EFFECT OF FLUID VISCOUS DAMPERS IN MULTI-STOREYED BUILDINGS

Similar documents
EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

Seismic Response Control of the Building using Passive Devices

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

ENHANCED SEISMIC RESISTANCE OF STEEL BUILDINGS USING VISCOUS FLUID DAMPERS

A DIRECT METHOD FOR THE DESIGN OF VISCOUS DAMPERS TO BE INSERTED IN EXISTING BUILDINGS

SEISMIC RESPONSE CONTROL OF ASYMMETRIC BUILDING USING VISCO-ELASTIC DAMPER

OPTIMUM POSITION OF OUTRIGGER SYSTEM FOR HIGH RAISED RC BUILDINGS USING ETABS (PUSH OVER ANALYSIS)

Static Analysis of Multistoreyed RC Buildings By Using Pushover Methodology

Parametric Study of Dual Structural System using NLTH Analysis Ismaeel Mohammed 1 S. M. Hashmi 2

MULTI-LEVEL FORTIFICATION INTENSITIES SEISMIC PERFORMANCE ASSESSMENT FOR REINFORCED CONCRETE FRAME- SHEAR WALL STRUCTURE WITH VISCOUS DAMPERS

Performance Based Seismic Design of Reinforced Concrete Building

Seismic Vibration Control of a MDOF Building Connected with Viscous and SAVFD Dampers

Nonlinear Pushover Analysis of Steel Frame Structure Dahal, Purna P., Graduate Student Southern Illinois University, Carbondale

[Mohammed* et al., 5(8): August, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

NONLINEAR STATIC ANALYSIS OF R.C.C. FRAMES (Software Implementation ETABS 9.7)

Shake table test a structure retrofitted using 2-4 Direction Displacement Dependent (D3) viscous dampers

PUSHOVER ANALYSIS FOR THE RC STRUCTURES WITH DIFFERENT ECCENTRICITY

OPTIMUM INSTALLATION OF VISCOUS LIQUID DAMPERS IN HIGH-RISE BUILDINGS

Comparative Study of the Static and Dynamic Analysis of Multi-Storey Irregular Building

EARTHQUAKE ANALYSIS OF A G+12 STOREY BUILDING WITH AND WITHOUT INFILL FOR BHUJ AND KOYNA EARTHQUAKE FUNCTIONS

ON DRIFT LIMITS ASSOCIATED WITH DIFFERENT DAMAGE LEVELS. Ahmed GHOBARAH 1 ABSTRACT

Seismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada

Comparative Study on Concentric Steel Braced Frame Structure due to Effect of Aspect Ratio using Pushover Analysis

Comparative analysis betweenstatic and Non Linear Dynamic analysis of irregular and regular building

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

Seismic Assessment of an RC Building Using Pushover Analysis

PERFORMANCE BASED SEISMIC EVALUATION OF MULTI-STOREYED REINFORCED CONCRETE BUILDINGS USING PUSHOVER ANALYSIS

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Seismic Base Isolation of RC Frame Structures With and Without Infill

THE USE OF FRICTION DAMPERS FOR SESIMIC RETROFIT OF THE MONTEREY COUNTY GOVERNMENT CENTER

ANALYTICAL INVESTIGATION ON THE PERFORMANCE OF TUBE-IN-TUBE STRUCTURES SUBJECTED TO LATERAL LOADS

COMPARISON BETWEEN TWO OPTIMIZATION PROCEDURES FOR DAMPER LOCATION IN STEEL FRAME STRUCTURES

PERFORMANCE- BASED SEISMIC DESIGN OF A BUILDING

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

Application of Pushover Analysis for Evaluating Seismic Performance of RC Building

NONLINEAR PERFORMANCE OF A TEN-STORY REINFORCED CONCRETE SPECIAL MOMENT RESISTING FRAME (SMRF)

Earthquake Analysis of Tall Building with Tuned Mass Damper.

Dynamic Time History Analysis of Plane Frame with Tuned Mass Considering Soil-Structure Interaction

Seismic Analysis and Design of Vertically Irregular RC Building Frames

SEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL

TO STUDY THE PERFORMANCE OF HIGH-RISE BUILDING UNDER LATERAL LOAD WITH BARE FRAME AND SHEAR WALL WITH OPENINGS

Available at ISSN

Effect of soft storey on multistoried reinforced concrete building frame

Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower

HYBRID MOMENT RESISTING STEEL FRAMES

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

COMPARISON BETWEEN THE DIRECT DISPLACEMENT BASED DESIGN AND THE FORCE BASED DESIGN METHODS IN REINFORCED CONCRETE FRAMED STRUCTURES

Effectiveness of Base Isolation Technique and Influence of Isolator Characteristics on Response of a Base Isolated Building

Seismic Vibration Control of Building with Lead Rubber Bearing Isolator

EQUIVALENT UNIFORM DAMPING RATIOS for Irregular in Height Concrete / Steel Structural systems

Yousef Zandi Member of Academic Staff, Department of Civil Engineering, Tabriz Branch, Islamic Azad University, Tabriz, Iran.

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

Nonlinear Static Pushover Analysis of a Shear Wall Building in Madinah

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

Analysis of G+12 Structures with different material of Shear wall using SAP2000

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

OPTIMUM DAMPING IN ISOLATION SYSTEM

SEISMIC EVALUATION OF BUILDINGS WITH POSTTENSIONED BEAMS BY NON-LINEAR STATIC ANALYSIS

This point intends to acquaint the reader with some of the basic concepts of the earthquake engineer:

Seismic Analysis of Steel Frames with Different Bracings using ETSBS Software.

Displacement Based Damage Estimation of RC Bare Frame Subjected to Earthquake Loads: A Case Study on 4 Storey Building

International Journal of Engineering Research And Management (IJERM) ISSN: , Volume-03, Issue-11, November 2016

How to protect buildings against the disastrous effects of earthquakes?

Pushover analysis of RC frame structure using ETABS 9.7.1

Study on Beam-to-Column Connection with Viscoelastic Hysteretic Dampers for Seismic Damage Control

Effect of Concentric Braces on the Behaviour of Steel Structure by Pushover Analysis

Prediction of Initial Column Size for Reinforced Concrete Frame Buildings with Intermediate Drift

Parametric Studies on Tuned Liquid Damper by Horizontal Shake Table Experiments

SEISMIC ANALYSIS OF SIX STOREYED RC FRAMED BUILDING WITH BRACING SYSTEMS

SEISMIC EVALUATION OF RC MULTISTOREY BUILDING OF ASYMMETRIC PLAN WITH VISCO-ELASTIC DAMPER

Seismic performance assessment of reinforced concrete buildings using pushover analysis

PERIODS OF REINFORCED CONCRETE FRAMES DURING NONLINEAR EARTHQUAKE RESPONSE

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 09, 2014 ISSN (online):

Evaluation of Earthquake Risk Buildings with Masonry Infill Panels

Concept of Earthquake Resistant Design

SSRG International Journal of Civil Engineering (SSRG-IJCE) volume 4 Issue 7 July 2017

Effects Of Vertical Geometric And Mass Irregularities In Structure

Investigation for Base Shear and Roof Displacement for Multi-Storey Building with Different Location of Shear Wall Using STAAD Pro

Seismic Behavior of Soft First Storey

Comparative study of Performance of RCC Multi-Storey Building for Koyna and Bhuj Earthquakes

PUSHOVER ANALYSIS OF A 19 STORY CONCRETE SHEAR WALL BUILDING

SEISMIC BEHAVIOR OF MULTI-STORY STRUCTURE WITH DIFFERENT TYPES OF SLABS

SEISMIC ANALYSIS OF SYMMETRIC BUILDING WITH BASE ISOLATION TECHNIQUE

MID-STORY SEISMIC ISOLATION FOR STRENGTHENING OF A MULTI-STORY BUILDING

Violating Capacity Design in Structures with Viscous Damping and Hysteretic Damping

COMPARATIVE STUDY ON SEISMIC BEHAVIOR OF SPECIAL CONCENTRIC BRACED FRAMES WITH ECCENTRIC BRACED FRAMES

STUDIES ON LOCATION OF SHEAR WALL IN BUILDINGS FOR STRUCTURAL STABILITY

Stability Analysis of Rigid Steel Frames With and Without Bracing Systems under the Effect of Seismic and Wind Loads

Base Isolation In Seismic Structural Design

COMPARISON OF PERFOMANCE OF THIN STEEL SHEAR WALLS AND CONCENTRIC BRACES BY CAPACITY SPECTRUM METHOD

Study of TMD-controlled Reinforced Concrete Framed Structure under Code-based Artificial Earthquake

DESIGN AND COMPARISON OF A RESIDENTIAL BUILDING (G+10) FOR SEISMIC FORCES USING THE CODES: IS1893, EURO CODE8, ASCE 7-10 AND BRITISH CODE

SEISMIC ANALYSIS ON MEZZANINE FLOORING SYSTEM

STUDY ON LAMINATED RUBBER BEARING BASE ISOLATORS FOR SEISMIC PROTECTION OF STRUCTURES

Floor Slab Isolation for Mitigating the Seismic Response of Building Systems

Chinmoy Kolay Research Engineer

RESPONSE STUDY OF MULTI-STORIED BUILDINGS WITH PLAN IRREGULARITY SUBJECTED TO EARTHQUAKE AND WIND LOADS USING LINEAR STATIC ANALYSIS

Moment Resistant Frames vs. Braced Frames -Steel Consumption Assessment and Structural Analysis Parameters

Non-Linear Static Analysis of RCC Frames

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 10, 2016 ISSN (online):

Transcription:

IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN(E): 2321-8843; ISSN(P): 2347-4599 Vol. 2, Issue 9, Sep 2014, 59-64 Impact Journals EFFECT OF FLUID VISCOUS DAMPERS IN MULTI-STOREYED BUILDINGS LIYA MATHEW 1 & C. PRABHA 2 1 Post Graduate Student, Department of Civil, Mar Athanasius College of Engineering, Kothamangalam, Kerala, India 2 Assistant Professor, Department of Civil, Mar Athanasius College of Engineering, Kothamangalam, Kerala, India ABSTRACT Buildings are subjected to various loading conditions. Special protective systems have been developed to enhance safety and reduce damage of structures during earthquakes. Fluid viscous damper (FVD) comes into prominence here. This paper deals with the study of reinforced concrete buildings with and without fluid viscous dampers. A parametric study for finding optimum damper properties for the reinforced concrete frames was conducted. Nonlinear time history analysis is done on a symmetrical square building. Analysis is carried out using SAP2000 software and comparisons are shown in graphical format. KEYWORDS: Fluid Viscous Damper, Pushover Analysis, Symmetrical Building, Time History Analysis INTRODUCTION Building design usually involves proportioning the elements of the structure such that the constraints on strength and serviceability limit states are satisfied. The conventional approach is to proportion the components to satisfy the strength limit states and then follow it up with serviceability checks. But based on the modern control theory, structural control has emerged to mitigate the negative effects that the external disturbances impose on the structures. Structural control has been investigated and shown great potential for reducing vibrations in various civil structures under dynamic loading. Structural control is usually classified by its method, or the type of device used to impart the control force. The three classes of structural control system are passive energy dissipation, active and semi-active energy dissipation. The first class of energy dissipating system, the passive systems are uncontrollable. The basic function of the passive devices is to absorb a part of input energy, reducing energy dissipation on structural members and minimizing the damage on structures. Contrary to semi-active or active systems there is no need of external power supply. The second class of energy dissipating devices, the active devices are controllable and require significant amount of external supply. The third class includes the semi-active devices which combine the aspects of active and passive devices. Passive devices are frequently used type of control system implemented because they involve no external power and such devices are inherently stable. Passive devices encompasses a range of materials and devices for enhancing damping and strength such as fluid viscous dampers, friction dampers and metallic dampers have been developed since the 1990 s. This papers deal with the study of fluid viscous damper on reinforced concrete buildings. GENERAL DESCRIPTION OF FLUID VISCOUS DAMPER Fluid viscous dampers in recent years have been incorporated into a large number of civil engineering structures. Impact Factor(JCC): 1.5548 - This article can be downloaded from www.impactjournals.us

60 Liya Mathew & C. Prabha The major parts of FVD are shown in Figure 1 [1]. When the fluid viscous damper is subjected to external loads, the piston rod with piston will make reciprocating motion in the cylinder to force the damping medium move back and forth between the two cavities separated by the piston. In the process, the friction force occurred between the molecules of the damping medium, the medium and the shaft and piston, the medium and the cylinder, and throttling damping force produced by the damping medium through the piston, all these action work together composed the damping force. These damping forces are 90 degrees out of phase with the displacement driven forces in the structure. This benefit can allow the reduction of shear walls, use of smaller columns and beams, use of smaller and less complicated foundations and overall reductions of concrete or steel mass, generally offsetting the cost of the fluid viscous dampers [1]. Figure 1: Fluid Viscous Damper The viscous dampers are modeled as Maxwell element, which is a nonlinear damper with a nonlinear spring. Viscous damper system will be modelled as pure stiffness-free damping behaviour. Stiffness of damper element is considered zero in order to reach the pure damping in linear analyses. To eliminate the spring effect, its stiffness should be considered significantly high in nonlinear analyses where series model of spring damper is used. The energy dissipation per cycle of FVD is a function of different parameters. The ideal damping force of viscous damper is given by, F = CV α (1) In (1), F is the damping force, C the damping coefficient, V the velocity of piston relative to cylinder and α is the damping exponent. MODELLING OF THE BUILDING Procedures have been developed through years for the seismic design of buildings equipped with fluid viscous dampers. The NEHRP (National Earthquake Hazards Reduction Program) [2] and other codes give a trial-and-error approach for identifying the mechanical characteristics of additional damping devices. A simple procedure for the determination of damping coefficient is been used in this study [3]. C = 2mξω (2) Equation (2) is used to find out the damping coefficient. In (2), m is the total floor mass is to be calculated by knowing the different dead loads acting on the structure, ξ is the damping coefficient and ω is the natural frequency of the structure. Modal analysis of the finite element model is done using SAP2000. From the modal analysis the time period T, is obtained. The natural frequency, ω of the structure can be calculate using, ω = 2π T (3) Index Copernicus Value: 3.0 - Articles can be sent to editor@impactjournals.us

Effect of Fluid Viscous Dampers in Multi-Storeyed Buildings 61 Knowing the value of ω and assuming a suitable value of damping ratio ξ, the damping coefficient is to be determined using (2). This value of damping coefficient C is used in the analysis of the structure in SAP2000. A six and ten storeyed square buildings have been considered for the analysis. Height of each storey is 3.0 m. It is considered to be located in the seismic zone V. Soil structure interaction has not been considered and the columns are fixed at a depth of 1.5 m below the ground level. The material properties of the building are assigned. Beam and column members have been defined as frame elements of dimension (200x300) mm. Slabs are defined as area elements having the properties of shell elements with the thickness of 150 mm. The building plan taken for the study is shown in Figure 2. Figure 2: Plan of 21x21 m Model After having modeled the structural components, the loads as per the codal provision are assigned. Gravity loads on the structure include the self weight of beams, columns, slabs and walls. The self weight of the beams and columns (frame members) and slabs (area sections) is automatically considered by the program itself. The wall loads have been calculated and assigned as uniformly distributed loads on the beams. Live loads have been assigned as uniform area loads on the slab elements as per IS: 875, (Part 2). Nonlinear time history analysis with El Centro accelerogram [3] has been carried out for determining various structural parameters of the model. The value of damping ratio ξ, and velocity exponent α is fixed by analyzing single bay square and rectangular building frames. From the different dynamic responses values of ξ and α are fixed as 0.2 and 0.5 respectively. The damping coefficient for 21x21 m plan buildings are calculated using (2). This study is concerned with the behavior of the structure under the bidirectional ground motion with and without the presence of FVD at different positions. PARAMETRIC STUDY Analysis is done to evaluate the performance of buildings under bidirectional seismic loading with and without FVD at different locations along the width and height of the building. To study the effect of placement of FVD along the width, six storey square plan building are taken into consideration and nonlinear time history analysis is carried out for structural models with and without FVD. To assess the effectiveness of placement of FVD along the height study is being done on symmetric square plan building of six and ten storey. Effect of FVD along the Width To study the effect of FVD along the height, analysis was done on 49x35 m six storied and ten storied buildings. From the previous section, it was concluded that, for rectangular plan case RTEC i.e., FVD on all the external corners was Impact Factor(JCC): 1.5548 - This article can be downloaded from www.impactjournals.us

62 Liya Mathew & C. Prabha found to be the most effective. The different cases that are taken into consideration to understand the effectiveness along the height are, (a) SQEM (b) SQEC Figure 3: Position of FVD in Square Plan (21x21 m) The different cases (Figure 3) which were considered for the square plan were, SQEM: FVD are placed in all the exterior middle bays. A total of 4 FVD will be there in each floor. SQEC: FVD are placed in all the exterior corners. A total of 8 FVD will be there in each floor. (a) Floor Displacement vs No. of Storey (b) Storey Drift vs No. of Storey (c) Floor Velocity vs No. of Storey (d) Base Shear Figure 4: Floor Responses for Square Plan Analysis results of the square plan with three different cases of damper position when subjected to bidirectional earthquake are obtained. From the analysis results it can be inferred that the percentage reduction in the peak displacement with respect to the bare frame is obtained to be 74% in all the three cases. From Figure 4 it can be inferred that the storey drift is maximum at the lower stories and it gradually decreases with the height. It was found out that the percentage reduction in base shear with respect to the bare frame for SQEM was 40% and for SQEC was 51%. From the floor responses of square plan it can be inferred that the percentage reduction in the base shear, interstorey drift and floor velocity is maximum in case SQEC. Thus for a square plan the most effective distribution of FVD is obtained as SQEC from the dynamic responses. Index Copernicus Value: 3.0 - Articles can be sent to editor@impactjournals.us

Effect of Fluid Viscous Dampers in Multi-Storeyed Buildings 63 Effect of FVD along the Height To study the effect of FVD along the height, analysis was done on square plans of six and ten storey s. From the previous section, it was concluded that, for the square plan case SQEC i.e., FVD on external corners was found to be the most effective. To understand the effect of FVD along the height, the above case was used for the further study. The different cases that are taken into consideration to understand the effectiveness along the height are FVD distributed uniformly FVD on alternative floors FVD on 1 st three floor (a) G+5 Storey (b) G+9 Storey Figure 5: Peak Displacement vs No. of Storey for Square Plan (21x21 m) Figure 5 shows the plot of peak displacement against the number of storey for the square plan for different cases. For the square plan with six storey building, the percentage reduction with respect to the bare frame in the displacement when FVD were placed uniformly on all floors, on alternative floors and 1 st three floors along the height was obtained as 74%, 71% and 78% respectively. For the same square plan with G+9 storey, the percentage reduction with respect to the bare frames in the displacement when FVD were placed uniformly, on alternative floors and 1 st three floors along the height was obtained as 65%, 58% and 52% respectively. (a) G+5 Storey (b) G+9 Storey Figure 6: Floor Velocity vs No. of Storey for Square Plan (21x21 m) For the square plan the floor velocities were plotted against the number of storey as shown in Figure 6. For the square plan with G+5 storey building, the percentage reduction with respect to bare frames in the velocity when FVD were placed uniformly, on alternative floors and 1 st three floors along the height was obtained as 71%, 62% and 57% respectively. For the G+9 storey building, the percentage reduction with respect to bare frames in the velocity when FVD were placed uniformly, on alternative floors and 1 st three floors along the height was obtained as 87%, 82% and 78% Impact Factor(JCC): 1.5548 - This article can be downloaded from www.impactjournals.us

64 Liya Mathew & C. Prabha respectively. (a) G+5 Storey (b) G+9 Storey Figure 7: Base Shear vs No. of Storey for Square Plan (21x21 m) The plot of base shear against the number of storey for the square plan is shown in Figure 7. For G+5 storey building, the percentage reduction with respect to bare frame in the base shear when FVD were placed uniformly, on alternative floors and 1 st three floors along the height was obtained as 51%, 48% and 51% respectively. For the G+9 storey building, the percentage reduction with respect to bare frame in the base shear when FVD were placed uniformly, on alternative floors and 1 st three floors along the height was obtained as 93%, 91% and 88% respectively. CONCLUSIONS The purpose of this study is to assess the seismic performance of buildings with fluid viscous dampers. Using nonlinear dynamic analysis, responses of structures have been evaluated and the following conclusions have been made. For maximum effectiveness in reducing the dynamic responses, a structure with FVD should be designed for damping ratio of 20% and the velocity exponent, α of the FVD as 0.5. Effectiveness of FVD along the Width From the dynamic floor responses of the buildings, it can be concluded that, placing FVD at the external corners on all four sides of the building is effective for square plans. Effectiveness of FVD along the Height The peak displacements and interstorey drifts are minimized most effectively by placing the FVD along the first three floors alone. But while considering the other dynamic responses such as the floor velocity and floor acceleration, placement of FVD all throughout the height is found to be effective. REFERENCES 1. Constantinou M. C, Soong T. T, Dargush G. F, (1995) Passive energy dissipation systems for structural design and retrofit. 2. FEMA 273/274 - Federal Emergency management Agency, (1997) NEHRP guidelines for the seismic rehabilitation of buildings, Report No. 273/274, Building Seismic Safety Council, Washington, D.C. 3. Stefano Silvestri, Giada Gasparini, Tomaso Trombetti, (2012) A Five-Step Procedure for the Dimensioning of Viscous Dampers to Be Inserted in Building Structures, Journal of Earthquake Engineering, 14: 417 447. Index Copernicus Value: 3.0 - Articles can be sent to editor@impactjournals.us