Safe anchorage by the system of Qualification, Approval, and Design. Seismic design and qualification requirements - Dewalt Workshop Taiwan

Similar documents
by Dr. Mark A. Ketchum, OPAC Consulting Engineers for the EERI 100 th Anniversary Earthquake Conference, April 17, 2006

E TA TECHNICAL REPORT. Design of Metal Anchors For Use In Concrete Under Seismic Actions. TR 45 Edition February 2013

Nonlinear Pushover Analysis of Steel Frame Structure Dahal, Purna P., Graduate Student Southern Illinois University, Carbondale

3.5 Tier 1 Analysis Overview Seismic Shear Forces

Seismic Design Criteria for Structures, Systems, and Components in Nuclear Facilities

Submittal / Substitution Request

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

English translation prepared by CSTB - Original version in French language POWERS PB-PRO-S

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS DIVISION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

DDI + (DECK INSERT) Threaded Insert for Metal Deck

Understanding the requirements for IBC seismic-compliant power systems

Seismic performance assessment of reinforced concrete buildings using pushover analysis

Seismic retrofit and shaking table test of medical equipment in a hospital

Council on Tall Buildings. and Urban Habitat

FLOOR AND ATTACHED COMPONENT SEISMIC AMPLIFICATION FACTORS FROM NONLINEAR TIME-HISTORY ANALYSIS

Adhesive Anchors SECTION CONTENTS. General Information. Installation Information Design Information Material Information Ordering Information

Damage-control Seismic Design of Moment-resisting RC Frame Buildings

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

Performance Based Seismic Design of Reinforced Concrete Building

Fragility Curves for Seismically Retrofitted Concrete Bridges

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

SEISMIC EFFECTS ON COUPLED SHEAR WALL STRUCTURE BY COUPLING BEAMS WITH SIDE BOLTED STEEL PLATES

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

SEISMIC RESPONSE OF MULTIPLE-ANCHOR CONNECTIONS TO CONCRETE

4.2 Tier 2 Analysis General Analysis Procedures for LSP & LDP

CALIFORNIA BUILDING CODE

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

Retrofit of an Existing Hospital to Immediate Occupancy Standards. One Year Later. Degenkolb Engineers

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

DISPLACEMENT-BASED SEISMIC DESIGN OF CONCRETE BRIDGES

Earthquake engineering is the science that studies the behavior of structures

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INTALLED CONCRETE ANCHORS

RESILIENT INFRASTRUCTURE June 1 4, 2016

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Index terms Diagrid, Nonlinear Static Analysis, SAP 2000.

Experimental Study on Wall-Frame Connection of Confined Masonry Wall

BASE SHEAR REDISTRIBUTION BETWEEN THE R/C DUAL SYSTEM STRUCTURAL COMPONENTS

DEFINING RIGID VS. FLEXIBLE NONSTRUCTURAL COMPONENTS

PERFORMANCE OF PRECAST CONCRETE CLADDING SYSTEMS UNDER IN-PLANE CYCLIC LOADING

SEISMIC CAPACITY EVALUATION OF POST-TENSIONED CONCRETE SLAB-COLUMN FRAME BUILDINGS BY PUSHOVER ANALYSIS

4.6 Procedures for Connections

REINFORCED CONCRETE WALL BOUNDARY ELEMENT LONGITUDINAL REINFORCING TERMINATION

VMA C (Revision 2)

APPENDIX A: Strength Design Performance Values

RESEARCH PROJECT AT UNIVERSITY OF NEVADA, RENO

Panduit Corporation Tinley Park, Illinois. Outset and Inset Cabinets Seismic Load Rating and Anchorage Design

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

Experimental Study on Seismic Performance of Equipment with Vibration Isolation Devices

Seismic Behaviour of RC Shear Walls

HYBRID MOMENT RESISTING STEEL FRAMES

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

Design of buildings using EC8

International Journal of Engineering Research And Management (IJERM) ISSN: , Volume-03, Issue-11, November 2016

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Comparative Study on Concentric Steel Braced Frame Structure due to Effect of Aspect Ratio using Pushover Analysis

New ICC/ACI Design Concept for Post-Installed Reinforcement Bars Kelly Chua, B.Eng (Civil and Structural)

A SIMPLIFIED METHOD FOR THE ESTIMATION OF THE SEISMIC RESISTANCE OF RC FRAMES WITH WEAK INFILL PANELS

Investigation on Behaviour of Reinforced Concrete Beam Column Joints Retrofitted with FRP Wrapping

LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS

Available at: Last Modified: December 2012

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

European Technical Assessment ETA-10/0422 of 08/01/2016

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

KINETICS Pipe & Duct Seismic Application Manual

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

Seismic Assessment of an RC Building Using Pushover Analysis

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

HVAC Ductwork and Strut Channels Suspended Ceilings

European Technical Assessment ETA-14/0454 of 11/12/2014

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

PERFORMANCE OF MECHANICAL SEISMIC LOAD TRANSMISSION DEVICE BASED ON IMPACT

EVALUATION OF THE NEED FOR WEAK BEAM-STRONG COLUMN DESIGN IN DUAL FRAME-WALL STRUCTURES

Span Length Effect on Seismic Demand on Column Splices in Steel Moment Resisting Frames

Analytical Investigation of Seismic Performance of Exterior RC Beam-Column Joints Rehabilitated with New Scheme

The cracking behaviour of reinforced concrete beams under static and dynamic loading

Transactions, SMiRT-22 San Francisco, California, USA - August 18-23, 2013 Division V

Seismic Design & Qualification Methods An Interpretation of the IBC 2006 & ASCE 7 Code

English translation prepared by CSTB - Original version in French language. Throughbolt PTB-ETA7-PRO

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

English translation prepared by CSTB - Original version in French language. Injection system DeWalt PURE110-PRO

We are IntechOpen, the first native scientific publisher of Open Access books. International authors and editors. Our authors are among the TOP 1%

PSEUDO-DYNAMIC TESTING OF UNREINFORCED MASONRY BUILDING WITH FLEXIBLE DIAPHRAGM. Jocelyn Paquette 1 and Michel Bruneau 2 ABSTRACT

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: MASON WEST, INC.

SEISMIC RETROFITTING OF REINFORCED CONCRETE COLUMNS USING CARBON FIBER REINFORCED POLYMER (CFRP)

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

Earthquake Design of Flexible Soil Retaining Structures

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

INHERENT DUCTILITY OF REINFORCED CONCRETE SHEAR WALLS WITH NON-SEISMIC DETAILING

Study on seismic performance of existing buildings in Romania

2C09 Design for seismic and climate changes

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

Structural Upgrade of Reinforced Concrete Column-Tie Beam Assembly using FRP Composites

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Seismic design of braced frame gusset plate connections

Seismic Performance Evaluation of Eccentrically Braced Frame Using PBPD Method

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

The Wood Products Council and AIA/CES. Concept, Performance and. Learning Objectives. FPInnovations - Background

Transcription:

Safe anchorage by the system of Qualification, Approval, and Design 2

Safe anchorage by the system of Qualification, Approval, and Design 3

Safe anchorage by the system of Qualification, Approval, and Design Seismic Approval Category C1/C2 /2 What s that? 4

The new European seismic design and qualification requirements for anchors Background and brief history of seismic anchorage Development of the new European seismic C2 qualification Comparison ACI 355 and ETAG C1/C2 seismic qualification Notes on seismic anchor design 5

Taken from FEMA E-74 Background and brief history of seismic anchorage 6

Background and brief history of seismic anchor approval Example of structural EQ damage caused by failure of anchorage 2011 Christchurch Earthquake Nearly collapsed façade due to insufficient anchorage of internal retrofit steel frame Detail of the displaced anchors at overhead footing of the retrofit steel frame 7

Background and brief history of seismic anchor approval Example of nonstructural EQ damage caused by failure of anchorage 2010 Chile Earthquake Silo for liquid storage toppled, tearing down further silos Detail of the failed anchor, rupture at the threaded section of the bolt 8

Background and brief history of seismic anchor approval Timeline of code development for anchors used in seismic applications EUR/GER First national approval of anchor in Germany 1975 German anchor qualification guideline for NPP (DIBt) 1997 1998 Anchor qualification guideline (ETAG 001) First ETA for anchor 1998 Seismic amendment ETAG 001 Annex E Seismic anchor design EOTA TR045 First ETA for seismic anchor 2013 USA/CAN 1975 First anchor certified code-compliant in USA 1991 CAN/CSA-N287.2 1994 Northridge EQ leads to temporary ban of post-installed anchors 1997 SEAOSC 2001 ACI 355.2 qualification Anchor: qualification, approval, design - Dewalt Workshop Taiwan 2002 ACI 318 design 9

Background and brief history of seismic anchor approval First European seismic approvals (ETA) For adhesive anchors: Powers/Dewalt AC100-Pro For mechanical anchors: Powers/Dewalt PTB-Pro 10

Background and brief history of seismic anchor approval Effect of seismic qualification on design data in the approval document Example for an adhesive anchor Reduction of steel strength in shear Reduction of pullout strength in tension Note: For adhesive anchor, pullout strength = bond strength 11

Background and brief history of seismic anchor approval Seismic anchor regulations in Europe and US Qualifcation Guideline EUROPE ETAG 001 + ETAG 001 Annex E Latest changes EAD mech&adh anchor + EOTA TR seismic anchor USA ACI 355.2 and ACI 355.4 AC 193 and AC 308 Technical Approval (Evaluation Report) European Technical Approval (ETA) European Technical Assessment (ETA) ICC-ES (ESR) Design Guideline ETAG 001 Annex C + EOTA TR 045 (seismic) CEN-TS 1992-4 (2009) EN 1992-4 (EC2 Part 4) ACI 318-11 Appendix D 12

Background and brief history of seismic anchor approval Simulated seismic tests: US / Candu CAN/CSA-N287.2 (1991) 340 load cycles in uncracked concrete tension shear USA/CAN SEAOSC (1997) 20 to 30 load cycles in uncracked concrete ACI 355.2 (2001) / ACI355.4 (2011) 140 load cycles in cracked concrete (0.5 mm) 13

serviceability suitability Background and brief history of seismic anchor approval Simulated seismic tests: Germany DIBt NPP guideline (1998) 15 load cycles in cracked concrete (1.5 mm) tension shear EUR/GER In addition tests with cycled cracks: 10 crack cycles (between 1.0 and 1.5 mm) while anchor permanently loaded 10 Further tests to determine characteristc strength in 1.0 mm 14

Background and brief history of seismic anchor approval Questions playing role in development of scientifically substantiated European seismic qualification guideline: nonstructural & structural connections Crack width: what is the seismic crack width? Load cycling: - which number of load cycles? - what pattern of load cycles? Crack cycling: - which number of load cycles? - what pattern of load cycles? How to test anchor performance on serviceabaility and on suitability level? 15

Development of the new European seismic C2 qualification 16

Development of the new European seismic C2 qualification Characteristics of actions during seismic events and how to test them on anchors Load cycling tests: cyclic load on anchor in static crack Crack cycling tests: permanent load on anchor in cyclic crack Monotonic tests: quasi-static load on anchor in static crack Large number of small amplitude cycles, but only moderate number of pronounced load and crack cycles 17

Development of the new European seismic C2 qualification Critical crack width in RC structures during earthquakes Tests in 0.5 mm crack Tests in 0.8 mm crack Stiffness and load capacity decreases substantially Taken from: M. Hoehler (2006): Behavior and Testing of Fastenings to Concrete for use in Seismic Applications Maximum crack width outside of plastic hinge zones: 0.8 mm 18

Example hstories for 8 story building; Northridge 1994 ground motion Development of the new European seismic C2 qualification Nonlinear simulations of RC typical structures stock return period of 475 years representing design level 7 building types subjected to 20 scaled ground motions 966 time histories generated for curvature and floor acceleration after: R. Wood & T. Hutchinson(2013) 19

after: R. Wood & T. Hutchinson(2013) Development of the new European seismic C2 qualification Processing of the nonlinear curvature and acceleration data Rainflow counting algorithm Curvature crack width Combination per buidling & Overall building ave. Crack protocol SDOF oscill. anchor load Concrete structure Load protocol Oscillators Floor Plastic hinges Ground 20

Example: cyclic crack protocol Development of the new European seismic C2 qualification Development of serviceability level and suitability level test protocols suitability serviceability Separate serviceability and suitability protocol results in high testing burden! Combine protocols to one unified protocol allowing evaluation by one test: anchor displacement on serviceability level & ultimate load on suitability level 21

Example: cyclic crack protocol Development of the new European seismic C2 qualification Development of unified test protocol and test parameters 0.8 mm crack width for adverse condition / extreme EQ event: suitability level 0.5 mm crack width for service condition / moderate EQ event: serviceability level Permanent anchor load at serviceability level = 0.8 times anchor load at suitability level 22

Development of the new European seismic C2 qualification Verification by experimental tests Cyclic load tests State-of-the-art test setup Cyclic crack tests 23

Development of the new European seismic C2 qualification Final load and crack cycling protocol as in ETAG 001 Annex E Anchor load F/F max Tension load cycling Shear load cycling Crack width cycling 24

Development of the new European seismic C2 qualification ETAG 001 Annex E Conclusive protocol set for anchor load and crack width cycling tests and corresponding reference tests Comprehensive investigation of critical test parameters Unified protocols allow evaluation of serviceability and suitability level performance Stepwise increasing protocols allow evaluation of anchor performance with increasing demand Further reading: Mahrenholtz (2012): Experimental Performance and Recommendations for Qualification of Post-installed Anchors for Seismic Applications, Dissertation 25

Comparison ACI 355 and ETAG C1/C2 seismic qualification 26

Comparison ACI 355 and ETAG C1/C2 seismic qualification Seismic qualification (w = crack width) Anchor load cycling Tension Shear Crack width cycling Reference tests Tension Shear ACI 355 ETAG C1 ETAG C2 - Cyclic tests (w = 0.5 mm) - Cyclic tests (w = 0.5 mm) - Crack movement tests (w max = 0.3 mm) Included in static ESR - Cyclic tests (w = 0.5 mm) - Cyclic tests (w = 0.5 mm) - Crack movement tests (w max = 0.3 mm) Included in static ETA - Cyclic tests (w max = 0.8 mm) - Cyclic tests (w max = 0.8 mm) - Cyclic tests (w max = 0.8 mm) - Monotonic tests (w = 0.8 mm) - Monotonic tests (w = 0.8 mm) 27

Comparison ACI 355 and ETAG C1/C2 seismic qualification Equivalency of ACI 355 and ETAG 001 C1 seismic qualification ACI 355 ETAG C1 = 28

Comparison ACI 355 and ETAG C1/C2 seismic qualification Recommended performance categories for seismic anchors ETAG 001 Annex E and EOTA TR 045 define 2 seismic performance categories: C1 corresponds to seismic qualification according to ACI 355 C2 for more extreme earthquakes nonstructural structural Recommendation depends on: Importance of building (similar to occupancy category) Seismicity, i.e. design ground acceleration 29

Comparison ACI 355 and ETAG C1/C2 seismic qualification Equivalency of ACI 355 and ETAG 001 C1 seismic qualification ACI 318 EOTA TR 045 1) 2) tension only (not for shear) = 2) 3) q a = 1.0 For load combinations which earthqake component is more than 20% 30

Comparison ACI 355 and ETAG C1/C2 seismic qualification Equivalency of elastic response spectra given in ASCE 7 and EN 1998 ASCE 7 EN 1998 (EC8) S DS 2.5 a g For example acceleration for rock ground type (soil factor S = 1.0): S DS = 2.5 a g 31

Comparison ACI 355 and ETAG C1/C2 seismic qualification Comparison of required seismic qualification for anchors based on the design ground acceleration S DS = 2.5 a g (short period, S = 1.0) 32

Comparison ACI 355 and ETAG C1/C2 seismic qualification Compare to California and Taiwan ETAG Annex E a g < 5% g 5% g < a g < 10% g a g > 10% g (PGA) (PGA) 33

Comparison ACI 355 and ETAG C1/C2 seismic qualification Seismic anchors approved acc. to ACI 355.2 ACI 355.4 (ESR - inch sizes) 34

Comparison ACI 355 and ETAG C1/C2 seismic qualification Seismic anchors approved acc. to ETAG 001 C1/C2 (ETA - metric sizes) C1 approved More to come PB-PRO C1 and C2 approved PTB-PRO 35

Comparison ACI 355 and ETAG C1/C2 seismic qualification ETAG 001 Annex E Concept for resisting seismic loads in design codes ACI 318 and EOTA TR 045 is very similar for anchors ETAG 001 C2 qualification address extreme seismic events beyond the scope of ACI 355 or C1 qualification Current EOTA TR 045 mandates C2 qualification for anchorage starting at relatively low design accelerations Requirements stipulated in EN 1992-4 still under debate for better harmonization within Europe and US Further reading: Mahrenholtz and Olsen (2014): Brief Comparison of US and European Regulations for the Qualification and Design of Seismic Anchors, IALCCE 14 conference paper 36

Notes on seismic anchor design 37

Notes on seismic anchor design Basic concept of seismic anchor design Qualification Technical Approval Design Design without requirement on anchor ductility Capacity design Design with requirement on anchor ductility Ductile anchor design ACI 318 detail for free stretch length ( Chilean design ) Only tension design! Max force design Elastic design Requirements: N sa x 1.2 < N cb Ratio f uta /f ya > 1.3 Free stretch length 8d Additional requirement in Europe: C2 qualification Requirements for ductile anchor design very demanding 38

Notes on seismic anchor design Seismic force from ground level to component level Seismic forces at component level: Further amplification Seismic forces at floor level: Amplified over height of building Seismic forces at ground level: Base shear force Note: NCS = Nonstructural Components and Systems 39

Notes on seismic anchor design Calculation of forces acting on anchor connections Forces acting on any nonstructural component and their connections can be calculated using : - US: ASCE 7 - Europe: EN 1998 (EC8) Examples for nonstructural connections Examples for structural connections Structural analysis using one of the known methodolgies: - Equivalent lateral force analysis - Modal response enalysis - Time-history analysis deliver seismic forcesacting on structural elements and their connections throughout the structure 40

Notes on seismic anchor design Seismic forces according to ASCE 7 and EN 1998 ASCE 7 EN 1998 (EC8) F = m a 41

Notes on seismic anchor design Structural and nonstructural applications of anchors Examples: 1 Floor mounted equipment, e.g. HVAC units 2 Suspended M&E and piping, e.g. sprinkler lines 3 Structural strengthening, e.g. for retrofitting 4 Facade elements, e.g. glass panels and doors Protect live Limit damage Keep civil protection operational 42

Notes on seismic anchor design Big structure collapse! 43

Notes on seismic anchor design So why do we care about nonstructural anchorage? Thank god the anchor is approved for cracked concrete! 44

Notes on seismic anchor design Some facts about earthquake damage Considerable portion of EQ damage is caused by wrongly designed or not adequately qualified anchors In particular nonstructural anchorage is often neglected in design 50% of building costs are related to nonstructural components 30% of all fatilities are attributed to nonstructural hazards Investment costs for safe seismic anchorage is very low 45

Notes on seismic anchor design Design example Seismic bracing of suspended piping 46

Notes on seismic anchor design Design example Calculation of seismic design force 47

Notes on seismic anchor design Design example Elastic design acc. ACI 318 Appendix D 2.0 kn = 3.5 kn = 3.5 kn = 3.5 kn = 1.9 kn 2.0 kn 48

Notes on seismic anchor design Design example Calculation of seismic design strength 49

Notes on seismic anchor design Design example Use of anchor design software 3.5 kn 2.0 kn 50

Key learnings Anchor technology and seismic anchoring has a tradition which Powers/Dewalt is a proud part of ETAG 001 C2 anchor qualification requirements reflect state-of-the-art knowledge of seismic actions on anchors While ETAG 001 C1 is equivalent to ACI 355 seismic qualification, ETAG 001 C2 adds extra safety for extreme seismic events and/or buildings of high importance Seismic design of nonstructural anchorage is important yet straight forward with a conclusive design approach 51