FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Architectural Decking panels and Fabrications REVISED 11.

Similar documents
FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Baffle Wall Panel Products and Fabrications REVISED 11.

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Hollow Core Building Panels Products and Fabrications REVISED 11.

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Molded Grating and Treads Products and Fabrications REVISED 11.

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Pultruded Grating/Treads and Fabrications REVISED

FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Structural Shapes/Plate and Fabrications REVISED

PROForms. Specifications SECTION FIBERGLASS REINFORCED POLYMER (FRP) PULTRUDED PRODUCTS

FRP Floor Panels Standard Specification

ENGINEERING SPECIFICATION. PULTRUDED PEDESTRIAN FIBERGLASS GRATING SAFE-T-SPAN T1210 VINYL ESTER and ISOPHTHALIC. October 25, 2004 Revision 1

FIBERGLASS DECKING SYSTEMS

ENGINEERING SPECIFICATION FIBERTRED MOLDED STAIR TREADS SECTION 06610

ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. March 16,

ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES FIBERGRATE MOLDED GRATING WITH GRATING PEDESTALS. January 24,

ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING

COMPOSOLITE FIBERGLASS BUILDING PANEL SYSTEM

FIBERGLASS HANDRAIL & LADDER SYSTEMS

FRP Baffle Wall Standard Specification-Section 11350

and FIBERGLASS FOAM AND HOLLOW CORE BUILDING PANELS

SECTION EXPANSION CONTROL

SECTION METAL FLOOR PLATE STAIRS

SECTION EXPANSION CONTROL

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Section PANEL SIGNAGE

A. The extent of extruded aluminum walkway covers is shown on the Drawings and as specified herein.

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS

SPECIFICATIONS: Architectural Aluminum Railings

American Metal Specialties, Inc.

FIBERGLASS ROUND CONTROL DAMPERS. Model K-RD INTRODUCTION M.K. PLASTICS PROVIDES FOUR DAMPER MODELS K-RD SUGGESTED SPECIFICATION

ST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

BAYFRONT PARK RAILING REQUEST FOR PROPOSALS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

Dynaform Structural Shapes

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

Product Specifications

FL200 13/4 x41/2 GUIDE SPECIFICATION. Non-Thermal Storefront

SPECIFICATION SECTION 05515: LADDERS O Keeffe s Aluminum Ladders

SECTION DECORATIVE METAL AND GLASS RAILING

SECTION FOOD DISPENSING EQUIPMENT- SNEEZE GUARDS AND PARTITION POSTS

EXCLUSIVELY MOLDED FIBERGLASS GRATING

SECTION STAINLESS STEEL FLEXIBLE CABLE MESH. Show hidden Specifier Notes for best results

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

A. This Section includes automatic entrance door systems operating as follows: 1. Swinging operation.

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PIPE AND TUBE RAILINGS

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

Guidelines for the Engineer & Designer

SECTION ROLLER GATES

RapiDeck TM Composite Equipment Platform

Product Guide Specification

Corium Brick Rainscreen System Specifications

SECTION ALUMINUM STORM WINDOWS

SECTION PLATE CONNECTED WOOD TRUSSES

Re-Grate Pultruded Grating

SL150 Guide Specification

A. Drawings and general provisions of the Contract, including General Conditions Specification Sections, apply to this section.

Guideline Specifications

Specifications for FL-100 Soffit Panel

Specification Lightning Protection Systems

MASTERSPEC - SHORT FORM. B. See Division 5 Section "Metal Stairs" for steel tube railings associated with metal stairs.

1. Section Steel Doors and Frames. 2. Section Flush Wood Doors 3. Section Aluminum Storefront Doors.

SECTION EXTERIOR GRILLS AND SCREENS

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION

PW251 21/2 x7 GUIDE SPECIFICATION. Curtain Wall

Dynaform Structural Shapes

DIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK

Code Compliance Research Report CCRR-0194

SECTION IMPACT RESISTANT WALL PROTECTION

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM

ATI Evaluation Service A Division of Architectural Testing Certification Services

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs.

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE

SECTION PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY 1.3 PERFORMANCE REQUIREMENTS

SECTION ALUMINUM WINDOWS

SECTION WATERTIGHT GATES & BARRIERS FOR FLOOD & SPILL CONTROL

General Overview SECTION PBR & R PANEL - PREFORMED ROOF AND WALL PANELS

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building


SECTION ALUMINUM GATES

PRODUCT SPECIFICATIONS

02800 SHADE STRUCTURES

MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications

STATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION PRE-ENGINEERED BUILDING INSULATION

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

WEIR PLATES & SCUM BAFFLES

Installation Instructions

BAND SHELLS Our versatile Band Shells perform in any community

SECTION PRE-ENGINEERED ALUMINUM STAIRS AND RAILINGS

Transcription:

FRP Specifications Section 06 73 13 Fiberglass Reinforced Polymer (FRP) Architectural Decking panels and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol, VA 24203-0580 USA (276) 645-8000 FAX (276) 645-8132 HIGHLANDS FACILITY CHATFIELD FACILITY 26770 Newbanks Road, Abingdon, VA 24210 USA 1610 Highway 52 South, Chatfield, MN 55923-9799 USA (276) 645-8000 FAX (276) 645-8132 (507) 867-3479 FAX (507) 867-4031 www.strongwell.com

Liability Disclaimer The specifications and material property information contained in these STRONGWELL SPECIFICATIONS are provided as a service to architects and Design Engineers who desire to use this information in the creation of construction specification documents. The use of these specifications is at your own risk. These specifications may contain errors, omissions, and inaccuracies. NEITHER STRONGWELL NOR ANY OTHER PARTY INVOLVED IN THE CREATION OF THESE SPECIFICATIONS SHALL BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, CONSEQUENTIAL, OR PUNITIVE DAMAGES ARISING OUT OF OR CONNECTED IN ANY MANNER WITH YOUR ACCESS TO OR USE OF THESE STRONGWELL SPECIFICATIONS INCLUDING, WITHOUT LIMITATION, ANY LOST PROFITS, BUSINESS INTERRUPTION, OR LOSS OF PROGRAMS OR INFORMATION, EVEN IF STRONGWELL HAS BEEN SPECIFICALLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. WITHOUT LIMITING THE FOREGOING, EVERYTHING IN THESE SPECIFICATIONS IS PROVIDED TO YOU AS IS WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESSED OR IMPLIED INCLUDING, BUT NOT LIMITED TO, THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, TITLE, NONINFRINGEMENT AND FREEDOM FROM COMPUTER VIRUS. Strongwell reserves the right to change its website at any time, including these STRONGWELL SPECIFICATIONS, as well as the terms and conditions of its website, and you will be bound by the terms of any such changes. In this regard, we suggest that you refer to Strongwell s website terms and conditions periodically so that you are aware of any changes. November 2016 067313-1

Table of Contents PART 1: GENERAL 1.01 Related Documents... 3 1.02 Summary... 3 1.03 Scope of Work... 3 1.04 Quality Assurance... 3 1.05 Design Criteria... 4 1.06 Submittals... 5 1.07 Shipping and Storage Instructions... 5 PART 2: PRODUCTS 2.01 General... 6 2.02 FRP STRONGDEK Decking panels... 7-8 PART 3: EXECUTION 3.01 Preparation... 9 3.02 Inspection and Testing... 9 3.03 Installation, General... 9 3.04 All FRP Installation... 9 067313-2 November 2016

SECTION 06 73 13 FIBERGLASS REINFORCED POLYMER (FRP) PRODUCTS AND FABRICATIONS PART 1 GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification Sections, apply to work of this section. 1.02 SUMMARY: A. This section includes FRP Products & Fabrications for FRP STRONGDEK Decking panels. 1.03 SCOPE OF WORK: A. Furnish all labor, materials, equipment and incidentals governed by this section necessary to install the fiberglass reinforced polymer (FRP) products as specified herein. 1.04 QUALITY ASSURANCE: A. The material covered by these specifications shall be furnished by an ISO-9001 certified manufacturer of proven ability who is regularly engaged in the manufacture, fabrication and installation of FRP systems. B. Substitution of any component or modification of system shall be made only when approved by the Architect or Design Engineer. C. Fabricator Qualifications: Firm experienced in successfully producing FRP fabrications similar to that indicated for this project, with sufficient production capacity to produce required units without causing delay in the work. D. In addition to requirements of these specifications, comply with manufacturer s instructions and recommendations for work. November 2016 067313-3

1.05 DESIGN CRITERIA: A. The design of FRP products including connections shall be in accordance with governing building codes and standards as applicable. B. Design load is considered as uniform loading over the entire decking panels. Design live loads of shall be in accordance with the following minimum design loads based on the latest adopted International Building Code: --60 psf live load (non-emergency exit walkways) --300 lb concentrated load (on 12 x 12 area) C. Decking panels shall not deflect more than ¼ and structural support members shall not deflect more than L/240 of span for structural members unless specifically stated otherwise in drawings and/or supplementary conditions. Connections shall be designed to transfer the design loads. D. Panels weakened by penetrations, cuts, etc. shall be stiffened or reinforced as necessary to restore their capacity to withstand the specified loading and deflection limits. E. Design decking panels in accordance with the Strongwell Design Manual for inservice temperatures of degrees Fahrenheit (example: 125 degrees) with ultimate stress retention of (example: 85% for 125 degrees) and a modulus of elasticity retention of (example: 90% for 125 degrees). 067313-4 November 2016

1.06 SUBMITTALS: A. Shop drawings of all fabricated pultruded STRONGDEK decking panels shall be submitted to the Design Engineer for approval in accordance with the requirements of Section. Fabrication shall not start until receipt of Design Engineer s approval marked Approved As Submitted or Approved As Noted. B. Manufacturer s catalog data showing: 1. Materials of construction 2. Dimensions, spacings, and construction of grating, handrails and building panels. C. Detail shop drawings showing: 1. Dimensions 2. Sectional assembly 3. Location and identification mark 4. Size and type of supporting frames required D. Samples of each type of product shall be submitted for approval in accordance with the requirements of Section. 1.07 SHIPPING AND STORAGE INSTRUCTIONS: A. All systems, sub-systems and structures shall be shop fabricated and assembled into the largest practical size suitable for transporting. B. All materials and equipment necessary for the fabrication and installation of pultruded STRONGDEK decking panels and appurtenances shall be stored before, during, and after shipment in a manner to prevent cracking, twisting, bending, breaking, chipping or damage of any kind to the materials or equipment, including damage due to over exposure to the sun. Any material which, in the opinion of the Design Engineer, has become damaged as to be unfit for use, shall be promptly removed from the site of work, and the Contractor shall receive no compensation for the damaged material or its removal. C. Identify and match-mark all materials, items and fabrications for installation and field assembly. November 2016 067313-5

PART 2 PRODUCTS 2.01 GENERAL: A. Materials used in the manufacture of the FRP products shall be raw materials in conformance with the specification and certified as meeting the manufacturer s approved list of raw materials. B. All raw materials shall be as specified by the contract. C. The visual quality of the pultruded shapes shall conform to ASTM D4385. D. FRP STRONGDEK panels shall be manufactured using a pultruded process utilizing (select polyester or vinyl ester) resin with flame retardant and ultraviolet (UV) inhibitor additives. A synthetic surface veil fabric shall encase the glass reinforcement. FRP shapes shall achieve a flame spread rating of 25 or less in accordance with ASTM test method E-84, the flammability characteristics of UL 94 V0 and the self-extinguishing requirements of ASTM D635. (Polyester resin is available without flame retardant and UV inhibitor additives.) E. If required, after fabrication, all cut ends, holes and abrasions of FRP shapes shall be sealed with a compatible resin coating. F. FRP products exposed to weather shall contain an ultraviolet inhibitor. Should additional ultraviolet protection be required, a one mil minimum UV coating can be applied. G. All exposed surfaces shall be smooth and true to form, consistent with ASTM D4385. H. Manufacturers: 1. Strongwell I. Pultruded FRP products shall be manufactured and fabricated in the USA. Manufacturer shall provide a written Certificate of Compliance. J. The materials covered by these specifications shall be furnished by an ISO-9001 certified manufacturer. K. For walkway surfaces the top of all panels shall have a non-skid grit surface. 067313-6 November 2016

2.02 FRP STRONGDEK PANEL A. Materials 1. Each STRONGDEK panel shall be manufactured by the pultrusion process. A minimum 7 mil. synthetic surface veil shall be the outermost layer covering the exterior surface. 2. STRONGDEK Panels shall be manufactured by Strongwell. B. Design STRONGDEK TM Load / Deflection Data I 12 = 0.31 in. 4 Wt = 2.58 lb/lin. ft SPAN 50 100 150 200 250 300 350 400 450 500 550 600 650 u 0.019 0.026 0.034 0.041 0.048 0.054 0.073 0.080 0.086 0.094 0.100 0.107 0.113 24 u (0.488) (0.671) (0.853) (1.036) (1.219) (1.372) (1.859) (2.042) (2.195) (2.377) (2.530) (2.713) (2.865) (610mm) c 0.016 0.022 0.028 0.034 0.04 0.045 0.061 0.067 0.072 0.078 0.083 0.089 0.094 c (0.406) (0.559) (0.711) (0.864) (1.016) (1.143) (1.549) (1.702) (1.829) (1.981) (2.108) (2.261) (2.388) u 0.032 0.041 0.056 0.069 0.081 0.096 0.117 0.131 0.144 0.155 0.165 0.179 30 u (0.800) (1.029) (1.410) (1.753) (2.057) (2.438) (2.972) (3.315) (3.658) (3.924) (4.191) (4.534) (762mm) c 0.021 0.027 0.037 0.046 0.054 0.064 0.078 0.087 0.096 0.103 0.11 0.119 c (0.533) (0.686) (0.940) (1.168) (1.372) (1.626) (1.981) (2.210) (2.438) (2.616) (2.794) (3.023) u 0.047 0.065 0.090 0.115 0.140 0.169 0.207 0.227 0.252 36 u (1.189) (1.646) (2.286) (2.926) (3.566) (4.298) (5.258) (5.761) (6.401) (914mm) c 0.026 0.036 0.05 0.064 0.078 0.094 0.115 0.126 0.14 c (0.660) (0.914) (1.270) (1.626) (1.981) (2.388) (2.921) (3.200) (3.556) u 0.067 0.101 0.145 0.191 0.239 0.288 0.340 0.365 42 u (1.707) (2.560) (3.680) (4.854) (6.081) (7.308) (8.641) (9.281) (1067mm) c 0.032 0.048 0.069 0.091 0.114 0.137 0.162 0.174 c (0.813) (1.219) (1.753) (2.311) (2.896) (3.480) (4.115) (4.420) u 0.096 0.158 0.233 0.310 0.391 0.463 48 u (2.438) (4.023) (5.913) (7.864) (9.936) (11.765) (1220mm) c 0.040 0.066 0.097 0.129 0.163 0.193 c (1.016) (1.676) (2.464) (3.277) (4.140) (4.902) u 0.138 0.246 0.370 0.497 0.626 54 u (3.498) (6.241) (9.395) (12.619) (15.911) (1372mm) c 0.051 0.091 0.137 0.184 0.232 c (1.295) (2.311) (3.480) (4.674) (5.893) u=uniform load in lbs/ft 2 (N/m 2 ). For example, a 100 lb. uniform load over 3 ft 2 is 300 lbs. of total load. u =Typical deflection under the uniform load in inches (mm) c=concentrated load in lbs/ft of width (N/m of width) c =Typical deflection under concentrated load in inches (mm) STRONGDEK TM panels were attached to beams with tek screws and tested in a multi-panel configuration. This data was used to create the STRONGDEK TM load table above for a single panel. November 2016 067313-7

C. Hardware 1. All fasteners, anchors, and structural hardware shall be 316 stainless steel. 2. All connections of STRONGDEK Panels to fiberglass columns or super structure shall be as shown on the approved shop drawings. D. Approved Manufacturers 1. STRONGWELL 067313-8 November 2016

PART 3 EXECUTION 3.01 PREPARATION: A. Coordinate and furnish anchorages, setting drawings, diagrams, templates, instructions and directions for installation of anchorages, including concrete inserts, sleeves, anchor bolts and miscellaneous items having integral anchors that are to be embedded in concrete or masonry construction. B. Coordinate delivery of all listed items to project site. 3.02 INSPECTION AND TESTING: A. The Design Engineer shall have the right to inspect and test all materials to be furnished under these specifications prior to their shipment from the point of manufacture. B. All labor, power, materials, equipment and appurtenances required for testing shall be furnished by the Contractor at no cost to the Owner. 3.03 INSTALLATION, GENERAL: A. Fastening to in-place construction: Provide anchorage devices and fasteners where necessary for securing miscellaneous FRP fabrications to in-place construction; include threaded fasteners for concrete and masonry inserts, toggle bolts, throughbolts, lag bolts and other connectors as determined by the Design Engineer. B. Cutting, fitting and placement: Perform cutting, drilling and fitting required for installation of miscellaneous FRP fabrications. Set FRP fabrication accurately in location, alignment and elevation; with edges and surfaces level, plumb, true and free of rack; measured from established lines and levels. C. Provide temporary bracing or anchors in form work for items that are to be built into concrete masonry or similar construction. 3.04 ALL FRP INSTALLATION: A. If required, all field cut and drilled edges, holes and abrasions shall be sealed with a catalyzed resin compatible with the original resin as recommended by the manufacturer. B. Install items specified as indicated and in accordance with manufacturer s instructions. End of Section 06600 November 2016 067313-9