Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents

Similar documents
EVALUATION FOR CHLORIDE INDUCED CORROSION OF CONCRETE WITH SILICATE TYPE SURFACE PENETRANT

Author: M Shaw, Sika Limited. Construction. A Guide to the Concrete Repair European Standards BS EN 1504 Series

Fundamentals of Concrete

CONSIDERATIONS ON THE THRESHOLD CHLORIDE CONTENT VALUES ON THE CORROSION OF STEEL BARS IN CONCRETE

Bridge Deck Preservation Treatment Options

Deterioration Control of Concrete Structures by Surface Coating Methods

Experimental Investigation on Diffusion Coefficient of Carbon Dioxide for Sustainable Construction Materials

Water Penetration into Micro-cracks in Reinforced Concrete

Durability of Marine Concrete with Mineral Admixture and Marine Aquatic Organism Layer

Cures, Sealers Densifiers & Crystal Technology Ultimate / Proven Concrete Protection

REFURBISHMENT Sika FerroGard -903 Plus THE UNIQUE MULTI-FUNCTIONAL SURFACE APPLIED CORROSION INHIBITOR FOR REINFORCED CONCRETE

Sika FerroGard Surface Applied Corrosion Inhibitor for Reinforced Concrete

THRESHOLD VALUES OF AIR PERMEABILITY OF CONCRETE COVER - A CASE STUDY IN JAPAN

SULFATE AND CHLORIDE RESISTANCE PROPERTIES OF PORTLAND CEMENT BLENDS

Decreasing Humidity in Concrete Facades after Water Repellent Treatments

Experimental investigation of the use of CFRP grid for shear strengthening of RC beams

CORROSION MONITORING IN REINFORCED CONCRETE BY ACOUSTIC EMISSION

SURVEY ON ENVIRONMENTAL IMPACT OF CARBONATION PROGRESS AND REBAR CORROSION IN ACTUAL CONCRETE STRUCTURE

The Effect of Different Exposure Conditions on the Chloride Diffusion into Concrete in the Persian Gulf Region

Durability Performance of Australian Commercial Concrete Modified with Permeability Reducing Admixture

A STUDY ON LONG-TERM PERFORMANCE OF CONCRETE OVER 50 MPa IN COMPRESSIVE STRENGTH

Properties of Concrete with GGBS and its Applications for Bridge Superstructures

Construction of bridge slab ends repair system

TK Products MCC April 12, 2018

Effect Of Age And Concrete Cover Thickness On Steel Reinforcement Corrosion At Splash Zone In Reinforced Concrete Hydraulic Structures

Reinforced Concrete Corrosion and Protection

Luca Bertolini (1), Elena Redaelli (1), Daniela Lattanzi (2) and Mari Mapelli (2)

VOL. 10, NO 20, NOVEMBER, 2015 ISSN ARPN Journal of Engineering and Applied Sciences

FLEXURAL FAILURE BEHAVIOR OF RC BEAMS WITH REBAR COR- ROSION AND DAMAGE EVALUATION BY ACOUSTIC EMMISSION

Concrete Deterioration Caused by Sulfuric Acid Attack

New Powdery Water Repellents For Dry Mortar Applications

ESTIMATION OF CONCRETE STRENGTH BY CONTRAST X-RAY

Investigation and Repair Work for Superstructures of Jetty Deteriorated by Chloride Induced Corrosion and ASR in the Osaka Port Container Terminal

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , &

Introduction of a Japan Concrete Institute Guideline: Practical Guideline for Investigation, Repair and Strengthening of Cracked Concrete Structures

ALKALI AGGREGATE REACTIVE MORTAR CYLINDERS PARTLY RESTRAINED BY EXTERNAL CFRP FABRIC EXPANSION AND CONFINEMENT

Madewell Products Corporation December Industrial Court Alpharetta, GA Office: (770) Fax: (770)

Total 30. Chapter 7 HARDENED CONCRETE

Technical Development of Highly Durable Pretension PC Girder

Durability Predictions Using Early-Age Durability Index Testing

MONITORING CORROSION ACTIVITY IN CHLORIDE CONTAMINATED CONCRETE WRAPPED WITH FIBER REINFORCED PLASTICS. Abstract. Introduction

Durability of fly ash based Geopolymer concrete against sulphuric acid attack

A STUDY ON THE ENHANCEMENT OF DURABILITY PERFORMANCE OF FACED SLAB CONCRETE IN CFRD

Properties of Concrete. Properties of Concrete. Properties of Concrete. Properties of Concrete. Properties of Concrete. Properties of Concrete

Journal of Engineering Sciences, Assiut University, Vol. 34, No. 4, pp , July 2006

By C.P. Atkins and J.A. Phipps Materials and Corrosion Engineering Group Mott MacDonald Ltd. Altrincham, UK

PVA-FIBER REINFORCED HIGH PERFORMANCE CEMENT BOARD

CYCLIC RESPONSE OF RC HOLLOW BOX BRIDGE COLUMNS STRENGTHENED USING CFRP AND RC JACKETING

A. HIGH-STRENGTH CONCRETE (HSC)

SHEAR BEHAVIOR OF RC BEAMS USING U-SHAPED UFC PERMANENT FORMWORK WITH SHEAR KEYS OR BOLTS

Solutions in cement. Holcim Ultra Durable

From Corrosion of Existing to Durability of New Concrete Structures

EFFECT OF CHLORIDE CONCENTRATION IN SOIL ON REINFORCEMENT CORROSION

An Experimental Investigation on Mechanical Behavior of Macro Synthetic Fiber Reinforced Concrete

Bridge Deck Issues. Paul D. Krauss, P. E. Wiss, Janney, Elstner, Associates

AFFECT OF ENVIRONMENTAL CONDITIONS DURING INSTALLATION PROCESS ON BOND STRENGTH BETWEEN CFRP LAMINATE AND CONCRETE SUBSTRATE

Product Data Sheet Product Description tio Uses tru n Characteristics / Advantages

CRACKING IN FIBRE CEMENT PRODUCTS

Industrial Sealers & Coatings

Codes in Structural Engineering Developments and Needs for International Practice

A SYSTEMATIC APPROACH FOR REPAIRS TO PARKING STRUCTURES PATRICK DUFFY APPLICATION FIELD MANAGER - REPAIR & PROTECTION SIKA CANADA INC.

SHEAR BEHAVIOR OF REINFORCED HIGH-STRENGTH CONCRETE MEMBERS

Experimental Study of Reinforced Concrete (RC) Beams Strengthened by Carbon Fiber Reinforced Polymer (CFRP): Effect of Beam Size and Length of CFRP.

IN SITU MONITORING OF REINFORCEMENT CORROSION BY MEANS OF ELECTROCHEMICAL METHODS

Introductory Chapter

Behaviour of Post-Installed GFRP Adhesive Anchors in Concrete

[AMN02] Durability of ferro cement structures in aggressive environment by laboratory tests

RESILIENT INFRASTRUCTURE June 1 4, 2016

Pumice Pozz vs. Fly Ash

SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket

Types of Cracking and Influencing Causes

EVALUATION OF HIGH PERFORMANCE CONCRETE USING ELECTRICAL RESISTIVITY TECHNIQUE

Chloride and sulphate concentration in concrete exposed to marine conditions

Durability Assessment Techniques

EVALUATION OF AIR-PERMEABILITY OF COVER CONCRETE BY SINGLE CHAMBER METHOD

European Standard En 1504

Rapid Repair Materials and Construction Rapid Bridge Repair Workshop Holiday Inn Tanglewood-Roanoke, Virginia May 21 and 22, 2009

FIVE STAR PRODUCTS, INC. (800)

Corrosion Under Insulation (CUI) and the Insulation System. By Soeren Nyborg Rasmussen ROCKWOOL Technical Insulation, Jubail, 10 December 2015

AN EXPERIMENTAL STUDY ON GLASS FIBRE REINFORCED CONCRETE

WATERPROOF CONCRETE: AUSTRALIAN STATE GOVERNMENT RESEARCH

Anti-Carbonation Ceramic Coating

MICROSTRUCTURE OF LONG TERM MARINE IMMERGED ANTI-WASHOUT CONCRETE

International Journal of Advance Engineering and Research Development. The Experimental Investigation of Durability Test on Concrete Cubes

Construction. Corrosion inhibiting impregnation (improved formulation) Product Description. Product Data Sheet Edition _1

SUMMARY INTRODUCTION. Koji TAKEWAKA 1 and Yuichi KANEKO 2

DURABILITY OF BASALT FIBERS IN CONCRETE MEDIUM

PERFORMANCE EVALUATION OF CORROSION INHIBITORS AND GALVANIZED STEEL IN CONCRETE EXPOSURE SPECIMENS

Service life extension of existing precast concrete girders

Effect of curing conditions on freeze-thaw de-icing salt resistance of blast furnace slag cement mortars

EVALUATION OF CONCRETE DECK AND CRACK SEALERS

CONCREEP 10. September 21-23, 2015 Vienna, Austria. SPONSORED BY RILEM Engineering Mechanics Institute of ASCE

Patching repair with ECC on cracked concrete surface

EFFECT OF COMBINED ENVIRONMENTAL CYCLES ON RC COLUMN WRAPPED WITH FRP SHEET

RATE OF ABSORPTION OF WATER BY LITECRETE LIGHTWEIGHT CONCRETE AND NORMAL CONCRETE

NRMCA is working on. Experimental Case Study Demonstrates Advantages of Performance Specifications

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

REFURBISHMENT THE REPAIR & PROTECTION OF REINFORCED CONCRETE

27/9/01 CFS0078 WERRIBEE 1966 TEST LINE - HISTORY & TEST RESULTS

DURABILITY DESIGN OF BRIDGES FOR SPECIFIED SERVICE LIFE

Transcription:

Hydrophobe V 5 th International Conference on Water Repellent Treatment of Building Materials Aedificatio Publishers, 299-310 (2008) Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents J. Dai 1, Y. Akira 1, E. Kato 1 and H. Yokota 1 1 Life Cycle Management Research Centre, Port and Airport Research Institute, Japan Abstract In this paper, results of a test are presented in which reinforced concrete (RC) prisms treated with different water repellent agents have been exposed to cyclic seawater shower for one year. Purpose of the test was to investigate how the water repellent treatment influences the water absorption and chloride ingress into reinforced concrete with and without the existence of cracks. Uncracked RC prisms, some cracked before the water repellent treatment, and some cracked after the water repellent treatment were prepared for comparison. Four types of water repellent agents, i.e., liquid silane, liquid silane/oligomeric siloxane, silane-based cream and silane-based gel were applied to treat the concrete surface. Time-dependent water absorption of all the un-cracked and cracked RC prisms was monitored. After one-year exposure, all the specimens were broken open. The penetration depths of water repellent agents in the treated specimens were measured and corrosion areas of the inner steel reinforcement were quantitatively evaluated. The chloride ingress profiles in the cracked and un-cracked RC prisms were evaluated using electron probe microscopy analysis (EPMA). Based on the test results, effectiveness of water repellent treatment as a water and chloride barrier of cracked concrete under marine environment is discussed. Keywords: cracks, concrete, water repellent agents, chloride ingress 299

J. Dai, Y. Akira, E. Kato and H. Yokota 1 Introduction Corrosion-induced deterioration is a great concern for reinforced concrete (RC) structures exposed to marine environment. To have structures in good condition during their service period it is required to have enhanced durability design at the initial designing stage and/or to perform strategic maintenance afterwards. Due to the relatively severe construction and service conditions, such as high humidity, salt attack, dry and wet cycling, and the difficulty in setting scaffolds during repair etc., marine RC structures require materials for new construction or repair which are easy to use but long-lasting. Recently, the application of water repellent agents to protect newly-built or to repair existing concrete structures has gained some popularity, particularly for building and highway structures in Japan [1]. This technique can reduce water penetration into concrete and its ease of application makes it attractive for the construction industry. Laboratory tests have shown that the water repellent treatment can establish a chloride barrier for concrete in saline environment [2, 3]. However, there are still two major concerns with respect to their effectiveness in increasing the durability of actual RC structures under marine environment, e.g. superstructures of port piers. One is the applicability of this technique to concrete with different initial conditions, e.g. relatively high internal humidity, carbonation etc. [4]. The other is the compatibility of the water repellent treatment with cracks, which will be the focus of this study. 2 Experimental 2.1 Materials and specimens Two types of test specimens were prepared. One is a cylinder-type concrete specimen of 100mm in diameter and 65mm in height (see Fig.1). The other is prism-type (150 100 100mm 3 ) reinforced concrete (RC) specimen (see Fig.2). The top surfaces of all cylinder-type specimens were treated with different water repellent agents and then cured for two weeks. The remaining surfaces were sealed with an epoxy resin (see Fig.1). All prism-type RC specimens had layers of deformed steel reinforcement located at 25mm and 50mm, respectively, from the concrete surface (see Fig.2). Three types of RC prisms were prepared. The first type had no cracks. In the second type cracks were introduced through splitting tests (see Fig.3) before the water repellent treatment. The crack widths were controlled using displacement transducer during the tests (see Fig.3). After the splitting tests, crack widths were measured through microscopic observation. For each cracked side surface, the average of five measured values was taken as the crack width index. In the third type cracks were 300

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents introduced after applying the water repellent agent on two side surfaces. Two side surfaces of the prism-type RC specimens were treated with water repellent agents while the remaining surfaces were sealed with an epoxy resin (see Fig.2). The surface moisture content was about 4.0% for both cylinder and prism-type specimens when the water repellent product was applied. Figure 1: Cylinder-type specimens Figure 2: Prism-type specimens Figure 3: Introducing cracks into RC prisms Figure 4: Cyclic sea-water shower spray The concrete specimens were made with a cement content of 248kg/m 3, a water to cement ratio of 0.68, and a fine-to-coarse aggregate ratio of 0.49. The compressive strength of concrete at 28 days curing was 34.0MPa. A rather large water to cement ratio was chosen for this research in order to obtain a good penetration depth and to enable a clear assessment of the performance of the four water repellent agents. Before the water repellent treatment, all the specimens had been exposed in room air (Tokyo climate) for three years. Since a relatively large water to cement ratio was used, all the cylinder-type specimens were found to have carbonated edge parts in an average depth of 7.8mm [4]. The prism-type RC specimens were also carbonated to an average depth of 3.6mm. 301

J. Dai, Y. Akira, E. Kato and H. Yokota Four types of water repellent agents were applied to the specimens. They are: liquid silane (A); silane-based cream (B); silane-based gel (C); and, liquid silane/oligomeric siloxane (D). Further details related to their properties and amount for use can be found [4]. Table 1 summarizes the test series. For each testing variable, two specimens were prepared. Table 1: Information of specimens Specimen Code Crack information NC BC AC Note 0-1(2) О Reference cylinder X(A~D)-1(2) О Cylinder 0-NC(BC)-1(2) О О Reference prism X-NC(BC, AC)-1(2) О О О Prism Note: X = A~D, type of water repellent agents; 0 = untreated ; NC = no crack; BC = crack introduced before surface treatment; and AC = crack introduced after surface treatment. Table 2: Crack width (mm) in the exposed sides of prism-type RC specimens Code 0-BC-1 A-BC-1 B-BC-1 C-BC-1 D-BC-1 A-AC-1 B-AC-1 C-AC-1 D-AC-1 Exposed side 1 0.21 0.12 0.15 0.14 0.20 0.12 0.09 0.12 0.08 Exposed side 2 0.09 0.17 0.13 0.13 0.14 0.10 0.12 0.07 0.18 Average 0.15 0.15 0.14 0.13 0.17 0.11 0.11 0.10 0.13 Code 0-BC-2 A-BC-2 B-BC-2 C-BC-2 D-BC-2 A-AC-2 B-AC-2 C-AC-2 D-AC-2 Exposed side 1 0.35 0.15 0.16 0.14 0.17 0.11 0.07 0.15 0.11 Exposed side 2 0.15 0.18 0.14 0.19 0.25 0.18 0.13 0.14 0.10 Average 0.25 0.16 0.15 0.17 0.21 0.14 0.10 0.14 0.10 2.2 Exposure environment and test methods Both cylinder-type and prism-type specimens were exposed to cyclic seawater shower as shown in Fig. 4. There were two wet/dry cycles in one day. Each cycle consists of a 4-hour of wet period and an 8-hour of dry period. The water absorption of all specimens was followed up during the exposure. After 770 dry/wet cycles (about one year), the specimens were washed, dried and split open. The penetration depth of the applied water repellent agents was determined based on the average value of five single measurements. For cylinder-type concrete specimens, slices were obtained by cutting at the depths of 5, 10, 20, 30, 45, and 50mm. Only the core part of each specimen (see the area enclosed in the dotted lines in 302

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents Fig. 5) was removed for the determination of the chloride penetration profile so as to avoid the interference of carbonation. The total chloride ion concentration in each slice was determined based on an automated ionselective electrode method. For the prism-type RC specimens, all the specimens with the code of - - 1 (see Table 1) were broken open and the corrosion areas of the internal steel reinforcement were measured. Those with the code of - -2 were left to continue their exposure. To see the effects of cracks on the chloride ingress profiles, five RC prisms from the reference series (0-NC-1, 0-BC- 1) and the series with maximum silane penetration depth (C-NC-1, C-BC- 1, and C-AC-1) were selected on which electron probe microscopy analysis (EPMA) was performed to determine the accurate chloride penetration profiles. For un-cracked RC prisms, the analysed part corresponds to 40 40mm 2 while for cracked RC prisms, 80 80mm 2 considering that chloride ions might penetrate deeper into cracked concrete. The locations of the removed parts are indicated in Fig. 6. Figure 5: Part for chloride penetration analysis in cylinder-type concrete specimens Figure 6: Part for chloride penetration analysis in prism-type RC specimens (A) (B) (C) (D) Figure 7: Split concrete cylinders after water spray (A) (B) (C) (D) Figure 8: Split RC prisms after water spray 303

J. Dai, Y. Akira, E. Kato and H. Yokota Figure 9: Penetration depth of different water repellent agents into concrete 3 Results and discussion 3.1 Penetration depth After one year exposure to cyclic seawater shower, all cylinder and prism specimens were split as to measure the penetration depth by spraying water on the split surface (see Figs.7 and 8). It turned out that the penetration of water repellent agents into concrete was influenced by both the type and the carbonation condition of the concrete. Although the authors found in the past studies that a very dry and carbonated concrete condition may reduce silane penetration [4], silanes generally achieved much greater penetration depth in the carbonated concrete part compared to a non-carbonated part (see Figs.7 and 9) because of the coarser pore structure of concrete after carbonation. 3.2 Water absorption Fig.10 plots the relationship between water absorption of treated and untreated cylinder-type concrete specimens and exposure time. The average water absorption of two specimens is presented. The exposure started in July 2006 and ended one year later. On the whole, it is seen that all the water repellent specimens (A, B, C, and D) show significant decrease of water absorption compared to the reference series (0). The specimens treated with water repellent agents even show some weight loss at the beginning stage. This is because the water repellent treatment can prevent the external water from penetrating but the internal water still can evaporate. The dual effects can keep effectively the internal 304

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents environment of concrete dry. On the other hand, it is shown that after relatively long-term exposure, the specimens treated with water repellent agents may show some water absorption. In particular for the water repellent agent D, which had the smallest penetration depth (see Fig. 7), the effectiveness of water repellent treatment decreases during the exposure possibly due to ultraviolet deterioration, physical abrasion etc. Therefore, a certain penetration depth has to be achieved in order to obtain a durable water repellent treatment. 50 40 0 A B C D Water absorption (g) 30 20 10 0-10 0 100 200 300 400 Exposure time (days) Figure 10: Water absorption during the exposure cylinder-type specimens Water absorption (g) 90 80 70 60 50 40 30 20 10 0-10 0-NC 0-BC A-NC A-BC A-AC B-NC B-BC B-AC 0 100 200 300 400 Exposure duration (days) Figure 11: Water absorption during the exposure: prism-type specimens Figs.11 and 12 present the effects of cracks on the water absorption of RC prisms treated with different water repellent agents. The series 0-NC and 0-BC are presented in both figures as reference. Again, the average water absorption of two RC prisms specimens is presented. For untreated RC prisms, as predicted, the specimens with pre-cracks (0-BC) show more water absorption than the un-cracked ones (0-NC) in terms of both water 305

J. Dai, Y. Akira, E. Kato and H. Yokota absorption rate and water absorption amount (see Fig.11). Those RC prisms treated with water repellent agents and cracked afterwards (A(B)- AC in Fig.11 and C(D)-AC in Fig.12) show larger water absorption than those cracked before the water repellent treatment (A(B)-BC in Fig.11 and C(D)-BC in Fig.12). Both specimens of BC and AC series show greater water absorption than the treated ones without cracks (A(B)-NC in Fig.11 and C(D)-NC in Fig.12). Nevertheless, compared to the untreated RC prisms and even the un-cracked ones (0-NC in Fig.11 and Fig.12), all the treated RC prisms still show clear decrease of water absorption. Therefore, the water repellent treatment is still effective in reducing the water absorption even though there are cracks induced before or after treatment. In the meantime, it shall be noticed that the effectiveness of water repellent treatment may be largely reduced particularly when the cracks are formulated after the treatment, e.g. the after-crack having a width of 0.10~0.21mm in the current study (Table 2). In other words, the application of water repellent treatment is more effective on concrete having stable cracks. Water absorption (g) 90 80 70 60 50 40 30 20 10 0-10 0-NC 0-BC C-NC C-BC C-AC D-NC D-BC D-AC 0 100 200 300 400 Exposure duration (days) Figure 12: Water absorption during the exposure: prism-type specimens 3.3 Chloride penetration Fig.13 shows the total chloride content distribution profiles in treated and untreated concrete cylinders. Both the penetration depths and the amount of chloride ions present decreases significantly when the water repellent agents A, B, and C are used. The chloride ions were mainly found in the first concrete slice. This is due to a certain extent of chloride adsorbed on the surface as well as the chloride penetration in the water repellent concrete layer (e.g. see C-NC-1 in Fig.14). The water repellent agent D did not appear to efficiently prevent the chloride ions from penetrating which could mainly be attributed to the loss of water repellency effectiveness during the exposure as discussed earlier for Fig.10. 306

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents Fig.14 presents the chloride ion mapping, obtained from EPMA, in the cracked concrete compared to those in un-cracked concrete. Only the reference series 0 and series C were analyzed for comparison purposes. Water repellent agent C was selected because it achieved the maximum penetration depth as mentioned above. The chloride content of the outer Chloride concentration(%) 0.35 0.30 0.25 0.20 0.15 0.10 0.05 0.00 0 10 20 30 40 50 Depth from surface (mm) 0 A B C D Figure 13: Chloride penetration profile in cylinder-type concrete specimens Figure 14: Chloride mapping in RC prisms obtained from EPMA 307

J. Dai, Y. Akira, E. Kato and H. Yokota thin layer (about 2mm) is low in all tested specimens, indicative for a complete carbonation. In the case of un-cracked concrete, the penetration depths of chloride ions in the un-treated sample 0-NC and the treated sample C-NC were 33mm and 10mm, respectively. In the cracked and untreated sample 0-BC-1 chloride ions penetrated throughout the whole specimen. The chloride ion content decreases gradually until the center of the specimen (50 mm deep from the exposure surface). For the treated specimen C-BC-1 with an average initial crack width of 0.13mm (see Table 2) before the water repellent treatment, the penetration depth of chloride ions is only about 8mm. The chloride ion contents near the crack are relatively high. However, the water repellent treatment is still effective in preventing the chloride ions from further penetration. The specimen C-AC-1 had an average crack width of 0.10mm introduced after the water repellent treatment. The crack width was 0.07mm on one exposure surface and 0,12 mm on the other surface. From Fig.14 one can see that the chloride ions penetrated into the concrete to a depth of 17mm from one exposure side, which is smaller than the penetration depth (25mm) of the water repellent agent C in specimen C-AC-1 (see Fig.9), while the penetration depth of chloride ions from the other exposure surface (with the 0.12 mm crack) is 70mm. Obviously, in case of cracks introduced after water repellent treatment an increase of the crack width from 0.07mm to 0.12mm causes a significant increase of chloride penetration. Cracks larger than 0.1mm in width are very common in engineering practice. Hence, it is recommended to apply water repellent treatment for concrete structures with stabilized cracks. If the cracks further propagate after the water repellent treatment, the application effectiveness may be significantly diminished. Of course, even with cracks occurring after the water repellent treatment, the chloride ions mainly concentrate near the crack surface. On zones away from cracks, the water repellent agent is still effective in preventing chloride penetration (see Fig.14). 3.4 Corrosion area of steel reinforcement Fig. 15 shows the influence of the different water repellent agents on the corrosion of internal steel reinforcement embedded in the RC prisms. The steel reinforcement was taken out after breaking open the RC prisms at the end of the exposure time. Then, the surface of steel reinforcement was mapped. The corrosion of steel reinforcement was evaluated using the ratio of corroded surface area to the whole initial surface area. In uncracked RC prisms (see NC series in Fig.15), steel reinforcement at the location of 20mm from the exposure surface in the reference specimen and the one treated with water repellent agent D was corroded. This is very consistent with the results of water absorption and chloride 308

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents penetration as presented in Figs.10 and 13. All steel reinforcement at the location of 50mm from the exposure surface remained uncorroded. Compared to non-cracked samples (NC), introducing a crack before water repellent treatment (BC) leads to an increase of the corrosion area of steel reinforcement for the untreated one and the one treated with D (see Fig.15). Application of cream-type (B) and gel-type (C) silanes to the prisms having crack width ranging from 0.13 to 0.19 mm prevented the corrosion of the steel reinforcement. When the crack was introduced after the water repellent treatment, all the RC prisms showed corrosion of internal steel reinforcement although the treated ones showed relatively less corrosion area, in other words, a decreased corrosion speed. The corrosion area of steel reinforcement at the location of 50mm from the exposure surface is not always less than that of steel reinforcement at the location of 20mm (see Fig.15). This is mainly due to the differences of crack widths in the two exposed sides of the specimen. In the AC series, only the steel reinforcement at the 20 mm location from the exposed surface which were treated with B and C, showed no or a rather small corrosion area. This can be attributed to the relatively small crack widths (0.09mm and 0.07mm) in the corresponding exposure surfaces. Hence, there may be a threshold value of crack width of around 0.09mm, beyond which the effectiveness of water repellent treatment will be lost. There is a need to further study how the water repellent treatment influences the corrosion rate of internal steel reinforcement in concrete when cracks are present. However, as a general conclusion, it is suggested not to apply water repellent treatments to RC concrete members with propagating cracks. Figure 15: Influence of water repellent treatment on the corrosion of steel reinforcement 309

J. Dai, Y. Akira, E. Kato and H. Yokota 4 Conclusions 1. For un-cracked concrete, the water repellent treatment proves its high efficiency both in reducing water absorption and as a chloride barrier under accelerated dry/wet exposure condition. Due to these dual effects, water repellent treatment can prevent corrosion of the internal steel reinforcement in concrete. 2. Considering that the water repellent applied to a concrete surface may be destroyed by UV deterioration, physical abrasion etc., a relatively large penetration depth should be achieved in order to keep the long-term effectiveness of water repellent treatment for the expected service life of the structure. 3. Silane-based cream and gel formulation appear to be superior to silane liquid when treating concrete surfaces with existing cracks. According to the current test results, steel reinforcement in untreated concrete has corroded heavily after 770 accelerated dry/wet cycling exposure. For those specimens with surface crack widths ranging from 0.13mm to 0.17mm before the water repellent treatment, the silane-based cream and gel still seem to be effective in reducing water absorption, chloride penetration, and stopping the internal steel reinforcement from corroding. 4. Water repellent treatments may not be effective in preventing water absorption, chloride penetration, and steel corrosion if cracks are developed in the concrete after the water repellent treatment unless the crack width can be controlled so as to keep it to a minimum width (<0.1 mm). References [1] Japan Society of Civil Engineers, JSCE-325 Committee Report on Concrete Surface Coating and Impregnation Technology, Concrete Engineering Series, No. 68(2006). [2] H. Zhan, F. H. Wittmann and T. Zhao, Chloride Barrier for Concrete in Saline Environment Established by Water Repellent Treatment, International Journal for Restoration of Buildings and Monuments, 9(5), 539-550(2003). [3] H. Zhan, F. H. Wittmann and T. Zhao, Relationship between the Silicon Resin Profiles in Water Repellent Treated Concrete and the Effectiveness as a Chloride Barrier, International Journal for Restoration of Buildings and Monuments, 11(1), 35-46(2005). [4] J. Dai, Y. Akira, H. Yokota and F. H. Wittmann, Surface Impregnation of Pre-conditioned Concrete Subjected to Seawater Immersion Test, International Journal for Restoration of Buildings and Monuments, 13(4), 2007, 229-240. 310