The Importance of Slab Edge & Balcony Thermal Bridges

Similar documents
Is Your Envelope Effective? BCBEC Luncheon January 29, 2009

Thermal Bridging in Building Thermal Envelope Assemblies: Repetitive Metal Penetrations

The Concept of Linear and Point Transmittance and its Value in Dealing with Thermal Bridges in Building Enclosures

Thermal Bridging and Whole Building Energy Performance

Thermal Bridging in Residential Construction

Impact of Insulated Concrete Curb on Concrete Balcony Slab

Thermal Performance of Nvelope NV1 Clip System

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

Thermal Performance of Nvelope NV1 Clip System

Why Control Heat flow? How to Control Heat Flow? Thermal Performance. Modes of heat transfer: Thermal Control: Insulation & Thermal Bridges

When R-Value Doesn t Measure Up

Building Science Fundamentals Thermal Control: Insulation & Thermal Bridges May 29-30, Straube buildingscience.com 1 of 24

PART 1 BUILDING ENVELOPE THERMAL ANALYSIS (BETA) GUIDE

Slab edge insulation is one of

Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure

2010 National Building Code Adoption and Associated Process Changes

Building Enclosure Details and Assemblies for Wood-Frame Buildings

Local Temperature Measurements on Full-Size Systems in the Laboratory: Insight into the Extent of Thermal Bridges in Building Envelope Components

COLD CLIMATE HOUSING RESEARCH CENTER CCHRC. Whole Wall R-Values

A New Insulation Solution

The Role of Control Layers in Building Enclosure Design

Cladding Attachment Solutions for Exterior Insulated Commercial Walls

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Superior strength, flexibility, safety and value.

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Understanding the National Energy Code of Canada for Buildings, 2011

Insulation Retrofit Options

THERMAL INSULATION FROM WOOD FOR BUILDINGS:

Continuous Insulation Systems for Exterior Walls

Insulation Technologies and Installation Specifications for Better Energy Performance of Commercial Buildings

THE OPTIMAL INSULATION DETAIL OF THE THERMAL BRIDGE ADJACENT TO HOT WATER PIPES IN APARTMENT BUILDING SLABS. Seung Yeong Song & Kwang Woo Kim

Experimental Assessment of Hygrothermal Performance of Wood Frame Wall System in Suzhou's Lake Tai Climate Zone

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Manitoba Energy Code for Buildings. Part 3 Building Envelope

Metal Buildings and Condensation. Welcome to Metalcon Condensation Description. Program Objectives. Dew Point Temperatures

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

Thermal Bridging: It Can Be Done Better

Zero Carbon Building Energy Modelling Guidelines. October 31, 2017

ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;

Building Enclosure Detailing for Balconies

Net Zero Building Enclosure Retrofits for Houses: An Analysis of Retrofit Strategies

Reconsidering the Approach towards Determining Overall Building Enclosure Thermal Performance for Code Compliance

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER

Spray Polyurethane Foam: The Need for Vapor Retarders in Above-Grade Residential Walls

R-Value. Effective. Energy efficiency of masonry s thermal mass is recognized by code 9" 2" R21 + R18 THERMAL MASS +13 R13 R18

Balancing the Control of Heat, Air, Moisture, and Competing Interests

Construction Report NYSERDA Residential Performance Challenge

Building America Special Research Project: High-R Walls Case Study Analysis

BUILDING ENCLOSURE DESIGN GUIDE WOOD FRAME MULTI-UNIT RESIDENTIAL BUILDINGS. Summary. 1. Introduction

A Study on the Evaluation of the Heat Transmission Performance and Improvement of Thermal Insulation of Stone Finished Curtain Wall System

building science.com Building Science Digest 106 Understanding Vapor Barriers (rev. April 2011) by Joseph Lstiburek Abstract:

Overview. Insulating Load-Bearing Masonry Buildings. Mass Walls (Rain Control) Inside or Outside Insulation? 11/17/2017

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide.

Energy equivalent R-value

HPW Protocol Reference Manual

Integrated Strip Foundation Systems for Small Residential Buildings Rasmussen, Torben Valdbjørn

Energy Conservation & Building Envelope. Objectives. Introduction. Determine the Building Envelope of a House Calculate Heat Loss of a Building

REFLECTIVE INSULATION, RADIANT BARRIERS, AND INTERIOR RADIATION CONTROL COATINGS FOR USE IN PRE-ENGINEERED METAL BUILDINGS

Breathability of building elements

Ontario s Building Code

Truss Heel Heights and Energy Code Requirements. Overview Revised 2/17/2017

TW50. Insulation STANDARD DETAILS FOR 50 MM INSULATION BOARD IN A 100 MM CAVITY. Low Energy Low Carbon Buildings. Wall lining. Inner leaf blockwork

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research

2013 COMMERCIAL PRODUCTS

Available online at ScienceDirect. Procedia Engineering 146 (2016 ) 60 68

Crawl Spaces and Basements: Defining the Building Envelope

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Chapter Meeting: Joint Meeting with Boston CSI and ICRI at Granite Links Insulating Load-Bearing Masonry Building January 8, 2014

Reduce Wall Condensation Potential with Insulated Sheathing TECH SOLUTIONS 214.0

RESEARCH HIGHLIGHT. Design Development of Low-Energy and Affordable Multi-Unit Residential Buildings

2006 INTERNATIONAL ENERGY CONSERVATION CODE

Top plates. Stud. Pre cut stud. 8 ft, 1 1/8 inch. 4 inch brick veneer ½ inch plywood sheathing. Insulation placed between the studs

Acceptable Construction Details, Thermal Bridging and Air Permeability. Sean Armstrong, Technical Adviser, Building Standards, DEHLG

Thermal insulation of buildings and cooling demand

Energy consumption and thermal comfort in a passive house built in Romania

The environmentally-friendly Beaver Barracks Redevelopment Project uses cutting edge thermal break elements in construction - Schöck Isokorb

Apartment building Sodastraße 40 in Ludwigshafen, DE

En e r g y Ef f i c i e n c y, Co n t i n u o u s In s u l at i o n a n d Ou t s u l at i o n Sy s t e m s

Condensation on Indoor Glass Surface

Advanced technologies for enhancing the building envelope. 3M Building and Construction Market

An Evaluation of the Total Energy Consumption of Educational Buildings: Prototype Case Studies in Saudi Arabia

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

Inspection of New One- and Two- Family Dwellings

Wood-Frame wall Assemblies

Energy Efficiency, Continuous Insulation and Outsulation Systems

Fenestration Energy Performance:

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International

Smart Vapor Retarders

Thermal Environment of Chinese Residential Buildings with Different Thermal Insulation Materials in Hot-Summer-and-Cold-Winter Zone of China

THERMAL MASS CHAPTER 6. Understanding thermal mass. Seasonal effects of thermal mass

Airspace R-Values. Educational Overview. Revised 12/6/2016

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont

Beginning of the Course

2006 Building Science Press All rights of reproduction in any form reserved.

Thermal optimization of curtain wall façade by application of aerogel technology

Using Thermal Modeling to Evaluate Cladding Support Systems

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

Transcription:

Exterior Exterior Thermal Break Prepared by Date RDH Building Engineering Ltd. September 24, 2013 Interior 18.6 C Interior 18.6 C Report # 2: Impact of Slab Thermal Breaks on Thermal Comfort and Condensation Control The Importance of Slab Edge & Balcony Thermal Bridges

The Importance of Slab Edge & Balcony Thermal Bridges Report # 2 - Impact on Thermal Comfort and Condensation Control Thermal bridging occurs when heat flow bypasses the insulated elements of the building enclosure. Bridging occurs through structural components such as the studs/plates, framing, and cladding supports as well as the larger columns, shear walls, and exposed floor slab edges and protruding balconies. While thermal bridging occurs through the roofs, floors, and below-grade assemblies, it is often most pronounced in above-grade wall assemblies. The heat flow through thermal bridges is significant and disproportionate to the overall enclosure area so that a seemingly well insulated building can often fail to meet energy code requirements, designer intent, or occupant expectations. Windows are often seen as the largest thermal bridge in buildings, as the thermal performance is often quite low compared to the surrounding walls (i.e., an R-2 metal frame window within an R-20 insulated wall); however, exposed concrete slab edges and balconies can have almost as large of an influence having effective R-values of approximately R-1. After accounting for windows and doors, exposed concrete slab edges and balconies can account for the second greatest source of thermal bridging in a multi-storey building. With a better understanding of the impacts of thermal bridging, the building industry has started to thermally improve building enclosures; for example, the use of exterior continuous insulation in walls is becoming more common. Unfortunately the impact of floor slab edges and balconies is still often overlooked. At the same time, the architectural look of exposed slab edges and protruding balconies or eyebrow elements is becoming more common. Many designers believe that these relatively small elements have a negligible impact on the overall performance of the building or see them as an unavoidable compromise to achieve a certain appearance. Unfortunately, the impact of exposed slab edges and balconies is very significant, as this report will demonstrate. The relative impact of these elements also increases as more highly insulated walls are required by upcoming building code changes or sustainable building programs. Fortunately, there are solutions available in the marketplace that help to minimize the thermal bridging impact at slab edges and balconies and allow for continued architectural design freedom under increasingly more stringent energy code requirements and occupant demands. This research report addresses the thermal control, comfort, energy, and cost impacts of exposed slab edges and balconies. It provides proven solutions and discussion of their implications with respect to these parameters. rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 1

Exposed Slab Edge & Balcony Thermal Bridge Research Study A research project was undertaken by RDH to quantify the thermal impact of exposed slab edges and balconies in mid- to high-rise residential buildings across climate zones in Canada. The impact of exposed slab edges and balconies on the effective wall R-values, indoor temperatures, and indoor thermal comfort was assessed. Space heating and cooling loads were also modeled in each climate zone for an archetypal multi-unit residential building to quantify the energy loss through exposed slab edges and balconies and to determine the space conditioning savings that could be achieved in typical scenarios when balcony and slab edge thermal break products are used. Canadian climate map showing Climate Zones 4 through 8 per the 2011 NECB. ASHRAE 90.1-2010 uses a similar climate zone map; however, Zone 4 is bumped into Zone 5 due to differences in reference climate data between NECB and ASHRAE. Thermal bridging paths through the enclosure of a concrete multi-storey building with balconies The study addresses the following topics: Quantification of effective R-values, linear transmittance values (ψ), and indoor surface temperatures for various typical North American wall assemblies with and without exposed slab edges and balconies and with various balcony thermal break solutions. Assessment of various thermal modeling parameters including floor finishes, in-slab heating, and balcony depth. Comparison of the effective thermal performance of several alternate balcony thermal break solutions, insulation strategies, and manufactured thermal break products. Comparison of the space conditioning (heating and cooling) energy consumption for multi-unit residential buildings with exposed slab edges and balconies and with the various thermal break solutions. This Report #2 of 4 specifically covers the impact of balcony and slab edge thermal break products on thermal comfort and condensation control. Report #1 covers R-values and energy code compliance and Report #3 covers energy modeling along with energy and cost savings. Report #4 covers thermal modeling considerations and alternate systems. rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 2

Methodology: Thermal Modeling of Exposed Concrete Slab Edges for Thermal Comfort and Condensation Thermal bridging at concrete slab edges results in heat bypassing the wall insulation, which not only reduces the effective R-value of the entire wall but also reduces the interior surface temperatures near the interface during the colder winter months, which affects occupant comfort and the potential for surface condensation and organic growth (mould and mildew). As part of this study, the thermal comfort impact of exposed slab edges and balconies was thermally modeled for several different wall assemblies (including window wall) commonly constructed within North America. Effective R-values and surface temperatures were calculated using the three-dimensional finite element thermal modeling software, Heat3. This program has been validated to ISO 10211 standards and is widely used by researchers and consultants to perform advanced thermal simulations to calculate 3D effective R-values of building enclosure assemblies and details. RDH has also performed in-house confirmation of the software results with published guarded hot-box laboratory testing and ASHRAE 90.1 thermal data. To calculate interior surface temperatures, a variety of different inputs were used within the Heat3 software. The models were created using published material properties and defined boundary conditions. Heat3 performs a finite difference calculation to determine the heat flow through the assembly, which is then divided by the temperature difference to determine the U-value. The inverse of the U-value is the R-value. Further information can be found within the Appendix. Photograph showing condensation and organic growth on the ceiling of a concrete slab adjacent to an exposed slab edge thermal bridge. Condensation has formed here frequently as a result of colder interior surface temperatures. The thermal impact of purpose-built cast-inplace concrete thermal breaks such as this Schoeck Isokorb product were evaluated within this study. rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 3

Thermal Comfort Impact of Exposed Slab Edges & Balconies The thermal comfort impact of exposed slab edges, eyebrows, and balconies is assessed by thermal modeling interior floor and ceiling surface temperatures for each slab edge design scenario. Cold surface temperatures of interior surfaces of walls and windows can create the feeling of drafts, lower the mean radiant temperature (the temperature of the surroundings with in which an occupant radiates heat), as well as the risk of condensation and organic growth as discussed in the subsequent section of this report. Floor Temperature 8.2 C Ceiling Temperature Exterior (-10 C ) Interior (21 C ) 8.2 C 3.8 C 5.4 C 7.0 C Exterior (-10 C ) Interior (21 C ) Interior-Insulated Exposed Concrete Wall Exterior (-10 C ) Interior (21 C ) 5.0 C 3.7 C 6.0 C Window Wall Temperature Scale Exterior-Insulated Wall -10 C 0 C 21 C rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 4

Condensation and Mould Potential Impact of Exposed Slab Edges & Balconies During the cold winter months, cold interior surface temperatures are not only uncomfortable to occupants but can lead to surface condensation and potentially organic growth. The adjacent graphs provide correlations between interior temperature and relative humidity and the dew point temperature ( c o n d e n s a t i o n ) a n d m o u l d temperature. These temperatures correspond with 100% and 80% relative humidity respectively. If the temperature of the coldest point on the interior surface of the enclosure assembly is less than the temperature determined using the graphs, there is a risk of condensation and/or organic growth. Mould Temperature [ C] Mould Temperature from Interior Conditions 20 18 16 Exterior-Insulated 14 12 10 Interior-Insulated 8 6 Window Wall 4 2 0 30% 40% 50% 60% Relative Humidity of Interior [%] 22 C 20 C 18 C Dew Point Temperature [ C] Dew Point Temperature from Interior Conditions 20 18 16 Exterior Insulated 14 12 10 Interior Insulated 8 6 Window Wall 4 2 0 30% 40% 50% 60% Relative Humidity of Interior [%] The coldest temperatures as identified in the isothermal image on the preceding page are overlaid on these graphs. For reference, North American climates and typical occupant loads and ventilation rates create typical winter month interior relative humidity levels of 40% to 50% in Climate Zones 1 to 4 and <30% to 40% in Climate Zones 5 to 8. Temperatures on the interior surface of various assemblies and calculated temperature indices are provided in a table in the appendix of this report. 22 C 20 C 18 C rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 5

Thermal Comfort Impact of Balcony Slab Edge Thermal Breaks The thermal comfort impact of balcony slab edge thermal breaks is assessed by thermal modeling of interior floor and ceiling surface temperatures for each slab edge design scenario with and without a thermal break installed. Balcony slab edge thermal breaks provide an opportunity to increase interior surface temperatures and thus improve thermal comfort. Floor Temperature Isokorb Thermal Break Temperature Scale -10 C 0 C 21 C Ceiling Temperature 3.8 C 9.0 C Window Wall Exterior Interior Exterior Interior 3.7 C Isokorb R-3.4 Thermal Break 5.4 C 8.2 C 15.6 C Interior-Insulated Exterior Interior 8.2 C Exterior Isokorb R-3.4 Thermal Break Interior 15.6 C Exterior-Insulated Exterior Interior Exterior Interior Isokorb R-3.4 Thermal Break 18.6 C 18.6 C rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 6

Condensation and Mould Potential Impact of Balcony Slab Edge Thermal Breaks During the winter months, cold interior surface temperatures are not only uncomfortable to occupants but can lead to surface condensation and potentially organic growth. The adjacent graphs provide correlations between interior temperature and relative humidity and the dew point temperature ( c o n d e n s a t i o n ) a n d m o u l d temperature. These temperatures correspond with 100% and 80% relative humidity respectively. If the temperature of the coldest point on the interior surface of the enclosure assembly is less than the temperature determined using the graphs, there is a risk of condensation and/or organic growth. Mould Temperature [ C] 20 18 16 14 12 10 8 6 4 2 Mould Temperature from Interior Conditions Exterior-Insulated with Isokorb Interior-Insulated with Isokorb 0 30% 40% 50% 60% Relative Humidity of Interior [%] 22 C 20 C 18 C Window Wall with Isokorb Dew Point Temperature [ C] 20 18 16 14 12 10 8 6 4 2 Dew Point Temperature from Interior Conditions Exterior-Insulated with Isokorb Interior-Insulated with Isokorb 0 30% 40% 50% 60% Relative Humidity of Interior [%] Window Wall with Isokorb The coldest temperatures as identified in the isothermal image on the preceding page are overlaid on these graphs. For reference, North American climates and typical occupant loads create typical wintertime interior relative humidity levels of 40% to 50% in Climate Zones 1 to 4 and <30% to 40% in Climate Zones 5 to 8. Temperatures on the interior surface of various assemblies and calculated temperature indices are provided in a table in the appendix of this report. 22 C 20 C 18 C rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 7

Conclusions: Thermal Comfort and Condensation Control Thermal bridging in building enclosure systems often significantly reduces the effective R-value of wall assemblies and affects indoor thermal comfort. As industry moves toward higher R-value assemblies to meet more stringent building codes, energy standards, and occupant expectations in terms of thermal comfort and condensation control, the reduction of this thermal bridging will be necessary. In many high-rise buildings, exposed concrete slab edges, balconies, and eyebrows are one of the most significant thermal bridging elements and are a large source of thermal comfort complaints and condensation. The incorporation of cast-in-place concrete slab thermal break systems can significantly improve building enclosure thermal performance. The interior surface temperatures during winter conditions are increased, which reduces the potential for condensation and organic growth and improves thermal comfort for building occupants. Both slab and wall surface temperatures are positively affected. Overall, balcony slab edge thermal break systems provide architectural freedom to designers while maintaining the thermal performance characteristics of the building to reduce building energy consumption, improve thermal comfort, and meet increasingly stringent building code requirements. While these systems are currently uncommon in typical North American construction, as the industry develops, the incorporation of these systems into building design will likely become increasingly commonplace. Exterior Exterior Interior Temperature plot showing the impact of a cast-in-place concrete balcony slab edge thermal break (below) vs. a typical uninsulated condition (above). Thermal Break Temperature Scale 18.6 C Interior 18.6 C -10 C 0 C 21 C rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 8

Appendix: Thermal Modeling Inputs & Material Data rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 9

Thermal Modeling: Determination of R-Values, U-values, and Linear Transmittance (ψ) The effective R-values for several typical wall assemblies with varying insulation levels were calculated using the three-dimensional finite element thermal modeling software, Heat3. This program has been validated to ISO 10211 standards and is widely used by researchers and consultants to perform advanced thermal simulations to calculate 3D effective R-values of building enclosure assemblies and details. RDH has also performed in-house confirmation of the software results with published guarded hot-box laboratory and ASHRAE 90.1 thermal data. To calculate R-values, a variety of different inputs were used within the Heat3 software. The models were created using the material properties provided on the following page and the boundary conditions as defined in the table below and illustrated in the image to the right. The exterior temperature was changed from the standard -17.8 C to -10 C to be more indicative of typical exterior conditions for the calculation of surface temperatures. Heat3 performs a finite difference calculation to determine the heat flow through the assembly, which is then divided by the temperature difference to determine U-value. The inverse of the U-value is the R-value. Boundary Conditions R-Value Models Linear transmittance was calculated by first modeling the wall without a slab edge or balcony and then modelling it with the slab edge or balcony detail to determine their respective U-values. Then, the formula below was used to calculated linear transmittance (ψ). Ψ = ( U Wall WithSlabEd ge U Wall NoSlabEdge ) L slab A wall Boundary Conditions Surface Temperature Models Boundary Condition Temperature ( C) Surface Film Coefficient (W/m² K) Exterior - R-Values -17.8 23.0 Exterior - For Surface Temperatures -10.0 23.0 Interior - R-Values 21.0 7.7 Interior - For Surface temperatures - Corner of Floor to Ceiling 21.0 4.0 Interior - For Surface Temperatures - Floor and Ceiling 21.0 6.0 Interior - For Surface Temperatures - Wall 21.0 7.7 rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 10

Material Properties for Thermal Modeling The following material properties were used within the Heat3 thermal models used to calculate Effective R-values and temperatures to assess thermal comfort. These properties are based on published material data from numerous industry sources including ASHRAE, NRC, and product manufacturers. Material Description Thermal Conductivity, k (W/m K) Mineral Fiber or Fiberglass Insulation R-3.0/inch Batts 0.048 R-3.4/inch Batts 0.042 R-3.6/inch Batts 0.040 R-3.8/inch Batts 0.038 R-4.2/inch Cavity Insulation 0.034 Extruded Polystyrene R-5/inch Board 0.029 Expanded Polystyrene R-4/inch Standard Board 0.030 R-4.6/inch Graphite-Enhanced 0.031 Closed-Cell Spray Foam R-6/inch 0.024 Concrete (Temperature Steel Reinforced) 2.000 Concrete (Light Beam Reinforced) 3.000 Concrete (Heavy Beam Reinforced) 4.700 Steel Galvanized Sheet (studs/girts) 62.000 Stainless (ANSI 304) 14.300 Rebar 50.000 Gypsum Sheathing/Drywall 0.160 Ventilated Airspace 0.450 Wood Framing 0.140 Plywood 0.110 Stucco (Cement-Lime) 0.720 Brick (North American Clay Brick) 0.450 Balcony/Slab Edge Thermal Break Schoeck Isokorb, Range of values for standard products. Actual project values will depend on structural requirements for balcony support. R-2.5 (80 mm, 3.25 ) 0.181 R-3.4 (80 mm, 3.25 ) 0.134 R-3.4 (120 mm, 5 ) 0.200 R-4.5 (120 mm, 5 ) 0.151 R-5.0 (120 mm, 5 ) 0.135 R-5.7 (120 mm, 5 ) 0.120 rdhbe.com Report #2 - Thermal Comfort and Condensation Control Page 11