Wall bracing panel requirements

Similar documents
GARAGES/ONE-STORY City of Grand Rapids Building Safety Division

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

R Code and Commentary for 2012 NC Residential Code final 03/06/13

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International

A Simple Solution for Meeting

MBOIA IRC Wall Bracing. Mark Halverson. Maine Building Officials and Inspectors Association. First Last

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.

POST FRAME BUILDING STANDARDS

Administrative Changes

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

RESIDENTIAL DETACHED STORAGE STRUCTURES (GARAGE)

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

City of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209)

2009 IRC Wall Bracing

TOWN OF SOUTH KINGSTOWN REQUIREMENTS FOR BUILDING PERMITS RESIDENTIAL SINGLE FAMILY

Evaluation of Full-Scale House Testing Under Lateral Loading

130 MPH EXPOSURE B WFCM GUIDE. Guide to Wood Frame Construction in High Wind Areas for One- and Two-Family Dwellings 2015 EDITION

2008 Special Design Provisions for Wind and Seismic

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

Minimum Requirements For One & Two Family Structures FBC 6 th Edition (2017)

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

Plan Check No. Checked by: An Appointment Is Required for Verification

TECHNICAL NOTE On Cold-Formed Steel Construction

Building Guide. Colorado Chapter of the International Code Council

PS 3000 Installation Manual Step-By-Step Procedures C.9. DOOR AND WINDOW OPENINGS C.9.1 PREPARE IN ADVANCE. C.9.2 VBUCK CONSTRUCTION.

TYPICAL BEARING WALL FRAMING

EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire

APPENDIX R STRAWBALE CONSTRUCTION

Detached Residential Garage or Accessory Building ~ Includes Garage Conversion to Habitable Space ~

2003 International Residential Building Code

RB Appendix R (New)

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing

Formulating a Korea Industrial Standard for light-frame wood construction

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

COFS Mission. AISI Standards Hierarchy. North American Standards for Cold-Formed Steel Framing. Member versus System Design. Specification 10/21/2016

Garage Construction. Permit Guide. Development Center. General Information. Zoning Ordinance Requirements. Building Code Requirements

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

SECTION PLATE CONNECTED WOOD TRUSSES

Prescriptive Design for Pole Barns Using the Larimer County Prescriptive Handout

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

Residential Detached Garage Handout

System Report. Design for Combined Shear and Uplift from Wind. and equipment, and Section Analysis

PHOTO 1: View from Inside the Structure. Note the Rotation of the WSP, Failure at the Lower Leading Edge and Deformation of the Top Plate

Supplemental Concrete Tilt Up Retrofit Plan Check Correction Sheet (2014 LABC)

FIGURE R502.2 FLOOR CONSTRUCTION

The following are details of the code requirements of the 2015 International Residential Code for single-story decks.

A. Types of lightgauge metal framing units include the following: 1. C-shaped structural steel studs Uniform Building Code.

See the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals.

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements

1 AND 2 FAMILY DWELLING REQUIREMENTS

Georgia State Amendments to the International Residential Code for One- and Two- Family Dwellings

BUILDING CODES Presented by CORUM ENGINEERING

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

CALCULATING WIND LOADS ON LOW-RISE STRUCTURES PER 2015 WFCM ENGINEERING PROVISIONS (STD342-1)

MAT109: Introduction to the Wood Frame Construction Manual

Detached Garages and Building Permits. 1 and 2 Family Dwellings

2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E.

SHEAR BRACE. Featuring ilevel Shear Braces for Engineered and Prescriptive Applications iLevel8 (

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708

Wood Frame Construction Manual for One- and Two-Family Dwellings 2015 EDITION WORKBOOK

ILLUSTRATED GUIDE. For Seismic Design of Houses. Lateral Bracing Requirements Part 9 BC Building Code 2012

Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

Exterior Stucco and Siding Installation

REPORT HOLDER: LOUISIANA-PACIFIC CORPORATION 414 UNION STREET, SUITE 2000 NASHVILLE, TENNESSEE EVALUATION SUBJECT:

TER No Cultured Stone & ProStone Applications Over Continuous Insulation

One and Two Family Additions

REPORT HOLDER: GEORGIA PACIFIC GYPSUM LLC 2861 MILLER ROAD DECATUR, GEORGIA EVALUATION SUBJECT: DENSELEMENT BARRIER SYSTEM

Gold Bond BRAND Gypsum Sheathing

STATUTORY AUTHORITY: NMSA 1978 Section and [ NMAC - Rp, , NMAC, ]

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC.

ADVANCED FRAMING LUMBER

INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO

CHAPTER 5 FLOORS SECTION R501

SECTION GYPSUM BOARD ASSEMBLIES

Table of Contents. Page Title

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

Specifications. Materials and Fabrication. Physical Properties. Environmental Impact. Sizes. Installation - General Requirements.

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: PROWALL BUILDING PRODUCTS, INC.

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

DuPont RainVent Batten Installation Guidelines

BEARING METAL STUD FRAMING

Custom 24 x 26 Garage Plan Roy Hartmann Plan #g218 By SDS-CAD Specialized Design Systems CLIENT

LP OSB Sheathing & Structural 1 Sheathing

INSTALLATION MANUAL. ZIP System R12 Sheathing. Contents. 07 ZIP System R12 Sheathing Window Installation 08 ZIP System R12 Sheathing Siding Guidelines

SEISMIC STRENGTHENING PROVISIONS FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS

The Carport - Bryan, Texas

Transcription:

Wall bracing panel requirements Building Inspections Exterior and interior walls must be braced in accordance with Minnesota State Building Code section R602 to resist wind loads and racking. Locations, spacing and amount of braced wall panels Braced wall panels must be located in a braced wall line in accordance with Section 602.10 and at least 25 feet on center. Braced wall panels may also be offset from the ends of the braced wall lines such that they begin no more than 12'-6" from the ends. However, if both ends are offset by more than 12', a collector system must be designed. The amount of bracing is based on a percentage of total wall length, see figure below. Amount required Table R602.10.1 Condition Bracing method Amount of Bracing One story Top of two or three story 1, 2, 3, 4, 5, 6, 7, or 8 At least 25' o.c., not less than 16% of braced wall line First story of two story Second story of three story 1, 2, 3, 4, 5, 6, 7, or 8 At least 25' o.c., not less than 16% of braced wall line for Method 3 and 25% for Methods 2,4-8 First story of three story 2, 3, 4, 5, 6, 7, or 8 At least 25' o.c., not less than 25% of braced wall line for Method 3 and 35% for Methods 2,4 8

Can there be off sets in a braced wall line? Braced wall panels that are counted as part of a braced wall line must be inline, except that offsets out of plane of up to 4 feet shall be permitted provided the total out-to-out offset in an braced wall line is not more then 8 feet. Braced wall panel methods Method Material Minimum Thickness Panel length* 1 2 let-in bracing attached to top and bottom plates diagonal wood boards @ 24" o.c. 1x4 per angle: 45 to 60 5/8" 3 Structural sheathing (most common) 5/16" for studs @ 16" o.c 3/8" for studs @ 24" o.c 4 structural fiberboard 1/2" or 25/32" for studs @ 16" o.c only 5 gypsum board (typical for interior walls) 1/2" fastened 7 o.c applied to both sides 96" applied to one side 6 particle board 7 Portland cement plaster 3/8" or 1/2" for studs @ 16" o.c only 3 coats with corrosion resistant lath 8 hardboard 7/16" Method 3 allowable reductions. (Most common) When continuously sheathing the entire structure using Method 3 braced wall panels, openings for windows or doors may be closer than 48 inches to the corners based on the wall height and

the height of the opening when in accordance with Table R602.10.5 but the percentages that are shown in table R602.10.1 must still be met. The maximum height of the wall is still 10 feet. However, this height may be increased to 12 feet with prior approval from the Building Official. Table R602.10.5 Length requirements for braced all panels in a continuously sheathed wall Minimum length of braced wall panel 8' wall 9' wall 10' wall Max. opening next to a braced wall panel (% of wall height) 54" 60" 100% 32" 36" 40" 85% 24" 27" 30" 65%* *The dimensions for a 65% height opening may be used for 100% height when the structure is only one story, i.e., one-story garages. Narrow walls adjacent to garage doors or other large openings If the braced wall panel lengths can t be achieved even with the allowed reductions permitted by Table R602.10.5, other methods can be allowed. The MN building code allows an Alternate Braced Wall Panel construction in accordance with R602.10.6. which consists of: One Story Buildings 1. Each panel must have a length of at least 16 inches and a height of not more than 10 feet.

2. Each panel shall be sheathed on one face with a single layer of 3/8 inch minimum thickness wood structural panel fastened with 8d common or galvanized box nails 3 inch O.C. in all framing. The sheathing shall extend up and over the header and shall be nailed to the header in a 3 inch grid pattern. 3. A minimum 2-2x12 header shall extend between the inside faces of the first full length outer studs of each panel. The clear span of the header between the inner studs of each panel shall be not less than 6 feet and not more than 18 feet in length. 4. A strap with at least 1000 # uplift capacity must attach the inner studs of the panel to the header. This strap must be on the opposite side of the header from the sheathing. 5. A single 5/8 inch anchor bolt and two hold-downs with a minimum uplift capacity of 4200 pounds are required to anchor the panel directly to the foundation. All hold-down devices must be the embedded strap type, installed per the manufacturer's installation requirements. The panels shall be supported directly on a foundation that is continuous across the entire length of the braced wall line. 6. When the footing depth is required to be 12 inches or greater, a 12" x 12" continuous foundation with a #4 rebar top and bottom can be used at door openings in the braced wall line. This reinforcement shall be lapped not less than 15 inches. First Story of Two Story Buildings: In the first story of a two story building, the requirements noted above shall be followed, except each wall panel shall be a minimum of 24 inches in length. Figure R602.10.6.2

Other approved methods If you wish to deviate from the prescriptive requirements of International Residential Code Section R602.10, then you must have the lateral load resisting system of your building designed by a registered design professional licensed in the State of Minnesota To determine wind load, the calculations must follow the requirements of Section 1609 of the International Building Code (IBC). The basic wind speed for The city is 90 mph. Most residential construction in the city qualifies as Exposure B with an Importance Factor (Iw) of 1.00. Please note: wind load must be applied to both windward and leeward sides simultaneously. Design Method and Calculations Section 2305 of the IBC, "General Design Requirements for Lateral-Force-ResistingSystems," and accepted engineering practice shall be employed in the design professional's calculations. Calculations, at a minimum, must: Show a detailed analysis of the wind load determination. Show a detailed design of the building diaphragms (Section 2305.2) and shear walls (Section 2305.3). Specify the sheathing thickness, nail sizes and nailing pattern for diaphragms and shear walls. Ensure there is an adequate load path to the foundation. Show a detailed analysis of all connections along the lateral load path. Show an analysis of the existing lateral load resisting system with the new applied loads when utilizing an existing structure to resist lateral loads of an addition. Ensure post-to-beam connections are capable of resisting shear and rotation. Bear the original signature and seal of the registered design professional. Calculations which do not meet the above requirements will not be approved by Building Plan Review during the permit application process. Construction Documents When submitting plans for a building that utilized an engineered design, the related calculations must be attached to the plans. The drawings must also include comprehensive details outlining the construction requirement of the diaphragms and shear walls. These detail sheets must also bear the original signature and seal of the responsible design professional. (This information is only to be used as a general guideline for building and does not contain all requirements.)