SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SPECIFICATION GUIDELINE

SPECIFICATION GUIDELINE

Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL FIBER FIREPROOFING REPORT HOLDER: UNIFRAX I LLC

By CTS Cement Manufacturing Corp.

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

FIRESTOPPING Products for Life Safety and Code Compliance

CSI SECTION MAINTENANCE OF CONCRETE Repair & Resurfacing with Rapid Hardening, High Strength, Low-Shrink, Non-Metallic Cementitious Materials

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

A. This Section includes acoustical panel ceilings installed with exposed suspension systems.

Protecting Penetrations in Fire Rated Construction

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

A. Source Limitations: Obtain each type of building insulation through one source.

A. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.

SECTION HVAC INSULATION

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS

SECTION PRE-ENGINEERED BUILDING INSULATION

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE

Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)

GigaCrete Specification PlasterMax. PlasterMax : Fire Rated Plaster for Direct Application over Cement Masonry Units (CMU) Interior Walls

A. Access doors and frames are part of an access door and frame allowance.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

ESR-1655 Reissued April 2014 This report is subject to renewal April 1, 2016.

SECTION BUILDING INSULATION. Display hidden notes to specifier. (Don't know how? Click Here)

TILE TILE

Design & Construction Standards, Revised January

GUIDE SPECIFICATION: DUCT LINER

International Fireproof Technology Inc.

SECTION ACOUSTICAL PANEL CEILINGS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

SECTION MANUFACTURED ROOF EXPANSION JOINTS

Fire Protection Product Applications by Contractor Trades Through Penetrations & Joints

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

Alply CLASSIC WALL Architectural Insulated Panel Wall System

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION CONCRETE PAVING SLABS SET IN MORTAR

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

SECTION COLD-FORMED METAL FRAMING

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

CELCORE CELLULAR INSULATING CONCRETE SPECIFICATION FOR RETROFIT PLACEMENT OVER EXISTING ROOF MEMBRANES

Originally Issued: 12/12/2014 Revised: 12/29/2017 Valid Through: 12/29/2018

SECTION COMMON WORK RESULTS FOR CONCRETE SSPECIALTY COATINGS

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: NATURAL POLYMERS, LLC

Pre & Post Occupancy Fire Barrier Management

Section Domestic Water Piping (Hot and Cold Water Potable Water Distribution)

SECTION RESILIENT SHEET FLOORING

***********************************************************************************

SECTION ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

FLUID APPLIED WATERPROOFING

Application Instructions for Dryvit Backstop NT For Use Beneath Claddings Other Than Dryvit EIFS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

SECTION CONCRETE AND MASONRY COATINGS

Duct Wrap 2x2 Duct Wrap 2x2+ Commercial Kitchen Grease Duct

Page 1 of 5

Retain "Preinstallation Conference" Paragraph below if Work of this Section is extensive or complex enough to justify a conference.

OptiLiner Banded Liner System, Thermal, Metal Building

BROADCAST: M BLOCKS, PLUGS, PLANKS NEW PRODUCT LAUNCH Date: June 16, 2016 Issued by: George Yoshida, Ted Colwell

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board

Florock Seamless Flooring Systems

(Project Location) (your firm's name)

SECTION ACOUSTICAL PANEL CEILINGS. A. Section includes acoustical panels and exposed suspension systems for ceilings.

HVAC Piping Insulation- FIBERGLAS Insulation

EcoTouch Insulation with PureFiber Technology

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers.

University of Delaware

Repair Maintenance Hangar Phase II August 2010

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BASF CORPORATION (RIGID PU SYSTEMS)

SECTION EXTERIOR INSULATION AND FINISH SYSTEMS

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

Installation Instructions

FIRESTOP SUBMITTAL PACKAGE

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

Trusted DIVISION: 07 SYSTEM. Conformity! ICC-ES Evaluation. not specifically. Copyright 2014

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

Florock Seamless Flooring Systems

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

3M CS-195+ Composite Sheet Product Description

BITUMEN-SET PRECAST CONCRETE PAVING SLABS

A. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Product Guide Specification

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

B. Related Sections: 1. Division 07 Section "Joint Sealants" for sealing of expansion, contraction, control, and isolation joints in tile surfaces.

Transcription:

PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 07 84 13 THROUGH-PENETRATION FIRESTOPPING A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. This section includes through-penetration firestop systems for penetrations through the following fire-resistance rated assemblies, including both blank openings and openings containing penetrating items: 1. Floor-ceiling assemblies. 2. Roof-ceiling assemblies. 3. Walls and partitions. 4. Smoke barriers. 5. Construction enclosing compartmentalized areas. B. Related Sections include the following: 1. Division 3 Section 03 30 00 Cast-In-Place Concrete 2. Division 4 Section 04 22 00 Concrete Unit Masonry 3. Division 7 Section 07 90 00 Joint Protection 4. Division 9 Section 09 20 00 Plaster and Gypsum Board 5. Division 22 Section 22 00 00 Plumbing 6. Division 22 Section 22 07 00 Plumbing Insulation 7. Division 23 Section 23 00 00 HVAC 8. Division 23 Section 23 07 00 HVAC Insulation 9. Division 26 Section 26 00 00 Electrical 10. Division 27 Section 27 00 00 Communications 1.3 PERFORMANCE CRITERIA A. FIRE TEST REQUIREMENTS 1. Underwriters Laboratories, Inc. (UL): a. ANSI/ UL1479, Fire Tests of Through Penetration Firestops. b. ANSI/ UL263, Fire Tests of Building Construction and Materials. c. ANSI/ UL723, Surface Burning Characteristics of Building Materials. 2. American Society of Testing and Materials (ASTM): a. ASTM E-814, Fire Tests of Penetration Fire Stops. b. ASTM E-119, Fire Tests of Building Construction and Materials. c. ASTM E-84, Surface Burning Characteristics of BuildingMaterials. d. ASTM E2174, Standard Practice for On Site Inspection of Installed Fire Stops. 1

B. REFERENCES 1. Underwriters Laboratories (UL) of Northbrook, IL Fire Resistance Directory. a. Through Penetration Firestop Systems (XHEZ) b. Fill, Void or Cavity Materials (XHHW) c. Firestop Devices (XHJI) d. Forming Materials (XHKU) e. Wall Opening Protective Materials (CLIV) 2. All major building codes: a. International Building Code published by ICC. (Note to specifier: Retain or delete the building codes listed above as applicable). 3. National Fire Protection Association (NFPA) of Quincy, MA NFPA 101: Life Safety Code. 4. National Fire Protection Association (NFPA) of Quincy, MA NFPA 70: National Electrical Code. 5. Factory Mutual Approvals (FM) of Norwood, MA FM 4991: Standard for Approval of Firestop Contractors. 6. Underwriters Laboratories (UL) of Northbrook, IL UL Qualified Firestop Contractor Program C. PERFORMANCE REQUIREMENTS 1. Provide products that upon curing do not re-emulsify, dissolve, leach, breakdown, or otherwise deteriorate over time from exposure to atmospheric moisture, sweating pipes, ponding water or other forms of moisture characteristic during and after construction. 2. When intumescent products are used, provide products that do not contain sodium silicate or any other water soluble intumescent ingredient in the formulation. 3. Provide firestop products that do not contain ethylene glycol. 4. Provide firestop sealants sufficiently flexible to accommodate motion such as pipe vibration, water hammer, thermal expansion and other normal building movement without damage to the seal. 5. Pipe insulation shall not be removed, cut away or otherwise interrupted through wall or floor openings. Provide products appropriately tested for the thickness and type of insulation utilized. 6. Fire rated pathway devices shall be the preferred product and shall be installed in all locations where frequent cable moves, add-ons and changes will occur. Such devices shall be: i. Capable of retrofit around existing cables ii. Designed such that two or more devices can be ganged together iii. Maintenance free such that no action is required to activate the smoke and fire sealing mechanism 7. When mechanical cable pathways are not practical, openings within walls and floors designed to accommodate voice, data and video cabling shall be provided with re-enterable products specifically designed for retrofit. 8. Provide through-penetration firestop systems and fire-resistive joint systems subjected to an air leakage test conducted in accordance with the Standards, ANSI/ UL1479 for penetration firestop systems, with 2

1.4 SUBMITTALS published L-Ratings for ambient and elevated temperatures as evidence of the ability of the fire-resistive joint system to restrict the movement of smoke. 9. Provide T-Rating Collar Devices tested in accordance with ASTM E-814 or ANSI/UL1479 for metallic pipe penetrations requiring T-Ratings per the applicable building code. 10. Provide a fire-rated grommet for all individual or small grouped cable applications up to 0.53 in. (14 mm). 11. Provide moisture-curing products where inclement weather or greater than transient water exposure is expected. A. Product Data: For each type of through-penetration firestop system product indicated. B. System Drawings: Submit documentation from a qualified third-party testing agency that is applicable to each through-penetration firestop system configuration for construction and penetrating items. C. Product Certificates: Certificate of conformance signed by manufacturers of through-penetration firestop system products certifying that products comply with requirements. 1.5 QUALITY ASSURANCE A. Provide through-penetration firestop systems that comply with the following requirements and those specified in Performance Criteria Article: 1. Firestopping tests are performed by a qualified, testing and inspection agency. A qualified testing and inspection agency is UL, or another agency performing testing and follow-up inspection services for firestop systems acceptable to authorities having jurisdiction. 2. Through-penetration firestop system products bear classification marking of qualified testing and inspection agency. B. Engage an experienced installer who is certified, licensed, FM Approved in accordance with FM 4991, Certified by UL as a Qualified Contractor, or otherwise qualified by the firestopping manufacturer as having been provided the necessary training to install firestop products per specified requirements. A manufacturer s willingness to sell its firestopping products to Contractor or to an installer engaged by Contractor does not in itself confer qualifications on buyer. C. Obtain firestop systems for each type of penetration or joint opening and construction condition indicated from a single manufacturer. D. Conduct conference at Project site to comply with requirements in Division 1 Section Project Meetings. 1.6 DELIVERY, STORAGE AND HANDLING A. Deliver through-penetration firestop system products to Project site in original, unopened containers or packages with intact and legible manufacturer s labels identifying product and manufacturer, date of manufacture; lot number; shelf life, if applicable; qualified testing and inspection agency s classification marking; and mixing instructions for multicomponent materials. 3

B. Store and handle materials for through-penetration firestop systems to prevent their deterioration or damage due to moisture, temperature changes, contaminants or other causes. 1.7 PROJECT CONDITIONS A. Do not install through-penetration firestop systems when ambient or substrate temperatures are outside limitations recommended by manufacturer. B. Do not install through-penetration firestop systems when substrates are wet due to rain, frost, condensation, or other causes. C. Do not use materials that contain flammable solvents. 1.8 COORDINATION A. Coordinate construction of openings and penetrating items to ensure that through-penetration firestop systems are installed according to specified requirements. B. Coordinate sizing of sleeves, openings, core-drilled holes or cut openings to accommodate through-penetration firestop systems. C. Schedule installation of firestopping after completion of penetrating item installation but prior to covering or concealing of openings. PART 2 PRODUCTS 2.1 FIRESTOPPING, GENERAL A. Provide through-penetration firestop systems that are compatible with one another, with the substrates forming openings, and with the items, if any, penetrating through-penetration firestop systems, under conditions of service and application, as demonstrated by through-penetration firestop system manufacturer based on testing and field experience. B. Provide components for each through-penetration firestop system that are needed to install fill materials. Use only components specified by the firestopping manufacturer and approved by the qualified testing agency for the designated fire-resistance-rated systems. 2.2 ACCEPTABLE MANUFACTURERS A. Subject to compliance with through-penetration firestop systems (XHEZ) and wall opening protective materials (CLIV) listed in Volume 2 of the UL Fire Resistance Directory, provide products of the following manufacturers as identified below: 1. Acceptable Manufacturer: Specified Technologies Inc., 210 Evans Way, Somerville, NJ 08876. Tel: (800) 992-1180, Fax: (908) 526-9623, Email: specseal@stifirestop.com, Website: www.stifirestop.com. 2. Substitutions: Not permitted. 3. Single Source: Obtain firestop systems for each type of penetration and construction condition indicated only from a single manufacturer. 4

2.3 MATERIALS A. General: Use only firestopping products that have been tested for specific fireresistance-rated construction conditions conforming to construction assembly type, penetrating item type or joint opening width and movement capabilities, annular space requirements, and fire-rating involved for each separate instance. B. Intumescent Sealants: Single component intumescent latex formulations containing no water soluble intumescent ingredients capable of expanding a minimum 8 times, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series SSS Intumescent Sealant 2. Specified Technologies, Inc. (STI) SpecSeal Series LCI Intumescent Sealant C. Endothermic Sealants: Single component latex formulations that upon cure do not re-emulsify during exposure to moisture, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series LC Endothermic Sealant D. Firestop Devices: Factory-assembled steel collars lined with intumescent material capable of expanding a minimum 30 times sized to fit specific outside diameter of penetrating item, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series SSC Firestop Collars 2. Specified Technologies, Inc. (STI) SpecSeal Series LCC Firestop Collars D. Fire Rated Cable Pathways: Gangable device modules capable of being retrofitted around existing cables and comprised of steel raceway with intumescent foam pads allowing 0 to 100 percent cable fill and requiring no additional action in the form of plugs, twisting closure, putty, pillow, or sealant to achieve fire and leakage ratings, the following products are acceptable: 1. Specified Technologies Inc. (STI) EZ-Path Fire Rated Pathway E. Wall Opening Protective Materials: Intumescent, non-curing pads or inserts for protection of electrical switch and receptacle boxes to reduce horizontal separation to less than 24 (610 mm), the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series SSP Firestop Putty Pads 2. Specified Technologies, Inc. (STI) SpecSeal Series EP PowerShield Insert Pads F. Firestop Putty: Intumescent, 100% solids, non-hardening, water resistant, butyl rubber based putties containing no solvents or silicone compounds, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series SSP Firestop Putty 5

G. Wrap Strips: Single component intumescent elastomeric strips faced on both sides with a plastic film and capable of expanding a minimum 30 times, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series RED2 Wrap Strip 2. Specified Technologies, Inc. (STI) SpecSeal Series BLU2 Wrap Strip H. Firestop Pillows: Re-enterable, non-curing, mineral fiber core encapsulated with an intumescent coating on all six sides contained in a flame retardant poly bag, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series SSB Firestop Pillows I. Mortar: Portland cement based dry-mix product formulated for mixing with water at Project site to form a non-shrinking, water-resistant, homogenous mortar, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series SSM Firestop Mortar J. Silicone Sealants: Moisture curing, single component, silicone elastomeric sealant for horizontal surfaces (pourable or nonsag) or vertical surface (nonsag), the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal SIL300 Silicone Firestop Sealant 2. Specified Technologies, Inc. (STI) SpecSeal SIL300 SL Self-Leveling Silicone Firestop Sealant K. Silicone Foam: Multicomponent, silicone-based liquid elastomers, that when mixed, expand and cure in place to produce a flexible, non-shrinking foam, the following products are acceptable: 1. Specified Technologies, Inc. (STI) Pensil 200 Silicone Foam L. Composite Sheet: Intumescent material sandwiched between a galvanized steel sheet and steel wire mesh protected with aluminum foil capable of sustaining a minimum 2,500 lbs (1,134 kg) when subjected to load testing, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal CS Composite Sheet M. Cast-In-Place Firestop Device: Single component molded firestop device installed on forms prior to concrete placement with totally encapsulated, tamperproof integral firestop system and smoke sealing gasket, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal CD Cast-In Firestop Device N. Fire-Rated HVAC Retaining Angles: Steel angle system with integral intumescent firestop gasket for use on steel HVAC ducts, the following products are acceptable: 6

1. Specified Technologies, Inc. (STI) SpecSeal FyreFlange Firestop Angles O. Firestop Plugs: Re-enterable, foam rubber plug impregnated with intumescent material capable of expanding minimum 10 times with expansion beginning at 350 F (177 C) for use in blank openings and cable sleeves, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series FP Firestop Plug P. Fire-Rated T Rating Collar Device: Louvered steel collar system with synthetic aluminized polymer coolant wrap installed on metallic pipes where T Ratings are required by applicable building code requirements, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal T-Collar Device Q. Fire-Rated Cable Grommet: Molded two-piece grommet made from plenum grade polymer with a foam inner core for sealing cable penetrations up to 0.53 in. (14 mm) diameter, the following products are acceptable: 1. Specified Technologies, Inc. (STI) Ready Firestop Grommet (RFG1 or RFG2) R. Fire-Rated Closet Flange Gasket: Molded, single-component, intumescent gasket for use beneath a closet flange in floor applications, the following products are acceptable: 1. Specified Technologies, Inc. (STI) SpecSeal Series CF34 Closet Flange Firestop Gasket PART 3 EXECUTION 3.1 PREPARATION A. Examination of Conditions: Examine areas and conditions under which work is to be performed and identify conditions detrimental to proper or timely completion. B. Surfaces to which firestop materials will be applied shall be free of dirt, grease, oil, scale, laitance, rust, release agents, water repellents, and any other substances that may inhibit optimum adhesion. C. Provide masking and temporary covering to prevent soiling of adjacent surfaces by firestopping materials. D. Do not proceed until unsatisfactory conditions have been corrected. 3.2 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLATION A. General Requirements: Install through-penetration firestop systems in accordance with Performance Criteria Article and in accordance with the conditions of testing and classification as specified in the published design. B. Manufacturer s Instructions: Comply with manufacturer s instructions for installation of through-penetration firestop systems products. 7

1. Seal all openings or voids made by penetrations to ensure an air and water resistant seal. 2. Consult with mechanical engineer, project manager, and damper manufacturer prior to installation of through-penetration firestop systems that might hamper the performance of fire dampers as it pertains to duct work. 3. Protect materials from damage on surfaces subjected to traffic. 3.3 FIELD QUALITY CONTROL A. Inspections: Owner shall engage a qualified independent inspection agency to inspect through-penetration firestop systems in accordance with ASTM E2174, Standard Practice for On Site Inspection of Installed Fire Stops. NOTE: Manufacturers are not qualified inspection agencies, and it is a conflict of interest for the manufacturer to perform inspections of installed firestopping systems according to the aforementioned inspection standards. B. Keep areas of work accessible until inspection by authorities having jurisdiction. C. Where deficiencies are found, repair or replace through-penetration firestop systems so they comply with requirements. 3.4 ADJUSTING AND CLEANING A. Remove equipment, materials and debris, leaving area in undamaged, clean condition. B. Clean all surfaces adjacent to sealed openings to be free of excess throughpenetration firestop system materials and soiling as work progresses. END OF SECTION SpecSeal Firestop Products EZ-Path Fire Rated Pathways Specified Technologies, Inc. 210 Evans Way Somerville, NJ 08876 (800) 992-1180 8