Technical Data Sheet. Hilti Firestop Foam CP 660. Firestop Solutions in Accordance with AS & AS BWA Report No

Similar documents
Technical Data Sheet. Hilti Firestop cable collar CFS-CC. European technical approval ETA N o 13 / Issue 10 / 2013

REGULATORY INFORMATION REPORT

Technical Data Sheet. Astro HPE Sealant. UIC of product-type: AFHPE

Tehnical Data Sheet Astro Intu Mastic. UIC of product-type: INTUM CPR-JA5015

Firestop and Fire Protection Systems

CERTIFICATE OF APPROVAL No CF 517 FSI LIMITED

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

CERTIFICATE OF APPROVAL No CF 816 BIP GMBH

AESTUVER fire-protection mastic For the AESTUVER expansion joint M

European Technical Assessment. ETA-11/0372 of Member of. General part

HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems

HILTI CP 601S Elastomeric Firestop Sealant

HILTI CP 657 Firestop Brick

This European technical approval

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

DECLARATION OF PERFORMANCE

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

HILTI CP 606 Flexible Firestop Sealant

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

CAULKING INSTRUCTIONS GRABBERGARD EFC & IFC

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the

Product Information High Performance Building Dow Corning Firestop 700 Silicone Sealant

FIRESTOP SUBMITTAL PACKAGE

Freedom One-Piece Barrier Free Showers Installation Instructions

PASSIVE FIRE PROTECTION PRODUCTS

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

GypLyner. GypLyner. Metal framed wall lining system. All our systems are covered by SpecSure when using genuine Gyproc and Isover products.

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

European Technical Assessment. ETA-12/0101 of Member of. General part

CERTIFICATE OF APPROVAL No CF 5363 NULLIFIRE LIMITED

Mapefix PE Wall. Chemical anchor for masonry and light loads

EasylationWall. External Wall Insulation System. bringing european innovation

FEATURES APPLICATIONS. Technical data sheet SSW - STEEL STRONG-WALL FOR TIMBER FRAME RACKING RESISTANCE.

Product Data Sheet SikaFuko Swell-1 Positioning Description Uses Advantages Approval / Standards Construction Product Data Packaging

High-performance anchoring adhesive. n Styrene-free n Low odour n Low wastage n No transportation restrictions

6032 SH 3P Residential Shower Installation Instructions Gelcoat & Solid Surface Bathware

Staggered stud acoustic partition system

This European technical approval

CERTIFICATE OF APPROVAL No CF 513 FSI LIMITED

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED

Installation in ceilings

3M CS-195+ Composite Sheet Product Description

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250

fermacell AESTUVER Mixed / Cable Penetration Seal S

UL Design System HW-D-1012 continued

European technical approval

Product Data Sheet Sikadur -31 CF Normal Product Description Uses ruction Const Characteristics / Advantages

SEALING & BONDING SIKA FIRE PROTECTION SOLUTIONS FOR JOINTS AND PENETRATIONS

aquapanel InstallatIon GuIde

Construction. Universal anchoring adhesive. Product Description. Tests. Product Data Sheet Edition _1. 1 Sika AnchorFix S 1/6

Property of Cooks Plumbing Supplies

European Technical Assessment ETA-17/0741 of 29/08/2017

Johns Manville MinWool Water & Fire Block Mineral Wool Insulation

LOW VISCOSITY STRUCTURAL EPOXY. Table of Contents. Made in the U.S.A. AF35LVE TECHNICAL DATA SHEET

European Technical Assessment. ETA-16/0320 of Member of. General part

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185

HILTI CP 643N Firestop collar

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS

Construction. Hydrophilic, swellable hose for sealing construction joints in watertight structures. (formerly Sika Injectoflex HPM)

U L - E U C E R T I F I C A T E

icore HR outperforms other building boards in many important ways including the following:

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 17.

Technical Bulletin Boston Street, Suite 200, Baltimore, Maryland Phone: or

FIVE STAR PRODUCTS, INC. (800)

The extra strong, extra durable, sound resistant system that you can direct fix to

Easy to Use A7 Saves You Time and Money

3M TM Polyurethane Foam Insulation Adhesive CR-20

SEPTEMBER construction type cavity barriers. SP Firestop Systems. The purpose-made solution for cavity fire stopping

Sormat ITH-Pe PRODUCT DATA SHEET. ITH-Pe - POLYESTER BASED RESIN STYRENE FREE. Polyester based injection resin, styrene free. ITH 165 Pe art.

Product Information Sheet

LIQUID NAILS HIGH STRENGTH CONSTRUCTION ADHESIVE. Product. Scope. Appraisal No. 325 [2016]

TREAT RISING DAMP AND REDECORATE IN UNDER 24HRS

FIRESTOP SUBMITTAL PACKAGE

Fire Resistant: Achieves FRL levels of 90/90/90 for load bearing walls.

PACTORep Fixer EASF AVAILABILITY. Working Hardening 3h 2h 1h30 1h Anchor Installation Resistance Admissible loads

84 Lapping & Jointing 86 Service Pipe Penetrations 87 Sealing to Cavity Wall Constructions 88 Protecting Membranes System Components.

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the

Dynamic Bonding Systems B.V. A division of Dutch Bonding Group B.V.

1-part elastic joint sealant and multipurpose adhesive

MODULAR ACOUSTIC FENCING INSTALLATION GUIDE

GypLyner UNIVERSAL Metal framed wall lining system

PYRO-SAFE. Passive fire protection products for through-penetrations

PRODUCT DATA SHEET Sikaflex PRO-3 WF

1-part polyurethane pourable self levelling floor joint sealant

European Technical Assessment ETA-16/0952 of 06/01/2017

SINTEF Building and Infrastructure confirms that. Separating floors with Hunton Silencio 36 / Hunton Silencio Thermo

St. Monica Food Pantry

SMARTPLY PROPASSIV - AIRTIGHT OSB

Sikaflex 221 is a high-adhesion, polyurethane-based sealing compound for Low-odour

Specialists in Acoustic Flooring and House to Flat Conversions

Innovative Fire Protection Systems ETA CATALOG

FIRE STOP PRODUCTS. As innovative manufacturers, we are continuously adding to our range, meeting the needs of a highly demanding market.

GIB Quiet Clip GIB CBI March Features and Benefits

SEALING & BONDING SIKA FIRE PROTECTION SOLUTIONS

Type II Environmental Declaration according ISO 14021:2001/A1:2011

RMF Intercell. NBS Specification 2013 K41

ÖSTERREICHISCHES INSTITUT FÜR BAUTECHNIK

Transcription:

Technical Data Sheet Hilti Firestop Foam CP 660 New Zealand Hilti Firestop Foam CP 660 Firestop Solutions in Accordance with AS 15.4-2005 & AS 4072.1-2005 BWA Report No. 2244100.1 Validity Extension EWFA 27912-00 Issue 1.2 Hilti Firestop Foam CP 660 Issue 1.2 page 1

Hilti Firestop Foam CP 660 Firestop Foam CP 660 Bauchemie Piktos_neu.ai Bauchemie Piktos_neu.ai Fields of Application 01.10.2006 01.10.2006 Technical Data CP 660 45%medium-sized openings Permanent firestop seals in small45% and (optimum size range: 100 x 100 mm to 0 x 0 mm) Cable trays, single cables, tied cable bundles, small conduits years years Colour Jahre Jahre Openings accommodating pipes and cables Features and Benefits 3-phase technology with optimum application characteristics (easily shapeable foam) Easily applied using the ergonomically-designed Hilti dispensers Neat and tidy application Very quick and easy to install a reliable firestop seal with only one product Easy subsequent installation of additional cables Outstanding sound insulation properties thanks to flexible foam structure Smoketightness and firestopping with one system Application temperature of pack / Storage and transport temperatures +10 C to +35 C / +5 C to +25 C Curing times Can be shaped after approx. 5 min. Can be cut after approx. 10 min. Dampfdichtigkeit Dampfdichtigkeit Easy installation without need for formwork or other aids 35% 35% 325 ml / 2.1 liters (freely foamed) und Gasdichtigkeit Rauch-Rauchund Gasdichtigkeit Metal pipes years years Red Foil pack volume / foam yield Wärmedämmend Wärmedämmend Reaction to fire, classification according to EN 13501-1 Class E Temperature resistance of the cured foam Shelf life C to + 60 C 9 months (at 23 C and stored in a dry place) Jahre Jahre The EWFA Approval can be obtained via your local Hilti contact. Ordering designation Firestop Foam CP 660 und Gasdichtigkeit Rauch-Rauchund Gasdichtigkeit und Gasdichtigkeit Rauch-Rauchund Gasdichtigkeit Volume Sales Quantity Item Number 12 pc 1 pc 203517 Dispenser HDM 3 Box 1 pc 1 pc 2005640 Cartridge holder HIT-CB 3 1 pc 1 pc 2007056 page 2 3ml Box Quantity Hilti Firestop Foam CP 660 Issue 1.2

Installation instructions Firestop Foam CP 660 is approved as a permanent firestop seal for indoor applications. The foam can be used to form a firestop seal around cables, cable trays, non-combustible pipes passing through medium-sized openings in fire compartment walls and floors. The approval must be observed. For industrial use only. Store in unopened container in a dry place. Read these instructions and safety precautions before using the product. Expiry date: See date printed on the manifold (DD/MMM/YY). Use of the foil pack after this date is not permissible! Transport and storage: Store in a cool, dry, dark place at a temperature of +5 C to +25 C Foil pack temperature: Must be between +10 C and +35 C during application. Base material temperature: Must be between 0 C and +40 C during application. Clean the opening to be sealed. The material around the opening must be dry, in sound condition and free from dust or grease. Check the foil pack holder for damage and ensure that it functions correctly. Slide the foil pack into the holder. Caution: Never use damaged foil packs and/or damaged or badly soiled foil pack holders. Remove the cap. Screw the mixing nozzle all the way onto the foil pack and tighten it securely. Check that the black mixing element is in place inside the nozzle! Do not use damaged mixing nozzles. Do not, under any circumstances, modify or tamper with the mixing nozzle. The foil pack should only be used together with the mixing nozzle supplied. A new mixing nozzle must be used with each new foil pack. Insert the holder containing the foil pack into the dispenser: Press the release button on the dispenser, pull the piston rod back as far as it will go and then insert the holder containing the foil pack into the dispenser. The foil pack opens automatically when dispensing begins. Never pierce a hole in the foil pack! This will cause the system to malfunction. Discard the unevenly mixed initial quantity: The foam dispensed by the first stroke of the dispenser must be discarded, e.g. in the empty outer packaging material. Apply the firestop foam in the opening to be sealed. The mixed components of the foam react and begin to expand approx. seconds after application (at 23 C). Fill the opening completely with firestop foam, including gaps between individual cables, etc. -NOTE It is generally best to begin in the middle of the opening, building up the foam by working from bottom to top. In openings with access from only one side, begin at the rear and work toward the front. The foam will harden in the mixing nozzle during pauses (i.e. >1 minute at 23 C; >20 seconds at 35 C). The mixing nozzle must then be changed. Release the pressure from the piston rod before changing the mixing nozzle. Use formwork made from an air-permeable material (e.g. perforated cardboard) when filling openings in floors. Recommendation: Residues in the foil pack should be completely dispensed. The remaining firestop foam can then be used for the next opening. Hilti Firestop Foam CP 660 Issue 1.2 page 3

The foam can be shaped or smoothed by hand The foam can be shaped or smoothed by hand (if necessary) after approx. 5 minutes (at 23 C). Wear protective gloves! After approx. 10 minutes (at 23 C) the foam becomes hard and it can then be cut. NOTE After hardening, any projecting foam can be trimmed off to the specified minimum depth. Trimmed-off scraps of hardened foam can be placed in the next opening and fresh foam applied around these. Subsequent installation of cables or pipes Additional cables or pipes can be installed in the opening without difficulty. Do not exceed the approved maximum number and size of cables or pipes. 1. The cable or pipe may be pushed directly through the foam. Where necessary, use a suitable tool (screwdriver or drill bit, etc.) to make a hole in the foam before pushing the cable or pipe through. Do not damage existing cables. 2. Seal any remaining gaps carefully with Firestop Foam CP 660. Additional instructions The firestop foam is not suitable for outdoor applications. The firestop foam is sensitive to UV light and is not weather-resistant. Do not allow the hardened foam to remain in contact with standing water. Distance requirements The distances are valid for single, multiple and mixed penetrations. A maximum of 60% of the seal area can can include penetrations. [mm] Wall Floor S 1 (distance between cables / cable supports and seal edge) 0 0 S 2 (distance between cable supports) 0 0 S 3 (distance between cables and upper seal edge) 25 0 S 4 (distance between cable supports and bottom seal edge) 0 0 S 5 (distance between cables and cable support above) 50 50 S 6 (distance between metal pipes and seal edge) 0 20 S 7 (distance between metal pipes and upper seal edge) 20 S 8 (distance between metal pipes) linear arrangement (distance between metal pipes) grouped arrangement) 0 40 15 20 Figure 1: Distance requirements page 4 Hilti Firestop Foam CP 660 Issue 1.2

Aperture framing / beading details for walls and floors The penetration seal depth is always 150 mm irrespective of the thickness of the wall or floor. For walls or floors with a thickness of less than 150 mm, an aperture framing or a beading must be used. Aperture framing: Box frame 150 mm deep, perpendicular to the wall/floor surface, made of gypsum or calcium silicate board at least 13 mm thick, centered in the wall (figure 2a, d). Beading: Gypsum or calcium silicate board strips at least 100 mm wide (w A, figure 2e) are installed around the opening with the necessary number of layers to form a frame on the top side of a floor, or two frames of the same height on both sides of a wall (figure 2b, c, e). The beading must be fixed by min 2 metal fasteners per plasterboard strip with a maximum distance of 150mm between the fixings. Use Hilti HUS 6, HUS-P or DBZ on rigid walls and HSP on plasterboard walls. Alternatively, follow instructions by the plasterboard system manufacturer. In case of a plasterboard wall with no insulation between the panels, an insulation that does not fill the space between the linings completely, an insulation of a density of less than 100 kg/m 3 or an insulation made from glass wool, an aperture framing has to be installed. It has to be made from material used to construct the wall, i.e. studs and boards with a minimum board thickness of 13 mm, as illustrated in figure 2a, d. Walls: The penetration seal is installed centered (figure 2a, b). Beading is applied to both sides. Floors: Flush to the soffit of the floor (figure 2c). Beading is applied to top only. a b c d e Figure 2: Aperture framing / beading and position of the seal in walls / floors Abbreviations used in figure 2 Abbreviation Description Abbreviation Description A Hilti firestop product t E Thickness of the building element E Building element (rigid or plasterboard wall construction, floor) w Width of the seal E 1 Support frame h Height of the seal t A Thickness of the seal w A Width of the frame Hilti Firestop Foam CP 660 Issue 1.2 page 5

Wall Penetrations The walls must be tested or otherwise asessed in accordance with AS15.4-2005 for the required fire resistance period. The intended use of Hilti firestop foam is to permanently or temporarily reinstate the fire resistance of: Plasterboard wall, figure 3, 4, top section (E) The wall must have a minimum thickness of 100 mm (t E ) and comprise of timber or steel studs lined on both faces and be tested to achieve a FRR of -/120/120 or 120/120/120. In addition the plasterboard wall construction shall include either 50mm thick mineral wool with density of 100kg/m 3 mineral wool cavity insulation as shown in figure 3 (top section) or the aperture of the penetration in the wall shall be lined with plasterboard to the same specification as the required on each side of the wall figure 4 (top section). Rigid wall, figure 4 bottom section (E) The wall must have a minimum thickness of 100 mm (t E ) and comprise of concrete, aerated concrete or masonry with a minimum density of 550 kg/m 3. Maximum opening size and services load Maximum opening size 400 mm 400 mm or equivalent surface area and 60% of the seal area can include penetrations. Seal thickness 150 mm (t A ). Figure 3: Blank wall seal, no services Figure 4: Details of filler Abbreviations used in figures 3, and 4 Abbreviation Description Abbreviation Description A Firestop products t A Thickness of penetration seal C, C 1, C 2,.. Penetrating services t E Thickness of the building element E, E 1, E 2,.. Building elements (wall, floor) Fire Resistant Ratings (FRR) in walls at least 100 mm thick Note: Refer to page 5, and ensure that seal thickness (t A ) 150mm Disciption of services FRR Blank opening up 400mm x 400mm -/120/120 Cable services Electrical cables: single up to 13mm or bundled up to 15 cables Communication cables: Single up to 12mm or bundled up to cables -/120/90 Electrical cable (up to 70mm) -/120/60 Steel Pipes Steel Pipes up to 100mm -/120/120 page 6 Hilti Firestop Foam CP 660 Issue 1.2

Floor Penetrations The floors must be tested or otherwise asessed in accordance with AS15.4-2005 for the required fire resistance period. The intended use of Hilti firestop foam is to permanently or temporarily reinstate the fire resistance of: Rigid floor, figure 6 (E) The Floor must have a minimum thickness of 120mm (t E ) and comprise of aerated concrete or concrete with a minimum density of 550 kg/m 3. Maximum opening size and services load Maximum opening size (w 2 x L) 400mm x 400mm or equivalent surface area and 60% of the seal area can include penetrations. Seal thickness 150m (t A ) Figure 5: Floor Penetration Abbreviations used in figures 5 Abbreviation Description Abbreviation Description A Firestop products t A Thickness of penetration seal C, C 1, C 2,.. Penetrating services t E Thickness of the building element E, E 1, E 2,.. Building elements (wall, floor) Fire Resistant Rating (FRR) in Floors at least 120 mm thick Note: Refer to page 5, and ensure that seal thickness (t A ) 150mm Disciption of services FRR Blank opening up 400mm x 400mm -/120/120 Cable services Electrical cables: single up to 13mm or bundled up to 15 cables Communication cables: Single up to 12mm or bundled up to cables -/180/90 Electrical cable (up to 70mm) -/120/90 Steel Pipes Steel Pipes up to 100mm -/120/120 Hilti Firestop Foam CP 660 Issue 1.2 page 7

page 8 Hilti Firestop Foam CP 660 Issue 1.2

Characteristics of CP 660 Additional Attributes Hilti Firestop products are comprehensively tested and individually tailored to the technical requirements of a building s mechanical and electrical installations. In addition to their superior behaviour in passive fire protection, Hilti Firestop products also meet the requirements in building technology that continue to gain significance and also help the designer and installer in meeting these additional requirements. The assessment of fitness for use has been made in accordance with EOTA ETAG N o 026 Part 2. Charecteristics Assessment of charecteristics Norm, standard, test Health and the environment Air permeability (gas thightness) Safety in use Resistance to impact / movement / Mechanical resistance and stability / Adhesion Protection against noise (Air borne sound insulation) Durability and serviceability p 50 Pa => 0.0007 q/a [m 3 /(h x m 2 )] (174 mm thickness of layer) p 250 Pa => 0.0007 q/a [m 3 /(h x m 2 )] Permeability regarding gases N 2, CO 2, CH 4 : tested Soft body impact: Energy 1200 Nm Hard body impact: Energy 10 Nm fullfills requirements of zones Type I, II, III and IV maximum opening 400 x 400 mm R w (C; Ctr) = 61 ( 1; 6) db D n,e,w (C; Ctr) = 69 ( 2; 7) db Category Y2 (suitable for penetration seals intended for use at temperatures between 20 C and + 70 C) no exposure to rain or UV May be coated with acrylic dispersion, alkyd resin, polyurethan / acrylic and epoxy resin) EN 1026 EOTA Technical Report TR001, A1 EN ISO 140-3 EN ISO 20140-10 EN ISO 717-1 Reaction to fire Class E EN 13501-1 EOTA Technical Report TR024 ETAG 026-2 Service With more than 20 years of firestop experience worldwide, Hilti is one of the leading suppliers of firestop systems. We actively help you manage your firestop projects better by providing: Quick engineering judgements Extensive technical literature On-site training and demonstration Sophisticated jobsite logistics Assurance of conformity with specific application requirements International network of Hilti firestop specialists Our network of experienced sales representatives, field engineers, firestop specialists and customer service representatives is just a phone call away - 0800 444 584 Hilti Firestop Foam CP 660 Issue 1.2 page 9

Hilti. Outperform. Outlast. Hilti (NZ) Limited 1B, 525 Great South Road, Penrose, Auckland 1061, New Zealand P.O. Box 112-0, Penrose page 10 Hilti Firestop Foam CP 660 Issue 1.2 T 0800 444 584 F 0800 329 445 www.hilti.co.nz