Certification Body: SAI Global Certification Services Pty Limited (ACN 108 716 669) Trading as SAI Global JAS-ANZ Accreditation No. Z1440295AS Address: 680 George Street, Sydney, NSW 2000 Website: www.saiglobal.com Certificate Holder: Type and/or use of product: THIS TO CERTIFY THAT KOOLTHERM K12 FRAMING BOARD AND K15 RAINSCREEN BOARD The Kooltherm K12 Framing Board is a thermal insulation board for use behind wall lining and framed walls. The Kooltherm K15 Rainscreen Board is a thermal insulation board for use behind Rainscreen cladding systems. Description of product: Certificate number: CM20047 The K12 Framing Board and the K15 Rainscreen Board consists of three layers as follows: The facing on both sides is a low emissivity composite foil autohesively bonded to the insulation core during manufacture. The core is a fibre free rigid thermoset phenolic insulation. COMPLIES WITH THE FOLLOWING BCA PROVISIONS AND STATE OR TERRITORY VARIATION(S) BCA 2016 Volume One Volume Two Kingspan Insulation Pty Ltd 266 Beringarra Avenue, Malaga, WA 6090 Tel: 1300 247 235 Fax: 1300 247 329 info@kingspaninsulation.com.au www.kingspaninsulation.com.au Deemed-to-Satisfy Provision(s): C1.10 (inter alia Specification C1.10 clause 7) Fire hazard properties 3.12.1.1 Building fabric thermal insulation (such that it is able to be used as part of a system outlined in clause 3.12.1.4 subject to applicable State and Territory variations). J1.2 Thermal construction general (such that it is able to be used as part of a system outlined in clause J1.5 subject to applicable State and Territory variations). Date of issue: 15/08/2017 Nicole Grantham General Manager SAI Global Certification Services George Petrovski Unrestricted Building Certifier Date of expiry: 21/03/2020 Certificate number: CM20047 This certificate is only valid when reproduced in its entirety. Page 1 of 5
State or territory variation(s): NSW Specification C1.10 Clause 7 NSW Section J Fire hazard properties Energy use - Applicable only to Class 3 and 5-9 buildings (Class 2 and 4 parts of buildings are subject to BASIX). NSW Part 3.12 NT BCA 2005 3.12.1.1 Energy Efficiency Part 3.12 does not apply in NSW. Building fabric thermal insulation (such that it is able to be used as part of a system outlined in clause 3.12.1.4). NT Section J Energy use - For a Class 2 building and a Class 4 part of a building, Section J is replaced with Section J of BCA 2009. Section J does not apply to Class 3 and 5-9 buildings. QLD Section J Energy use - In Queensland, for a Class 2 building, Section J is replaced with Section J of BCA 2009. SUBJECT TO THE FOLLOWING LIMITATIONS AND CONDITIONS AND THE PRODUCT TECHNICAL DATA IN APPENDIX A AND EVALUATION STATEMENTS IN APPENDIX B 1. For the purposes of the Building Code of Australia Volume One 2016 Specification C1.10 clause 7, the K12 framing board has been tested to AS 1530.3 and achieved a Spread of Flame Index of 0 and a Smoke Developed Index 2. 2. For the purposes of the Building Code of Australia Volume One 2016 Specification C1.10 clause 7, the K15 Rainscreen Board has been tested to AS 1530.3 and achieved a Spread of Flame Index of 0 and a Smoke Developed Index 0-1. 3. The product(s) must be used for its intended purpose. Scope of certification: The CodeMark Scheme is a building product certification scheme. The rules of the Scheme are available at the ABCB website www.abcb.gov.au. This Certificate of Conformity is to confirm that the relevant requirements of the Building Code of Australia (BCA) as claimed against have been met. The responsibility for the product performance and its fitness for the intended use remain with the certificate holder. The certification is not transferrable to a manufacturer not listed on Appendix A of this certificate. Disclaimer: The Scheme Owner, Scheme Administrator and Scheme Accreditation Body do not make any representations, warranties or guarantees, and accept no legal liability whatsoever arising from or connected to, the accuracy, reliability, currency or completeness of any material contained within this certificate; and the Scheme Owner, Scheme Administrator and Scheme Accreditation Body disclaim to the extent permitted by law, all liability (including negligence) for claims of losses, expenses, damages and costs arising as a result of the use of the product(s) referred to in this certificate. Certificate number: CM20047 This certificate is only valid when reproduced in its entirety. Page 2 of 5
APPENDIX A PRODUCT TECHNICAL DATA A1 Type and intended use of product See type and/or use of product on page 1 A2 Description of product See Description of product on page 1 A3 Product specification The product specifications are contained within the following manuals; 1. Kooltherm K12 Framing Board INSULATION FOR USE BEHIND WALL LINING AND FRAMED WALLS manual (Issue 9 Apr 2017): This contains the specification and installation methods of the product. 2. Kooltherm K15 Rainscreen Board INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS manual (Issue 4 Nov 2015): This contains the specification and installation methods of the product. A4 Manufacturer and manufacturing plant(s) Kingspan Insulation Pty Ltd 266 Beringarra Avenue, Malaga, WA 6090. Manufactured in 25 O Herns Road, Somerton, VIC, 3062, Australia A5 Installation requirements The installation must be carried out in accordance with the following manuals; 1. Kooltherm K12 Framing Board INSULATION FOR USE BEHIND WALL LINING AND FRAMED WALLS manual (Issue 9 Apr 2017): 2. Kooltherm K15 Rainscreen Board INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS manual (Issue 4 Nov 2015): A6 Other relevant technical data Certificate number: CM20047 This certificate is only valid when reproduced in its entirety. Page 3 of 5
Nil APPENDIX B EVALUATION STATEMENTS B1 Evaluation methods The system has been assessed as complying with the identified Deemed-to-Satisfy Provision(s) of the BCA 2016. This involved a review of product specifications, test reports, installation manuals, and associated documentation. 1. Fire hazard properties assessment A2.2(a)(i) Report from NATA Accredited laboratory. 2. Energy use (inc NSW Variation, QLD Variation and NT Variation - A2.2(a)(i) / 1.2.2(a)(i) Report from NATA Accredited laboratory. 3. Energy use A0.5(c) Report from an appropriately qualified person. In addition; SAI Global CODEMARK Certification Evaluation Report dated 8 August 2017, Certification audit of Kingspan Insulation Pty Ltd 25 O Herns Road, Somerton, VIC, 3062, Australia dated 15/2/2017 which include assessments of the following; a) The Manufacturing details b) Operating and Maintenance procedures B2 Reports 1. AWTA - ASTM C518-2010 Steady-State Thermal Transmission Properties by Means of the Heat Flow Apparatus, Kooltherm 38mm thick (test number: 17-002821, dated 13/07/2017): 2. AWTA - ASTM C518-2010 Steady-State Thermal Transmission Properties by Means of the Heat Flow Apparatus, Kooltherm 50mm thick (test number: 17-001265, dated 12/05/2017): 3. AWTA - ASTM C518-2010 Steady-State Thermal Transmission Properties by Means of the Heat Flow Apparatus, Kooltherm 60mm thick (test number: 17-002824, dated 17/07/2017): Certificate number: CM20047 This certificate is only valid when reproduced in its entirety. Page 4 of 5
4. AWTA - ASTM C518-2010 Steady-State Thermal Transmission Properties by Means of the Heat Flow Apparatus, Kooltherm 80mm thick (test number: 17-001255, dated 27/04/2017): 5. AWTA - AS/NZS 1530.3-1999 Methods for Fire Tests on Building Materials, Components and Structures Part 3: Simultaneous Determination of Ignitability, Flame Propagation, Heat Release and Smoke Release (test number: 14-0001428, dated 24/11/2014): This report provides the results of testing to AS/NZS 1530.3-1999 and specifies the Ignitability, Flame Propagation, Heat Release and Smoke Release indices. 6. AWTA - AS/NZS 1530.3-1999 Methods for Fire Tests on Building Materials, Components and Structures Part 3: Simultaneous Determination of Ignitability, Flame Propagation, Heat Release and Smoke Release (test number: 17-000424, dated 22/02/2017): This report provides the results of testing to AS/NZS 1530.3-1999 and specifies the Ignitability, Flame Propagation, Heat Release and Smoke Release indices. 7. Acronem Consulting Australia Pty Ltd - Report on Thermal Performance of 25 mm Kooltherm by Dr Cameron Chick (dated 3/08/2017): This report considers the relationship between Thermal Resistance and Thermal Conductivity with respect to the product thickness. The calculations in this report determines that 25mm thick Kooltherm Framing Board is capable of achieving an R-Value in the range of R1.21 to R1.29. Certificate number: CM20047 This certificate is only valid when reproduced in its entirety. Page 5 of 5