CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS

Similar documents
S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013)

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY ORANGE & ROCKLAND UTILITIES 390 WEST ROUTE 59 SPRING VALLEY, NY 10977

SECTION MEDIUM VOLTAGE TRANSFORMERS

SECTION HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

GST001 MV/LV TRANSFORMERS LOCAL SECTION CELG D

roduct Scope: Substation

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

SECTION SLUDGE HOLDING TANK DECANTER PUMP

ADDITIONAL CONTACT INFORMATION:

OPERATING PROCEDURE NO. 310

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

UNDERGROUND SERVICES SECONDARY

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

Unit Substation Transformer Construction Checklist (under 500 kva)

DIVISION LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM UNDER METAL ROOFING

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

SECTION INFLUENT EQUALIZATION TANK PUMPS

G2D Series Performance Data Discharge: 1-1/4 Solids: 1/4. Wholesale Products Page: JP10075SSD-1 Section: Performance Data Dated: January, 2011

NEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS

TESTING PTE EARTHING

Diffused Aeration Piping Equipment

The complete guide to transformers and packaged substations

REQUIREMENTS FOR INDOOR INSTALLATION OF PADMOUNTED TRANSFORMERS

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

SECTION HEAT TRACING FOR PLUMBING PIPING

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

METERING INSTALLATION

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

1. General regulations

ELECTRIC METERING GENERAL

Electric Service Standards

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

15 kv EPR Insulated, Jacketed, URD Cable

MR 120/2015. SUPPLY OF 2 X 2MVA 415V/11kV 3 PHASE TRANSFORMERS

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Medium Voltage Switchgear. Basis of Design.

SP Standard Profile. Flanged to Duct Install Type THERMAL BREAKS OPPOSED ACTION PARALLEL ACTION. T.A. Morrison & Co. Inc.

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

Power Zone Center. Your solution for power distribution and control systems

REQUEST FOR PROPOSAL 18/24/30 MVA 138 kv to kv 3φ Power Transformers with LTC WEATHERFORD MUNICIPAL UTILITY SYSTEM

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION

Pre Delivery & Installation Guide GX 480 GX 480 DT GX 480 APC GX 480 DT APC GX 600 GX 800 GX 1000

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

Customer Owned Meter Enclosures for Self-Contained Watthour Meters

UNIFIED FACILITIES GUIDE SPECIFICATIONS

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

Standard of Practice - Campus Electrical Distribution System

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

SPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S

Low Voltage Switchgear Construction Checklist (under 500 kva)

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

Pre-installation Manual CONCEPT 301 D/401 D/501 D

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

SECTION OUTLET, PULL, AND JUNCTION BOXES

Monolithic Isolation Fittings

ELECTRICAL INSPECTION BULLETIN (Effective )

SECTION INSULATED WIRE AND CABLE

2/2 % ) Direct Acting Subminiature Solenoid Valves. 1/8" and 1/4" NPT. Features. Construction. Electrical

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

SUGGESTED SPECIFICATIONS

SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY 1234 MARKET STREET, PHILADELPHIA, PA 19107

SUGGESTED SPECIFICATIONS Pump Frames through 64132

GENERAL PROVISIONS: Furnish and install one steel platform motor truck scale and associated electronic controls.

660 Volts 630 & 800AMP

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

UNIFIED FACILITIES GUIDE SPECIFICATIONS

VENTILATED DRY TYPE TRANSFORMERS

Welcome to Douglas County PUD

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE Magnetic Shielding

SK75/100. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK100 SK Liters/Second Capacity-U.S. G.P.M.

40'-0" PIPE SUPPORT (TYP.) (SEE DWG. NO. SK-2 OR DWG. NO. SK-4)

HUP. Performance Data. Wholesale Products Page: Section: Performance Data Dated: January RPM: 1550 Discharge: 1" Solids: 1/8" GPM: TDH:

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

Rosemount 1152 Alphaline Nuclear Pressure Transmitter

NatureWood Construction Product Specification Guide

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Technical Specification for LV ABC Fuse Switch Disconnectors

Superior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C

Service Entrance Cable Fittings

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

Extended-Frequency SMA Connectors

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER

Powering reliable solutions. for the commercial and industrial market

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

Transcription:

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS Original Issue 1/84 Revised 1/91 Revised 6/02 Revised 11/05 Revised 11/09 Revised 1/12 Revised 11/12 Revised 5/14 Revised 9/15

SPECIFICATIONS PADMOUNTED SINGLE-PHASE DISTRIBUTION TRANSFORMERS 12470 GRD Y/7200 VOLTS 1. GENERAL REQUIREMENTS This specification covers new, single-phase, low-profile, deadfront, loop feed, padmounted transformers for use on a 12.47/7.2 kv multi-grounded wye, 60 HZ distribution system. The transformers to be offered under this bid shall conform to the characteristics, definitions, terminology and voltage designations specified in the appropriate standards except as otherwise noted. The standards covering this specification include the most recent revisions of: IEEE C57.12.00, ANSI C57.12.25, ANSI C57.12.28, IEEE C57.12.70, IEEE C57.12.80, IEEE C57.12.90, IEEE C57.147, IEEE 386, ANSI Z535, NEMA 260, and NEMA TR-1. The core shall be grain-oriented silicon steel. Amorphous cores will not be accepted. Transformer rating to be 3" yellow letters on green or black background mounted 4" above lid handle. Transformers with taps to have the rating suffixed by the letter "T". All units shall have an externally operated tap changer. Transformer oil shall be non-pcb containing less than 1 ppm of PCB. Transformer nameplate to be stamped as follows: NON-PCB/LESS THAN 1 PPM PCB WHEN MANUFACTURED Mineral oil or natural ester fluids which meet the requirements of IEEE C57.147, IEEE Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers are acceptable. All transformers may be retrofilled with mineral oil so they shall be designed for mineral oil. The bottom and two inches up the sides shall have a coat of coal tar epoxy paint (or equivalent approved by CPU Standards Engineer) applied to the bare metal to a dry film thickness of 5 mils minimum. Page 1 of 7

2. RATINGS All transformers shall have 12470 Grd Y/7200 volt primaries and 240/120 or 120/240 volt secondaries. All primary windings shall be furnished with 4-2½% taps below 100%. kva ratings shall be 25, 50, 75 or 100 kva as specified on the description sheets. All transformers rated 25, 50 and 75 kva shall have maximum either lineto-ground and line-to-line short circuit current of 10,000 amp symmetrical at the external low voltage bushing terminals. All 100 kva transformers shall have a maximum 14,000 amp symmetrical short circuit current either line-to-ground and line-to-line at the external low voltage bushing terminals. These limits shall be based upon the assumption that the high voltage bushing terminals are infinite short circuit current source. The maximum and minimum %Z for each kva size shall be as follows: KVA Max %Z Min %Z 25 2.0 1.04 50 3.0 2.08 75 4.0 3.13 100 4.0 2.98 3. CONNECTORS AND TERMINALS All units shall have high-voltage, externally-bolted, universal bushing wells with removable studs. The number, location, and arrangement of the high-voltage connectors and low-voltage terminals shall be as shown in Figure 2 of ANSI C57.12.25. Loadbreak bushing inserts shall be provided. There shall be a clear area around all primary bushings so that Cooper feed-through inserts can be installed when needed. The low voltage bushings shall be externally bolted and have copper stud terminals on the phase and neutral. Studs size shall be in accordance with ANSI C57.12.25. Page 2 of 7

4. FUSING All transformers shall be equipped with Cooper flapper-valve bayonet primary fuses and Cooper isolation links. Each bayonet shall have a drip shield below it and arranged to prevent oil from dripping onto elbow terminators or cables. Fuse links shall be furnished and installed as follows: KVA Bayonet Fuse Isolation Link 25 358C05 1861A02 50 358C08 1861A03 75 358C10 1861A05 100 358C10 1861A05 All units shall have provisions for storing one spare replacement fuse link in a moisture-proof container and one link of the proper size shall be included. 5. CONSTRUCTION FEATURES A. A removable front sill such that the transformer can be lifted, skidded, or slid into place on the mounting pad without disturbing the high or low voltage cables. B. A fully insulated low voltage neutral terminal and a ground pad on the outer surface of the tank. C. A removable ground strap, sized for the rating of the transformer, connected between the low voltage neutral bushing and the tank. D. Stainless steel hinges. E. Stainless steel pins. F. Pentahead bolt in a recessed cup as per ANSI C57.12.25, Figure 3. G. A pressure relief valve, with the following characteristics as described in ANSI C57.12.25 Section 6.5.2. Page 3 of 7

H. All 25kVA, 50kVA and 75kVA padmount transformers shall meet the following dimensions: Minimum Maximum Height 24 n/a Width 34 38 Depth n/a 38.5 All 100kVA padmount transformers shall meet the following dimensions: Minimum Maximum Height 24 n/a Width 34 38 Depth n/a 45 6. NAME PLATE In addition to the ANSI standard nameplate information, the nameplate shall show: 1.) The maximum low voltage, line-toground, short circuit current. It shall be shown "Max. L.V. L-G Isc = xxxx where xxxx = the actual maximum Isc, 2.) total weight, and 3.) gallons of oil. 7. SHIPPING PALLETS All shipping pallets shall have the following general requirements. A. The minimum clearance for lift truck forks shall be 3 inches. B. Two-way access is acceptable. C. Four-way access is preferred. D Pallet strength and design shall be adequate to contain the load for which it is intended. Stackable pallets are acceptable as long as they protect the paint and transformers from shipping damage. Double stacking is the maximum allowed. E. Materials or equipment shall be secured to pallets with suitable bands, bolts, screws, or nails. Page 4 of 7

7.1 RETURNABLE SHIPPING PALLETS A. Returnable shipping pallets shall be adequately marked to identify the owner and return location. B. No environmentally harmful substance shall leach from or be abradable from the pallets. 7.2 NON-RETURNABLE SHIPPING PALLETS A. Non-returnable shipping pallets shall be biodegradable. B. Non-returnable shipping pallets shall be made with natural wood, dimensional lumber, and metal nails, screws, or bolts. C. No adhesive or non-metal fastening will be permitted. D. No paint is allowed. E. No composite materials such as, but not limited to, plywood, particle board, flake board, or paper products are acceptable. F. No plastics are acceptable. 7.3 It shall be the responsibility of the vendor to deliver all transformers free from mechanical or electrical damage and/or damage to the paint system. 8. ANSI Z535 SAFETY SIGNS Clark Public Utilities will provide its own custom danger and warning signs which will be placed on the transformers in the Clark Public Utilities warehouse once they are received. The transformer manufacturer does not need to provide these signs. Page 5 of 7

9. MAXIMUM LOSSES Losses shall not exceed the values shown on the following table. No-load (core) and load (copper) losses shall be independent of each other. No combining or averaging is acceptable. 1Ø Padmount Transformer Maximum Losses kva No-load (watts)* Load (watts)* 25 80 245 50 115 495 75 174 600 100 149 1045 Note: All loss values are based upon the maximum values from bid data for 1990 through 2005. * No-load losses calculated at 20 C and load losses at 85 C CPU does not specify efficiencies. It is expected that the transformer manufacturer will meet whatever the current DOE efficiencies are without exceeding the maximum losses as outlined in this section. 9.1 Transformers Purchased by Contractors Certified loss data on all transformers will be required from contractors during the installation inspection for review and approval before the facility will be accepted and energized. Transformers which exceed maximum losses for each kva as outlined in the table above will be subject to loss dollar penalties on losses over the maximum. Cost of losses will be $4,277/kW no-load (core) and $2,007/kW load (copper) for 1Ø units. 9.2 Transformers Purchased by Clark Public Utilities Clark Public Utilities will evaluate losses on all bids and quotes. However, all designs must not exceed the maximum losses in the table above. Certified loss data on all transformers will be required for each shipment of transformers. Transformers which exceed the design losses quoted will be subject to loss dollar penalties. Cost of losses will be $4,277/kW no-load (core) and $2,007/kW load (copper) for 1Ø units. Page 6 of 7

BID DATA SHEET PADMOUNT TRANSFORMER SINGLE-PHASE Distributor Date Manufacturer Manufacturing Plant Location Clark Stock Code Number Bid Number KVA High Voltage (ANSI Desig.) KV Low Voltage (ANSI Desig.) Volts High Voltage Taps AN BN Impedance Voltage % Maximum L.V. Short Circuit Current KA Maximum L.V. Short Circuit Current is at L-L or L-N Short Circuit Impedance % Total Weight Pounds Dimensions Height inches Width inches Depth inches Oil Gallons H.V. Winding Metal L.V. Winding Metal Core Metal, Type (Grain oriented, only) Minimum Paint Thickness (Tank) Mils No-load losses watts Load losses watts Total losses watts Efficiency Rating (Informational only) % Minimum bottom and lower side coating (corrosion resistance) describe below: A separate Bid Data Sheet must be completed for each KVA size and voltage rating. This form must be completely filled in and included with all bid submittals at the time bids are due. Bid submittals without the Bid Data Sheet will be deemed non-responsive and will not be evaluated for award. Only Clark s Bid Data Sheets will be acceptable. Page 7 of 7