SECTION ELASTOMERIC MEMBRANE ROOFING

Similar documents
SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION 07530CP EPDM MEMBRANE ROOFING

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

SECTION MANUFACTURED ROOF EXPANSION JOINTS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS

ACFoam-II HCFC Free "Green" Polyiso Specification

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):

A. Submit product data sheets and literature verifying physical properties of materials.

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208

SECTION CO-POLYMER ELASTOMERIC COOL-ROOF COATING

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

Light-Metal Roof Edge, Raised

1.1 SECTION INCLUDES Verify Scope, including identification of plies and type of coating.

SECTION CLAY BARREL TILE ROOFING Removals Flashing and Sheet Metal.

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers.

MEMBRANE ROOFING Christ on the Mountain

SECTION PREPARATION FOR RE-ROOFING

Firestone Polyiso Boards

SCOPE OF WORK PROJECT IDENTIFICATION

(Project Location) (your firm's name)

FOAMULAR Commercial Roofing

SECTION mil thickness COLD FLUID-APPLIED WATERPROOFING

Master Guide Specification Page 1

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING

SECTION PRE-ENGINEERED BUILDING INSULATION

SECTION ROOF SPECIALTIES

SECTION TURBINE VENTILATORS

Application Specification:

SECTION METAL ROOF PANELS

RUBBERGARD EPDM SA APPLICATION GUIDE

Guideline Specification ACRYMAX ARS-1-C Reinforced Composite Elastomeric Membrane System for Concrete Roofs Fluid-Applied Roofing

1. Project Location: Phase II Roof Troughs and Aluminum Gutters at the Morial Convention Center.

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

ARCHITECTURAL GUIDE SPECIFICATION REROOFING OVER EXISTING BUR C-EPDM SYSTEM 2001 FOR STEEL AND WOOD DECKS

SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING

Design and Construction Standards. Division 07 Thermal and Moisture Protection

APPLICATION SAFETY TOOLS REQUIRED

ASSEMBLY DESIGN CRITERIA

SECTION SELF-ADHERING SHEET WATERPROOFING

ERSYSTEM ONESTEP PLUS

Floor Insulation Underlayment Section Sound Control Matting

TOPCOAT Restoration Specifications Structural Concrete

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

FOAMULAR Insulation, PRMA, Horizontal Waterproofing

SECTION ALPHAGUARD RESTORATION 20 YEAR WARRANTY SYSTEM. f. Conditions and Division 01 Specification Sections, apply to this Section.

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

ENKASONIC FLOOR UNDERLAYMENT 9110

MULE-HIDE PRODUCTS CO., INC. MULE-HIDE SELF-ADHERING TPO ROOFING SYSTEM

CS-100 Guide Specifications

SECTION PVC SINGLE PLY ROOFING

UL Evaluation Report UL ER Issued: December 19, 2014 Revised: August 14, UL Category Code: ULFB. CSI MasterFormat

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

GE SCM3500 High Solids Silicone Roof Coating

ROXUL Roof and Deck Insulation Section Master Guide Specification Page 1 April 2016

SUBMITTALS Descriptive literature: Submit manufacturer's application instructions and technical data sheets or catalog cuts on materials.

Product Technical Bulletin APS-5T

1. Clean the existing totally adhered or mechanically attached roof membrane: TPO, EPDM, Hyplon,

Metal Roof Panels


GenFlex EZ TPO Peel & Stick SA (HW) APPLICATION GUIDE

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016

.1 Provide submittals in accordance with Section Submittal Procedures.

SPECIFICATION GUIDELINE

A. Source Limitations: Obtain each type of building insulation through one source.

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC.

SECTION EPDM MEMBRANE WATERPROOFING

TTR SYSTEMS ROOF SPECIFICATION

PG 9600 HIGH SOLIDS SILICONE ROOF COATING

J41 Reinforced bitumen membrane roof coverings

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

LAKEWOOD HIGH SCHOOL RECOAT/REROOF PROJECT 100% OWNER REVIEW

A. Manufacturer: A firm that produces primary glass or fabricated glass as defined in referenced glazing publications.

SPECIFICATION GUIDELINE

REPORT HOLDER: CARLISLE SYNTEC POST OFFICE BOX 7000 CARLISLE, PENNSYLVANIA EVALUATION SUBJECT:

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate

TOPCOAT System Specifications Corrugated Transite Panels

Corium Brick Rainscreen System Specifications

SECTION ATHLETIC AND RECREATIONAL SURFACING. A. ASTM C 67 - Standard Test Methods for Sampling and Testing Brick and Structural Clay Tile.

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.

Construction. S-Vap 5000E SA Self-adhesive Vapour Barrier. Product Description

A. Product Data: Submit manufacturer s product data, with complete general and specific installation instructions, recommendations, and limitations.

ROXUL Roof and Deck Insulation Section Master Guide Specification (MONOBOARD ) Page 1 April 2016

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

FIRESTONE ULTRAPLY TPO SA APPLICATION GUIDE

Product Technical Bulletin SPM-4H-250

TEKTON Flashings and TEKTON Construction Tape

IPE WOOD DECK TILES National Distribution SPEC - SECTION 07760

Alply CLASSIC WALL Architectural Insulated Panel Wall System

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

Transcription:

SECTION 07 5300 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Elastomeric roofing membrane, mechanically fastened conventional application. B. Insulation, flat and tapered. C. Flashings. D. Roofing cant strips, stack boots, roofing expansion joints, and walkway pads. 1.02 RELATED REQUIREMENTS A. Section 06 1000 - Rough Carpentry: Wood nailers and curbs. B. Section 07 6200 - Sheet Metal Flashing and Trim: Counterflashings, reglets,. C. Section 07 7200 - Roof Accessories: Roof-mounted units; prefabricated curbs. 1.03 REFERENCE STANDARDS A. ASTM C1289 - Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board; 2014. B. ASTM D412 - Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers- Tension; 2006a (Reapproved 2013). C. ASTM D624 - Standard Test Method for Tear Strength of Conventional Vulcanized Rubber and Thermoplastic Elastomers; 2000 (Reapproved 2012). D. ASTM D746 - Standard Test Method for Brittleness Temperature of Plastics and Elastomers by Impact; 2013. E. ASTM D2240 - Standard Test Method for Rubber Property--Durometer Hardness; 2005 (Reapproved 2010). F. ASTM D4637/D4637M - Standard Specification for EPDM Sheet Used in Single-Ply Roof Membrane; 2013. G. ASTM E96/E96M - Standard Test Methods for Water Vapor Transmission of Materials; 2013. H. FM DS 1-28 - Wind Design; Factory Mutual Research Corporation; 2007. I. NRCA ML104 - The NRCA Roofing and Waterproofing Manual; National Roofing Contractors Association; Fifth Edition, with interim updates. J. UL (RMSD) - Roofing Materials and Systems Directory; Underwriters Laboratories Inc.; current edition. 1.04 SUBMITTALS A. See Section 01 3000 - Administrative Requirements, for submittal procedures. Edison Elementary Addition - Bid Package 3 07 5300-1

B. Product Data: Provide data indicating membrane materials, flashing materials, insulation, and fasteners. C. Shop Drawings: Indicate joint or termination detail conditions, conditions of interface with other materials, setting plan for tapered insulation, and paver layout. D. Warranty: Submit manufacturer warranty and ensure forms have been completed in Owner's name and registered with manufacturer. 1.05 QUALITY ASSURANCE A. Perform work in accordance with NRCA Roofing and Waterproofing Manual and manufacturer's instructions. B. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years of documented experience. C. Installer Qualifications: Company specializing in performing the work of this section with minimum three years documented experience, and approved by manufacturer. 1.06 DELIVERY, STORAGE, AND HANDLING A. Deliver products in manufacturer's original containers, dry, undamaged, with seals and labels intact. B. Store products in weather protected environment, clear of ground and moisture. C. Protect foam insulation from direct exposure to sunlight. 1.07 FIELD CONDITIONS A. Do not apply roofing membrane during unsuitable weather. B. Do not apply roofing membrane when ambient temperature is below 40 degrees F (5 degrees C) or above 100 degrees F (38 degrees C). C. Do not apply roofing membrane to damp or frozen deck surface or when precipitation is expected or occurring. D. Do not expose materials vulnerable to water or sun damage in quantities greater than can be weatherproofed the same day. 1.08 WARRANTY A. See Section 01 7800 - Closeout Submittals, for additional warranty requirements. B. Correct defective Work within a two year period after Date of Substantial Completion. C. General Warranty: The warranties specified in this Article shall not deprive the Owner of other rights the Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by the Contractor under requirements of the Contract Documents. D. Provide 20 year manufacturer's material and labor warranty to cover failure to prevent penetration of water. Edison Elementary Addition - Bid Package 3 07 5300-2

PART 2 PRODUCTS 2.01 MANUFACTURERS A. EPDM Membrane Materials: 1. Carlisle Roofing Systems, Inc; Sure-Seal EPDM: www.carlisle-syntec.com. 2. Firestone Building Products, LLC: www.firestonebpco.com. 3. GenFlex Roofing Systems, LLC: www.genflex.com. 4. Versico Roofing Systems: www.versico.com. 5. Substitutions: See Section 01 6000 - Product Requirements. B. Insulation: 1. Atlas Roofing Corporation: www.atlasroofing.com. 2. GAF: www.gaf.com. 3. Dow Chemical Co: www.dow.com. 4. Owens Corning Corp: www.owenscorning.com. 5. Insulation manufactured by the membrane manufacturer is approved. 2.02 ROOFING - UNBALLASTED APPLICATIONS A. Elastomeric Membrane Roofing <EPDM-2>: One ply membrane, mechanically fastened, over insulation. B. Roofing Assembly Requirements: 1. Roof Covering External Fire-Resistance Classification: UL Class A. 2. Factory Mutual Classification: Class I and windstorm resistance of I-75, in accordance with FM DS 1-28. C. Acceptable Insulation Types - Constant Thickness Application: Any of the types specified. 1. Minimum 2 layers of polyisocyanurate board. D. Acceptable Insulation Types - Tapered Application: Any of the types specified. 1. Tapered polyisocyanurate board. 2.03 ROOFING MEMBRANE AND ASSOCIATED MATERIALS A. Membrane: Ethylene-propylene-diene-terpolymer (EPDM); externally reinforced with fabric; complying with minimum properties of ASTM D4637. 1. Thickness: 0.060 inch (1.5 mm). 2. Color: Black. 3. Tensile Strength: 1,400 psi (9,652 MPa), measured in accordance with ASTM D412. 4. Ultimate Elongation: 300 percent, measured in accordance with ASTM D412. 5. Hardness: 60+10, measured in accordance with ASTM D2240, using Type A durometer. 6. Tear Strength: 150 lbf/in (26.3 kn/m), measured in accordance with ASTM D624. 7. Water Vapor Permeability: 0.5 perm inch (0.33 ng/(pa s m)), measured in accordance with ASTM E96/E96M. 8. Brittleness Temperature: -60 deg F. (-51 deg C), measured in accordance with ASTM D746. B. Seaming Materials: As recommended by membrane manufacturer. C. Membrane Fasteners: As recommended by and approved by membrane manufacturer. D. Flexible Flashing Material: Same material as membrane; conforming to the following: Edison Elementary Addition - Bid Package 3 07 5300-3

2.04 INSULATION 1. Thickness: 60 mil (1.5 mm). 2. Color: Black. A. Polyisocyanurate Board Insulation <INSUL-51>: Rigid cellular foam, complying with ASTM C1289, Type II, Class 1, cellulose felt or glass fiber mat both faces; Grade 2 and with the following characteristics: 1. Compressive Strength: 20 psi (138 kpa) 2. Board Edges: Square. 2.05 ACCESSORIES A. Prefabricated Roofing Expansion Joint Flashing: Sheet butyl over closed-cell foam backing seamed to galvanized steel flanges. B. Stack Boots: Prefabricated flexible boot and collar for pipe stacks through membrane; same material as membrane. C. Cant and Edge Strips: Wood fiberboard, compatible with roofing materials; cants formed to 45 degree angle. D. Insulation Fasteners: Appropriate for purpose intended and approved by roofing manufacturer. E. Membrane Adhesive: As recommended by membrane manufacturer. F. Surface Conditioner for Adhesives: Compatible with membrane and adhesives. G. Thinners and Cleaners: As recommended by adhesive manufacturer, compatible with membrane. H. Sealants: As recommended by membrane manufacturer. I. Walkway Pads: Suitable for maintenance traffic, contrasting color or otherwise visually distinctive from roof membrane. 1. Composition: Roofing membrane manufacturer's standard. 2. Surface Color: As selected by Architect. PART 3 EXECUTION 3.01 EXAMINATION A. Verify that surfaces and site conditions are ready to receive work. B. Verify deck is supported and secure. C. Verify deck is clean and smooth, flat, free of depressions, waves, or projections, properly sloped and suitable for installation of roof system. D. Verify deck surfaces are dry and free of snow or ice. E. Verify that roof openings, curbs, and penetrations through roof are solidly set, and cant strips are in place. Edison Elementary Addition - Bid Package 3 07 5300-4

3.02 INSULATION - UNDER MEMBRANE A. Attachment of Insulation: 1. Mechanically fasten first layer of insulation to deck in accordance with roofing manufacturer's instructions and Factory Mutual requirements. B. Lay subsequent layers of insulation with joints staggered minimum 6 inch (150 mm) from joints of preceding layer. C. Place tapered insulation to the required slope pattern in accordance with manufacturer's instructions. D. Lay boards with edges in moderate contact without forcing. Cut insulation to fit neatly to perimeter blocking and around penetrations through roof. E. At roof drains, use factory-tapered boards to slope down to roof drains over a distance of 18 inches (450 mm). F. Do not apply more insulation than can be covered with membrane in same day. 3.03 MEMBRANE APPLICATION A. Roll out membrane, free from wrinkles or tears. Place sheet into place without stretching. B. Shingle joints on sloped substrate in direction of drainage. C. Overlap edges and ends and seal seams by contact adhesive, minimum 3 inches (75 mm). Seal permanently waterproof. Apply uniform bead of sealant to joint edge. D. Mechanical Attachment: Apply membrane and mechanical attachment devices in accordance with manufacturer's instructions. E. At intersections with vertical surfaces: 1. Extend membrane over cant strips and up a minimum of 4 inches (100 mm) onto vertical surfaces. 2. Fully adhere flexible flashing over membrane and up to nailing strips. F. Around roof penetrations, seal flanges and flashings with flexible flashing. G. Install roofing expansion joints where indicated. Make joints watertight. 1. Install prefabricated joint components in accordance with manufacturer's instructions. H. Coordinate installation of roof drains and sumps and related flashings. 3.04 CLEANING A. Remove bituminous markings from finished surfaces. B. In areas where finished surfaces are soiled by work of this section, consult manufacturer of surfaces for cleaning advice and conform to their documented instructions. C. Repair or replace defaced or damaged finishes caused by work of this section. 3.05 PROTECTION A. Protect installed roofing and flashings from construction operations. Edison Elementary Addition - Bid Package 3 07 5300-5

B. Where traffic must continue over finished roof membrane, protect surfaces using durable materials. END OF SECTION Edison Elementary Addition - Bid Package 3 07 5300-6