St. Monica Food Pantry

Similar documents
SECTION THROUGH-PENETRATION FIRE STOP SYSTEMS

SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION BUILDING INSULATION. Display hidden notes to specifier. (Don't know how? Click Here)

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL FIBER FIREPROOFING REPORT HOLDER: UNIFRAX I LLC

SECTION 07530CP EPDM MEMBRANE ROOFING

A. Source Limitations: Obtain each type of building insulation through one source.

Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp.

Protecting Penetrations in Fire Rated Construction

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

ACOUSTICAL WALL TREATMENT SECTION 09840

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

SECTION MANUFACTURED ROOF EXPANSION JOINTS

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

Alply CLASSIC WALL Architectural Insulated Panel Wall System

FIRESTOP SUBMITTAL PACKAGE

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

Fire Barrier Duct Wrap 615+

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION HVAC INSULATION

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

(Project Location) (your firm's name)

Design & Construction Standards, Revised January

FastWrap+ 1 1 /2 Commercial Kitchen Grease Duct Air Ventilation Duct

SECTION EXPANSION CONTROL

Pyroscat Duct Wrap XL

SECTION ACOUSTICAL PANEL CEILINGS

SECTION PRE-ENGINEERED BUILDING INSULATION

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

Residential Building Inspections

EcoTouch Insulation with PureFiber Technology

UL Design System HW-D-1012 continued

SECTION GYPSUM BOARD

SPECIFICATION GUIDELINE

Questar ThermWise Duct Technical Specifications

Floor Insulation Underlayment Section Sound Control Matting

3M CS-195+ Composite Sheet Product Description

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

GYPSUM BOARD SECTION GYPSUM BOARD PART 1 - GENERAL

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

SECTION COLD-FORMED METAL FRAMING

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

ENKASONIC FLOOR UNDERLAYMENT 9110

SPECIFICATION GUIDELINE

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS

C. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each product.

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

TILE TILE

HPW Protocol Reference Manual

A. This Section includes acoustical panel ceilings installed with exposed suspension systems.

SECTION RESILIENT SHEET FLOORING

E. Manufacturers Standardization Society of the Valve and Fittings Industry:

Duct Wrap 2x2 Duct Wrap 2x2+ Commercial Kitchen Grease Duct

Tehnical Data Sheet Astro Intu Mastic. UIC of product-type: INTUM CPR-JA5015

SECTION ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL

A. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.

3M Fire Barrier Duct Wrap 615+ Product Data Sheet and Installation Guide (Condensed Version)

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO

ADA APPROVED SURFACE APPLIED DETECTABLE WARNING SYSTEM

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

RAY-CORE Structural Insulated Roof and Wall Panels

OptiLiner Banded Liner System, Thermal, Metal Building

Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)

E. Manufacturers Standardization Society of the Valve and Fittings Industry:

ROXUL Blanket (and Batt) Insulation Section Master Guide Specification (AFB) Page 1 April 2015

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

FireMaster FastWrap XL

Union County Vocational - Technical Schools Scotch Plains, New Jersey

ROCKWOOL Blanket (and Batt) Insulation Section Master Guide Specification Page 1 Jan 2017

Pella 250 Series. Wood Frame Construction with Vinyl Siding... V250-ID-888 Wood Frame Construction with Brick Veneer...

SECTION ACCORDION FOLDING PARTITIONS

Façade Architectural Wall Panel System - Guide Specification 3/11/2017 SECTION FRAMED DECORATIVE PANEL SYSTEMS PART 1 - GENERAL 1.

International Fireproof Technology Inc.

EDGEWATER, FLORIDA JUNE 14, 2010

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING

Building Codes and Ordinances ARC 227

SECTION COPPER WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.***

FLUID APPLIED WATERPROOFING

SEALING & BONDING SIKA FIRE PROTECTION SOLUTIONS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

Common Firestop Code Violations

FireMaster FastWrap XL

ROXUL Roof and Deck Insulation Section Master Guide Specification (MONOBOARD ) Page 1 April 2016

1. Interior gypsum wallboard. 2. Exterior gypsum board panels for ceilings and soffits. 3. Tile backing panels.

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

3M Fire Protection Products. Confidence. Even Under Fire. Principal Products Ltd I Ph: I

FIRE AND SMOKE PROTECTION FEATURES

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

DECEMBER Phone: Fax:

A. This Section includes joint sealants for the following applications, including those specified by reference to this Section:

Fire Protection Product Applications by Contractor Trades Through Penetrations & Joints

HILTI CP 606 Flexible Firestop Sealant

Transcription:

St. Monica Food Pantry 07 8400-1 SECTION 07 8400 - FIRESTOPPING PART 1 - GENERAL 1.1 SUMMARY: A. Related work: 1. Concrete. 2. Mortar and grout. 3. Brick masonry. 4. Concrete unit masonry. 5. Structural steel. 6. Metal decking. 7. Metal fabrications. 8. Rough carpentry. 9. Thermal insulation. 10. Joint sealants. 11. Windows. 12. Gypsum board. 13. Fire protection specialties. 14. Mechanical. 15. Plumbing. 16. Electrical. 1.2 SYSTEM PERFORMANCE REQUIREMENTS: A. systems shall provide resistance to spread of fire, and passage of smoke and other gases according to requirements indicated, including but not limited to the following: 1. Firestop penetrations passing through fire resistance rated wall and floor assemblies and other locations as indicated on drawings. 2. Penetration firestopping systems shall have been tested and approved by third party testing agency. 3. Through-penetration firestop systems and devices shall resist spread of fire, and passage of smoke and other gases according to requirements indicated, including but not limited to the following: a. F - rating shall equal or exceed the rating of the fire-resistive construction assembly through which the penetration is made, as determined by ASTM E814-08b, but shall be not less than 1-hour. b. T - rating, in addition to F-rating, at penetrations located outside of a wall cavity, shall equal fire-resistive rating of floor construction, as determined by ASTM E814-08b, but shall be not less than 1-hour. c. L - rating: In addition to F and T ratings, firestopping shall have an L - rating, as determined by UL 1479, where indicated by code. d. W - rating: In addition to F, T and L ratings, firestopping shall have W - rating, as determined by UL 1479, where indicated. 4. Fire-resistive joints shall have fire-resistance ratings indicated, as determined by UL 2079, but not less than fire-resistance rating of construction in which the joint occurs. 5. Firestop systems using cementitious fill materials shall not be permitted. 6. Systems shall be free of asbestos and volatile organic compounds (VOCs). 7. Where there is no specific third party tested and classified firestop system available for a particular firestop configurations, obtain from firestop manufacturer, an Engineering Judgement (EJ) or Equivalent Fire Resistance Rated Assembly (EFFRA). 8. Systems used within or adjacent to occupied spaces shall be free of volatile solvents, noxious fumes and strong odors.

St. Monica Food Pantry 07 8400-2 1.3 SUBMITTALS: 9. used for this project shall be FMR approved as listed in the current edition of the FMR Building Material Approval Guide. A. Shop drawings: Submit detailed drawings of each type and size penetration through fire-rated construction, indicating materials, dimensions, assembly construction and rating. Indicate through-penetration firestop system design listings, including illustrations from a qualified testing and inspection agency for each type penetration. B. Product data: Submit product data and installation instructions for each type of installation. Include installation details and test reports indicating that firestopping materials, systems and devices meet specified requirements and design criteria. Indicate Classification marking of qualified testing and inspection agency. C. Certifications: 1. Submit written certification that firestop materials are asbestos free and that materials comply with local regulations. 2. Submit written certification that firestop materials comply with local regulations controlling use of volatile organic compounds (VOC s) and are non-toxic to building occupants. D. LEED submittals: 1. Product Data for Credit IEQ 4.1: For penetration firestopping sealants and sealant primers, documentation including printed statement of VOC content. 1.4 QUALITY ASSURANCE: A. Applicable standards; standards of the following, as referenced herein: 1. ASTM International (ASTM). 2. Factory Mutual Research (FMR). 3. National Fire Protection Association (NFPA). 4. Underwriters Laboratories, Inc. (UL). B. Fire-test-response characteristics: Provide firestopping system design listing by a testing and inspection agency in accord with the specified UL standards. C. Acceptable installer shall be: 1. Installer Qualifications: A firm that has been approved by FM Global according to FM Global 4991, "Approval of Firestop Contractors," or been evaluated by UL and found to comply with UL's "Qualified Firestop Contractor Program Requirements." 2. Licensed by state or local authority, where applicable. 3. Successfully completed not less than 5 comparable scale projects. D. Single source responsibility: Obtain firestop systems for each kind of penetration and construction condition indicated from a single primary firestop systems manufacturer. 1. Materials from different manufacturer than allowed by tested and listed system shall not be intermixed in the same firestop system or opening. 2. Install tested and listed firestop systems before installing an Engineering Judgement or Equivalent Fire Resistance Rated Assembly (EFFRA).

St. Monica Food Pantry 07 8400-3 1.5 DELIVERY STORAGE AND HANDLING: A. Deliver firestopping materials in original, unopened containers or packages with intact and legible manufacturers labels identifying product and manufacturer. B. Store and handle firestopping materials in accord with manufacturer s product data. 1.6 JOB CONDITIONS: A. Coordinate firestopping installation with other work requiring penetrations through fire-resistive construction. Install penetrating elements prior to installation of firestopping systems or devices. B. Secure inspection and approval of firestopping work by building officials prior to concealment. C. Support penetrating elements independently of firestopping systems or devices. D. Do not cover up firestopping installations until Owner s inspection agency or Authorities Having Jurisdiction have examined each installation. PART 2 - PRODUCTS 2.1 MATERIALS, GENERAL: A. VOC Content: Penetration firestopping sealants and sealant primers shall comply with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24): 1. Sealants: 250 g/l. 2. Sealant Primers for Nonporous Substrates: 250 g/l. 3. Sealant Primers for Porous Substrates: 775 g/l. 2.2 THROUGH-PENETRATION FIRESTOP SYSTEMS: A. Acceptable manufacturers; subject to compliance with specified requirements: 1. Grace Construction Products. 2. Hilti USA. 3. 3M Fire Protection Products. 4. Nelson Firestop Products. 5. Rector Seal Corp. 6. Specified Technologies, Inc. (STI). 7. Tremco, Inc. B. System description: Field-constructed firestopping for penetrations through walls and floors composed of specified materials and accessories assembled in accord with Through-Penetration System Numbers, listed in UL Building Materials Directory, current Edition, and tested in accord with ASTM E814-08b. C. Materials: UL Classified for use in through-penetration firestop systems. 1. Firestop sealant: Single-component, elastomeric silicone or endothermic latex sealant compound; self-adhering, flexible and watertight; non-sag and self-leveling types as required. 2. Firestop foam: Two-part, room temperature vulcanizing, silicone elastomer, non-combustible foam void seal. 3. Intumescent sealants and putties: Single-component, synthetic, organic/inorganic intumescent elastomers.

St. Monica Food Pantry 07 8400-4 4. Intumescent wrap strips: One-part, organic/inorganic, intumescent elastomeric sheet; aluminum foil-faced one side. 5. Intumescent composite sheets: Composite sheets composed of organic/inorganic intumescent elastomeric core bonded on one side to 28 ga. galvanized steel sheet and other side reinforced with steel wire mesh, covered with aluminum foil. 6. Mineral wool or ceramic fiber safing: Non-combustible fiber tested in accord with ASTM E136-09, with melting point in excess of 2000 degrees F.; flame spread of 15 maximum and 0 smoke development when tested in accord with ASTM E84-09. Thickness and density shall be as required by Through-Penetration Firestop System designs. D. Accessories: 1. Primers, adhesives and backer rods: As required by manufacturer's product data and system designs. 2. Forming, damming and packing materials: Types as indicated in Through-Penetration Firestop Systems. 3. Restricting collars: Manufacturer's standard design as required for firestop system. 4. Fasteners, anchor clips, sleeves, clamps, spacers, ties, cover plates and miscellaneous accessories: Provide as required by manufacturer's product data and in accord with Through-Penetration Firestop System designs. 2.3 THROUGH-PENETRATION FIRESTOP DEVICES: A. Acceptable manufacturers; subject to compliance with specified requirements: 1. Grace Construction Products. 2. Hilti USA. 3. Isolatek International, Inc. 4. Nelson Firestop Products. 5. ProSet Systems, Inc. 6. Specified Technologies, Inc. (STI). 7. Tremco, Inc. B. Types: Factory-assembled, self-contained firestopping devices for penetrations through walls and floors; UL Classified for Through-Penetration Firestop Devices as listed in UL Building Materials Directory, current Edition, and tested in accord with ASTM E814-08b. C. Accessories: Provide sealants, adhesives, fasteners, sleeves, clamps, spacers, anchor clips, ties and accessories in accord with manufacturer's product data and as required for complete installation. 2.4 FIRESTOP SEALANTS: A. Acceptable products; subject to compliance with specified requirements: 1. Grace Construction Products, FlameSafe Silicone Sealant. 2. Hilti USA, CP 601S Firestop Sealant. 3. Nelson Firestop Products, CLK. 4. 3M Fire Protection Products, Fire Barrier Silicone Sealant 2000 N/S. 5. Rector Seal Corp., Metacaulk 835+. 6. Specified Technologies, Inc. (STI), SpecSeal Pen 300 Silicone Joint Sealant. 7. Tremco, Inc., Fyre-Sil. B. Characteristics: Single-component, self-adhering, flexible, watertight, elastomeric silicone sealant compound; UL Classified. Provide self-leveling type for horizontal applications, non-sag type for all other applications.

St. Monica Food Pantry 07 8400-5 2.5 SAFING: A. Acceptable products; subject to compliance with specified requirements: 1. Thermal Ceramics, Cerablanket F.S. 2. Thermafiber Inc., Thermafiber Safing Insulation. B. Characteristics: 1. Material: Semi-rigid mineral fiber insulation, meeting ASTM C665-06, Type 1. 2. Density: 4.0 pcf. 3. Thickness: As indicated. 4. Facing: Unfaced. 5. Fire resistance properties: a. Melting point: Minimum of 2000 F. when tested in accord with ASTM C24-09. b. Non-combustible: As defined by ASTM E136-09 and NFPA. c. Fire hazard characteristics: Maximum flame spread of 15 and smoke development of 5 when tested in accord with ASTM E84-09 (unfaced). C. Accessories: 1. Clips: Insulation manufacturer's standard galvanized steel impaling clips for attachment of safing. 2. Sealant: Manufacturer's tested sealant material for foil-faced smoke seal. PART 3 - EXECUTION 3.1 PRE-INSTALLATION REQUIREMENTS: A. Pre-installation meeting: Prior to beginning firestopping work, a pre-installation meeting shall be held to review work to be accomplished. 1. Contractor, Architect, firestopping system manufacturers' representatives, installer and other subcontractors whose work involves firestopping shall be present. 2. Contractor shall notify all parties at least seven days prior to time for meeting. 3. Contractor shall record minutes of meeting and distribute to attending parties. 3.2 EXAMINATION: A. Examine areas to receive firestopping materials prior to beginning work. Verify that opening areas and dimensions for penetrations to receive firestopping systems and devices do not exceed design requirements. B. Remove projections interfering with installation. Prepare surfaces in accord with manufacturer's product data and UL Through-Penetration Firestop Devices Numbers. 3.3 PREPARATION: A. Priming: Prime substrates where recommended by firestopping manufacturer using that manufacturer s recommended products and methods. Confine primers to areas of bond. Do not allow spillage and migration onto exposed surfaces.

St. Monica Food Pantry 07 8400-6 B. Masking tape: Use masking tape to prevent firestopping from contacting adjoining surfaces that will remain exposed upon completion of the Work. Remove tape as soon as it is possible to do so without disturbing the firestopping seal with substrates. 3.4 INSTALLATION: A. General: 1. Comply with manufacturer's product data and UL Classified for Through- Penetration Firestop Devices Numbers. 2. Install firestopping materials fitted to adjacent construction to fill voids. 3. Firestop penetrations through fire-rated walls, partitions, floors and floor/ceiling assemblies with tested assemblies in accord with UL 1479 or with a through-penetration firestop system or device when tested in accord with ASTM E814-08b. 4. shall comply with code requirements. B. Fire and smoke barrier identification: 1. Fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other rated wall required to have protected openings shall be effectively and permanently identified with signs or stenciling in a manner acceptable to the Authority having Jurisdiction. 2. Such identification shall be above any decorative ceiling and in concealed spaces, and near the top of the wall or barrier in unfinished spaces. 3. Such identification shall be letters a minimum of 2" (51 mm) high on a contrasting background, spaced at 12'-0" o.c. maximum, with a minimum of one per wall or barrier. Comply with code requirements. 4. Suggested wording for fire and smoke barriers: HOUR FIRE AND SMOKE BARRIER PROTECT ALL OPENINGS. C. Through-penetration firestop systems and devices: 1. Install at penetrations through fire-rated floor and wall construction, including partitions and floor/ceiling assemblies, in accord with manufacturer's product data and UL System Numbers. Provide materials and accessories as required. 2. Install intumescent type firestop systems where plastic piping, cable, conduit and other combustible items, including insulated metal pipes, penetrate fire-rated construction. 3. At Contractor's option, through-penetration firestop devices of similar function may be installed in lieu of firestop systems. 4. Do not remove forming materials unless specified in system designs. D. Firestop sealant: Seal perimeters, voids and joints of fire-rated walls and partitions, including abutment of floor and roof or ceiling structure,and flutes of metal decking. 1. If required by UL Design, install mineral wool or ceramic fiber in cavities, packed full and tight with allowance for sealant installation. 2. Seal both faces of walls and partitions with firestop sealant. Tool sealant flush with adjacent finish. 3. In accord with UL Fire Resistance Directory Designs, packed concrete and masonry joints shall be sealed using firestop sealant or using sealant as specified in Joint Sealants section. E. Mineral fiber safing: 1. Install safing in cavities of penetrations through non-rated floor and wall construction, including spaces around piping, conduits, cables and duct penetrations.

St. Monica Food Pantry 07 8400-7 2. Install safing in voids and joints of non-rated walls and partitions abutting metal decking of floor and roof structures. Pack flutes of metal decking solid with safing material. 3. Safing shall be installed at joints and penetrations in non-rated construction not exposed to view and concealed in finish work. Secure safing by compressing into voids or joints and using manufacturer's standard clips or closure plates as required. F. Seal voids and joints of non-rated walls and partitions abutting concrete floor and roof construction using sealant as specified in other sections. 3.5 FIELD QUALITY CONTROL: A. Inspection: Independent inspection agency employed and paid by Owner, will examine penetration firestopping in accord with ASTM E2174-04 and ASTM E2393-04. Inspection agency will examine firestopping and will determine, in general, that firestopping has been installed in compliance with tested and listed firestop system, and that installation process conforms to FM 4991 - Standard for Approval of Firestop Contractors or UL Qualified Firestop Contractor Program. B. Inspector will advise contractor of deficiencies noted within one working day. C. Do not proceed to enclose firestopping with other construction until inspection agency has verified firestop installation complies with requirements of Contract Documents. D. Where deficiencies are found, repair or replace firestopping so that it complies with requirements of tested and listed system design. 3.6 CLEANING: A. Clean off excess fill materials and sealants adjacent to openings and joints as work progresses. Use methods and cleaning materials approved by manufacturers of firestopping products and or assemblies in which openings and joints occur. B. Protect firestopping during and after curing period from contact with contaminating substances. End of Section