSION

Threshold Chloride Concentration of Stainless Steels in Simulated Concrete Pore Solution

Electrochemistry Written Response

IN SITU MONITORING OF REINFORCEMENT CORROSION BY MEANS OF ELECTROCHEMICAL METHODS

Corrosion Resistance of Heat Exchanger Fin Materials to Potassium Hydroxide Sodium Hypochlorite-Based Cleaning Chemicals and Ammonia

ONLINE MONITORING OF UNDERCOATING CORROSIONS UTILIZING COUPLED MULTIELECTRODE SENSORS. Xiaodong Sun Corr Instruments, LLC San Antonio TX, USA ABSTRACT

Corrosion Mechanisms, Monitoring, and Service Life Enhancement of Reinforced Concrete Structures

CONSIDERATIONS ON THE THRESHOLD CHLORIDE CONTENT VALUES ON THE CORROSION OF STEEL BARS IN CONCRETE

STRESS CORROSION CRACKING OF STAINLESS STEELS IN HIGH PRESSURE ALKALINE ELECTROLYSERS

1 Graphite is a form of carbon. (a) Graphite is used as a lubricant. Write down one property of graphite that explains why it is used as a lubricant.

Frequently Asked Questions (FAQ) about Epoxy-Coated Reinforcing Bars

Ulf NürnbergerN. Contribution of the group Metallic

Electricity and Chemistry

Reference Electrode for Monitoring Cathodic Protection Potential

Galvanic corrosion evaluation of 6061 aluminum coupled to CVD coated stainless steel Elizabeth Sikora and Barbara Shaw 6/9/2016

Technical Note. Chicago. Figure 2 shows epoxy-coated reinforcing. bars on a bridge deck on I-294 near

TWEED RIVER HIGH SCHOOL 2006 PRELIMINARY CHEMISTRY. Unit 2 Metals

Covered Bureau ofmaterials and Research, Research Unit 2300 Southwest Van Buren Street Januarv August 2002 Topeka, Kansas

Computational Methods in Science and Engineering

Stainless Steel & Stainless Steel Fasteners Chemical, Physical and Mechanical Properties

Ductile Iron Piles Corrosion Resistance

The Evaluation of Corrosion Behavior of AISI 347 Stainless Steel to ASTM A335 Low Alloy Steel Dissimilar Welds

SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket

ONLINE MONITORING OF CORROSION UNDER CATHODIC PROTECTION CONDITIONS UTILIZING COUPLED MULTIELECTRODE SENSORS

Machinability Enhancement of PM Stainless Steels Using Easy-Machinable Stainless Steel Powder. Bo Hu, Roland T. Warzel III, Sydney Luk

Nickel Based Superalloy Incoloy 800 (UNS N08800)

ASIAN JOURNAL OF CIVIL ENGINEERING (BUILDING AND HOUSING) VOL. 6, NO. 3 (2005) PAGES

Corrosion Protection for Concrete Structures in Marine Environments. D.B.McDonald, Ph.D., P.E, FACI

Nickel Electroplating

(a) To find out which is the more reactive metal, zinc or tin, the following experiment could be carried out. piece of zinc shiny surface

ATI FLAT ROLLED PRODUCTS Brackenridge, PA for technical competence in the field of

Oxidation and Reduction

DAMAGE RESISTANCE OF REINFORCED CONCRETE STRUCTURES THAT UTILIZE HIGH PERFORMANCE HYBRID FIBER REINFORCED (HYFRC) COMPOSITES

Methods of Corrosion Control. Corrosion Control or Corrosion Management?

SECTION REINFORCING STEEL

Design Aspects of Cathodic Protection

High-Temperature Cathodic Disbondment Testing Part 2: Parallel Testing

TECHNICAL ASSISTANCE REPORT EFFECT OF CONCRETE REMOVAL EQUIPMENT AND METHODS ON THE CONDITION OF DECK CONCRETE LEFT IN PLACE

Corrosion Rate Measurement on C-Steel

INTRODUCTION TO ELECTROCHEMISTRY: CURRENT, VOLTAGE, & BATTERIES. Introduction. Electrochemistry Revised 4/28/14

Boiling point in C. Colour in aqueous solution. Fluorine 188 colourless. Chlorine 35 pale green. Bromine X orange.

INVESTIGATION OF THE CORROSION PROPAGATION CHARACTERISTICS OF NEW METALLIC REINFORCING BARS

Standard Specification for Chemical Passivation Treatments for Stainless Steel Parts 1

CO forms CO 2. forms. (a) The coke reacts with the oxygen in the air to form carbon dioxide. C + O 2

The Selection of Magnesium alloys as Sacrificial Anode for the Cathodic Protection of Underground Steel Structure

CHEMISTRY 112 EXAM 3 JUNE 17, 2011 FORM A

a: potential difference before direct current is applied b: potential difference after the application of current

Product Test Report. PTR-3074 Swagelok Company. Rev. B Solon Road January 2015 Solon, Ohio U.S.A. Page 1 of 5

PRO S AND CON S OF HALF-CELL POTENTIALS AND CORROSION RATE MEASUREMENTS

Standard Specification for Stainless Chromium-Nickel Steel-Clad Plate 1

Introduction to Cathodic Protection

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

EFFECTS OF HAMMER PEENING AND AGING TREATMENT ON MICROSTRUCTURE, MECHANICAL PROPERTIES AND CORROSION RESISTANCE OF OIL-GRADE ALLOY 718

The surface layer of austempered ductile iron investment castings properties

Effect Of Age And Concrete Cover Thickness On Steel Reinforcement Corrosion At Splash Zone In Reinforced Concrete Hydraulic Structures

2. Wet Corrosion: Characteristics, Prevention and Corrosion Rate

P-6. Optimization of Citric Acid Passivation for Corrosion Resistance of Stainless Steel 440C. Chi Tat Kwok 1,2 and Wen He Ding 1.

Passivity Definitions and Influencing Parameters

One of the main ores of zinc is zinc blende, ZnS. There are two stages in the extraction of zinc from this ore.

ICSE-Science 2 (Chemistry) 2004

Energizer Silver Oxide (Zn/Ag ² O) Application Manual

Florida Atlantic University, U.S.A, D = diffusion coefficient ( m / s ) eff

IRON CARBONATE SCALE GROWTH AND THE EFFECT OF INHIBITION IN CO 2 CORROSION OF MILD STEEL

Study of Electrochemical Polishing Applications in some alloys to obtain high surface finish

The Effect of Cement Type on Behavior of Reinforced Concrete against Attack Sulfate Salt

CHAPTER 7 STUDIES ON CORROSION RESISTANCE OF STAINLESS STEEL CLADDINGS

European Standard En 1504

STATE OF ILLINOIS WILLIAM G. STRATTON, Governor

Chloride-induced reinforcement corrosion in blended cement concretes expores to chloride-sulfate environments

Material and Process. Specification

Sensitization & Corrosion Behaviour of Austenitic Stainless Steel 304 & 316

Study and evaluation of active corrosion protection coatings for reinforcement steel

MATERIAL SPECIFICATION FOR STEEL REINFORCEMENT FOR CONCRETE

DESIGN OF COPPER ELECTROWINNING CIRCUIT USING CONVENTIONAL CELLS

FINAL REPORT EVALUATION OF CORROSION INHIBITORS FOR CONCRETE BRIDGE DECK PATCHES AND OVERLAYS. Michael M. Sprinkel, P.E. Associate Director

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE

15 Cr-Cb ULTRA FORM STAINLESS STEEL

Offshore Wind Turbines Power Electronics Design and Reliability Research

BUMAX product portfolio

Frequently Asked Questions (FAQ) About Stainless Steel Reinforcing Bars

5072 CHEMISTRY (NEW PAPERS WITH SPA) TOPIC 9: METALS 5067 CHEMISTRY (NEW PAPERS WITH PRACTICAL EXAM) TOPIC 9: METALS

FORMATION OF TiO 2 THIN FILM BY ION-BEAM-MIXING METHOD AND ITS APPLICATION AS THE CORROSION PROTECTING FILM

Typical Applications: Chimneys, bridges, tubular bridges, façades, containers, tanks.

Corrosion Control and Cathodic Protection Data Sheet

Sealing of Hard Chrome Plating

Transcription:

RAPID MACROCELL TESTS OF LDX 2101 STAINLESS STEEL BARS By Matthew O Reilly W. Joseph Sturgeon David Darwin JoAnn Browning A Report on Research Sponsored by OUTOKUMPU STAINLESS NORTH AMERICA Structural Engineering and Engineering Materials SL Report 10-2 May 2010 THE UNIVERSITY OF KANSAS CENTER FOR RESEARCH, INC. 2385 Irving Hill Road, Lawrence, Kansas 66045-7563

RAPID MACROCELL TESTS OF LDX 2101 STAINLESS STEEL BARS By Matthew O Reilly W. Joseph Sturgeon David Darwin JoAnn Browning Research supported by OUTOKUMPU STAINLESS NORTH AMERICA Structural Engineering and Engineering Materials SL Report 10-2 THE UNIVERSITY OF KANSAS CENTER FOR RESEARCH, INC. LAWRENCE, KANSAS May 2010

ABSTRACT The corrosion resistance of LDX 2101 duplex stainless steel bars is evaluated using the rapid macrocell test specified in Annex A2 of ASTM A955-09b and compared to the performance of 2205 pickled stainless steel (2205p). LDX 2101 bars were tested in the asreceived condition as well as after submersion in simulated concrete pore solution with a ph of 13.4 for two weeks prior to testing. The LDX 2101 stainless steel bars meet the requirements of ASTM A955-09b, exhibiting limited staining and slight corrosion on the bars in salt solution with a maximum individual corrosion rate of 0.44 µm/yr and a maximum average corrosion rate of 0.10 µm/yr. No significant difference was observed in the behavior between bars tested in the as-received condition and bars tested after submersion in simulated concrete pore solution. The 2205p bars exhibited no visible corrosion products on the bars in salt solution and no measureable corrosion. Both the LDX 2101 and 2205p stainless steel bars exhibited moderate staining of the bars used as cathodes in oxygenated pore solution. Keywords: chlorides, concrete, corrosion, macrocell, reinforcing steel, stainless steel i

ACKNOWLEDGEMENTS The research described in this report was supported by Outokumpu Stainless North America. The 2205 stainless steel used in this study was provided by Gerdau AmeriSteel. ii

INTRODUCTION This report describes the tests used to evaluate the corrosion performance of LDX 2101 stainless steel bars. Performance is compared to that of pickled 2205 stainless steel. EXPERIMENTAL WORK Materials Tests were performed on No. 6 (No. 19) LDX 2101 stainless steel bars. The bars were inspected upon receipt and found to be in good condition with the exception of wear on the bars from tie-down straps used in shipping (Figure 1) and isolated defects to the surface (Figure 2). Sections of bar affected by the wear or damage were not used in testing. The deformation pattern on the bars is noted in Figures 1 and 2. The pattern features a taper on the transverse deformations and three equally spaced longitudinal ribs. Two longitudinal ribs are currently standard for bars meeting the provisions of ASTM A955-09b. Damaged Areas Figure 1: Damage to stainless steel sustained during shipping. 1

Defects Figure 2: Surface defects in stainless steel. According to the supplier, the LDX 2101 bars underwent a two-cycle cleaning and pickling procedure. Each cycle consisted of shot-blasting to remove surface scale followed by pickling for one hour at 140 F in a mix of nitric acid and hydrofluoric acid, followed by a water rinse. The 2205p bars were blasted to a near white condition with stainless grit and pickled in a 25% nitric acid, 3-6% hydrofluoric acid solution at 110 F for 40-50 minutes. The chemical compositions of the two stainless steels are given in Tables 2a and 2b. Table 2a: Chemical Compositions of Stainless Steels (Provided by Manufacturers) Material Cr Ni C Mn N P S Mo Si Sn Cu Nb LDX 2101 21.58 1.49 0.035 4.81 0.231 0.024 0.001 0.14 0.712 0.010 0.306 0.015 2205p 22.27 4.88 0.020 1.37 0.192 0.023 0.001 3.26 0.420-0.300-2

Table 2b: Chemical Compositions of Stainless Steels (Continued) Material W V Co Ti As B Pb Ca Ta LDX 2101 0.050 0.150 0.051 0.006 0.011 0.0019 0.0001 0.0032 0.005 2205p - - - - - - - - - Experimental Procedures Rapid Macrocell Test A total of 15 specimens were tested in accordance with the rapid macrocell corrosion test outlined in Annex A2 of ASTM A955-09b and pictured in Figure 3. Each bar used in the rapid macrocell is 5 in. long and is drilled and tapped at one end to accept a 0.5-in. 10-24 stainless steel machine screw. Bars are cleaned with acetone to remove surface oil and contaminants introduced by machining. A length of 16-gauge insulated copper wire is attached to each bar via the machine screw. The electrical connection is coated with an epoxy to protect the wire from corrosion. A single rapid macrocell specimen consists of an anode and a cathode. The cathode consists of two bars submerged in simulated pore solution in a plastic container, as shown in Figure 3. One liter of pore solution consists of 974.8 g of distilled water, 18.81 g of potassium hydroxide (KOH), and 17.87 g of sodium hydroxide (NaOH). The solution has a ph of about 13.4. Air, scrubbed to remove carbon dioxide, is bubbled into the cathode solution. The anode consists of a single bar submerged in a solution consisting of simulated pore solution and 15 percent sodium chloride (NaCl). The salt solution is prepared by adding 172.1 g of NaCl to one liter of pore solution. The solutions are changed every five weeks to limit the effects of carbonation. The anode and cathode are connected electrically across a 10-ohm resistor. A 3

potassium chloride salt bridge provides an ionic connection between the anode and the cathode (Figure 3). Voltmeter V Terminal Box 10 Ohm Scrubbed air Salt bridge Lid Lid Simulated Pore Solution with NaCl Simulated Pore Solution Anode Cathode Figure 3: Rapid Macrocell Test Setup ASTM A955-09b calls for No. 5 (No. 16) bars submerged to a depth of 3 in. Because No. 6 (No. 19) bars were provided, the depth of submersion was reduced to 2.44 in. to maintain the same exposed area of metal (end and sides) as obtained with No. 5 (No. 16) bars submerged to a depth of 3 in. The corrosion rate is calculated based on the voltage drop across the 10-ohm resistor using Faraday s equation. V m Rate K = n F D R A (2) where the Rate is given in μm/yr, and K = conversion factor = 31.5 10 4 amp μm sec/μa cm yr V = measured voltage drop across resistor, millivolts m = atomic weight of the metal (for iron, m = 55.8 g/g-atom) 4

n = number of ion equivalents exchanged (for iron, n = 2 equivalents) F = Faraday s constant = 96485 coulombs/equivalent D = density of the metal, g/cm 3 (for iron, D = 7.87 g/cm 3 ) R = resistance of resistor, ohms = 10 ohms for the test A = surface area of anode exposed to solution, 39.9 cm 2 Using the values listed above, the corrosion rate simplifies to: Rate = 29.V 0 (3) To satisfy ASTM A955-09b, no individual reading may exceed 0.50 μm/yr and the average rate of all specimens may not exceed 0.25 μm/yr. In both cases, the corrosion current must be such as to indicate net corrosion at the anode. Current indicating a negative value of corrosion, independent of value, does not indicate corrosion of the anode and is caused by minor differences in oxidation rate between the single anode bar and the two cathode bars. In addition to the corrosion rate, the corrosion potential is measured at the anode and cathode using a saturated calomel electrode (SCE). Readings are taken daily for the first week and weekly thereafter. A total of 12 LDX 2101 stainless steel specimens were tested. Nine were tested in the as-received condition but avoiding sections of bar with visible damage. Testing on specimens 7-9 began two weeks after starting testing on specimens 1-6. The remaining three specimens were completely submerged in pore solution for two weeks prior to the start of testing to simulate exposure to concrete prior to contact with chlorides. In addition, three specimens containing 2205 pickled stainless steel (2205p) were tested to serve as a comparison sample. 5

RESULTS Individual corrosion rate data for the nine specimens tested in the as-received condition are shown in Figure 4 (Specimens 1-6) and Figure 5 (Specimens 7-9). Average corrosion rate data for all nine specimens is shown in Figure 6. As shown in the figures, the predominant corrosion rate is negative, which, as explained before, is caused by minor differences in oxidation rate between the single anode bar and the two cathode bars. Figure 4 shows that specimen 3 exhibited a positive corrosion rate of 2.24 μm/yr at week 5, before the solution was changed. Immediately after the solution change, however, the corrosion rate fell to 0.44 μm/yr. It is believed that the single high corrosion rate data point is a statistical outlier or erroneous reading and is not sufficient reason to fail the stainless steel. No other specimen exceeded the 0.50 μm/yr limit during the course of the test. Excluding the Week 5 reading for specimen 3, individual corrosion rates ranged from 1.68 μm/yr to +0.38 μm/yr. As shown in Figure 6, the average corrosion rate ranged from 0.32 μm/yr to +0.10 μm/yr and was positive at week 5 and during weeks 14 and 15, never exceeding the +0.25 μm/yr limit (Figure 6). During the tests, the bars in pore solution without salt (cathode bars) exhibited staining, possibly due to a reaction in the oxygenated cathodic environment. Although this behavior was observed for most specimens, it is not indicative of a susceptibility to corrosion in a chloridecontaminated concrete environment. 6

2.50 2.00 Corrosion Rate (μm/yr)... 1.50 1.00 0.50 0.00-0.50-1.00-1.50-2.00 0 3 6 9 12 15 Time (weeks) M-2101p-1 M-2101p-2 M-2101p-3 M-2101p-4 M-2101p-5 M-2101p-6 Figure 4: Individual corrosion rate. LDX 2101 specimens 1-6, as received condition. 2.50 2.00 Corrosion Rate (μm/yr)... 1.50 1.00 0.50 0.00-0.50-1.00-1.50-2.00 0 3 6 9 12 15 Time (weeks) M-2101p-7 M-2101p-8 M-2101p-9 Figure 5: Individual corrosion rate. LDX 2101 specimens 7-9, as received condition. 7

0.15 0.10 Corrosion Rate (μm/yr)... 0.05 0.00-0.05-0.10-0.15-0.20-0.25-0.30-0.35 0 3 6 9 12 15 Time (weeks) Figure 6: Average corrosion rate. LDX 2101 specimens 1-9, as received condition Individual corrosion potentials with respect to a saturated calomel electrode are shown in Figures 7 and 8 for the bars in salt and pore solutions respectively. As seen in Figures 7 and 8, bars in salt solution and bars in pore solution exhibit corrosion potentials in the range of 0.100 V to 0.250 V with respect to a saturated calomel electrode. ASTM C876 states a corrosion potential more negative than -0.275 V with respect to a saturated calomel electrode ( 0.350 V with respect to a copper/copper sulfate electrode) represents a greater than 90% probability of corrosion in concrete. Although all specimens exhibited corrosion potentials more positive than 8

0.000-0.050 Corrosion Potential (V) -0.100-0.150-0.200-0.250-0.300 0 3 6 9 12 15 Time (weeks) M-2101p-1 M-2101p-2 M-2101p-3 M-2101p-4 M-2101p-5 M-2101p-6 M-2101p-7 M-2101p-8 M-2101p-9 Figure 7: Individual corrosion potential with respect to SCE. Bars in salt solution (anode). LDX 2101 specimens 1-9, as received condition. 0.000-0.050 Corrosion Potential (V) -0.100-0.150-0.200-0.250-0.300 0 3 6 9 12 15 Time (weeks) M-2101p-1 M-2101p-2 M-2101p-3 M-2101p-4 M-2101p-5 M-2101p-6 M-2101p-7 M-2101p-8 M-2101p-9 Figure 8: Individual corrosion potential with respect to SCE. Bars in pore solution (cathode). LDX 2101 specimens 1-9, as received condition. 9

0.275 V, the tests are conducted in simulated pore solution and a direct comparison to C876 cannot be made. Potentials for bars in the pore solution were on average 40 mv more negative than bars in salt solution, as would be expected based on the negative corrosion rate observed in Figures 4-6. Individual and average corrosion rate data for the three specimens submerged in simulated pore solution prior to testing are shown in Figures 9 and 10, respectively. Individual corrosion rates ranged from 0.83 μm/yr to +0.34 μm/yr. As shown in Figure 10, the average corrosion rate ranged from 0.44 μm/yr to +0.06 μm/yr and was positive at day 4 and week 6. Individual specimens exhibited positive corrosion rates at various points throughout the test (Figure 9), but at no point were the limits specified by Annex A2 of ASTM A955-09b exceeded. Overall, the performance of the specimens submerged in simulated pore solution prior to testing was similar to that of the bars tested in the as-received condition. 0.4 0.2 Corrosion Rate (μm/yr)... 0.0-0.2-0.4-0.6-0.8-1.0 0 3 6 9 12 15 Time (weeks) M-2101p-p-1 M-2101p-p-2 M-2101p-p-3 Figure 9: Individual corrosion rate. LDX 2101 specimens 1-3, submerged in simulated pore solution prior to testing. 10

0.1 0.0 Corrosion Rate (μm/yr)... -0.1-0.2-0.3-0.4-0.5 0 3 6 9 12 15 Time (weeks) Figure 10: Average corrosion rate. LDX 2101 specimens 1-3, submerged in simulated pore solution prior to testing. Individual corrosion potential data with respect to a saturated calomel electrode are shown in Figures 11 and 12 for the bars submerged in simulated pore solution prior to testing in salt solution and pore solution, respectively. Potentials for bars in the pore solution were on average 20-30 mv more negative than for bars in the salt solution, similar to the bars tested in the as-received condition. 11

0.000-0.050 Corrosion Potential (V) -0.100-0.150-0.200-0.250 0 3 6 9 12 15 Time (weeks) M-2101p-p-1 M-2101p-p-2 M-2101p-p-3 Figure 11: Individual corrosion potential with respect to SCE. Bars in salt solution (anode). LDX 2101 specimens 1-3 submerged in simulated pore solution prior to testing. 0.000 Corrosion Potential (V) -0.050-0.100-0.150-0.200-0.250 0 3 6 9 12 15 Time (weeks) M-2101p-p-1 M-2101p-p-2 M-2101p-p-3 Figure 12: Individual corrosion potential with respect to SCE. Bars in pore solution (cathode). LDX 2101 specimens 1-3, submerged in simulated pore solution prior to testing. 12

Individual and average corrosion rate data for the 2205 pickled stainless steel specimens are shown in Figures 13 and 14, respectively. As shown in Figures 13 and 14, the 2205p stainless steel specimens exhibited negative corrosion similar to LDX 2101 steel, but to a lesser degree. Individual corrosion rates ranged from 0.50 μm/yr to 0.0 μm/yr. At no point was a measurable positive corrosion rate observed for the 2205 stainless steel specimens. Average corrosion rate data are shown in Figure 14. The average corrosion rate varied from - 0.21 μm/yr to 0.0 μm/yr, meeting all requirements of Annex A2 of ASTM A955-09b. 0.00 Corrosion Rate (μm/yr)... -0.10-0.20-0.30-0.40-0.50-0.60 0 3 6 9 12 15 Time (weeks) M-2205p-1 M-2205p-2 M-2205p-3 Figure 13: Individual corrosion rate. 2205 specimens 1-3. 13

0.00-0.05 Corrosion Rate (μm/yr)... -0.10-0.15-0.20-0.25 0 3 6 9 12 15 Time (weeks) Figure 14: Average corrosion rate. 2205 specimens 1-3. Individual corrosion potential data with respect to a saturated calomel electrode are shown in Figures 15 and 16 for the 2205p bars in the salt and pore solutions, respectively. Potentials for bars in pore solution, however, were on average 40 mv more negative than bars in salt solution, similar to observed potentials for specimens with LDX 2101 stainless steel. Corrosion potentials at the bars in pore solution for the 2205p stainless steel specimens were slightly more negative than those observed for LDX 2101 stainless steel. However, corrosion rates for 2205p specimens were lower than those of LDX 2101 specimens (compare Figures 6 and 14). 14

0.000-0.050 Corrosion Potential (V) -0.100-0.150-0.200-0.250-0.300 0 3 6 9 12 15 Time (weeks) M-2205p-1 M-2205p-2 M-2205p-3 Figure 15: Individual corrosion potential with respect to SCE. Bars in salt solution (anode). 2205p specimens 1-3. 0.000 Corrosion Potential (V) -0.050-0.100-0.150-0.200-0.250-0.300 0 3 6 9 12 15 Time (weeks) M-2205p-1 M-2205p-2 M-2205p-3 Figure 16: Individual corrosion potential with respect to SCE. Bars in pore solution (cathode). 2205 specimens 1-3. 15

After testing, specimens were inspected for signs of corrosion. For the nine specimens tested in the as received condition, all specimens showed significant staining on the cathode bars (Figure 17). Furthermore, 7 of the 9 specimens showed limited corrosion products on the anode (Figure 18). Photos of all specimens appear in Appendix A. Anode Bar Figure 17: LDX 2101 specimen 3, as received condition. Bars at end of test showing staining. Figure 18: LDX 2101 specimen 6, as received condition. Anode bar at end of test. Limited staining on bar in salt solution. 16

Of the three LDX 2101 specimens submerged in simulated pore solution prior to testing, one specimen showed moderate staining on the anode (Figure 19), one specimen showed limited staining on the anode (Figure 20), and one specimen showed no staining on the anode. All specimens exhibited moderate staining on the cathode bars. Anode Bar Figure 19: LDX 2101 specimen 1, submerged in simulated pore solution prior to testing. Bars at end of test showing staining. Figure 20: LDX 2101 specimen 2, submerged in simulated pore solution prior to testing. Anode bar at end of test. Limited staining on bar in salt solution. 17

For the three 2205p specimens, all specimens showed light to moderate staining on the cathode bars (Figure 21). No corrosion products were observed on the bars in salt solution. Anode Bar Figure 21: 2205p specimen 3 showing staining at end of test. SUMMARY AND CONCLUSIONS: The corrosion resistance of LDX 2101 bars was tested using rapid macrocell tests performed in accordance with Annex A2 of ASTM 955-09b with the exception that No. 6 (No. 19) bars were used in place of No. 5 (No. 16) bars. Comparisons were also made with pickled 2205 stainless steel. The following conclusions are based on the test results presented in this report: 1. The corrosion resistance of LDX 2101 stainless steel meets the requirements of ASTM A955-09b. 2. The corrosion resistance of the 2205p stainless steel bars exceeds that of LDX 2101 bars when tested in accordance with ASTM A955-09b. 3. Staining on bars in pore solution was observed on all specimens but is not indicative of a susceptibility to chloride-induced corrosion in concrete. 18

REFERENCES ACI Committee 408, 2007, Splice and Development Length of High Relative Rib Area Reinforcing Bars in Tension (ACI 408.3-01), American Concrete Institute, Farmington Hills, MI. ASTM A955, 2009, Standard Specification for Plain and Deformed Stainless-Steel Bars for Concrete Reinforcement (ASTM A955/A955M 09b), ASTM International, West Conshohocken, PA, 11 pp. ASTM C876, 2009, Standard Test Method for Corrosion Potentials of Uncoated Reinforcing Steel in Concrete (ASTM C876-09), ASTM International, West Conshohocken PA, 7 pp. Choi, Oan Chul, Hadje-Ghaffari. Hossain, Darwin, David and McCabe, Steven L., 1990, Bond of Epoxy-Coated Reinforcement to Concrete: Bar Parameters, SL Report 90-1, University of Kansas Center for Research, Lawrence, 43 pp. Darwin, D. and Graham, E. K., 1993, Effect of Deformation Height and Spacing on Bond Strength of Reinforcing Bars, ACI Structural Journal, Vol. 90, No. 6, Nov.-Dec., pp. 646-657. 19

APPENDIX A: END OF TEST SPECIMEN PHOTOS Anode Bar Figure A1: LDX 2101 specimen 1, as received condition. Side A. Anode Bar Figure A2: LDX 2101 specimen 1, as received condition. Side B. 20

Anode Bar Figure A3: LDX 2101 specimen 2, as received condition. Side A. Anode Bar Figure A4: LDX 2101 specimen 2, as received condition. Side B 21

Anode Bar Figure A5: LDX 2101 specimen 3, as received condition. Side A. Anode Bar Figure A6: LDX 2101 specimen 3, as received condition. Side B. Figure A7: LDX 2101 specimen 3, as received condition. Anode bar. 22

Anode Bar Figure A8: LDX 2101 specimen 4, as received condition. Side A. Anode Bar Figure A9: LDX 2101 specimen 4, as received condition. Side B. 23

Anode Bar Figure A10: LDX 2101 specimen 5, as received condition. Side A. Anode Bar Figure A11: LDX 2101 specimen 5, as received condition. Side B. 24

. Anode Bar Figure A12: LDX 2101 specimen 6, as received condition. Side A. Anode Bar Figure A13: LDX 2101 specimen 6, as received condition. Side B. Figure A14: LDX 2101 specimen 6, as received condition. Anode bar. 25

Anode Bar Figure A15: LDX 2101 specimen 7, as received condition. Side A. Anode Bar Figure A16: LDX 2101 specimen 7, as received condition. Side B. Figure A17: LDX 2101 specimen 7, as received condition. Anode bar. 26

Anode Bar Figure A18: LDX 2101 specimen 8, as received condition. Side A. Anode Bar Figure A19: LDX 2101 specimen 8, as received condition. Side B. Figure A20: LDX 2101 specimen 8, as received condition. Anode bar. 27

Anode Bar Figure A21: LDX 2101 specimen 9, as received condition. Side A. Anode Bar Figure A22: LDX 2101 specimen 9, as received condition. Side B. 28

Anode Bar Figure A23: LDX 2101 specimen 1, submerged in simulated pore solution prior to testing. Side A. Anode Bar Figure A24: LDX 2101 specimen 1, submerged in simulated pore solution prior to testing. Side B. 29

Anode Bar Figure A25: LDX 2101 specimen 2, submerged in simulated pore solution prior to testing. Side A. Anode Bar Figure A26: LDX 2101 specimen 2, submerged in simulated pore solution prior to testing. Side B. 30

Anode Bar Figure A27: LDX 2101 specimen 3, submerged in simulated pore solution prior to testing. Side A. Anode Bar Figure A28: LDX 2101 specimen 3, submerged in simulated pore solution prior to testing. Side B. 31

Anode Bar Figure A29: 2205p specimen 1. Side A. Anode Bar Figure A30: 2205p specimen 1. Side B. 32

Anode Bar Figure A31: 2205p specimen 2. Side A. Anode Bar Figure A32: 2205p specimen 2. Side B. 33

Anode Bar Figure A33: 2205p specimen 3. Side A. Anode Bar Figure A33: 2205p specimen 3. Side B. 34