ST-4 Polygeneration plant. Parc de l Alba Cerdanyola del Vallès

Similar documents
CASE STUDIES IN CATALONIA

Low temperature cogeneration using waste heat from research reactor as a source for heat pump

SorTech package solution description

Rank. Rank Technology.

POLYCITY PROJECT. 3 cities cooperate in the sustainable energy supply of urban development projects: 1. Ostfildern/Stuttgart. 2.

Modeling and analyzing solar cooling systems in Polysun

BUILDINGS & OFFICE SPACES INDUSTRIAL SOLUTIONS. Combined production of Heat and Power. Waste Heat Recovery Bottoming Cycle

Over 3 decades, the company has helped customers to be competitive and earn community goodwill by :

ANDERS DYRELUND, RAMBOLL INTEGRATION OF WIND AND SOLAR IN THE SMART ENERGY SYSTEM INTEGRATION OF WIND AND SOLAR IN THE SMART ENERGY SYSTEM

Energy Audit Summary Report Audit No. 72. Food Industry Bakery

Absorption Chillers in Industry

Performance evaluation of a small-scale polygeneration plant including a desiccant cooling system and an innovative natural gas ICE

Combination of wind solar plants and district heating power plants

TransPacific Energy Advantage: Case Studies

Héctor Rubio Plana Gas Natural, SDG S.A. 18th. June 2009

!"#$%&"#'"$( (% +, -

Perspectives and evolution of reciprocating cogeneration systems. Pasquale Campanile

Efficient utilization of energy sources

POLYCITY- WORKSHOP BASEL SUSTAINABLE TOWN PLANNING AND ENERGY BENCHMARKING OF BUILDINGS

Energy demand analysis for small and medium scale heat users in Rotorua aiming at converting existing heating systems to bioenergy.

EVALUATION OF AN INTEGRATED BIOMASS GASIFICATION/FUEL CELL POWER PLANT

Messiah College Natural Gas and Combined Cooling, Heat and Power Plant

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

2016 BioCleantech Forum TURBODEN ORC TECHNOLOGY: STATE-OF-THE-ART. Ilaria Peretti. Manager, Sales and Business Development North America

APPLICATION OF CUSTOMIZED ABSORPTION HEAT PUMPS WITH HEATING CAPACITIES ABOVE 500 kw PROJECT: ACKERMANNBOGEN, MUNICH

KWK Modellstadt Berlin

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

Cogeneration. Thermal Chillers. and. .. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012

District cooling/heating systems in China: Challenges and Opportunities

Providing free cooling from low temperature waste heat

OPTIMIZATION OF DISTRICT HEATING SYSTEMS

24th World Gas Conference ARGENTINA WOC 5.1: Industrial Utilisation CHP - Sharing on Gas District Cooling (GDC) in Malaysia

BUILDING FOR THE FUTURE

DISTRICT HEAT DRIVEN ABSORPTION COOLING OF DISTRICT COOLING PLANTS IN TRONDHEIM, NORWAY

Heat Recovery. Integrated CHP Systems Corp.

COMBINED CYCLE OPPORTUNITIES FOR SMALL GAS TURBINES

RES - Status Quo, Potential and Prospects Vasileios Tsolakidis, CRES

Absorption Chillers in Commerce

energiestro The most economical energy for remote sites Energiestro is an innovative system for energy production and storage.

Energy hub modelling and optimisation

DISTRICT COOLING IN FINLAND

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Energy efficiency of a solar domestic hot water system

Content. State of the Art in Solar Cooling. Solar cooling technology developments. Market developments & barriers

Deliverable 3.a (Combining former deliverables 3.1; 3.2; 3.5)

Cogeneration in a Hospital: a case Study

Small Scale CHP Using the Organic Rankine Cycle

Del 2.3 Technology specification for different E-HUB district scenarios

Large Solar Thermal Systems

DEVELOPMENT OF A HIGH EFFICIENCY ABSORPTION CHILLER-HEATER AND A COMPACT ABSORPTION CHILLER-HEATER

BIRMINGHAM DISTRICT ENERGY DELIVERING LOW CARBON ENERGY

SOME ENERGY-EFFICIENT TECHNOLOGIES IN JAPAN

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

RETScreen ICE AND CURLING RINKS Model

2. TECHNICAL DESCRIPTION OF THE PROJECT

ENERGY EFFICIENT SYSTEMS Recover & recycle your waste heat

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

DH/CHP in EU Smart Energy Cities Wroclaw, of March 2012

Turboden Biomass Solutions

Thomas F. Edgar University of Texas-Austin NSF Workshop on Shale Gas Monetization Montgomery, TX, March 27, 2014

NLP optimization of a methanol plant by using H 2 co-product in fuel cells

Advanced Solar Thermal (AST) SOLID Energy, Inc.

CHP and Enwave March 2017

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Available online at ScienceDirect. Energy Procedia 48 (2014 )

EFFICIENT SOLAR COOLING

Chromasun Micro-Concentrator

Project summary. 2 MW project Schalkwijk Haarlem Netherlands

8Combined Cooling, Heating and Power Technologies (CHP): An Overview

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

Development of 1MW high efficiency gas engine cogeneration system

Ground-Coupled Heat Pump And Energy Storage

EMERGING ENERGY TECHNOLOGIES FOR SUSTAINABLE BUILDINGS IN MALAYSIA

Heat Integration Across Plants Considering Distance Factor

Absorption Heat Pumps Current deployement and potential. Titre de la présentation

Action 3.1 GCHP Case Studies from Italy

obcbobk`bp=afpqof`q=eb^qfkd=pvpqbj= =Epl^=h~íK=ldNN=Ó=ldVF=

Chapter 2.7: Cogeneration

CLUSTER PROFILE PUNJAB DAIRY INDUSTRIES

Australian Solar Cooling 2013 Conference April 12th, 2013 North Ryde, Australia. All-in-oneSolar Thermal CoolingandHeatingSystem

Heat recovery from diesel engines and gas turbines

Gas vs. Diesel Generator Sets Performance Cost & Application Differences

Conceptual Design of Nuclear CCHP Using Absorption Cycle

Workshop Industrial application of SOFC systems: the DEMOSOFC project

Siemens Solar Energy. Buenos Aires, November 2011 By Rolf Schumacher R2 Siemens AG All rights reserved

Control Products & Systems OEM siemens.com/buildingtechnologies-oem

GAS TURBINE COGENERATION ACTIVITIES NEW POWER PLANTS FOR URALKALI S FACILITIES

LIFE CYCLE COST ANALYSIS OF WASTE HEAT OPERATED ABSORPTION COOLING SYSTEMS FOR BUILDING HVAC APPLICATIONS

EC CONCERTOII project REMINING-Lowex

Experiences from design studies, simulation studies and installations

Bifluid Geothermal System New Generation

Inventaire des installations de climatisation solaires en Europe Inventory of solar cooling installations in Europe

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Technology and Prospect of Process Heat Application of HTR(High temperature gas cooled reactor) Applications in Oil Refining Industry

Renewable Energy Based Active Cooling System

COMBINED HEAT AND POWER (CHP) MARKET MARKET SIZE, SEGMENTATION, REGULATIONS AND KEY COUNTRY ANALYSIS TO 2025

Sustainable Solutions In Energy & Environment

Renewable Energy Systems 10

TECHNIQUES OF CCHP AS A RIGHT WAY TO APPLY THE 2 ND LAW OF THERMODYNAMIC: CASE STUDY (PART ONE)

Energy Efficient Buildings in Germany An Introduction

Transcription:

ST-4 Polygeneration plant Parc de l Alba Cerdanyola del Vallès 1

2

POLYCITY project 5 Energy supply in Parc de l Alba 6 District Heating and Cooling network 8 ST-4 Polygeneration plant 10 Production of electricity and heating 11 Production of chilled water 13 Plant control 17 Energetic analysis including future expansions 19 ST-2 Renewable plant 21 Biomass gasification plant 21 Solar cooling plant 22 3

4

POLYCITY project The objective of the POLYCITY project, financed by the European Commission s initiative CONCERTO (VI Framework Programme), is to reduce the consumption of fossil and non-renewable fuels by means of: - Measures to reduce the energy demand of buildings. - Improvement in the energy efficiency of energy production and supply systems (polygeneration). - Increase in the use of renewable energy systems. The research undertaken in the framework of the project focuses on using technological innovation to save energy. In this regard, simulation processes are used to optimise energy production and to improve the design of buildings. POLYCITY supports various aspects of the urban development of three European cities: new buildings and the polygeneration system in the Directional Centre of Cerdanyola del Vallès (Barcelona), the rehabilitation of the Arquata district of Turin, and new buildings and the improvement of supply in Scharnhauser Park, a former military zone near Stuttgart. POLYCITY s innovation in these three urban areas is managed by the various regional partners who ensure that the results are effectively exploited and disseminated. The purpose of this leaflet is to present the first polygeneration plant installed in the Directional Centre of Cerdanyola del Vallès. For further information, please contact the Directional Centre Urban Development Consortium. Contact Consorci Urbanístic del Centre Direccional de Cerdanyola del Vallès Passeig d Horta 66-68 E-08290 Cerdanyola del Vallès Tel. (+34) 93 591 07 80 consorci@parcdelalba.cat www.parcdelalba.com www.polycity.net 5

Energy supply in Parc de l Alba The Polycity project is taking place in a 340-hectare site in Cerdanyola del Vallès. It will finally have a roof area of 1,890,000 m 2, a residential area for 15,000 inhabitants and an activity area that will create 40,000 jobs. A high efficiency energy system is to be implemented in the new urban development called Parc de l Alba (formerly known as the Directional Centre), in order to produce electricity, heating and cooling. This polygeneration system will comprise high efficiency natural gas cogeneration plants with thermal cooling facilities and a district heating and cooling network to connect the plant with the Science and Technology Park, the core of Parc de l Alba. Parc de l Alba will include a Science and Technology Park with the Synchrotron Light Facility (ALBA) as well as residential buildings. The polygeneration plant ST-4 will provide electricity, hot and chilled water for the Synchrotron and the technological park buildings through a four-pipe district heating and cooling network. The development is managed by the Consorci del Centre Direccional, consisting of the city council of Cerdanyola del Vallès and the Institut Català del Sòl. The foreseen DHC network and the polygeneration plants the following distribution: Foreseen energy supply plants and DHC network in Parc de l Alba 6

ST-4 Polygeneration Plant The Parc de l Alba in Cerdanyola del Vallès will be developed in several stages in line with the pace of the urban development: Phase I: construction of an energy production plant ST-4 in the technological park, to supply energy to the Synchrotron Laboratory (ALBA) and other users of the park (442,700 m 2 office space and 62,000 m 2 facilities). This stage was completed in July 2010. The ST-4 will use a district heating and cooling network to provide hot and chilled water simultaneously. Next phases: enlargement of the ST-4 plant and construction of three new energy supply plants (ST-2, ST-3 and ST-5). ST-4 Polygeneration Plant, double effect absorption chiller (left), natural gas boiler (center) and compression chiller (right) 7

District Heating and Cooling network District heating and cooling (DHC) is an integrative technology that can significantly reduce emissions of carbon dioxide and air pollution and increase energy security. The fundamental idea of DHC is to connect multiple thermal energy users through a piping network to environmentally optimum energy sources. The ability to assemble and connect thermal loads enables these sources to be used in a costeffective way. DHC is important for implementing cogeneration because it extends the pool of potential users of recovered thermal energy beyond the industrial sector to include commercial, institutional and multi-unit residential buildings. In Cerdanyola s Parc de l Alba new urban development, a District Heating and Cooling network will be implemented within the Science and Technology Park, which represents the core of Parc de l Alba, as well as the commercial area and some of the public and private equipment buildings. DHC network. Pipes instalation 8

The residential area has not been included in the DHC network, since its demand profile does not justify the additional investment required. As a result, the DHC network will cover heating and cooling demands of a total floor area of above 1,63 million m 2. This network, as a part of the Cerdanyola polygeneration system, has been designed according to criteria of maximum availability and modularity, and it will be connected to 4 cogeneration plants that will supply both hot and chilled water. The total length of the network will be 32,6 km. The implementation of the first stage of the district heating and cooling network has already been finished. It is a 4-tube network with diameters ranging from DN150 to DN800. It interconnects two cogeneration plants with all the land plots of this stage of urban development (around 600.000 m 2 of built surface) and has a total length of 15,3 km. The design temperatures are as follows: Chilled water: supply 6 ºC, return 13 ºC Hot water: supply 90 ºC, return 75 ºC Regardless of the district network, specific interconnecting pipelines have been designed to meet the requirements of the Synchrotron Light Laboratory. The Synchrotron building has been connected directly to ST-4 polygeneration plant, with the following pipelines: Chilled water: DN500 (508/630 mm) pre-insulated pipe, with diffusion barrier and builtin surveillance system. Total length: 770 m Hot water: DN150 (168/250 mm) pre-insulated pipe, with diffusion barrier and builtin surveillance system. Total length: 770 m DHC pumps in ST-4 plant 9

ST-4 Polygeneration plant This facility, which simultaneously produces electricity, hot and chilled water (known as a polygeneration power plant), provides service of exceptional quality and reliability and is therefore the main supplier of power to the Alba synchrotron. Generating power near the supply point avoids the significant energy loss of traditional systems during transport from large power plants to the many points of use. Additionally, the facility can supply a significant part of the demand for hot and chiller water by using residual energy, the heat given off during the production of electricity. Local generation and distribution of energy allows for much higher levels of energy efficiency, close to 86%, which is well above the levels achieved using traditional systems. This system reduces the use of primary energy sources and CO 2 emissions by up to 27% The main installations in the plant are: - 3 cogeneration engines, of 3.35 MW each. - 2 absorption chillers. - 1 natural gas boiler. - 1 electrical compression chiller. - 1 chilled water storage tank that enables the plant to shift demand peak loads. - A cooling tower ST-4 energy services 10

Production of electricity and heating Cogeneration engines The cogeneration engines are the main units of the ST-4 plant. The engines driven with natural gas produce electricity and heat (in the form of hot water and exhaust gases) that can be used to supply the heating demand and/or to produce cooling by means of absorption chillers. The high efficiency of these engines ensures the maximum energy efficiency of the input fuel. Jenbacher engine JMS 620 Currently the ST-4 polygeneration plant has three Jenbacher JMS 620 cogeneration engines. The nominal electrical capacity of each engine is 3,354 kw with a recoverable thermal energy of 3,102 kw (approximately). The electrical efficiency is 45% and the total efficiency is 86.5%. The number of engines installed can be increased from three to five as the amount of surface area increases, so the electrical output of the ST-4 (10 MW) can be increased to 16 MW. Energy performance for each engine (rated) 11

Exhausts gas outlet of one of the engines (left) Heat exchangers to produce hot water from the jacket water circuit (rigth) Natural gas boiler A natural gas boiler producing hot water up to 95 ºC has been installed as a backup, for peak demand periods or for periods of low energy demand. The hot water produced is injected directly into the district heating network. The gas burner capacity of the boiler is 5MW with a 90% efficiency. Natural gas boiler 12

Production of chilled water The heat produced by the cogeneration engines can be used to supply the heating demand or to produce cooling by means of absorption chillers. At present the ST-4 plant has installed two absorption chillers: a double effect absorption chiller driven directly by exhaust gases, and a simple effect absorption chiller driven by the hot water produced in the cogeneration engines. Double effect absorption chiller The Thermax ED 80C CX absorption chiller has a capacity of 5 MW and it is fired directly with the exhaust gases of the cogeneration engines. It has a high efficiency (COP = 1.3) and ensures good energy recovery from the exhaust gases. A second double effect absorption chiller also driven with exhaust gases and with a cooling capacity of 3 MW is foreseen as the demand grows. Energy performance for DE Absorption chiller (rated) Thermax ED 80C CX double effect absorption chiller 13

Exhausts gases inletoutlet and by-pass in the double effect absorption chiller Simple effect absorption chiller The simple effect absorption chiller produces chilled water using the hot water obtained from the cogeneration engines. This absorption chiller has an efficiency of COP = 0.75. A second simple effect absorption chiller with a nominal cooling capacity of 2 MW is foreseen as the cooling demand grows. Energy performance for the simple effect Absorption chiller (rated) Thermax LT105T simple effect absorption chiller 14

Compression chiller The purpose of the compression chiller is to produce cooling in peak demand periods when the capacity of the absorption chillers is not enough. A cooling capacity of 5 MW and a second compression chiller with the same characteristics is foreseen as the demand grows. Energy performance for the compression chiller (rated) Compression chiller Carrier 19XR8587 Cooling storage system An underground chilled water storage tank has been installed to enable the plant to shift demand peak loads. The tank can hold up to 4,000 m 3 meaning 7 MW for 2.5 hours with a temperature difference of 6ºC. A plate heat exchanger is used to charge or discharge the tank to the cooling network. Charge- Discharge operation of the cooling storage system (bottom temperature of the tank during five days) 15

Cooling tower Energy dissipated in the cooling tower (rated) The cooling towers dissipate the heat from a water stream at low temperature (37-30 ºC). All the heat produced in the oil refrigeration circuit of the engines, the condenser/absorber of the absorption chillers and the condenser of the compression chiller is dissipated in these cooling towers. Due to the operational characteristics of the absorption chillers, the cooling towers are indispensable if these chillers are to operate properly. The use of cooling towers to refrigerate the compression chillers means that they work at higher efficiencies than conventional applications. Cooling tower with a cooling capacity of 22 MW 16

Plant control A complete control system has been installed to ensure the reliability and security of the whole plant. The mass flow rate and the temperature for all the input and output streams of each unit are monitored so that the performance of each unit can be calculated individually. Several calculations are performed in order to calculate the efficiencies and the primary energy consumptions. Exhausts gases of the engines used to drive the double effect absorption chiller Production of chilled water with the absorption chillers and the compression chiller. 17

Monitored temperatures of the absorption chiller during five days The control system enables the production of energy (electricity, heating and cooling) to be calculated for the whole plant and for each unit. The primary energy consumption and the overall efficiency is calculated for the whole plant, as are the efficiencies of each unit. Energy production and efficiencies calculation 18

Energetic analysis including future extensions An energy analysis has been carried out for all the units envisaged (including future extensions) and the energy demand expected in 2014, so that the demands of the full operation of the plant can be taken into account. The objective of this energy analysis is to assess the energy savings of the polygeneration system with respect to conventional supply systems. The main units considered are listed below: 5 Jenbacher JMS 620cogeneration engines 2 double effect absorption chillers 2 simple effect absorption chillers 2 compression chillers Annual energy demand: Electricity: 32.7 GWh Heating: 17.0 GWh Cooling: 73.6 GWh Foreseen annual energy flow for 2014 considering the ST-4 plant 19

Foreseen annual energy flow for 2014 considering the conventional system The energy analysis was carried out bearing in mind the expected operational conditions of the engines and optimizing the operation of the rest of the plant in order to maximize the economic benefits. Considering this hypothesis, half the electricity produced is exported to the grid and the rest is used to supply the electrical demand of the Syncrotrhon Alba and other plant utilities. Taking into account the electricity exported to the grid (43.7 GWh/year), the net primary energy consumption is 105 GWh/year. The polygeneration system can be compared with a conventional system in order to assess the potential in energy savings. In the conventional system a highly efficient combined cycle is considered for the separate production of electricity (electrical grid) and individual boilers and compression chillers to produce heating and cooling, respectively. In comparison to the conventional system, the polygeneration system can save up to 27% of primary energy and CO 2 emissions. 20

ST-2 Renewable plant Besides the ST-4 polygeneration plant, more energy plants are planned as the energy demand grows. One of these, the ST-2 plant, uses renewable sources to produce electricity and chilled water. The ST-2 plant is currently at the engineering stage and consists of a solar cooling plant and a biomass gasification plant. ST-2 plant Biomass gasification plant In the biomass gasification process, the biomass is converted into a gaseous fuel, the major components of which are carbon monoxide and hydrogen. The gas produced is used as a fuel for a cogeneration engine and is usually contaminated with tar and dust that should be removed first. The electricity produced can be sold to the grid and the heating (hot water and exhaust gases) is used to drive an absorption chiller to produce cooling. The gasification plant is planned to have a capacity of 1,000 kg/h of biomass, which will provide an electrical output of 1 MW. Energy flow for the biomass plant 21

Gasification plant installed by Energia Natural de Móra S.L. producing 2,500 Nm 3 /h of synthesis gas with LHV 5,319 kj/nm 3 from 1,000 kg/h of wood residues Solar cooling plant The ST-2 plant has been planned to include a solar cooling plant. Combining thermal solar energy with thermal cooling equipment produces solar air-conditioning systems. These systems have the great virtue of satisfying the maximum cooling demand when most solar energy is available: i.e. in summer. They are used as a source of renewable energy that reduces the use of fossil fuels and consequently CO 2 emissions. In Parc de l Alba a solar thermal plant with a surface area of 1600 m 2 is to be constructed with flat plate solar collectors. These collectors will be connected to adsorption chillers that have a thermal output of 600 kw and which will provide 700 MWh of cold water at 7 ºC to be distributed by the district heating and cooling network. Annual energy balance in the solar cooling plant using evacuated tube collector 22

23

Polycity partners with the collaboration of 24