SUSTAINABLE CONCRETE COLUMNS WITH INNOVATIVE MULTI-SPIRAL SHEAR REINFORCEMENT ABSTRACT

Similar documents
Residual Post-Fire Behaviour of Pre-Damaged Confined Concrete

BEHAVIOUR OF SPIRAL REINFORCED LIGHTWEIGHT AGGREGATE CONCRETE COLUMNS

Seismic Retrofit Of RC Columns With Inadequate Lap-Splice Length By External Post-Tensioned High-Strength Strips

EXPERIMENTAL STUDY ON CONFINED CONCRETE OF THIN COLUMN SECTIONS (070S)

Tests of Concrete Bridge Columns with Interlocking Spiral Reinforcement

Pile to Slab Bridge Connections

This document is downloaded from DR-NTU, Nanyang Technological University Library, Singapore.

> 0. 1 f, they are treated as beam-columns.

SHAKE TABLE TESTING OF BRIDGE REINFORCED CONCRETE COLUMNS UNDER COMBINED ACTIONS

Comparison of Prefabricated Cage System with Existing Reinforcement Methods in Concrete Columns

Experimental study on seismic behavior of composite concrete and

SEISMIC RETROFIT OF A TYPICAL REINFORCED CONCRETE BUILDING THROUGH FRP JACKETING OF EXTENDED RECTANGULAR COLUMNS

USE OF CFRP ANCHORS TO STRENGTHEN LAP SPLICES OF RECTANGULAR RC COLUMNS

AXIAL TESTING OF CONCRETE COLUMNS CONFINED WITH CARBON FRP: EFFECT OF FIBER ORIENTATION. Abstract

COLUMNS 1- Definition: The Egyptian code defines columns as : 2- Types of concrete columns

Seismic Behavior of Concrete Columns Confined with Steel and Fiber-Reinforced Polymers

Upgrading the shear strength of non-ductile reinforced concrete frame connections using FRP overlay systems

Repair of Earthquake-Damaged RC Columns with FRP Wraps

EXPERIMENTAL STUDY ON THE SEISMIC PERFORMANCE OF EXTERNALLY CONFINED REINFORCED CONCRETE COLUMNS

Concrete-filled fiber reinforced polymer tube-footing interaction in bending

RETROFITTING OF COLUMNS WITH RC JACKETTING AN EXPERIMENTAL BEHAVIOR

Behaviour of Corner Beam Column Joint with Rectangular Spiral Reinforcement and Longitudinal FRP Bars

Special Reinforced Concrete Structural Walls

SECTION H COLUMNS SUBJECTED TO FLEXURE AND AXIAL

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING

Slenderness ratio effect on the behavior of steel and carbon-frp reinforced concrete-filled FRP tubes

Softening Coefficients for Prestressed Steel Fiber Reinforced Concrete. Prestressed Steel Fiber Reinforced Concrete in Tension.

INHERENT DUCTILITY OF REINFORCED CONCRETE SHEAR WALLS WITH NON-SEISMIC DETAILING

SHEAR STRENGTH OF BEAMS REINFORCED WITH SYNTHETIC MACRO-FIBERS AND STIRRUPS

GFRP retrofitted RC frames with columns subjected to high axial stresses

IMPROVEMENT OF THE DEFORMATION CAPACITY BY THE USE OF FIBERS

Seismic Behaviour of RC Shear Walls

CYCLIC BEHAVIOR OF SLENDER R/C COLUMNS WITH INSUFFICIENT LAP SPLICE LENGTH

GFRP HOLLOW-CORE REBARS FOR CONCRETE BEAMS

CYCLIC LOADING TEST OF REINFORCED CONCRETE COLUMN WITH HOLLOW SECTION AND HIGH LONGITUDIAL STEEL RATIO UNDER HIGH AXIAL LOADING

SEISMIC RETROFITTING OF REINFORCED CONCRETE COLUMNS USING CARBON FIBER REINFORCED POLYMER (CFRP)

Development of a FRP-Wrapped Spiral Corrugated Tube for Seismic Performance of Reinforced Concrete Columns

Effect of beam dimensions on structural performance of wide beam-column joints

SEISMIC PERFORMANCE OF FLAT-SLAB SHEAR REINFORCEMENT

Reinforced Concrete Column Design

Studies on ductility of RC beams in flexure and size effect

CRACKING BEHAVIOR AND CRACK WIDTH PREDICTIONS OF CONCRETE BEAMS PRESTRESSED WITH BONDED FRP TENDONS

Moment curvature analysis of concrete flexural members confined with CFRP grids

Behaviour of FRP wrapped circular reinforced concrete columns

PERFORMANCE OF LAP SPLICES IN CONCRETE MASONRY SHEAR WALLS UNDER IN-PLANE LOADING

EXPERIMENTAL STUDY ON REINFORCED CONCRETE COLUMN STRENGTHENED WITH FERROCEMENT JACKET

Experimental Study on Wall-Frame Connection of Confined Masonry Wall

EVALUATION OF THE SEISMIC PERFORMANCE OF BRIDGE REINFORCED CONCRETE COLUMNS UNDER COMBINED ACTIONS USING SHAKE TABLE

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure

High Performance and Efficiency of Joints in Precast Members

FINITE ELEMENT MODELING OF NON-DUCTILE REINFORCED CONCRETE COLUMNS

STABILITY ANALYSIS OF CONCRETE COLUMN - STEEL BEAM JOINT UNDER SEISMIC LOADING

Experimental Study on behavior of Interior RC Beam Column Joints Subjected to Cyclic Loading P.Rajaram 1 A.Murugesan 2 and G.S.

Response of columns and joints with spiral shear reinforcement

1. INTRODUCTION. Fig.1 Dimension of test specimen

In-plane testing of precast concrete wall panels with grouted sleeve

Fragility Curves for Seismically Retrofitted Concrete Bridges

Tests on Seismic Behavior of Pre-cast Shear Walls with Vertical Reinforcements Spliced by Two Different Grout Ways

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

Experimental Study on Shear Splitting Failure of Full-Scale Composite Concrete Encased Steel Beams

SEISMIC RETROFIT OF BEAM-COLUMN JOINTS WITH FRP SHEETS

DEVELOPMENT OF ACCELERATED BRIDGE CONSTRUCTION DETAIL FOR SEISMIC REGIONS. W. Phillip Yen 1 and Amjad Aref 2

Modelling of RC moment resisting frames with precast-prestressed flooring system

Pacific Earthquake Engineering Research Center

Reinforced concrete beam-column joints with lap splices under cyclic loading

Effect of Reinforcement Grade and Ratio on Seismic Performance of Reinforced Concrete Columns

Compression Behavior, Strength, and Ductility of Confined Concrete after Inelastic Tensile Cyclic Loading

A Study on Hybrid FRP Wrapped Axially Loaded RC Capsule Column

INELASTIC WEB CRUSHING CAPACITY OF HIGH-STRENGTH-CONCRETE STRUCTURAL WALLS ABSTRACT

Analytical Models for Reinforced Concrete Columns Retrofitted with Fiber-Reinforced Polymer Composites

Structural Behaviors of Deep RC Beams under Combined Axial and Bending Force

Interaction between ductile RC perimeter frames and floor slabs containing precast units

RESILIENT INFRASTRUCTURE June 1 4, 2016

CONFINEMENT EFFECT OF FRP AND TRANSVERSE STEEL ON RETROFITTING SQUARE CONCRETE COLUMNS

SHEAR STRENGTH CAPACITY OF PRESTRESSED CONCRETE BEAM- COLUMN JOINT FOCUSING ON TENDON ANCHORAGE LOCATION

Seismic Detailing of RC Structures (IS: )

The cracking behaviour of reinforced concrete beams under static and dynamic loading

CYCLIC TESTING OF BOLTED CONTINUOUS I-BEAM-TO-HOLLOW SECTION COLUMN CONNECTIONS

USE OF 500 GRADE STEEL IN THE DESIGN OF REINFORCED CONCRETE SLAB. Prof. M. Shafiul Bari, Ph.D Department of Civil Engg., BUET

USE OF HIGH-STRENGTH REINFORCEMENT FOR EARTHQUAKE- RESISTANT CONCRETE STRUCTURES

SEISMIC PERFORMANCE AND RETROFIT OF BRIDGE FOOTINGS. David I. McLean 1

AN ANALYSIS OF THE BEHAVIOR OF HYBRID STEEL BEAM RC COLUMN CONNECTION

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

Study on Metering Scheme of Seismic Experiment for Shear Wall Built with Precast Hollow Slab

FRP-Confinement of Hollow Concrete Cylinders and Prisms

SEISMIC RETROFIT OF NON-DUCTILE RECTANGULAR REINFORCED CONCRETE COLUMNS BY CFRP JACKETING

DETERMINATION OF MOMENT RESISTING RC FRAMES OF RESPONSE REDUCTION FACTORS

CFT Column-to-Cap Beam Connections for. Accelerated Bridge Construction in Seismic Regions. Lisa Marie Berg. Master of Science in Civil Engineering

USE OF HEADED BARS AS SHEAR REINFORCEMENT

Behavior and Strength of Slab-Edge Beam-Column Connections under Shear Force and Moment

ctbuh.org/papers A Study of Flat Plate Slab Column Connections with Shear Plate in Tall Concrete Building using Experimental and Numerical Analysis

AXIAL LOAD FAILURE OF SHEAR CRITICAL COLUMNS SUBJECTED TO HIGH LEVELS OF AXIAL LOAD

STRUCTURAL CHARACTERISTICS OF CONCRETE-FILLED GLASS FIBER REINFORCED COMPOSITE PILES. Abstract

5.4 Analysis for Torsion

EXPERIMENTAL STUDY ON FLEXURAL BEHAVIOR OF RC BEAMS STRENGTHENED WITH SMPM

PERFORMANCE OF RC BRIDGE COLUMNS SUBJECTED TO LATERAL LOADING

Analysis, Design, and Construction of SMA-Reinforced FRP- Confined Concrete Columns

STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES

406 A.R. Khaloo and A. Esmaili This method does not enhance column moment capacity and stiness signicantly. Therefore, additional earthquake forces in

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress

Transcription:

SUSTAINABLE CONCRETE COLUMNS WITH INNOVATIVE MULTI-SPIRAL SHEAR REINFORCEMENT Samuel Y. L. Yin a, Raymond Wang b, and Tony C. Liu c ABSTRACT Lateral reinforcement used to provide shear strength, concrete confinement, and support to longitudinal steel reinforcement. The efficiency of the confinement generally depends on the shape and spacing of the confinement steel. Spirals are usually used in circular columns, while rectilinear stirrups, with or without cross ties, are generally used in rectangular columns. It has been recognized that rectilinear stirrups are less effective for concrete confinement because of the uneven distribution of the lateral confining stress. This paper presents the development of an innovative multi-spiral confinement design for rectangular concrete columns. The development involved testing and evaluation of a large number of full-scale reinforced concrete columns in axial compression and lateral cyclic loadings. Test results concluded that rectangular columns with interlocking multi-spiral design exhibit higher compressive strength and ductility as compared to columns with conventional stirrup design. Based on the laboratory research and practical design and construction experience, a proposed design approach for multi-spiral confinement design is presented. Case studies of sustainable design of concrete columns with multi-spiral shear reinforcement are also presented. Lower consumption of steel required for multi-spiral confinement design results in energy saving and carbon reduction and; therefore, the multi-spiral confinement design offers a sustainability advantage. Keywords: Concrete column; concrete confinement; ductility; shear strength; spiral reinforcement; stirrups; sustainability a Adjunct Professor, Department of Civil Engineering, National Taiwan University and CEO and Chief R&D Officer, Ruentex Group, Taipei, Taiwan, Republic of China b Senior Manager, Research Group, Ruentex Engineering and Construction Co., Ltd., Taipei, Taiwan, Republic of China c Visiting Professor, Department of Civil Engineering, National Taiwan University, Taipei, Taiwan, Republic of China 1

INTRODUCTION Lateral reinforcement in columns is used to provide shear strength, concrete confinement, and support to longitudinal bars. As a result of confinement, concrete columns display significant improvement in ductility and, in some cases, additional strength. The efficiency of the confinement generally depends on the shape and spacing of the confinement steel 1-3. Spirals are usually used in circular columns, while rectilinear stirrups, with or without cross ties, are generally used in rectangular columns. It has been recognized that rectilinear stirrups are less effective for concrete confinement compared with circular spirals because of the uneven distribution of the lateral confining stress. Furthermore, construction of stirrups is more laborious that leads to highly expensive operation. Recently, an innovative interlocking multi-spiral confinement design for rectangular concrete columns has been developed by Yin et al 4, typical examples of which are shown in Figures 1(g) and 1(h). This development involved testing and evaluation of a large number of full-scale reinforced concrete columns in axial compression and lateral cyclic loadings. Test results clearly verified that columns with interlocking multi-spiral confinement design exhibit higher compressive strength and ductility as compared to columns with conventional stirrup design. EXPERIMENTAL PROGRAM In Phase I of the experimental program, full-scale reinforced concrete columns were tested under axial compressive loading. Ten specimens with different steel configurations, as shown in Figure 1, were designed to study confinement in square columns. These included typical rectilinear lateral steel stirrups arrangements as well as different types of multi-spirals and combinations of spiral and ties. All the specimens in this phase were 600 mm square and 1200 mm high. The nominal compressive strength of concrete at 28 days was 35 MPa. The tensile strength of both transverse and longitudinal reinforcement was 280 MPa. Figure 2 shows the test setup for the axial compression tests. A 6,000 metric ton hydraulic jack was used to apply the axial compressive force at a constant strain rate of 25 /sec. 2

(a) Conventional (b) One-bar (c) Wire Mesh (d) 3 Welded Hoops (e) Twin-hexagon Confinement (f) Twin-ellipse (g) 4 Spirals (h) 5 Spirals (i) Spiral + Cross Ties (j) Spiral + 4 Tie Ears Fig. 1 Confinement configuration details of the Phase I tests strong frame Experimental Setup 6000 ton Hydraulic jack cross-section 60 cm 60 cm Loading plate Test specimen Bearing plate 2 cm LVDT adjustable rod 120cm Fig. 2 Experimental setup for axial compression tests Table 1 lists the results of the Phase I tests. The unconfined compressive strengths (f c ) of the concrete cylinders for the three groups of specimens were 35.6, 43.0, and 37.6 MPa, respectively. The peak strengths (f cc ) of the test specimens with the different confinement details were all greater than their corresponding unconfined concrete compressive strengths. The f cc was defined as P c /A g, where P c is the load carried by concrete (i.e., total load 3

load carried by steel) and A g is the gross area of concrete section. The ratio of f cc to f c varied from 1.04 to 1.68. The cumulative strain energy E 80 of the test specimens given in Table 1 is defined as the area below the stress-strain curve up to the strain value corresponding to 0.8 f cc. The cumulative strain energies of the test specimens with different confinement details varied from 0.05 N-mm/mm 3 to 1.21 N-mm/mm 3. The energy ratios (E 80 /E 80(a) ) of the tested specimens with respect to the benchmark (specimen a) ranged from 0.28 to 6.34. Table 1 Details of Specimens in Phase I No. Confinement (See Fig.2) Strength(MPa) Strain Energy f' c f' cc E f MPa MPa cc /f 80 c N-mm/mm 3 E 80 /E 80(a) 1 (a) 35.6 54.2 1.52 0.19 1.00 2 (b) 35.6 42.1 1.18 0.14 0.74 3 (c) 35.6 37.0 1.04 0.05 0.28 4 (d) 35.6 41.4 1.17 0.11 0.57 5 (e) 43.0 64.9 1.51 0.66 3.44 6 (f) 43.0 53.5 1.25 0.40 2.07 7 (g) 43.0 59.2 1.38 1.04 5.44 8 (h) 37.6 57.7 1.53 1.21 6.34 9 (i) 37.6 63.2 1.68 0.80 4.15 10 (j) 37.6 50.6 1.34 0.55 2.86 f cc 0.8f cc E 80 The stress-strain responses of concrete columns under axial compressive loading are shown in Figures 3a, 3b, and 3c. The test results showed that the multi-spiral designs provide significant contributions to concrete confinement that enhances strength and ductility of the columns. The columns with four or five interlocking spirals (Specimen g and h) have better ductility than the other columns. 4

Axial Stress (MPa) 80 60 40 20 (a) (b) (c) (d) a b c d 0 0 0.01 0.02 0.03 0.04 Axial Strain (a) 80 Axial Stress (MPa) 60 40 20 (a) (e) (f) a e f 0 0 0.01 0.02 0.03 0.04 Axial Strain (b) 5

Axial Stress (MPa) 80 60 40 20 a g h i j (a) (g) (h) (i) (j) 0 0 0.01 0.02 0.03 0.04 Axial Strain (c) Fig. 3 Stress-strain response of concrete columns with different confinement arrangements Test results of Phase I revealed that most of the test specimens with spiral confinements exhibited higher compressive strength and energy capacity than the specimens with rectilinear confinement. Among them, the multi-spiral designs (Specimens g and h in Fig. 1) and a design with a spiral and cross ties (Specimen i in Fig. 1) exhibited better confinement effectiveness and therefore they were selected for further investigations. In Phase II of the test program, the specimens were subjected to axial compressive loads. Table 2 lists the design details of the 18 specimens tested under axial compression in Phase II. All the specimens were also 600 mm square in cross section and 1200 mm high. Four types of confinement designs including the traditional stirrup design (T), the combination of a spiral and cross ties (ST), the combination of four spirals (4S), and the combination of five spirals (5S) were tested. As shown in Table 2, the compressive strength ( ' f c ) of concrete was 34.4 MPa in all columns except three in which it was 68.7 MPa. The yield strengths ( f yt ) of the confinement steel was 274.7 MPa in the columns made with 34.4 MPa concrete and 412.0 MPa in the three columns that used higher strength concrete (68.7 MPa). Sixteen No. 8 (area = 506.7 mm 2 ) longitudinal bars with yield strength of 412 MPa were used for all specimens. The confinement reinforcement sizes varied from No. 3 (area = 71.3 mm 2 ) to No. 5 (area = 198.6 mm 2 ). The spacing of the confinement reinforcement 6

varied from 45 mm to 100 mm. Figure 4 shows the typical failure modes of the specimens with multi-spiral design and traditional stirrup design. For traditional stirrup design, lateral dilation of concrete resulted in the failure of cross ties at the 90-degree bends of the stirrups (see Figure 4b). This is similar to failure reported by earlier investigators 5. For specimens with multi-spiral confinement design, the fracture of the spiral reinforcement followed by buckling of the longitudinal bars as can be seen in Figure 4a. The fracture of the spiral confinement was caused by the large lateral dilation of the concrete and the bearing of the buckled reinforcement against the spirals. (a) (b) Fig. 4 Typical Failure Modes of Compression Test Specimens 7

Table 2 Details of Specimens in Phase II Concrete Confinement Reinforcement Specimen f c (MPa) Pitch (mm) Bar size f yt (Mpa) * (%) * (req) (%) shape T1 34.4 85 #4 274.7 2.2 2.26 T2 68.7 65 #4 412.0 2.9 3.01 4S1 34.4 75 #4 274.7 2.05 1.63 4S2 68.7 50 #4 412.0 3.07 2.17 4S3 34.4 50 #5 274.7 4.74 1.63 4S4 34.4 65 #5 274.7 3.65 1.63 4S5 34.4 100 #4 274.7 1.54 1.63 5S1 34.4 50 #4 274.7 2.64 1.64 5S2 68.7 75 #4 274.7 1.76 2.19 5S3 34.4 70 #5 274.7 70 #4 274.7 2.24 1.64 5S4 34.4 60 #4 274.7 2.2 1.64 5S5 34.4 50 #3 274.7 1.26 1.64 ST1 34.4 ST2 68.7 ST3 34.4 ST4 34.4 ST5 34.4 ST6 34.4 spiral 60 #4 274.7 ties 60 #3 274.7 spiral 95 #5 412.0 ties 95 #5 412.0 spiral 75 #5 274.7 ties 75 #4 274.7 spiral 45 #5 274.7 ties 45 #3 274.7 spiral 55 #5 274.7 ties 55 #3 274.7 spiral 80 #5 274.7 ties 80 #3 274.7 1.55 / 2.09 / 2.06 / 2.75 / 2.25 / 1.55 / 4-360 mm 1-420 mm 4-210 mm 1-520 mm * is the volumetric ratio of the confinement reinforcement to the gross area of concrete section of the specimen. * (req) is the minimum volumetric ratio of the confinement reinforcement as required by ACI 318-08 in Sections 10.9.3 and 21.6.4.4 8

Figure 5(a) shows the monotonic compression stress-strain relationships for specimens with traditional stirrup design. Figures 5(b) to 5(d) show the stress-strain relationships for the other three confinement designs. A comparison of the behavior of different columns in these figures shows that the confined concrete response can be improved with closer spiral pitches and higher volumetric ratios of confinement steel. It can also be seen that a more brittle response of higher strength concrete can be compensated by higher strength lateral steel. The results demonstrated that the multi-spiral confinement designs perform much better than the traditional lateral reinforcement detail consisting of stirrups and cross ties. Stress (MPa) 80 60 40 20 T1 T2 Stress (MPa) 80 60 40 20 4S1 4S2 4S3 4S4 4S5 Stress (MPa) 80 60 40 20 0 0 0 0.01 0.02 0.03 5S1 5S2 5S3 5S4 5S5 strain Strain (a) 0 0.01 0.02 0.03 strain Strain (c) Stress (MPa) 0 80 60 40 20 0 0 0.01 0.02 0.03 strain Strain (b) 0 0.01 0.02 0.03 strain Strain (d) ST1 ST2 ST3 ST4 ST5 ST6 Fig. 5 Effect of amount of lateral reinforcement and spacing on concrete response In Phase III, the specimens were subjected to combined axial compression and lateral cyclic loads. Figure 6 shows the test setup of the combined axial compression and lateral cyclic loading tests. The confinement designs used for the three column specimens were: a traditional stirrup design as the benchmark (CT), and two multi-spiral designs denoted as S4 and S5. All the specimens 9

had a cross section of 600 mm square and were 2.5 m high. An axial force of 126 tons (~0.1f c A g ) was applied at the top of the specimens by a 200 ton jack that remained constant throughout the test. loading plates 100 ton actuator CT 60 mm C4S C5S 750 mm 2450 mm Fig. 6 Experimental setup of the lateral cyclic loading tests Table 3 lists the design details of the Phase III specimens. The confinement layout for Specimen CT was the same as that of specimen T1 in Table 2. Specimens C4S and C5S are columns with multi-spiral confinement designs and were the same as that of the specimens 4S1 and 5S4 in Table 2. Table 3 Details of specimens in phase III Confinement Reinforcement f c Longitudinal Specimen Size f (MPa) Bars Design y Spacing s (mm) (MPa) (mm) (%) CT 34.4 CT 13 274.7 85 2.2 f y =412 MPa C4S 34.4 4S 13 274.7 75 2.05 16-#8 C5S 34.4 5S 13 274.7 60 2.2 Figure 7 shows the lateral load vs. displacement hysteresis loops of the three specimens tested under lateral cyclic loading while subjected to constant axial load. Specimen C5S exhibited the highest strength and ductility capacity 10

among the three columns. The response of specimen C4S was close to that of C5S, whereas specimen CT exhibited the lowest strength and ductility capacity, as expected. Fig. 7 Force-displacement relations for the three test specimens PROPOSED DESIGN APPROACH Based on the experimental and analytical research, as well as practical design and construction experience, the proposed design approach for multi-spiral shear reinforcement for columns is as follows. The volumetric spiral reinforcement ratio, s, required for multi-spiral should be determined according to Equations (10-5) and (21-3) of ACI 318-08. ' A f c 1) Eq. (10-5) f g s 0.45( Ach f ' c y y s 0.12 Eq. (21-3) f 11

For columns with interlocking multi-spirals, the volumetric spiral reinforcement ratio provided for each spiral should be calculated independently. The volumetric spiral reinforcement ratio provided by each spiral should not be less than the calculation of the required s required by Eq. (10-5). For the s, the area A ch in Eq. (10-5) is measured to the outside edges of the spirals as defined in Section 2.1 of ACI 318-08 and A g is the gross area of concrete section. COST ADVANTAGES OF MULTI-SPIRAL DESIGN The multi-spiral design has been successfully used for 14 construction projects such as office and factory buildings, shopping malls, high-rise residential buildings, public stadium, and bridge piers in Taiwan. The cost advantage of the multi-spiral design is significant. First, the improvement of confinement efficiency can greatly reduce the total amount of lateral steel. More importantly, the multi-spiral detail can be produced automatically in the prefabrication plants. The time-consuming bending and labor required for conventional stirrups are greatly reduced, which can result in lower cost as well as shortened total construction time. Table 4 shows the cost evaluation of multi-spiral confinement design for an 11-story apartment project in Taiwan. It can be seen that the cost of the total confinement steel reduced by 41% when the multi-spiral confinement is used instead of the conventional stirrups. Considering the even higher labor cost in the developed countries, its economical advantages will be more pronounced. 12

Table 4 Cost evaluation of multi-spiral design Item Conventional stirrups StirrupWeight fy MPa Unit price NT$/kg Total stirrup price Ton MaterialBendingAssembleMillion % 420 717 14.6 0.00 3.36 12.9 100 Multi-spirals 420 407 14.6 1.76 2.24 7.6 59 SUSTAINABLE CONCRETE COLUMNS CASE STUDIES CASE I. SPORTS COMPLEX FOR THE 21 ST SUMMER DEAFLYMPICS The design of the sports complex for the 21 st Summer Deaflympics in Taipei, Taiwan started in December 2006 and the construction was completed in April 2009. This sports complex consists of three major structures: main stadium, sports center, and warm-up field (Fig. 8). The multi-spiral shear reinforcement design for columns in this sports complex results in energy saving and carbon reduction. a. Use of multi-spiral shear reinforcement design for columns. The use of multi-spiral shear reinforcement design instead of the conventional stirrups in rectangular columns reduces the amount of shear steel by 144 tons. It was estimated that manufacture of each ton of steel emits about 923 tons of CO 2. Therefore, reduction of 144 tons of steel results in 133 tons of CO 2 reduction. b. Replace 20% of portland cement with slag in concrete mixtures. The total portland cement and slag used for columns in this project were 294 tons and 68 tons, respectively. Since each ton of cement and slag contribute about 880 kg and 68 kg of CO 2, respectively, the slag replacement reduced 55 tons of CO 2 emissions in this project. Concrete containing slag not only meets the strength requirements but also enhances the durability and promotes structural longevity. 13

Figure 8 Sports Complex for the 21 st Summer Deaflympics, 2009 CASE II: RUENTEX RITZ APARTMENT, TAIPEI, TAIWAN The Ruentex Ritz Apartment in Taipei, Taiwan (Fig. 9) is an 11-story apartment building. As can be seen from Table 4, the use of multi-spiral shear reinforcement design instead of the conventional stirrups in rectangular columns reduces the amount of shear steel by 388 tons resulting in 358 tons of CO 2 reduction. Lower consumption of steel required for multi-spiral confinement design results in energy saving and carbon reduction. Figure 9 Ruentex Ritz Apartment Building 14

CONCLUDING REMARKS The innovative interlocking multi-spiral confinement design offers an attractive and superior alternative to traditional stirrup confinement design for rectangular concrete columns. The laboratory tests and field experience have shown clearly that multi-spiral confinement design can provide effective confinement with increased strength and ductility, and reduced cost. Furthermore, the multi-spiral confinement design is also the most efficient layout in terms of automatic assembly. These reinforcement cages can be built quickly and economically and are very cost-effective for precast construction. Lower consumption of steel required for multi-spiral confinement design results in energy saving and carbon reduction and; therefore, the multi-spiral confinement design offers a sustainability advantage. REFERENCES 1. Sheikh, S.A., and Uzumeri, S.M., Strength and Ductility of Tied Concrete Columns, Journal of the Structural Division, ASCE, Vol. 106, No. ST5, May, 1980, pp. 1079-1102. 2. Sheikh, S.A., and Uzumeri, S.M., Analytical Model for Concrete Confinement in Tied Columns, Journal of the Structural Division, ASCE, Vol. 108, No. ST12, December, 1982, pp. 2703-2722. 3. Mander, J.B., Priestly, M.J.N., and Park, R., Theoretical Stress-Strain Model for Confined Concrete, Journal of the Structural Division, ASCE, Vol. 114, No. 8, 1988, pp. 1804-1826. 4. Yin, S. Y. L., Wang, J. C., and Wang, P. H., Development of Multi-Spiral Confinements in Rectangular Columns, Paper accepted for publication in the Journal of the Chinese Institute of Engineers, 2010. 5. Sheikh, S.A. and Yeh, C.C., Tied Concrete Columns Under Axial Load and Flexure, Journal of the Structural Division, ASCE, Vol. 116, No. 10, October 1990, pp. 2780-2800. 15