THERMAL STRATIFICATION PERFORMANCE OF UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEMS

Similar documents
DISPLACEMENT VENTILATION

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Underf loor For Schools

Evaluation of Underfloor Air Distribution

UNDERFLOOR DISTRIBUTION PRODUCTS UFAD

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Compliance to the IgCC. September 29, 2011

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

Italcementi Center for Research and Innovation

MEP's Letter of Assurance

Supply Fan Energy Use in Pressurized Underfloor Air Distribution Systems

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

MEP's Letter of Assurance

UC Berkeley HVAC Systems

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Assessment of Indoor Climate: Learning from Buildings

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

VENTILATION REQUIREMENTS TO PREVENT PIT AIR UP-DRAFTING IN

A Protocol to Determine the Performance of South Facing Double Glass Façade System

UC Berkeley Indoor Environmental Quality (IEQ)

Cost Benefits of SunGuard SN 54

Hourly Analysis Program v.4.1 Page 1 of 1

The optimization of the mechanical night cooling system in the office building

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

COMFORT-PRODUCTIVITY Building costs COMFORT-PERFORMANCE. Radiant Heating and Cooling Systems for Better Comfort and Energy Efficiency INDOOR - OUTDOOR

Comparative Analysis of Retrofit Window Film to Replacement with High Performance Windows

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION

While underfloor air. Learning objectives

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1

Air Conditioning Inspections for Buildings Assessing Equipment Sizing

Milwaukee, WI. Darron Rempel

HVAC Simulation Guidebook Volume. VolumeIII

Attached Solar Greenhouse Plans for a solar heated greenhouse attached to your home

Using the Whole-Building Design Approach to Incorporate Daylighting into a Retail Space

An experimental investigation of a passive chilled beam system in subtropical

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy

The Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2

The pros and cons of chilled beams

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

PRODUCTS DISPLACEMENT VENTILATION ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

McCarran International Airport Terminal 3

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment

White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD

Heat Transfer Analysis Collector

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY

In general, passive-solar components can be described by the U-value (heat loss coefficient) and

PDHengineer.com Course M-3020

Visible Ventilation: A Return to Passive Cooling

Green Building. Metrics. May 7, Mark Frankel

Michigan Energy Code Training and Implementation Program

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Sustainable Chilled Beam Design

5.0 Daylighting Analysis (Breathe Study)

Energy modeling in IDA ICE according to ASHRAE , app. G

Selecting Energy Efficient New Windows in Tennessee

Great Ocean Rd Ice Creamery

Selecting Energy Efficient New Windows in Nevada

AIRCOOL VENTILATORS FURTHER INFORMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

UC Berkeley HVAC Systems

Chapel House- Design Process- Envelope and Energy savings

Technical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis

BUILDING ENERGY EFFICIENCY CERTIFICATE

Selecting Energy Efficient Replacement Windows in Arizona

Selecting Energy Efficient New Windows in Illinois

BUILDING ENERGY EFFICIENCY CERTIFICATE

Development of New Self-Comparison Test Suites for EnergyPlus

Solar Hot Air Collectors. Rob Taisey Assured Solar Energy

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

ASHRAE 62.2: What s New in 2016

A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers

PRODUCT BROCHURE. Fixed Helical Swirl Diffuser HSC-FD HSC-FD : smartemp.com

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

When R-Value Doesn t Measure Up

Local Temperature Measurements on Full-Size Systems in the Laboratory: Insight into the Extent of Thermal Bridges in Building Envelope Components

Energy Efficiency / Renewable Energy (EE/RE) Projects in Texas Public Schools

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

A STUDY OF DAYLIGHTING TECHNIQUES AND THEIR ENERGY IMPLICATIONS USING A DESIGNER FRIENDLY SIMULATION SOFTWARE

Solar Flat Plate Thermal Collector

MEP Engineer's Letter of Assurance

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

EVALUATION OF THE THERMAL PERFORMANCE OF FIVE REFRIGERATED VANS

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

Designing Air-Distribution Systems To Maximize Comfort

DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE

LEED v4 Building Design and Construction Quiz #8 EQ

ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;

Introduction to Skylighting in equest Quick Energy Simulation Tool

Best Practice Recommendations for Wall Retrofit on the Two-Story Flexible Research Platform (FRP) at Oak Ridge National Laboratory (ORNL).

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

Impact of Sustainable Cool Roof Technology on Building Energy Consumption

Transcription:

THEMAL TATIFICATION PEFOMANCE OF UNDEFLOO AI DITIBUTION (UFAD) YTEM Tom Webster, Fred Bauman and Mingyu hi Center for the Built Environment, University of California, Berkeley, CA James eese York International, York, PA ABTACT Tests were conducted to determine the impact of room airflow and supply air temperature (AT) on the thermal stratification in interior spaces, and the effect of blinds in perimeter spaces for UFAD systems. oom airflow was varied over the range of 0.7-5.1 (L/s)/m 2 (0.3-1.0 cfm/ft 2 ) and ATs over 15-19 C (60-67 F) for constant nominal interior heat input of 55-59 W/m 2 (5.2-5.5 W/ft 2 ). esults show that spaces can be highly stratified when the airflow is reduced for a given load. When AT is varied, the shape of the temperature profile does not change; it only moves to higher or lower temperatures. Perimeter space tests conducted at a heat load of 116 W/m 2 (10.7 W/ft 2 ) and constant room airflow of 5.1 (L/s)/m 2 (1.0 cfm/ft 2 ) with blinds opened or closed showed that room load is reduced when blinds are closed due to bypassing of window gains directly to the ceiling return via a convective plume. INDEX TEM Underfloor air distribution, UFAD, thermal stratification, full-scale testing INTODUCTION Despite the fact that UFAD systems are being applied in the field in increasing numbers, there is a strong need for an improved fundamental understanding of several key performance features of these systems. Most of the potential performance advantages of UFAD systems over conventional air distribution systems are related to the fact that conditioned air is delivered at or near floor level and is returned at or near ceiling level. Under cooling conditions, this upward movement of air in the room takes advantage of the natural buoyancy of heat gain to the space, producing a vertical temperature gradient, similar to that achieved in the displacement ventilation (DV) systems used commonly in Europe (Nielsen 1996). Unlike classic DV systems that deliver air at very low velocities, however, typical UFAD systems deliver air through floor diffusers with greater supply air velocities. In addition to increasing the amount of mixing and therefore potentially diminishing the ventilation performance compared to DV systems, these more powerful supply air conditions can also have significant impacts on room air stratification and thermal comfort in the occupied zone. The purpose of this paper is to report on a series of full-scale laboratory experiments investigating the impact of various system design and operating parameters on room air stratification. The control and optimization of this stratification can be crucial to proper design, system sizing, energy efficient operation, and comfort performance of UFAD systems. METHOD TET CHAMBE AND INTUMENTATION TET CHAMBE - All tests were performed within a 5 m 5 m (16 ft x 16 ft) test chamber, constructed with a 0.6 m (2 ft) high raised floor (Figure 1) and located inside an office building. Walls consist of steel studs 0.6 m (2 ft) o.c., insulated with Fiberglas with a thermal resistance of Thermal tratification Performance of Underfloor Air Distribution (UFAD) ystems PAGE 1

0.52 W/m 2 -K (11) and covered with standard sheet rock inside and out. A suspended acoustical tile ceiling contains four ventilated parabolic fluorescent lighting fixtures. A 5 cm (2 in.) wide slotreturn immediately above the curtain wall directs return air into a 0.6 m (2 ft) high return plenum above the ceiling tile. An insulated plastic covering tops the ceiling plenum. A 4.6 m (15 ft) wide 3 m (10 ft) high section of curtain wall is installed between the test chamber and a weather chamber on the west side of the test chamber as illustrated in Figure 1. The curtain wall glazing is double pane low-e glass with a shading coefficient of 0.23 and an overall conductance of 3.95 W/m 2 - C (0.7 Btuh/(ft 2 - F)) (calculated by Window 5.0 window thermal analysis program (Mitchell, 2001)). The weather chamber is temperature controlled and contains a bank of high intensity lights that simulate the solar spectrum. The specified solar intensity based on floor area at the curtain wall of 2.9 W/m 2 (31.3 W/ft 2 ) was confirmed by an 18-point test with a solar pyranometer to within 1%. Besides the overhead lighting fixtures, internal heat gain was provided by laptop computers, CT monitors, computer towers, printers, desk lamps, and occupants arranged as shown in Figure 1. Two types of floor diffusers were used; variable area (VA) with a design flow rate of 70 L/s (150 cfm) and swirl (W) with a design flow rate of 42 L/s (90 cfm). INTUMENTATION - All air temperatures were measured with 100 ohm TDs and all surface temperatures were measured with Type K or T thermocouples. TDs have a published accuracy of ±0.3 C (0.5 F) and were calibrated with a precision mercury thermometer with 0.06 C (0.1 F) resolution. In addition to 23 sensors on the profile tree and pressures and airflow measurements, 27 temperatures were measured by TDs and thermocouples placed throughout the test chamber. AT was measured in three locations in the supply plenum and return temperatures in three locations each in the return slot and plenum. All TDs were connected to a modular 64-channel data acquisition system. Channels were sampled at 3-second intervals for 2 minutes yielding 40 readings averaged for each temperature measurement at the end of each test. Diffuser flow rates were measured manually with a calibrated balometer. oom airflow rates were later confirmed with a calibrated orifice meter installed in the ductwork to the supply plenum. The range of estimated measurement uncertainties at 95% confidence for temperatures is 0.1-1.0 C (0.18-1.8 F) and 4-7% for measured heat removal (room airflow multiplied by overall delta T (supply to return temperature difference). Heat flux measurements (and associated inside/outside surface temperatures) were made to check wall surface-to-surface heat conductances (U-values). The results found the U-values to be very close to the assumed values from AHAE (AHAE, 2001). 5 m (16 ft) outh outh Door olar imulator Lights/Weather West Chamber 1 2 6 5 m (16 ft) FIGUE 1. Test facility plan and layout North Door East North W Diffuser VA Diffuser Profile Tree eturn ensor upply ensor Thermocouples Occupied Zone Delta T (Tavg 1.8 -Tsat), 0-1.8 m, C 12 10 8 6 4 2 0 y = 0.62x + 0.56 2 = 0.95 2 4 6 8 10 12 LV - W/(L/) FIGUE 2. Average room temperature (0-1.8 m) difference vs. LV (interior loads, ~17 C AT) Thermal tratification Performance of Underfloor Air Distribution (UFAD) ystems PAGE 2

POCEDUE AND ANALYI POCEDUE Before each series of tests the facility was setup and all TDs calibrated. The access floor panel joints were all taped to eliminate floor leakage as an uncontrolled variable. Profile measurements were made at three locations in the room at the end of each test. The tree locations were adjusted as necessary to maintain a 0.6-0.9 m (2-3 ft) clearance from the nearest diffuser. As a result, the stratification profiles presented here represent temperature conditions in the ambient space outside of the direct influence of the supply diffusers. The range of test conditions were 1.6-5.1 (L/s)/m 2 (0.3-1.0 cfm/ft 2 ) for room airflow, 25%-120% of design for diffuser airflow (diffuser air flow ratio), and 15-19 C (60-67 F) for AT. For most tests nominal total heat input representative of peak load conditions was used. Interior space heat input range was 55-59 W/m 2 (5.1-5.5 W/ft 2 ) including 100% of overhead lighting; perimeter spaces including solar gain was 116 W/m 2 (10.7 W/ft 2 ). Tests were normally run for 1.5 to 4 hours to achieve steady state. Tests were conducted in pairs or triplet to study the effect of one parameter while other variables and heat input were held constant. ANALYI The approach used to analyze results is to examine stratification profile shape differences between two or more tests where a parametric change was made for a given variable (e.g., room airflow rate, diffuser type). Following the load factor concept of Nielson (Nielson, 1996) the primary factor for distinguishing room operating conditions is the load to volume ratio (LV), the ratio of measured heat removal to room airflow rate, which is directly proportional to overall delta T. Figure 2 is a chart of occupied zone average temperature difference (average from floor to 1.8 m (6 ft)) minus AT) plotted against LV for interior loads (the slope of this line represents Nielson s load factor). Included in this chart are tests that represent a broad range of room operating conditions, two diffuser types operating at different diffuser design ratios, and ATs of about 17 C (63 F). Certain tests where high stratification was intentionally elicited were not included. This shows that performance varied widely for these tests but the high correlation ( 2 =0.95) indicates little effect due to diffuser characteristics. (The effect of diffusers on performance is reported in more detail in a companion paper (Webster, In press).) HEAT BALANCE To achieve a heat balance in the chamber calculated loads should equal the measured load. Calculated loads were based on measured surface and air temperatures, measured internal gains, and standard AHAE conductances. However, no definitive data was obtained for the contribution of lighting heat to room load. Therefore, load calculations were made for assumed fractions of 10% to 40%. The best correlation with measured heat removal occurred at 20% where the curve fit ( 2 =0.94) was very close to heat balance (i.e., slope=1.025). EULT EFFECT OF OOM AIFLOW Figure 3 shows an example of interior load stratification profiles where room airflow rates were varied for constant heat input. Additional data for these tests are reported in Table 1. From the results the following observations can be made: = As the total room airflow increases, room air stratification decreases producing a more vertical profile characteristic of a well-mixed space. = As airflow increases, the measured heat removal rate also increases. (ee Discussion.) = For the range of conditions tested, the temperature near the floor remains relatively constant for all room airflows; i.e., the profile pivots around a fixed temperature. Thermal tratification Performance of Underfloor Air Distribution (UFAD) ystems PAGE 3

= The gradients in the occupied zone of the space (between the floor and 1.2 m (4 ft) for a seated or 1.8 m (6 ft) for a standing occupant) increased as the room airflow is reduced resulting in a relatively large change in temperature at the typical thermostat level (1.5 m (5 ft)). Table 1 shows the temperature stratification in the occupied zone (0.1 m to 1.7 m (4 in. to 67 in.)) exceeds the upper limit of 3 C (5 F) recommended by AHAE (AHAE, 1992) at the lowest room airflow rate (Test 2-2c). Also shown in Table 1 is the fact that as the airflow changes, the change in temperature at 1.5 m (5 ft) is about twice that of the change in average occupied zone temperature. 3.5 3.0 3.5 3.0 Bypass, blinds closed 2.5 2.5 Height, m 2.0 1.5 Height, m 2.0 1.5 4-1a, Blinds Closed 1.0 1.0 4-1b, Blinds Open 0.5 2-2a 2-2b 2-2c 0.5 0.0 21 22 23 24 25 26 27 28 Temperature, C FIGUE 3. Effect of room airflow variation, interior loads (see Table 1) 0.0 22 24 26 28 30 32 34 36 Temperature, C FIGUE 5. Effect of blinds, perimeter loads (see Key) Height, m 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 4-9a 4-9b 4-9c 21 22 23 24 25 26 Temperature, C Test Conditions Key (Figures 4, 5) Nominal Total Heat Gain: Interior: 59.0 W/m 2 (5.48 W/ft 2 ) Perimeter: 116 W/m 2 (10.76 W/ft 2 ) oom Airflow (L/s/m 2 ) Ht. em. m. [Tot.] (W/m 2 ) Test Load Type AT ( C) 4-9a Int 2.7 25.2 15.8 4-9b Int 2.7 29.1 17.4 4-9c Int 2.7 20.1 19.3 4-1a Per 5.1 61.5 [117] 17.1 4-1b Per 5.1 73.2 [99] 17.0 FIGUE 4. Effect of AT, interior loads (see Key) TABLE 1. Test conditions for room airflow variation Test 2-2a 2-2b 2-2c Nominal total heat input, W/m 2 (W/ft 2 ) 56.6 (5.2) 56.6 (5.2) 56.6 (5.2) LV, W/(L/s) (W/cfm) 7.3 (3.3) 9.1 (4.1) 11.1 (5.0) oom airflow, (L/s)/m 2 (cfm/ft 2 ) 5.0 (1.0) 3.1 (0.6) 1.7 (0.3) oom temperature @Thermostat, C ( F) 23.4 (74.1) 24.9 (76.8) 26.7 (80.1) Average room temp, 0-1.8 m, C ( F) 23.1 (73.6) 23.8 (74.8) 25.1 (77.2) Average room temp, 0-1.2 m, C ( F) 23.0 (73.4) 23.4 (74.1) 24.2 (75.6) Head-foot temp. diff., 0.1 m - 1.7 m, C ( F) 0.7 (1.3) 1.8 (3.2) 3.8 (6.8) Thermal tratification Performance of Underfloor Air Distribution (UFAD) ystems PAGE 4

EFFECT OF UPPLY AI TEMPEATUE (AT) Figure 4 shows results for tests where AT was varied over the range of 17-19 C (60-67 F) for constant heat input and room airflow rate for a simulated interior space. As shown, the temperatures of the profiles increase or decrease, but keep approximately the same shape. PEIMETE PACE OOM LOAD BYPAING Figure 5 shows the difference in performance between perimeter space tests with blinds closed and open for the same total heat input (solar plus internal gains) and room airflow. Note the large temperature difference between the ceiling of the room (measured at 0.05 m (2 in.) below the ceiling) and the slot return temperature for both cases, and how much greater it is with blinds closed. This indicates that the use of blinds increases the strength of the window thermal plume, thereby facilitating bypassing of convective energy directly to the return and reducing the total gain to the room. The bypassed energy is about 26% and 48% of the total heat removal for blinds open and closed, respectively, almost twice as much for lowered blinds. The key for Figure 5 confirms that the measured room heat removal is lower for closed blinds, which would be expected if the total gain is reduced. Note that the total heat removal (measured heat removal using the slot return temperature) is greater for closed blinds (Test 4-1a). This represents the total load on the HVAC system. (ee Discussion.) DICUION OOM AIFLOW AND AT The room airflow tests exemplify how the magnitude of the load can vary between tests. Although the heat input from solar and internal sources was constant between tests, the measured heat removal (the best measure of actual load) was not. Differences in load will occur to the extent that differences in room profiles affect the heat transfer across surfaces. ome of this variability is due to heat transfer through the chamber non-adiabatic chamber walls combined with uncontrolled outside conditions. For real interior spaces this change in load would occur primarily as a function of changes in the ceiling and floor heat transfer; thus we would expect the differences in load to be smaller than those shown. For perimeter spaces, changes in heat transfer at the outside wall also would affect the load. imilar arguments can be made for the variability associated with AT change. In real interior spaces there would be no outside walls so conduction differences would be confined to ceiling and floor. The sensitivity likely would be greater than shown here. Increasing AT will always decrease conduction loads; i.e., for outside conditions both higher (wall delta T decreases thus reducing heat gain) and lower (wall delta T increases thus increasing heat loss and lowering net heat input) than room temperature. PEIMETE PACE BYPAING The perimeter space tests with blinds open and closed demonstrate a potential fundamental difference between UFAD and overhead systems. In overhead systems virtually all the solar and conduction gain appears in the room load due to mixing produced by ceiling diffusers. For UFAD the entire heat balance of the room is different for closed vs. open blinds. ome heat gain components increase (e.g., ceiling heat gain increases significantly when blinds are closed) while others decrease. The net result, however, is lower room load for closed blinds. The fact that bypass energy is shown for open blinds indicates that conduction heat gains also create thermal plumes. In addition, it seems counter intuitive that system load increases with blinds closed while room load decreases. Lower total load for open blinds can be partly explained by direct solar gain absorbed at the floor being lost to the supply plenum where it is not accounted for as part of the system load; i.e., the AT was adjusted to be the same for both tests. It is unlikely that this factor explains all of the difference suggesting that a complex thermal exchange is occurring at the window. Decreasing room load can be a significant benefit since the number of diffusers and fan sizes can be reduced, but there may be a tradeoff in terms of total cooling energy. Thermal tratification Performance of Underfloor Air Distribution (UFAD) ystems PAGE 5

CONCLUION AND IMPLICATION The following are conclusions from full-scale experiments of UFAD systems conducted to investigate the effect on temperature stratification in simulated interior and perimeter spaces. INTEIO PACE When room airflow was reduced over the range of 5.1-1.7 (L/s)/m 2 (0.9-0.3 cfm/ft 2 ) with constant total heat input, the temperature difference at 0.1 m-1.7m (4 in.- 67 in) increased from 0.7 C to 3.8 C (1.3 to 6.8 F). The change in average temperature in the occupied zone (floor to 1.2 m (4 ft)) was about half that at the thermostat height. Changing AT over the range of 15-19 C (60-67 F) did not change the profile shape; it only moved to higher or lower temperatures. PEIMETE PACE Tests conducted at 116 W/m 2 (10.8 W/ft 2 ) total input for both closed and open blinds, resulted in lower room load for closed blinds due to bypassing directly to the ceiling return via a convective plume. However, system load (total load on the HVAC system) was found to increase. This bypass phenomenon is one of the factors that distinguish UFAD load conditions from overhead systems. Other important factors include floor loss (the underfloor plenum provides a heat sink that reduces room load by 5.4-13.5 W/m 2 (0.5-1.3 W/ft 2 ) and stratification (reduces airflow requirements). The results of this work, along with planned future research, will be used to develop design and operating guidelines for optimizing stratification performance in UFAD systems to improve thermal comfort, reduce energy use, and reduce systems costs. ACKNOWLEDGMENT This work was sponsored by the Center for the Built Environment (CBE), a NF/Industry/University Cooperative esearch Center at the University of California, Berkeley. We gratefully acknowledge the support of our CBE Partners (please see www.cbe.berkeley.edu) and York International for supporting the use of the test facility. This material is based upon work supported in part by the National cience Foundation under Grant No. 9711282. EFEENCE AHAE (1992). "Thermal environmental conditions for human occupancy," ANI/AHAE tandard 55-1992, American ociety of Heating, efrigerating, and Air-Conditioning Engineers, Inc. AHAE (2001). 2001 AHAE Handbook, Fundamentals. Atlanta: American ociety of Heating, efrigerating, and Air-Conditioning Engineers, Inc. Mitchell,., C. Kohler, et al. (2001). "Window 5.0 User Manual," LBNL-44789, Lawrence Berkeley National Laboratory, November. Nielsen, P. V. (1996). "Displacement Ventilation - Theory and Design," IN 0902-8005 U9306, Department of Building Technology and tructural Engineering, Aalborg University. Webster, T., F.. Bauman, J. eese and M. hi. (In press). "Underfloor Air Distribution (UFAD): Thermal tratification Performance," AHAE Journal, American ociety of Heating, efrigerating, and Air-Conditioning Engineers, Inc. Thermal tratification Performance of Underfloor Air Distribution (UFAD) ystems PAGE 6