NPS/001/024 Technical Specification for Low Voltage Aerial Bundled Conductor Fittings

Similar documents
NPS/002/001 Technical Specification for Earthing Materials

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/002/023 Technical Specification for 132kV Power Cables.

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

Version: 1.1 Date of Issue: March 2017 Page: 1 of 23

NPS/003/033 Technical Specification for Substation Support Structures

NPS/001/007 Technical Specification for Overhead Line Conductors

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application

Specification for Prefabricated Glass Reinforced Plastic Enclosures

Technical Specification for LV ABC Fuse Switch Disconnectors

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Technical Specification for Live Line Tap Connectors

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

NSP/004/105 (OHI 5) - Guidance on the selection, erection and sagging of O/H line conductors

TECHNICAL SPECIFICATION A.B. CABLE

TESTING PTE EARTHING

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

UTILUX CABLE MANAGEMENT

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

Product Application. Prestige Power Post in White Epoxy Coated Aluminium Finish

SECTION HANGERS AND SUPPORTS FOR PLUMBING

Fixings, bonds and clamps

ELECTRO-FENCE. Fence Protection System. System Manual. EF_System_V1.1

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

Engineering Recommendation G81 Part 7 Issue

*** Supercedes: BECO E and COM , , & ***

SECTION ROOF SPECIALTIES

SPECIFICATION FOR TUBULAR STEEL LIGHTING COLUMN. Reference is made in this Specification to the following:

P.V.C. INSULATED UNARMOURED COPPER CABLES

Trench Sheeting CONSTRUCTION

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

CONTENTS INSTRUCTIONS. UK POWER NETWORKS LV JOINTING MANUAL I Version Section Index I Page 1

SPECIFICATION FOR REINFORCED SOIL WALL

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

Cables for Railway Signalling Applications General Requirements

SECTION CHAIN-LINK FENCES AND GATES 02821/1

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

TS 805 POLES TTS CONSTRUCTION SPECIFICATION FOR POLE INSTALLATION TTS MATERIAL SPECIFICATION FOR STEEL POLES BASE MOUNTED

TECHNICAL SPECIFICATIONS LAYING OF DIFFERENT WIRES & CABLES MOUNTED ON POLES FOR BRPL/BYPL

Cable junction boxes with intrinsic fire resistance and insulation integrity

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

COMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY V SINGH. Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009

BUILDER S CONSTRUCTION SUPPLIES (Temporary in permanent position) REQUIREMENTS. March 2014

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

HAS/042/001 Code of Practice for Work on Street Lighting and Street Furniture including Installation, Repairs and Maintenance

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

Shackles. Applications. Range. Design. CAD drawings. Finish

SECTION PLATE CONNECTED WOOD TRUSSES

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.

SECTION 4 - SECONDARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

EI INSTALLATION OF UNDERGROUND CABLES - LV TO 132KV

Think Safety, Think Safesite O&M - KEEGUARD

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D

Steel Floor Framing Solutions

DRAFT UGANDA STANDARD

Raychem brand S1125 Adhesive

ELECTRICAL SAFETY Information Bulletin

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF POLES

Construction guideline

TEST REPORT IEC Information technology equipment Safety Part 22: Equipment to be installed outdoors

CHAPTER 5 METERING REQUIREMENTS

Single core conductor BETAtherm 145

Glass Reinforced Polyester Enclosures BPG. Glass Reinforced Polyester Enclosures

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Service Entrance Cable Fittings

Evaluation Report CCMC R HELICAL PILE

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

American Metal Specialties, Inc.

TEMPORARY PROTECTIVE GROUNDING EQUIPMENT

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Guide to Documentation and Marking Part 6 General Accessories and Components for Slings

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

SECTION SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED PART 1 GENERAL 1.1 DESCRIPTION:

LINDSEY EMERGENCY RESTORATION SYSTEM

SECTION HEAT TRACING FOR PLUMBING PIPING

Safety Barrier Solutions

UNDERGROUND SERVICES SECONDARY

Connectors. Multi-purpose connecting clamps. Stainless steel cross connectors

Page 1 PRODUCT DESCRIPTION SECTION SECTIONAL OVERHEAD DOORS MODEL 900 PRODUCT FEATURES

Cryogenic Pipe Support Systems

GUIDE TO SUPPLY AND METERING ARRANGEMENT ON CUSTOMER S INTERNAL DISTRIBUTION SYSTEM

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems.

Transcription:

Version:- 5.0 Date of Issue:- July 2017 Page 1 of 12 NPS/001/024 Technical Specification for Low Voltage Aerial Bundled Conductor Fittings 1. Purpose The purpose of this document is to outline the technical requirements for fittings used with low voltage Aerial Bundled Conductor overhead lines on the Northern Powergrid distribution networks. This document supersedes the following documents, all copies of which should be destroyed. Ref Version Date Title NPS/001/024 4.0 Aug 2014 Technical Specification for Low Voltage Aerial Bundled Conductor Fittings 2. Scope This specification applies to ABC fittings including conductor clamps, connectors, service boxes and other accessories. The majority of items are detailed in ENA TS 43-14 Issue 3: 2013 - Insulated Aerial Bundled Conductors for Low Voltage Overhead Distribution Systems Conductor Fittings and Associated Apparatus. The products described within this specification shall comply with all current versions of the relevant International Standards, British Standard Specifications and all relevant Energy Networks Association Technical Specifications (ENATS) current at the time of supply. This specification includes the following appendices: - Appendix 1 Schedule of Components Appendix 2 Self Certification Conformance Declaration Appendix 3 Addendum to Suppliers Requirements Appendix 4 Technical Information Check List

Version:- 5.0 Date of Issue:- July 2017 Page 2 of 12 2.1. Table of Contents 1. Purpose... 1 2. Scope... 1 2.1. Table of Contents... 2 3. Technical Requirements... 3 3.1. General... 3 3.2. Specification Requirements... 3 4. References... 6 4.1. External Documentation... 6 4.2. Internal documentation... 6 4.3. Amendments from Previous Version... 6 5. Definitions... 6 6. Authority for issue... 7 6.1. CDS Assurance... 7 6.2. Author... 7 6.3. Technical Assurance... 7 6.4. Authorisation... 7 Appendix 1 Schedule of Components... 8 Appendix 2 Self Certification Conformance Declaration... 9 Aerial Bundled Conductor Fittings... 10 Appendix 3 Addendum to Supplier Requirements... 11 Appendix 4 Technical Information Check List... 12

Version:- 5.0 Date of Issue:- July 2017 Page 3 of 12 3. Technical Requirements 3.1. General ENA TS 43-14 details the standard to which ABC fittings shall generally be supplied. Appendix 2 of this specification provides a self-certification conformance declaration that shall be completed for each item offered. All items shall be designed to meet the performance requirements of the various sections of this specification. They must be adequately rated for their intended application and retain this rating during their normal life in an outdoor environment. The finish shall be such that outer surfaces are free from sharp edges and burrs that could result in damage to adjacent materials or personnel. Items comprising different component parts shall be so designed that they can be applied without disassembly. Materials shall be resistant to climatic stress and all insulating materials shall be UV stable as detailed in BS4892-1. Steel components shall be hot-dip galvanised to BS EN 1461 and other metallic parts shall be of a non-corrosive type. Non-metallic materials shall be fire retardant in accordance with ENA TS 43-14, Section 4.1.3. The ABC fittings detailed within this specification shall be designed for use with the following types and sizes of ABC conductor which have been manufactured in accordance with NPS/001/007. 2 or 4-core 35mm 2 4-core 50mm, 4-core 70mm, 4-core 95mm 4-core 120mm 2 or 4-core 120mm with an additional 25mm 2 selfsupporting earth protective conductor. All conductor fittings shall be durably marked with the manufacturer s identification mark. This marking shall also be applied to all major components of a fitting which are separable. Where fittings are marked by colour to indicate the size of the conductor on which they are to be used, the colour shall be in accordance with the table below. Where fittings can be used on several sizes of conductor, the largest and smallest sizes of the range shall be indicated. The colours shall be applied in a form sufficiently durable to ensure their retention during storage and application. Conductor 25 35 50 70 95 120 size (mm2) Colour Orange Red Yellow White Grey Pink 3.2. Specification Requirements 3.2.1. Anchor Clamps Anchor clamps are a fitting which transfers the tensile forces within the tensioned conductor cores to the supporting structure and shall be designed for use with 2, 4 and 5 core conductors in the range 35mm 2 120mm 2. They shall be provided in two classes: Heavy duty for conductors operating at full line tension and light duty for conductors operating at a reduced tension for services attached to buildings. Full tension 4 or 5-core anchor clamps shall be range taking 35mm 2 120mm 2 ABC. Anchor clamps shall be designed for attachment to hook and eye bolts as detailed in ENA TS 43-13 Section 5. Details of the range of fittings required are listed in Appendix 1.

Version:- 5.0 Date of Issue:- July 2017 Page 4 of 12 3.2.2. Suspension Roller Clamp The clamp shall be designed to allow the ABC to be erected without the use of a traditional conductor running blocks and to be clamped in place on completion. The clamp shall be suitable for angles of deviation up to 60º when using 2, 4 and 5 core 35mm 2 120mm 2 ABC. The clamp shall incorporate a means of securing the conductors in place. Suspension clamps shall be tested in accordance with ENA TS 43-14 Section 7.3. The clamp shall be designed to accommodate angles of deviation of up to 30, without the need for any additional extension rollers, however for angles between 30-60 it is expected that the clamp will need to be supplemented with removable extension rollers which are only used for the stringing process. Suppliers shall include details of any temporary extension rollers needed. Details of the range of fittings required are listed in Appendix 1. 3.2.3. Branch and Service Connections Insulation piercing connectors shall be designed and tested in accordance with BS EN 50483-4 and test to Class A requirements as defined in BS EN 50483-5. This includes a short-circuit current test in addition to the heat cycle testing. The connector shall be of a type, which has been designed for application to the main conductors without the removal of the insulation (insulation piercing), and simultaneously pierce the insulation of the ABC main and tap conductors. The connector shall be waterproof in accordance with category IP68 and satisfy the degree of protection requirements as specified in BS EN 60529. The design must incorporate an end cap that shall be suitable for location on either side of the connector and which becomes integral to the body of the connector once the tap-off conductor is in place. The connectors shall be suitable for installation without any special tooling and supplied with bolts designed to shear at the required torque. The connectors shall be range taking where possible and suitable for ABC connections to ABC, ABC to service cables using bare Copper or Plain Aluminium conductors and service cables to service cables. Multi-tap Connectors The multi-tap connectors are specially designed for use with universal piercing connectors to facilitate the connection of between 2-4 service connections using service cables ranging between 6mm² - 35mm² (4.5mm to 11mm diameter). Each branch conductor can be connected with a separate screw and is insulation piercing. The multi-tap connectors are suitable for connection to the ABC Bundle with single IPC s (commodity code 242137). Details of the range of fittings required are listed in Appendix 1. 3.2.4. Mains Earth Fitting Shall be manufactured to the same standard as branch and service IPC connectors detailed in 3.2.3 but incorporate the facility for testing, application of earthing lead or generator connection. They shall be range taking and suitable for use on 25mm 2 to 120mm 2 ABC. 3.2.5. Cable End Cap End caps shall be insulated and provide protection against the ingress of moisture and also ensure that the system is fully insulated. They shall maintain the degree of protection offered by IP68 in accordance with BS EN 60529. The caps shall be permanent cold applied, range taking and suitable for installation on 25mm 2 120mm 2 ABC. Push fit cable end caps are not suitable as accidental contact can result in them being removed and exposing live cores.

Version:- 5.0 Date of Issue:- July 2017 Page 5 of 12 3.2.6. Conductor Joint Insulation Sleeve Shall be suitable for application over compression joints associated with 25mm 2 120mm 2 ABC. The sleeve shall be applied without the use of heat or special tooling and shall protect against the ingress of moisture whilst restoring the system insulation properties. 3.2.7. Proximity Shrouding Wall mounted proximity shrouding shall be suitable for use on 4or 5-core 35mm 2 120mm 2 ABC and supplied in 2.5 metre lengths. The material shall be non-rigid, extruded black tube with a wall thickness of 1.5mm. 3.2.8. Cleats Wall Mounted Wall mounted cleats shall provide 100mm of stand-off and be capable of carrying 4 or 5-core 35mm 2 120mm 2 ABC. They shall be designed to be secured to the fabric of the building and include an integral means of securing the cable. Pole Mounted Pole cleats shall be suitable for mounting on steel or wood poles. They shall be range taking and accept 4 or 5-core 35mm 2 120mm 2 ABC. For steel poles steel bandit tape (max 20mm wide) and buckles shall be supplied with each cleat.

Version:- 5.0 Date of Issue:- July 2017 Page 6 of 12 4. References The products described within this specification shall comply with all current versions of the relevant International Standards, British Standard Specifications and all relevant Energy Networks Association Technical Specifications (ENATS) current at the time of supply. 4.1. External Documentation Reference ENA TS 43-14 Issue 3 2013 BS EN ISO 1461: 2009 BS EN 60529: 1992 BS EN 50483 4: 2009 BS 4892-1: 2001 Title Insulated Aerial Bundled Conductors for Low Voltage Overhead Distribution Systems Conductor Fittings and Associated Apparatus Hot dipped galvanised coating on fabricated iron or steel articles. Specification and test methods. Degrees of Protection Provided by Enclosures. (IP rating) Test requirements for low voltage aerial bundled cable accessories. Connectors Methods of exposure to laboratory light sources. General 4.2. Internal documentation Reference NPS/001/007 Title Technical Specification for Conductors for Overhead Lines 4.3. Amendments from Previous Version Clause Subject Amendments 3.2.3 Multi-tap connectors New range of fittings added to specification 3.2.7 ABC service distribution boxes Item removed from the specification Appendix 1 Schedule of Items 2 items removed from the table and 3 new items added Appendix 2 Self-certification Conformance Declaration Instructions for completion updated to reflect current policy 5. Definitions Reference Aerial Bundled Conductor (ABC) Anchor Clamp Insulation Piercing Compression Connector Roller Suspension Clamp Weak Link Multi-tap connector Title The term ABC in this Specification refers to the assembly of 2, 4 or 5 conductors to ENATS 43-13. A fitting which transfers the tensile forces within the tensioned conductor cores to the supporting structure An Insulation piercing compression connector (IPCC) is one that can be applied to an insulated conductor without prior removal of the insulation. A fitting which encloses and supports all ABC cores at an intermediate support. This type of fitting also incorporates a stringing roller. A fitting which is designed to fail at a predetermined load, generally less than the ultimate tensile strength of the ABC or the support. An IPC connector that allows up to either 2 or 4 service connections per main conductor when used in conjunction a standard IPC mains connector.

Version:- 5.0 Date of Issue:- July 2017 Page 7 of 12 6. Authority for issue 6.1. CDS Assurance 6.2. Author I sign to confirm that I have completed and checked this document and I am satisfied with its content and submit it for approval and authorisation. Sign Date Kelvin Thom CDS Administrator Kelvin Thom 13/07/17 I sign to confirm that I have completed and checked this document and I am satisfied with its content and submit it for approval and authorisation. Review Period - This document should be reviewed within the following time period. Standard CDS review of 3 years? Non Standard Review Period & Reason No Period: 5 Years Reason: Update will be dictated by contact renewal date or any significant changes in the specification or documents referenced. Should this document be displayed on the Northern Powergrid external website? Yes Steven Salkeld Policy and Standards Engineer Steven Salkeld 13/07/17 6.3. Technical Assurance I sign to confirm that I am satisfied with all aspects of the content and preparation of this document and submit it for approval and authorisation. Sign Date Ged Hammel Senior Policy and Standards Engineer Ged Hammel 17/07/17 Sign Date 6.4. Authorisation Authorisation is granted for publication of this document. Sign Date David Gazda Policy and Standards Manager David Gazda 18/07/17

Version:- 5.0 Date of Issue:- July 2017 Page 8 of 12 Appendix 1 Schedule of Components Commodity Code Description Clause 242359 Anchor Clamp, Full Tension 50mm 2 120mm 2 4/5-core 3.2.1 220772 Anchor Clamp, Full Tension 35mm 2 4-core 3.2.1 221085 Anchor Clamp, Full Tension 35mm 2 2-core 3.2.1 221069 Anchor Clamp, Reduced Tension 1.4KN 35mm 2 4-core 3.2.1 221077 Anchor Clamp, Reduced Tension 1.4KN 35mm 2 2-core 3.2.1 242217 Combined Running Block/Suspension Clamp 50mm 2 120mm 2 2 and 3.2.2 4/5-core 297173 ABC-FIT Extension Rollers for ABC suspension/running clamp to drg 1.09.145.0021 SHT 1 242132 Insulation Piercing Connector, Single Bolt 50mm 2-120mm 2 ABC main 3.2.3 to 6mm 2-35 mm 2 tap conductor 222307 Insulation Piercing Connector, Single Bolt 25mm 2-95 mm 2 ABC main 3.2.3 to 6mm 2-35mm 2 tap conductor 222323 Insulation Piercing Connector, Double Bolt 50mm 2-120mm 2 main to 3.2.3 6mm 2-35mm 2 tap 241996 Insulation Piercing Connector, Double Bolt 25mm 2-120mm 2 ABC 3.2.3 main to 16mm 2-120mm 2 tap 242024 Insulation Piercing Connector, Double Bolt for 35mm 2 120mm 2 ABC 3.2.3 Main to bare or covered open wire conductors (32mm 2 100mm 2 Cu. or 50mm 2 100mm 2 Plain Al.) 242137 Insulation Piercing Connector, Single Bolt, 25mm - 150mm Main to 3.2.3 25mm - 95mm Tap 242388 Insulation Piercing Connector (services) for 4-35mm to 4-35mm 3.2.3 Copper or Aluminium service conductor 242034 ABC Fitting: 2-Way Multi-tap IPC Connector for 4 x 6-35mm Service 3.2.3 Connections 242033 ABC Fitting: 4-Way Multi-tap IPC Connector for 4 x 6-35mm Service 3.2.3 Connections 222364 Insulation Piercing Connector, Earthing Fitting for 35mm 2 to 120 3.2.4 mm 2 ABC Main 265524 Cable End Cap (cold applied) for 25mm 2 120mm 2 ABC 3.2.5 262210 Joint Insulation Sleeve 3.2.6 265774 Proximity Shrouding, 2.5 metre Length 3.2.7 262051 Wall Mount Cleat 3.2.8 242560 Pole Cleat for Wood and Steel Poles 3.2.8

Version:- 5.0 Date of Issue:- July 2017 Page 9 of 12 Appendix 2 Self Certification Conformance Declaration The Conductor Fittings and Associated Apparatus covered by this specification shall comply with the latest issues of the relevant International, European and British Standards. This specification is intended to amplify and/or clarify the requirements of those Standards. The manufacturer shall declare conformance or otherwise, clause by clause, using the following levels of conformance declaration codes. Conformance declaration codes N/A = Clause is not applicable/ appropriate to the product Cs1 = The product conforms fully with the requirements of this clause Cs2 = The product conforms partially with the requirements of this clause Cs3 = The product does not conform to the requirements of this clause Cs4 = The product does not currently conform to the requirements of this clause, but the manufacturer proposes to modify and test the product in order to conform. Instructions for completion When Cs1 code is entered the supplier shall provide evidence to confirm conformance. When any other code is entered the reason and supporting evidence for non-conformance shall be entered Prefix each remark with the relevant BS EN, IEC or ENATS as appropriate Manufacturer: Product Reference: Name: Signature: Date:

Version:- 5.0 Date of Issue:- July 2017 Page 1 0 of 12 Aerial Bundled Conductor Fittings ENA TS 43-14 Clause/Sub-clause Requirement Conformance Code Remarks Section 4.1 Section 4.2 Section 4.4 Section 6.1.3 Section 7.3 Section 8.3 Section 9.4 Section 12.2.3 Section 12.2.3 General Requirements for Materials Tests - General Identification and Markings Test for Wall Mounted Cleats Tests for Anchor Clamps Tests for Suspension Clamps Tests for Insulation Piercing Connectors (additional Class A test required as detailed in section 3.2.3 of this specification) Tests for Proximity Shrouding and Cable End Caps Tests Applicable to Conductor Joint Insulation Sleeve

Version:- 5.0 Date of Issue:- July 2017 Page 11 of 12 Appendix 3 Addendum to Supplier Requirements Packaging and Delivery Information Details of how this product will be packaged and delivered shall be provided. Fittings shall be supplied in appropriate quantities within cardboard or similar boxes. The fitting and container shall be clearly labelled to allow identification of the product including the Northern Powergrid commodity code, item description and range of sizes/number of cores covered. The weight of each package shall not exceed 25kG.

Version:- 5.0 Date of Issue:- July 2017 Page 12 of 12 Appendix 4 Technical Information Check List The following information shall be provided by the supplier for technical review by Northern Powergrid. Additional information shall be provided if requested. Requirement Full product descriptions and part number/reference Appendix 2 Completed self-certification conformance declaration Complete set of drawings and data sheets for each variant, including any details of the extension rollers required for the suspension roller clamps Type test evidence Routine test plan (example) Packaging/delivery information - as required in Appendix 3 Provided (Y/N)