TEST REPORT. Bushfire resistance test of an external wall system to BAL A40 in accordance with AS EWFA Report No:

Similar documents
TEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS

Property of Cooks Plumbing Supplies

REGULATORY INFORMATION REPORT

Fire Engineering, the BCA (NCC) & Bushfire Calculator. Keith Nicholls - Manager Product Testing and Assessments (Australia) Exova Group Limited

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

BRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services

Party Wall Roof Junction Design Guide

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening, Vandal Resistant, Lift Landing Doorsets. WF Assessment Report No:

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: Prepared for: Klefer SA

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications.

Annex C Cavity Closures

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Thermaflex International Holding B.V.

Fully framed glass panels

Fire Rated Glazing System Guide

This classification report consists of five pages and may only be used or reproduced in its entirety.

Fire Safety and Performance of Wood in Multi-Residential and Commercial Buildings. Boris Iskra Forest & Wood Products Australia

SECTION B Steel Frame Wall Systems. Contents. Steel Stud Selection Tables. Introduction. Design Considerations. Installation.

BS 476: Part 6: Method Of Test For Fire Propagation For Products. WF Additional Report Number: Date: 18 th February 2008.

Page No 1 Introduction... 3

RUUKKI FORMA DESIGN INSTRUCTION

Code Compliance Research Report CCRR-0228

NFP Epiradiateur Test. WF Report Number: (Issue 2) Test Sponsor: Fiba Tech Industries Limited. Date of original report:

SYSTEMS+ STEEL STUD WALLS INNOVATIVE SYSTEMS SOLUTIONS USGBORAL.COM

SEPARATING WALLS CLASS 1A

Title: The Fire Resistance Performance of Modified Timber Based Panelled Doorsets. WF Assessment Report No: Issue 8.

Patent No. 9,045,900 Technical Glass Products Architectural Specification Manual

CLASSIFICATION OF FIRE RESISTANCE IN ACCORDANCE WITH BS EN : A1:2009

BRE Global Test Report

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

The great Aussie shed deserves great Australian insulation

Thermal Performance of Plasterboard Lined Steel Stud Walls

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250

BRE Global Assessment Report

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

Fire Resistant: Achieves FRL levels of 90/90/90 for load bearing walls.

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-03 SURFACE BURNING CHARACTERISTICS. We Identify and S.T.O.P. Your Noise Problem.

TECHNICAL GUIDANCE XXXX 2015 EXXON QUESTION ANSWER. page 1 of 9

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

DD CEN/TS 1187: 2012 Test 4

Pronto Panel Multi-Storey External Technical Manual. January Version 3.0

AcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details

The extra strong, extra durable, sound resistant system that you can direct fix to

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

Design Manual Facade, riveted Panel fixed to T-Sections

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

TEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System

NU-WALL EXTRUDED ALUMINIUM CLADDING. Installation Specifications Vertical orientation (over cavity)

SOL UTIONS LIVING SOLUTIONS LIVING SOLUTIONS

ELEVATION FOR DETAIL REFERENCE ONLY

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

UL Design System HW-D-1012 continued

ASTM E 1354 Caloric Content Determination of "3M Polyurethane Adhesive Sealant 550 Fast Cure + AC63"

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: EQUITONE

Windows & Doors Bushfire & Energy Efficient Solutions Tony Paarhammer Paarhammer Pty. Ltd

FLASHCLAD HORIZONTAL WEATHERBOARD CAVITY CLADDING SYSTEM. Product. Scope. Appraisal No. 800 [2013] Appraisal No. 800 (2013) Amended 05 February 2016.

Installation Guide and Safety Manual

Symonite Decorative Panelling

All panels can be supplied in a range of styles, to suit the applications pictured below.

GypLyner (walls) Metal framed wall lining system. GypLyner.

SLIDING Product Information

PRODUCT DATA ECMS EC-200 SYSTEM COMPOSITE WALL PANEL 8/25/2016

Building Design Data

Fire Crunch. firecrunch.com.au. TECHNICAL MANUAL Installation : Fire Rate FRL Systems. Alternative Australian Certified Building Solutions

Controlled Environments. KS1100 CS Data Sheet. Controlled Environment Panels. Insulated Panels

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Assessment Number BTC 14254FA

Rondo steel stud. Framing Systems Installation Manual. revised: october 2008

Low Rise Multi-Residential Intertenancy Walls. Design and Installation Guide

Roof Systems. Span Tables & Thermal Ratings. Custom Roof Panel

Open mono-stringer. design elements

EVALUATION OF DIZAL INC

Is Your Envelope Effective? BCBEC Luncheon January 29, 2009

A GUIDE TO WINDOW AND DOOR SELECTION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

ALSPEC ALUMINIUM SYSTEMS TECHNICAL MANUAL

SI T T FST

3M CS-195+ Composite Sheet Product Description


CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

BRE Global Assessment Report

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

KNIGHT WALL SYSTEMS GUIDE DETAILS:

research report Fire Resistance Ratings of Load Bearing Steel Stud Walls With Gypsum Wallboard Protection RESEARCH REPORT RP REVISION 2007

Appendix 3 Treads. design elements

Gas Fireplaces. P36D-10 Gas Fireplace. Unit Dimensions With Vignette Faceplate. *** Important: Framing height requires consideration of the hearth

C05. S03. P02 P08 FireWall

Construction in Bushfire Zones

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER:

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

DD CEN/TS 1187: 2012 Test 4

SOLITEX EXTASANA WALL PROTECTION MEMBRANE. Product. Scope. Building Regulations. Appraisal No. 822 [2013] Appraisal No. 822 (2013) Amended 06 May 2014

Finish coat painted with a 100% acrylic. Multi purpose scratch coat

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

PERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System

HP Partial Fill. Robust, long-lasting protection

Transcription:

TEST REPORT Bushfire resistance test of an external wall system to BAL A40 in accordance with AS1530.8.1-2007 EWFA Report No: 38031900.1 Report Sponsor: Ullrich Aluminium PO BOX 246 Carole Park QLD 4300 Test Date: 19 December 2016

Page 2 of 25 DOCUMENT REVISION STATUS Date Issued Issue No Description 20/02/2017 38031900.1 Initial Issue CONTACT INFORMATION Exova Warringtonfire Aus Pty Ltd - ABN 81 050 241 524 NATA Registered Laboratory Unit 2, 409-411 Hammond Road Dandenong Victoria 3175 Australia T: +61 (0)3 9767 1000 New South Wales Suite 2002a, Level 20, 44 Market Street Sydney NSW 2000 Australia T: +61 (0)2 8270 7600 Queensland Northpoint, Unit 29, Level 6 231 North Quay Brisbane QLD 4000 Australia T: +61 (0)7 3238 1700 SIGNATORIES Prepared by Reviewed by Reviewed by Kai Loh Mandeep Kamal Steven Halliday GENERAL CONDITIONS OF USE This report may only be reproduced in full without modifications by the report sponsor only. Copies, extracts or abridgments of this report in any form shall not be made distributed or published by other organisations or individuals without the permission in writing from a Director of Exova Warringtonfire Aus Pty Ltd.

Page 3 of 25 CONTENTS 1 Construction Details 4 Test Assembly 4 Test Specimens 4 Assembly and Installation Methods 4 Orientation 4 2 Schedule of Components 5 3 Test Procedure 9 Statement of compliance 9 Variations to test method 9 Pre-test conditioning 9 Sampling / Specimen Selection 9 Ambient Temperature 9 Test Duration 9 Instrumentation and Equipment 9 4 Test Measurements 9 Incident Heat Flux Measurements 9 Specimen Temperatures 9 Observations 9 5 Test Results 10 6 Application of Test Results 10 Test Limitations 10 Variations from the Tested Specimens 10 Uncertainty of measurement 10 APPENDIX 1 DRAWINGS OF TEST ASSEMBLY 11 APPENDIX 2 TEST OBSERVATIONS 15 APPENDIX 3 DIRECT FIELD OF APPLICATION 16 A 3.1 General 16 APPENDIX 4 INSTRUMENTATION POSITIONS 17 APPENDIX 5 TEST DATA 19 A 5.1 Heat Flux Measurements 19 A 5.2 Measure Heat Flux Received 19 APPENDIX 6 PHOTOGRAPHS 24

Page 4 of 25 1 CONSTRUCTION DETAILS TEST ASSEMBLY TEST SPECIMENS The test assembly comprised a nominal 3000mm wide 3000mm long 340mm thick wall system. The wall system consisted of two 70 30 timber stud frames; the central frame offset 250mm back incorporating an 800mm 800mm aluminium framed window and eaves detail. The unexposed side was faced with 10mm Gyprock plasterboard while the exposed side had Ullrich Aluminium - Ulltraclad Shadoline Weatherboard panels. Further details are provided in Figures A1.1 to A1.4 and the Schedule of Components. ASSEMBLY AND INSTALLATION METHODS ORIENTATION Sponsor constructed timber frame and aluminium panel assembly offsite and delivered to Exova on the 2 December 2016. Exova representatives mounted the specimen assembly onto test frame on 15 December 2016 and unexposed plasterboard was installed on 16 December 2016. The unexposed cladding, framing materials and window were sourced by EWFA. The specimen was asymmetrical with the exposed side of the wall compromised of Ullrich Aluminium - Ulltraclad Shadoline Weatherboard cladding and plasterboard on the unexposed side. It was confirmed that the system was exposed from the side that would normally face the outside of the building.

Page 5 of 25 2 SCHEDULE OF COMPONENTS No. Item Description Substrate Product Material Size Linear Mass Density Location/ Fixing Ullrich Aluminium - Ulltraclad Shadoline Weatherboard Aluminium 1500mm wide 205mm high 15.0mm deep with 1.5mm thick aluminium 1.3 kg/m (measured) The panels were installed horizontally from the bottom up on the exposed side of the timber frame (item 13) with a layer of sarking (item 8) in between. A starting channel (item 2) was used at the bottom perimeter while a locator clip (item 5) was installed in between the panels. 1 Top Panel Locator Clip Bottom Panel Support System Item Name A top channel (item 4) was installed at the top edge of the panels along the perimeter. The panels were screwed to the studs of the timber frame (item 13) with Square Head Square Drive 8g 50mm long Coarse Thread screws. See Figure A1.4 for illustration. Window Flashing Aluminium extrusion 2 Product Size Installation 3 Item Name Soffit Clip Base 65mm 18.5mm 1.5mm thick The window flashing was used as bottom and vertical edge channel and was riveted to the panels (item 1).

Page 6 of 25 No. Item Description Aluminium extrusion Product Size Installation Item Name 70.0mm 15.0mm 1.6mm thick The channel was installed at the sill on top of panels and riveted to the panel. Soffit Clip Top Aluminium extrusion 4 Product Size Installation Item Name 65mm 14.0mm 1.6mm thick The channel was installed at the sill and on top of the wall and riveted to the panel. Ulrich Aluminium Locator Clip Aluminium extrusion 5 Product Size Installation Item Name Product 35.8mm 13.91mm 1.5mm thick Installed at each panel level and screw fixed to studs with Bugle Head Square Drive 8g 30 Coarse Thread screws. Male Flat Corner Aluminium extrusion 6 Size 32.81mm 32.81mm 1.5mm thick Installation Installed at the framing side of wall at the outer corner and mated with the outer female flat corner with panels between them. Installed at the exposed side of panels at the inner corner and mated with the inner female flat corner with panels between them.

Page 7 of 25 No. Item Description Item Name Female Flat Corner Product Aluminium extrusion 7 Size 45.0mm 14.0mm 1.5mm thick Installation Installed at the framing side of wall at the inner corner and mated with the outer male flat corner with panels between them. Wraps and Sealants Installed at the exposed side of panels at the outer corner and mated with the inner male flat corner with panels between them. 8 Product Size Ametalin SILVERWRAP MD-M3 1350mm tall sheet, full width of wall Insulation Location Between the timber frame and exposed cladding (item 1). 9 Item Name Product Size Density Location Cavity Insulation Bradford R1.5 Wall and Floor Batts 1160mm high 580mm wide 75mm thick 8.8kg/m 3 (measured) Installed in the cavity of the wall system. Unexposed Cladding 10 Product Size Density Location Fixings 10mm Gyprock RE Plasterboard 1200mm wide 3000mm long 10mm thick sheets cut to suit. 660 kg/m 3 (measured) Clad horizontally on the unexposed side of the timber framing. 32mm 6g Bugle Head Drill Point Fine Thread ZY Plasterboard Screws at nominal 300mm centres. Window 11 12 Frame Glazing Size Product Size Location Extruded Aluminium 6TF Grade A Safety Glass 6mm thick toughened glass OD: Nominal 800mm wide 800mm high 52mm deep. ID: 720mm wide 720mm high (to glazing). Screen Mesh Overall size of nominally 790mm wide 790high 0.85mm thick powder coated stainless steel with 2.25mm square holes. Screen installed on the exposed side of the glazed window and screw fixed to glazing frame with 8g 25mm long square drive, stainless steel screws at nominal 165mm centres. Framing

Page 8 of 25 No. Item Description Product Boral F27 13 Lining 14 Density 70mm 35mm Density 928kg/m 3 (measured) Location Refer to figures A1.1 and A1.2 for frame details. Eaves and 6.0mm Hardieflex sheet sill lining

Page 9 of 25 3 TEST PROCEDURE STATEMENT OF COMPLIANCE The test was performed in accordance with the requirements of AS 1530.8.1: 2007 Section 15 as appropriate for walls. VARIATIONS TO TEST METHOD None PRE-TEST CONDITIONING The wall construction was delivered to EWFA on the 2 nd of December 2016. During this period the test specimen was subjected to normal laboratory temperatures and conditions. SAMPLING / SPECIMEN SELECTION The laboratory was not involved in the sampling or selection of the test specimen for the fire resistance test. AMBIENT TEMPERATURE TEST DURATION The ambient temperature at the start of the test was 32 C and varied between 31 C and 36 C during the test. The test was terminated after 60 minutes in accordance with the procedures of AS1530.8.1-2007. INSTRUMENTATION AND EQUIPMENT The instrumentation was provided in accordance with AS1530.8.1: 2007 and as detailed below: A 3 mm gap gauge was available during the test to assess the performance of the test specimen under the criteria of integrity. Radiant heat flux measurements to determine the irradiance transmitted from the exposed face of the specimen were made using Medtherm Heat Flux Gauges. During calibration, a Heat Flux Gauge was centrally located with respect to the specimen at a distance equal to the leading surface of the specimen. A second Heat Flux Gauge was located close to the vertical centre of the specimen, at the leading edge, in the South wall section at a height of 2265mm from the floor. During the test, the Heat Flux Gauge 2265mm from the floor remained in place, using values found during an ancillary pre-test calibration to determine the heat flux at the leading edge of the glazing. During the test, a second Heat Flux Gauge was located centrally with respect to the glazed element on the wall to determine the radiant heat flux 250mm from the exposed side of the specimen in the period 20 to 60 minutes. The Heat Flux Gauge positions are shown in Figure A4.1 in Appendix 4. 4 TEST MEASUREMENTS INCIDENT HEAT FLUX MEASUREMENTS Heat flux measurements are provided in Figure A5.1 in Appendix 5. SPECIMEN TEMPERATURES OBSERVATIONS Specimen temperature data is provided in A 5.3 and Table A5.1 in Appendix 5. A table that includes observations of the significant behaviour of the specimen and details of the occurrence of the various performance criteria specified in AS 1530.8.1-2007 is provided in Appendix 2. Photographs of the specimen are included in Appendix 6.

Page 10 of 25 5 TEST RESULTS The test specimen achieved the following performance when tested in accordance with AS 1530.8.1-2007 Clause 14 and 15 as appropriate for walls. Table 1: Results for Radiant Exposure and Class A Crib Performance Criteria Formation of through-gaps greater than 3 mm during 60 minutes test period Time to Failure (min) Position of Failure No failure - Sustained flaming for 10 s on the non-fire side No failure - Flaming on the fire-exposed side at the end of the 60 minute test period. No failure - Radiant heat flux 365mm from the non-fire side -2 Not applicable NA exceeding 15 kw m Mean and maximum temperature rises greater than 140K and 180K on non-fire side during the 60 minutes test period. Radiant heat flux 250 mm from the specimen, greater than 3 kw m -2 between 20 min and 60 min Mean and maximum temperature of internal faces exceeding 250 ºC and 300ºC respectively between 20 min and 60 min after commencement of test No failure - No failure - No failure - Crib class A Peak heat flux 40 kw/m 2 Test Result BAL-A40 6 APPLICATION OF TEST RESULTS TEST LIMITATIONS The results of this fire test may be used to directly assess fire hazard, but it should be recognized that a single test method will not provide a full assessment of fire hazard under all fire conditions. The results only relate to the behaviour of the specimen of the element of the construction under the particular conditions of the test; they are not intended to be the sole criteria for assessing the potential fire performance of the element in use nor do they necessarily reflect the actual behaviour in fires. VARIATIONS FROM THE TESTED SPECIMENS This report details the methods of construction, the test conditions and the results obtained when the specific element of construction described herein was tested following the general procedure outlined in AS1530.8.1. Any significant variation with respect to size, constructional details, loads, stresses, edge or end conditions, other than those allowed under the field of direct application in the relevant test method, is not addressed by this report. It is recommended that any proposed variation to the tested configuration other than as permitted under the field of direct application specified in Appendix 3 should be referred to the test sponsor in the first instance to obtain appropriate documentary evidence of compliance from Exova Warringtonfire Aus Pty Ltd or another Registered Testing Authority. UNCERTAINTY OF MEASUREMENT Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result.

Page 11 of 25 APPENDIX 1 DRAWINGS OF TEST ASSEMBLY Figure A1.1: Front frame elevation and Isometric view Drawings provided by client and verified by Exova

Page 12 of 25 Figure A1.2: Rear frame elevation and Isometric view Drawings provided by client and verified by Exova

Page 13 of 25 Figure A1.3: Finished timber framing Drawings provided by client and verified by Exova

Page 14 of 25 Figure A1.4: Finished assembly (Item numbers correspond to Schedule of Components in Section 2 Drawings provided by client and verified by Exova

Page 15 of 25 APPENDIX 2 TEST OBSERVATIONS The following observations include observations of the significant behaviour of the specimen. All observations are from the unexposed side unless otherwise stated. min Time sec Observation 0 00 Bushfire test was commenced and the burning crib was placed against the specimen The ambient temperature was 32 C 0 05 The screen was removed and the specimen was exposed to the radiant heat profile for BAL 40 as specified in AS1530.8.1-2007. 1 00 Crackling sound heard from the specimen 1 30 Smoke emitting from the specimen 2 10 Darkening of the panels close to the crib 2 30 Flaming of the panel surface above the crib and close to the bottom right hand corner of the window 10 00 Screen positioned in front of the furnace and exposure to the radiant heat profile for BAL 40 ceased. Monitoring of the specimen to the criteria specified in AS1530.8.1-2007 continued. 60 00 No further changes to the specimen observed. The bushfire test was stopped in accordance with the procedures of AS1530.8.1-2007.

Page 16 of 25 APPENDIX 3 DIRECT FIELD OF APPLICATION A 3.1 GENERAL AS 1530.8.1-2007 Section 15.7 states: The results of a fire test contained in the test report are directly applicable, without reference to the testing authority for a technical opinion, to similar constructions where one or more of the following changes have been made, provided no individual component is removed or reduced: a) Increase in the length of a wall of identical construction to the specimen. b) Increase in thickness of the wall. c) For framed walls- (i) (ii) (iii) (iv) (v) increase in timber density; increase in cross-sectional dimensions of the framing element(s); decrease in sheet or panel sizes; decrease in stud spacing; or decrease in fixing centres of wall sheet materials.

Page 17 of 25 APPENDIX 4 INSTRUMENTATION POSITIONS The instrumentation was positioned in accordance with the requirements of AS1530.8.1-2007, Clause 16.3 as summarised below. Figure A4.1: Thermocouple locations on wall system Note: The crib was located in the south internal corner of the recess to the exposed side

Page 18 of 25 Table A4.1: Thermocouple Locations Position T/C Location x y 011 750 2250 Internal 012 2250 2250 Quarter 013 250 1500 Points 014 2750 1500 015 1500 600 024 750 2250 External Quarter Points Eave Crib Heat Flux Gauge Positions Description Internal cavity surfaces - Mean temperature rise 025 2250 2250 026 250 1620 Unexposed face - Mean temperature rise 027 2750 1500 028 1500 600 016 550 2755 017 1500 2755 Internal surface of eaves - Max and mean temperature rise 018 1900 2755 019 325 385 Internal cavity surfaces - Max temperature rise adjacent to south 020 555 385 crib 021 555 535 Internal cavity surface - Max temperature rise above south crib 022 325 385 023 555 385 Unexposed face - Max temperature rise adjacent to south crib HFG1 250 1500 Embedded in surface of exposed face. HFG2 1500 1500 250mm from exposed side from 20 min to 60 min of test.

Irradiance (kw/m 2 ) Report No. 38031900.1 Page 19 of 25 APPENDIX 5 TEST DATA A 5.1 HEAT FLUX MEASUREMENTS Before the test heat flux emitted by the radiant panel was measured at the centre and quarter points and the results are indicated below at a distance of 3m. 0.213 0.197 0.267 0.205 0.175 The average of the irradiance received at each of the quarter points was 74% of that at the central point and therefore met the requirements of AS1530.8.1-2007, Clause 13.3. A 5.2 45 40 35 MEASURE HEAT FLUX RECEIVED 40.7 30 25 26.2 20 16.3 15 12.0 10 5 8.5 6.9 5.2 4.1 2.9 0 0 1 2 3 4 5 6 7 8 9 10 Time (min) BAL40 Standard Exposure Average Actual Exposure Figure A5.1: Averaged irradiance levels during the test to the external facade Less than 0.4 kw/m 2 heat flux radiation was received by the heat flux gauge positioned centrally to the front of the specimen, 250mm from the wall during the time period 20 to 60 minutes.

Temperature (deg C) Temperature (deg C) Report No. 38031900.1 Page 20 of 25 A 5.3 SPECIMEN TEMPERATURES 350 300 250 200 150 100 50 0 0 10 20 30 40 50 60 Time (minutes) 011 012 013 014 015 Figure A5.2: Specimen temperatures. Temperatures vs. time, Internal quarter points 140 120 100 80 60 40 20 0 0 10 20 30 40 50 60 Time (minutes) 024 025 026 027 028 Figure A5.3: Specimen temperatures. Temperatures vs. time, Unexposed quarter points

Temperature (deg C) Temperature (deg C) Report No. 38031900.1 Page 21 of 25 350 300 250 200 150 100 50 0 0 10 20 30 40 50 60 Time (minutes) 016 017 018 Figure A5.4: Specimen temperatures. Temperatures vs. time, Eave mean and maximum 350 300 250 200 150 100 50 0 0 10 20 30 40 50 60 Time (minutes) 019 020 021 Figure A5.5: Specimen temperatures. Temperatures vs. time, Internal around crib TC 019 had disconnected between 7-11 minutes hence data has been omitted for that duration.

Temperature (deg C) Report No. 38031900.1 Page 22 of 25 140 120 100 80 60 40 20 0 0 10 20 30 40 50 60 Time (minutes) 022 023 Figure A5.6: Specimen temperatures. Temperatures vs. time, Unexposed around crib

Page 23 of 25 Table A5.1: Test Specimen Temperatures T/C Description 3 Temp ( C) at t (min) Limit 1,2 0 15 30 45 60 011 Upper south internal quarter point 63 139 68 51 45-012 Upper north internal quarter point 64 143 66 50 44-013 South internal quarter point 56 102 60 50 45-014 North internal quarter point 52 101 61 51 46-015 Bottom internal quarter point 60 129 64 50 44 - Average of internal quarter points 59 123 64 50 45-024 Upper south surface quarter point 36 50 43 38 35-025 Upper north surface quarter point 36 49 42 37 35-026 South surface quarter point 34 45 40 37 35-027 North surface quarter point 32 38 36 35 34-028 North surface quarter point 32 36 35 35 35 - Average of surface quarter points 34 44 39 36 35-016 Eave above crib 41 87 58 48 44-017 Eave at middle of specimen 42 86 62 51 46-018 Eave above north window reveal 43 90 62 50 44-019 Centre of crib on inside of return wall 26 228 142 83 64-020 Centre of crib on inside of back wall 42 211 142 86 66-021 Above mid-width of crib inside of back wall 49 188 117 75 59-022 Centre of crib on unexposed side of return wall 31 39 39 37 36-023 Centre of crib on unexposed side of back wall 31 34 34 34 34 - Note 1 Limit time is the time to the nearest whole minute, rounded down to the s nearest minute, at which the temperature recorded by any surface thermocouple does not rise by more than 180 C above the initial temperature. Limit time for the average of surface quarter points is the time to the nearest whole minute, rounded down to the nearest minute, at which the average measured temperature does not rise by more than 140 C above the initial temperature. 2 Limit time is the time to the nearest whole minute, rounded down to the nearest minute, at which the temperature recorded by any internal thermocouple does not reach 300 C. Limit time for the average of internal quarter points is the time to the nearest whole minute, rounded down to the nearest minute, at which the average measured temperature does not reach 250 C. 3 Refer to Appendix 4 for locations of thermocouples as only a generic description is included in the table. # Thermocouple failure. - Under limit column indicates the temperature limit was not exceeded during the test period or up until the time of integrity failure if a failure occurred. Mins

Page 24 of 25 APPENDIX 6 PHOTOGRAPHS South North Figure A6.1: Unexposed face of specimen before commencement of the fire-resistance test North South Figure A6.2: Exposed face of specimen before commencement of the fire-resistance test

Page 25 of 25 South North Figure A6.3: Unexposed face of specimen at the end of the test North South Figure A6.4: Exposed face of specimen at the end of the test