Innovating Continuous Exterior Insulation. Theresa A. Weston, PhD. 1

Similar documents
Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure

Thermal Bridging in Residential Construction

Integrated Air & Water Barrier Systems

How do you install yours?

Low-cost Construction for High-energy Savings. Brian J. Wimmer Construction Manager Rochester Area Habitat for Humanity

Advanced technologies for enhancing the building envelope. 3M Building and Construction Market

Air Barrier Requirements for Low-Slope Roof Assemblies Myths vs. Facts

Moisture Considerations for Insulated Building Assemblies

Building Enclosure Performance for Existing and New Buildings

Smart Vapor Retarders

NEXT GENERATION HIGH PERFORMANCE WALLS

HPW Protocol Reference Manual

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide.

breathability to prevent the potential for moisture condensation within exterior walls...

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition

The Role of Control Layers in Building Enclosure Design

2013 COMMERCIAL PRODUCTS

ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;

Building Enclosure Details and Assemblies for Wood-Frame Buildings

2006 INTERNATIONAL ENERGY CONSERVATION CODE

Managing Rainwater at the Window-Wall Interface

How to Meet Code and Manage Moisture in an Environment of Increasing Air Tightness Requirements. Ted Winslow

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

When R-Value Doesn t Measure Up

Introducing TJ Insulated Structural Framing Components

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

(Project Location) (your firm's name)

Feature Zone IECC 2009 IECC

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

Defining Failures in Residential Construction

Rainscreen Gaps in Exterior Walls

Airspace R-Values. Educational Overview. Revised 12/6/2016

Why Control Heat flow? How to Control Heat Flow? Thermal Performance. Modes of heat transfer: Thermal Control: Insulation & Thermal Bridges

Alternate Means and Materials for Code Compliance

United States Army Corp of Engineers Requirements for Air Barrier Systems in Buildings

Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)

Building Science Fundamentals Thermal Control: Insulation & Thermal Bridges May 29-30, Straube buildingscience.com 1 of 24

Insulations, Sheathings and Vapor Retarders

The Role of Control Layers in Building Enclosure Design

Exterior Building Materials & Detailing

2010 National Building Code Adoption and Associated Process Changes

Introduction. Introduction. Designing Building Envelopes to Meet Sustainable and Aesthetic Goals Part 1

Building America Special Research Project: High-R Walls Case Study Analysis

AIR BARRIERS & WATER-RESISTIVE BARRIERS

2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building

Reduce Wall Condensation Potential with Insulated Sheathing TECH SOLUTIONS 214.0

building science.com Building Science Digest 106 Understanding Vapor Barriers (rev. April 2011) by Joseph Lstiburek Abstract:

Crawl Space Moisture Control

Insight. Stress Relief. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

Figures 1A-1C Light frame and mass wall systems with continuous insulation for codecompliant. commercial building construction.

Hygrothermal Modeling & Building Enclosure Design. Introduction

Throughout the balance of this paper the terms attic and roof will and can be used interchangeably.

Weather Resistant Barrier

CHANGES TO THE US ENERGY CODES COMMERCIAL & RESIDENTIAL

PIMA PERFORMANCE BULLETIN Foil-Faced Polyiso and Unfaced Mineral Wool Board in Commercial Wall Applications

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Insulating Exterior Assemblies : Batt, Blown / Spray, Board and Beyond

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont

Henry Blueskin VP160 Air Barrier System Installation Manual

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262

Learning Objectives 9/3/2013

INSULATION OWENS CORNING INSULATION PRODUCTS IN THIS SECTION:

Better Buildings. Performance. Fundamentals. The Rules

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Spray Polyurethane Foam: The Need for Vapor Retarders in Above-Grade Residential Walls

Michigan Energy Code Training and Implementation Program

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

Sealing the Envelope with SPF Insulation

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

Durability, Resilience and Energy Efficiency: Working Together to Make Sustainable Buildings

Insulation Technologies and Installation Specifications for Better Energy Performance of Commercial Buildings

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

FMA / AAMA / WDMA Installation Committee Update. Jim Katsaros / DuPont Building Innovations FMA Installation Committee April 24, 2012

1 Exam Prep Prov Module: Thermal and Moisture Protection Questions and Answers

Experimental Assessment of Hygrothermal Performance of Wood Frame Wall System in Suzhou's Lake Tai Climate Zone

Hardin County Planning and Development Commission

Continuous Insulation Systems for Exterior Walls

United States R E S I D E N T I A L. The Value of Residing With STYROFOAM Brand XPS Insulation

Armourwall Stucco Systems

Air Infiltration & Insulation

EIFS Performance Beyond Code Compliance

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

SINGLE FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

Building Enclosure Commissioning: Who, What, When, Why, and How?

FMA_AAMA_WDMA Installation Committee Update FMA Conference May 8, Naples, FL. Jim Katsaros FMA_AAMA_WDMA Installation Committee

WEB BASED APPLICATION SPECIFIC INSTALLATION INSTRUCTIONS

Changes to California s Building Code for Construction in Wildfire Prone Areas: Impact on Wood and Wood-based Materials

Inspection of New One- and Two- Family Dwellings

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

Vapour Diffusion for Residential Construction. Canada and Northern USA VAPOUR DIFFUSION FOR RESIDENTIAL CONSTRUCTION CANADA AND NORTHERN USA

Evaluating effectiveness of window/wall interface details to manage rainwater Selected Results from US Window Installation Practice

MULTI-FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

Chicago Roofing Contractors Association

PREP + INSULATION. DISCLAIMER: These tools are for illustrative purposes only and

Improve Energy Efficiency and Air Sealing in Above-Grade Walls

R-Value. Effective. Energy efficiency of masonry s thermal mass is recognized by code 9" 2" R21 + R18 THERMAL MASS +13 R13 R18

Transcription:

ABSTRACT Innovating Continuous Exterior Insulation Theresa A. Weston, PhD. 1 As the need to reduce energy usage and carbon consumption has increased, the need for energy efficient building envelopes has increased. The application of continuous exterior insulation in frame construction is a key technology to achieving an energy efficient building envelope. Continuous exterior insulation includes a variety of products, including insulating sheathing and insulated claddings and while these products have long been available, recent advances in the energy codes have spurred innovation in products and application techniques. This paper reviews the benefits of exterior continuous insulation, including the increase in wall effective R- value, reduction of thermal bridging, and reduction of potential for vapor condensation. The challenges of integrating exterior insulation into a wall system, including the complications of interfaces with other building components and the reduction in wall drying potential and water management will also be reviewed. Finally, this paper will describe recently introduced continuous insulation products and explore how they meet these challenges. INTRODUCTION Energy codes and certification have increased the interest in increasing the insulation level of opaque building envelope assemblies and spurred the development of new insulation materials and systems. One key building block in the design of energy efficient wall systems is incorporating exterior continuous insulation. Polystyrene and poly-isocyanurate foam boards have traditionally been used to provide continuous insulation, but because of their low vapor permeability they can present challenges to water management of wall systems. Integration with other building components such as windows and siding can also be an issue. As the drive to become more energy efficient increases, new insulation products have been brought to the market to address some of the deficiencies in the traditional products. ENERGY CODE EVOLUTION The challenges of diminishing resources and the need to reduce global climate change have led to an increased desire for energy efficiency. When residential and commercial occupancies are combined, the building sector comprises about 41% of the U.S. Energy consumption [U. S. Department of Energy]. 1 Senior Research Fellow, DuPont Building Innovations, 5401 Jefferson Davis Highway, Richmond, VA 23234, 804-241-6426, theresa.a.weston@dupont.com 114

% US Energy Usage 30% 22% 29% 19% Transportation Commercial Buildings Residential Buildings Industrial Figure 1. U. S. Energy Usage by Sector Early energy efficiency gains had been made through utility and green building programs, most notably through the EPA's Energy Star for New Homes Program. Over the last 5 to 10 years, energy codes have picked up momentum, following the U.S. Federal government s setting of goals for improvements in both the residential and commercial energy codes. The actual energy efficiency determinations for residential energy codes versus the federal goal are shown in Table 1. Table 1. Energy Code Determinations vs. Federal Goals US DOE Goal Improvement US DOE Actual Determination IECC 2006 IECC 2009 IECC 2012 IECC 2015 Baseline 17% 30% 50% Baseline 14% 32% 34% Key components in the advancement of the energy codes, have been an increase in the insulation required in opaque wall assemblies and more stringent air leakage requirements. As an example, the increase in R-value requirements in the Residential wood frame wall prescriptive path is shown in Table 2. [ICC 2006, ICC 2009, ICC 2012, ICC 2015-2] The increase in overall minimum R-values, as well as the increase in continuous insulation use, is evident. 115

Table 2. IECC Residential Wood Frame Wall R-value Requirements CLIMATE ZONE 2006 IECC 2009 IECC 2012 & 2015 IECC 1 13 13 13 2 13 13 13 3 13 13 20 or 13+5 4 X-MARINE 13 13 20 or 13+5 4 MARINE 19 or 13+5 20 or 13+5 20 or 13+5 5 19 or 13+5 20 or 13+5 20 or 13+5 6 19 or 13+5 20 or 13+5 20+5 or 13+10 7 21 21 20+5 or 13+10 8 21 21 20+5 or 13+10 The development of residential air leakage requirements in the IECC provisions is shown in Figure 2. In 2006, air leakage requirements were vague and difficult to demonstrate compliance and enforce. In 2009, methods of demonstrating compliance were detailed with options for visual inspection or whole-building air leakage testing. The whole-building air leakage maximum at 7 ACH 50, was quite modest. In 2012 and upheld in 2015 was mandatory visual inspection and whole-building air leakage testing. The wholebuilding leakage maximum was reduced to much more challenging 5 ACH 50 in climate zones 1 and 2, and 3 ACH 50 in climate zones 3 through 8. Air leakage reduction is not only important to meet code, but it also improves the performance of insulation. The standard test method to determine R-value is conducted with no air pressure difference across the sample. In real conditions, air pressures differences from wind, mechanical systems or stack pressure can induce airflow through the insulation, resulting in reduced effective R-value. As shown in Figure 3, testing of thermal performance of wall assemblies with and without air flow demonstrates effective R-value can be reduced by more than 50% under low to moderate wind loads, especially when an air barrier is included in the wall system [Jones, 1995]. 116

Qualitative requirement and location li t Compliance options: Checklist or Testing 7 ACH Qualitative requirement and location li t Compliance e options: Checklist and Testing Z1,2: < 5ACH 50 5ACH 50 Z3-8:: < 3ACH 50 2006 2009 2012 & 2015 Figure 2. IECC Residential Air Leakage Requirements 117

Figure 3. Wall Assembly Effective R-value as a Function of Simulated Wind Load INSULATION DEVELOPMENT CRITERIA Analysis of the energy code evolution showed that there was opportunity for new product development in insulation products. Key desired attributes include: Insulating performance: impact increased with continuous insulation performance Air barrier performance: provide a continuous and durable air barrier for the wall system which can be integrated with other building envelope assemblies Water management performance: include both the ability to be detailed and perform as a water-resistive barrier and providing forgiveness (drying) in the event of incidental water entry. Each of these performance requirements is described in more detail in the following sections. Insulating Performance: Benefits of Continuous Insulation. The primary benefit of continuous insulation is the reduction in thermal bridging at the studs leading to a more uniform and higher thermal resistance for the wall system. The results can easily be seen when houses with and without exterior insulation are compared using infrared (IR) photography as can be seen 118

in Figures 4 and 5. These figures show two houses in the Columbus, OH region. The only difference in the wall system design is the inclusion of continuous exterior insulation in the house in Figure 5. Thermal bridging reduces the overall R-value of the wall system, as is quantified in the calculations shown in Table 3. An additional benefit of exterior continuous insulation is the warming of the interior sheathing surface. This surface is a potential plane of winter-time condensation if vapor intrudes past the interior vapor/air barrier. Its warming reduces the potential for water condensing within the wall assembly. Because of the various benefits provided by exterior continuous insulation, it should be a focus of product innovation. 119

Figure 4. IR Photography of house in Columbus, OH with no exterior insulation. Figure 5. IR Photography of house in Columbus, OH with exterior continuous insulation. 120

Table 3. Total Calculated Wall R-value for Different Wall Assemblies Wall Assembly Component Studs Cavity Studs Cavity Studs Cavity Outside Air Film 0.17 0.17 0.17 0.17 0.17 0.17 Exterior Insulation n/a n/a n/a n/a 5 5 ½ OSB 0.62 0.62 0.62 0.62 0.62 0.62 Stud Wood 3.71 n/a 5.83 n/a 3.71 n/a Cavity Insulation ½ Gypsum Wallboard 2x4 2x6 2x4 + c.i. n/a 13 n/a 20 n/a 13 0.45 0.45 0.45 0.45 0.45 0.45 Interior Air Film 0.68 0.68 0.68 0.68 0.68 0.68 Total 5.6 14.9 7.75 21.9 10.6 19.9 Total Wall (Standard Framing - 23%) Total Wall (Advanced Framing 17%) 10.8 15.4 16.6 16.7 Air Barrier Performance. Many materials have been used to reduce air leakage in buildings. For residential wall systems, the most common air barrier material is a continuous sheet material, sometimes referred to as a house wrap, which is detailed as an air barrier at interfaces and connections. Performance of house wraps to provide air leakage protection was reviewed in 2006 [Weston, 2006]. This study concluded that Significant research has been conducted to characterize the performance of house wrap materials and their ability to control air leakage in residential construction. The research clearly shows that house wraps if installed correctly can 121

significantly reduce air leakage and provide the associated energy savings. The performance of house wraps to control air leakage was also documented in a field study on a high performance home showed that with correct detailing and installation a house wrap can provide the air barrier performance sufficient to meet the 2012 and 2015 air leakage requirements [Oberg, 2011]. Taping the seams of board products has been proposed to provide air barrier performance. However, taping of board products, such as foam sheathing, may not provide a durable air barrier. Figure 6 shows the results of air leakage testing of taped foam board and typical house wrap wall assemblies. Both assemblies were tested as built and after thermal cycling. While both assemblies met assembly air barrier requirements as-built, after thermal cycling the foam sheathing wall exhibited air leakage in excess of the maximum allowable air leakage while the house wrap wall continued to meet requirements. The data can indicate that exterior insulation wall assembly innovation should focus on insulation systems that either include a separate air barrier layer, or incorporate an air barrier layer that be integrated to provide air barrier continuity as part of the insulation product. Figure 6. Air Leakage of Wall Assemblies As-Built and after Thermal Cycling Water Management Performance. To manage water properly, a wall system must not only resist wetting it must also allow drying if there is any incidental moisture entry. The building code requirements focus on four areas of water management of wall assemblies: Flashing at intersections Water-resistive barrier 122

Means of draining water Protection against condensation The first three items deal with prevention of bulk water intrusion, such as from precipitation. Protection against condensation will be increased to some extent by any exterior insulation because the warming of the exterior sheathing surface and will be increased by air barrier incorporation. Performance of a water-resistive barrier is dependent on both material and installation. The International Residential Code provides the basic requirements for both materials and installation [ICC 2015-3]: One layer of No. 15 asphalt felt, free from holes and breaks, complying with ASTM D226 for Type 1 felt or other approved water-resistive barrier shall be applied over studs or sheathing of all exterior walls. Such felt or material shall be applied horizontally, with the upper layer lapped over the lower layer not less than 2 inches (51 mm). Where joints occur, felt shall be lapped not less than 6 inches (152 mm). The felt or other approved material shall be continuous to the top of walls and terminated at penetrations and building appendages in a manner to meet the requirements of the exterior wall envelope as described in Section R703.1. The requirements invoke shingling as a traditional method of water management. Taped board products have been proposed to perform as a water-resistive barrier. These systems do not utilize shingling to allow water to drain off the assembly, but rely on the tape adhesion to prevent water entry. The tape joint is very dependent on installation conditions to perform. For examples, poor adhesion can result if the substrate surface is cold, wet, or dirty during installation. Additionally, for board products that have significant thermal expansion and contraction, the tape joint will be stressed as the assembly is subjected to normal temperature cycles. This has been noted in past studies, With some question as to the long term dimensional stability of insulating sheathing products, this should only be used in areas with limited rainfall and exposure, where rain water management is not as critical [Baker, 2006]. To examine the performance of taped seams of foam sheathing for water intrusion, wall assemblies were tested before and after thermal cycling using ASTM E331 [ASTM, 2009]. Figure 7 shows water (dyed red) has intruded at taped foam-board interfaces. To best prevent water intrusion, an exterior continuous insulation product would need to be flexible enough to be installed and integrated with flashings in shingled manner or to be installed with a separate water resistive barrier. For wall systems involving rigid board exterior insulation a separate water-resistive barrier is advisable. 123

Figure 7. Wall Specimen after Testing with E331 showing water intrusion at foam insulation board taped seams. The second key to good water management is to allow for drying. The ability for a wall to dry will help provide for durability whether the source is bulk water, condensation from air leakage or vapor diffusion, or built-in construction moisture. The codes require interior vapor retarders in cold climates to reduce winter-time moisture condensation. Problems may occur, however, if exterior insulation has low vapor permeability. In this case, there is restricted drying at both the exterior and interior boundaries of the wall assembly. In a modeling study of different wall assemblies subjected to small amounts to water intrusion concluded that this wall assembly condition was at increased risk of moisture accumulation [Weston 2012]. Figure 8 shows the results of 3-year moisture simulations in Minneapolis climate zone with either no water intrusion, or with intrusion of 1% of the water that impacts the exterior wall surface. The results compare walls with exterior foam sheathing (vapor retarder) with walls with a vapor permeable exterior insulation. Both walls had kraft paper vapor retarder to meet the minimum code requirement. The results show year-over-year accumulation in wall total water content in the wall with foam sheathing, while the vapor permeable exterior insulation was able to manage the water intrusion with no total water content accumulation. These results indicate that a vapor permeable exterior insulation would be preferred to effectively manage water. 124

The need for a vapor open exterior insulation has begun to be included in code provisions. In 2015, the International Building Code included restrictions on interior vapor retarders when walls incorporate vapor impermeable exterior insulation: [ICC 2015-1] 1405.3.12 Class III vapor retarders. Only Class III vapor retarders shall be used on the interior side of frame walls where foam plastic insulating sheathing with perm rating of less than 1 perm is applied in accordance with Table 1405.3.1 on the exterior side of the frame wall. Simulation: Minneapolis Total Wall Water Content vs. Time No Bulk Water Intrusion 1% Bulk Water Defect Exterior Foam Sheathing Vapor Permeable Exterior insulation Figure 8. Moisture Simulations indicating higher moisture accumulation risk with both exterior and interior vapor barriers. 125

PRODUCT DEVELOPMENT RECOMMENDATIONS Weighing the factors of thermal performance, air leakage reduction and water management, an insulation product was developed. It was a 1 ¼ polymer fibrous batt that was faced with vapor permeable air and water-resistive barrier sheet. The product is provided in roll form with flaps of the facing that can be used to shingle over previously installed layers. This is just one possible insulation solution. Many other products of systems could be designed. The criteria described in this paper is a starting point but the choice of specific solution need to respond to constructability and cost concerns of a specific project. Constructability concerns include: Safety & ergonomics during the construction process Job-site storage requirements Installation dependence on environmental conditions Ease of installation o Is the new system installed in a similar way to existing products? o Can it be installed by existing trades? o Does it require a high level of specialization to install? Reliability & repeatability of the installation. Integration with other products (Can the next group of laborers work easily on top of it?) Finally cost assessment should not be confined to first material cost. Also included should be costs of implementing a new product including costs associated with design changes and required contractor training or re-training. Installation costs should include any required environmental conditions required by the system and any adaptation needed by adjacent components. Finally, the costs associated with call-backs and long term moisture intrusion should be assessed. SUMMARY AND CONCLUSIONS The increasing stringency in energy and building codes is stirring interest in innovation of insulating products and systems. Product innovation should not focus on the single attribute of material R-value, but should evaluate durability and insulation effectiveness of the entire wall system. Water resistance concerns in existing systems were discussed. Product development recommendations include energy efficiency performance, moisture management performance and constructability of the system. REFERENCES ASTM (2009), E331-00(2009) Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure 126

Difference, ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959 Baker, Peter (2006), Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure, ACEEE Summer Study on Energy Efficiency in Buildings, August 2006. ICC (2006), International Energy Conservation Code, International Code Council, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFE (422-7233). ICC (2009), International Energy Conservation Code, International Code Council, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFE (422-7233). ICC (2012), International Energy Conservation Code, International Code Council, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFE (422-7233). ICC (2015-1), International Building Code, International Code Council, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFE (422-7233). ICC (2015-2), International Energy Conservation Code, International Code Council, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFE (422-7233). ICC (2015-3), International Residential Code, International Code Council, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFE (422-7233). Jones, David C. (1995). Impact of Airflow on the Thermal Performance of Various Residential Wall Systems Utilizing a Calibrated Hot Box. Thermal Performance of the Exterior Envelopes of Buildings VI. December. Oberg, B, Energy Efficiency Lab Home: Case Study, EEBA Conference, September 2011 U. S. Department of Energy (2011), Buildings Energy Data Book, http://buildingsdatabook.eren.doe.gov/databooks.aspx Weston, T. A. (2006). A Review of Housewrap Performance and Its Implications for Energy Savings, Proceedings of ACEEE Summer Study Conference, Asilomar, CA, August, 2006. Weston, T. A. (2013), Using Hygrothermal Simulation to Assess Risk of Water Accumulation from Wall Assembly Defects, Presented at ASTM Symposium on Building Walls Subject to Water Intrusion and Accumulation: Lessons from the Past and Recommendations for the Future, Indianapolis, IN, April 2013 127