Designing a Snow Melting System for 5MWe Sabalan Geothermal Pilot Power Plant Project

Similar documents
Use of Geothermal Energy in Snow Melting and Deicing of Transportation Infrastructures

Technical Information

Renewable Energy Systems 10

Geothermal HVAC Systems - The Basics and Applications (Draft) George Hu, P.E., LEED AP Air Water Energy Engineers, Inc.

ACTIVE SOLAR SYSTEMS

White Paper. Geothermal Heating and Cooling

PEX EXPANDED POLYSTYRENE RADIANT-HEATING HYDRONIC PIPING FLOOR PANELS

Cooling Tower Operation

Solar Thermal. [Strategy]

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Energy Recovery Ventilation Equipment

Dynalene Ethylene Glycol Series

Heat Integration Schematic

Chapters 5, 6, and 7. Use T 0 = 20 C and p 0 = 100 kpa and constant specific heats unless otherwise noted. Note also that 1 bar = 100 kpa.

Great Ocean Rd Ice Creamery

ENGINEERING INFORMATION Hot water and steam service

ENERGY RECOVERY IMPROVEMENT USING ORGANIC RANKINE CYCLE AT COVANTA S HAVERHILL FACILITY

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

Low-Temperature District Heating and Earth Energy Systems By: Frank Lenarduzzi and Robert Mancini

Potential Reduction in Energy and Environmental Pollutants by Solar Assisted Ground Coupled Heat Pump Systems

GEOTHERMAL HEAT PUMPS CONFIGURATIONS/INSTALLATION

Size: length ft., bay width ft., number of bays: Square feet of floor space: Sq. ft. of bench/floor space covered by crops:

Interpretation of the Injection and Heat Up tests at Sabalan geothermal field, Iran

THERMAL ASSESSMENT OF PASSIVE COOLED FOUNDATION SOILS BENEATH THE TRANS-ALASKA PIPELINE AT ATIGUN PASS

Chilled Water Plant Redesign

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

A BASIC IMMERSION FIRETUBE FLOWNEX MODEL

Solar Thermal Radiant Heating at Pohakuloa Training Area

Heat exchangers and thermal energy storage concepts for the off-gas heat of steelmaking devices

EVALUATION SUBJECT: TEEL BQ POLYPROPYLENE (PP-RCT) PIPING SYSTEM

Green FSRU for the future

Ground-Coupled Heat Pump And Energy Storage

ENERGY SAVING IN BUILDING USING PCM IN WINDOWS

Geothermal Heating & Cooling in Health Care Applications

MDS TL5 Minimum Deflection Systems

ScienceDirect. Compact hot water storage systems combining copper tube with high conductivity graphite and phase change materials

INTERCOOL BIOGREENHeat Transfer Fluids. Renewably Sourced Susterra 1,3-Propanediol

Thermal Bridging in Residential Construction

TEP: Bite of Science Mechanical Engineering

Analysis of the air conditioning systems in a blown films manufacturing plant in the southeastern United States

Installation Instructions

Residential Swimming Pool Heating with Geothermal Heat Pump Systems

Designing Air-Distribution Systems To Maximize Comfort

Anti-icing & Anti-skid Overlay

Recent Technologies for Steam Turbines

POLICE DEPARTMENT. Bid Package SITE MAINTENANCE

This Technical Note is to notify you that Tecvalco has changed the brand of glycol in the CWT Heater. This change took affect in April 2016.

Solar Energy Overview

Roof & Gutter Ice/Snow Melting Design Guide

MDS TL4 Minimum Deflection Systems

EVALUATION SUBJECT: NIRON POLYPROPYLENE (PP-RCT) PIPING SYSTEM DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING

LEED Commissioning and Actual Energy Use. John Kokko, P.Eng. LEED A.P. Vice President Enermodal Engineering

EVALUATION AND DESIGN OF DOWNHOLE HEAT EXCHANGERS FOR DIRECT APPLICATION

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC

IECC Commercial Significant Changes Summary Tier I

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

INSIDE: ASHRAE Hall of Fame

downtown (Fig. E This enhances safety and has minimal costs (the original

Introduction to Environmental Physics

DOWTHERM and SYLTHERM Heat Transfer Fluids in Sub-Zero Systems

Large University Central Chiller Plant Design Considerations

Heat recovery from diesel engines and gas turbines

Review Questions for the FE Examination

1/58 Components of solar systems

Design guidelines for direct ground cooling systems in different climates

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

PROPOSAL FOR THE PROMOTION OF GEOTHERMAL HEATING FOR THE TOWN OF MONO. June 2009 CONTENTS

Soil Temperature Monitoring and Study of Geothermal Heat Pump Systems

Design of Experiment for Solar Water Heater Performance Analysis

Use of MathCad and Excel to Enhance the Study of Psychrometric Processes for Buildings in an Air Conditioning Course

AN ASSESSMENT OF CAPPED POLYALKYLENE GLYCOL TECHNOLOGY FOR CO 2 REFRIGERATION. Elizabeth Dixon

Secondary Coolant Systems for Supermarkets

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

GEOFAR : Innovative geothermal technologies Last modifications: BINARY PLANTS

GROUND THAWING & CONCRETE CURING REFERENCE GUIDE.

3/6/2017 Past president & currently on the board of directors for the Wisconsin Geothermal Association

Honeywell Refrigerants Improving the Uptake of Heat Recovery Technologies 1

is a possibility of the existence of permafrost as a result

WELLHEAD POWER PLANTS

Thermal cooling basin exploration for thermal calculations

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Geothermal Tunnel Linings. Principles of Geothermal Tunnel Linings

Heat Rejection using Cooling Towers

Energy Efficiency & Renewable Energy Resources

Solar Flat Plate Thermal Collector

Critical Structures Construction Issues

Chapter 9: Applications of the Laws of Thermodynamics

Susterra 1,3 Propanediol For Brewery Heat Transfer Fluids

CEN/TC 89 - Thermal performance of buildings and building components

Top of Line Corrosion and Water Condensation Rates in Wet Gas Pipelines

AR No. # Solar Thermal. Assessment Recommendation Savings Summary Source. Cost Savings Natural Gas. $984 * 1 MMBtu = 1,000,000 Btu

Metal Buildings and Condensation. Welcome to Metalcon Condensation Description. Program Objectives. Dew Point Temperatures

EVALUATION OF GROUND COUPLED HEAT PUMPS FOR THE STATE OF WISCONSIN

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

BUILDING FOR THE FUTURE

Thermal Performance of Nvelope NV1 Clip System

FLATE Hillsborough Community College - Brandon (813)

Moving Toward Net Zero Energy: Ideas on how to get there

7. Electrical Facility Ratings

Transcription:

Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Designing a Snow Melting System for 5MWe Sabalan Geothermal Pilot Power Plant Project Alireza Najafabadi, Morteza Sarikhani, Behnam Radmehr No 46, Third Alley, Shahid Arab St., After the Khaghani intersection, Damavand St, Tehran, IRAN Alireza.najafabadi@gmail.com, Morteza_sarikhani@yahoo.com, radmehr.beh@gmail.com Keywords: Geothermal, Snow melting, Power plant ABSTRACT The Sabalan geothermal field is a high-temperature area under development. Geothermal exploration was started in 1975 by the Ministry of Energy of Iran. After revolution in 1979 in Iran, it was stopped, and it was started again in 1998 by SUNA the Renewable Energy Organization of Iran. Three deep exploration wells and two shallow reinjection wells were drilled in 2002-2004 in three sites A, B and C, by SUNA beside the preparation of two sites D and E for new drilling. This area is about 16 km southeast of the town of Meshkinshahr. There is an overall potential for the generation of about 200 MWe over the greater prospect area. SKM (main consultants 1998-2006) assesses that commercial geothermal power generation can be achieved at Sabalan at a levelised cost of electricity of less than 5 USc/kWh. SUNA is planning to drill thirteen new wells, and build a 50 MWe power plant, when these wells will be drilled. As the first part of project, SUNA will build a pilot power plant in order to confirm, that a geothermal power plant can be operated in Iran. Moshanir was the consultant for civil work 1998-2006 and since 2006 the consortium of Moshanir, EDC and Lahmeyer was selected as main consultant for geothermal field that the new drilling was started since of 2008 till 2011. In this stage 5 deep wells were drilled and one of the previous well was be deeper. Well NWS-6D is the sixth drilled well in the second stage of exploration and third to be discharged. This well was flow tested in the time period of 7th September to 31th may in 2011 In this paper we discuss the designing of a hydronic snow melting system in above mentioned project. The snow melting system designing is presented based on criteria established by ASHRAE and supposed to be designed only for main access road from the administration building to the power house in the site of this geothermal pilot power plant, Geothermal energy is supplied to system through a heat exchanger so It is a closed cycle type and the fluid which is required for this system is supplied from a heat exchanger. The heating water which will be used in heat exchanger will be supplied from the silencer and separator drain. For designing the snow melting system we need to know about the location and the climatic condition of the power plant site which designing depends on such as the rate of snow fall, air temperature, relative humidity and wind velocity. Piping materials are cross linked polyethylene (PEX) tubing and applicable fittings due to corrosion Problems. 1. INTRODUCTION Snow melting using geothermal hot water and steam has been demonstrated in several countries, including Argentina, Japan and the United States. Snow melting in industrial applications is used where safe, clean and easy access is critical. These installations include sidewalks, roadways and bridges. Most commonly it is done with a glycol solution, hot water or steam being circulated in pipes within or below the area, using either heat pipes or geothermal fluids, however, in one instances hot water has been sprinkled directly onto it. In this paper we discuss the designing of the snow melting system in the Sabalan Geothermal Power Plant project. Figure 1.Snow Melting Implementation in Iceland 2. DESIGN CRITERIA Designing factors for snow melting systems depend on four atmospheric factors: (1) rate of snow fall, (2) air temperature, (3) relative humidity, and (4) wind velocity (ASHRAE Handbook, 1995). The snow melting system must first melt the snow and then evaporate the resulting water film. The rate of snowfall identifies the heat required to warm the snow to 32 o F and to melt it. The 1

evaporation rate of the melted snow from the road is affected by the wind speed and by the difference in vapor pressure between the air and the melted snow. Since the vapor pressure is established by the relative humidity and temperature of the air, and as the road surface temperature is usually fixed, the resulting evaporation rate varies with changes in air temperature, and wind speed. Convection and radiation loss from the melted snow depends on the film coefficient and the difference in temperature between the surface and air. The film coefficient is just a function of wind speed, and since the road temperature is fixed, convection and radiation losses vary with changes in air temperature and wind speed (ASHRAE Handbook, 1995). Chapman (1952) derives and explains equations for the heating requirement of a snow-melting system. Chapmanand Katunich (1956) derive the general equation for the required road heat output (q o ) in Btu/h.ft 2 : q o = q s + q m + A r (q e + q h ) (1) where q s, q m, A r, q e, q h are sensible heat transferred to the snow ( Btu Btu h.ft2.), heat of fusion (latent heat flux) ( h.ft 2.), ratio of snow-free area to total area (dimensionless), heat of evaporation ( Btu 2.), and heat transfer by convection and radiation(from snow-free surface) ( Btu 2.), respectively. h.ft The sensible heat q s to bring the snow to 32 o F is: h.ft q s = s c p ρ (32 t a ) / c 1 (2) where s, c p, ρ, t a, c 1 are rate of snowfall (inches of water equivalent per hour), specific heat of snow (0.5 Btu ), density of water lb. equivalent of snow (62.4 lbs/ft 3 ), air temperature ( ) and conversion factor (12 in/ft), respectively. For hot water (hydronic) systems, the above reduces to: q s = 2.6 s (32 t a ) (3) The heat of fusion q m to melt the snow is: q m = sh f ρ / c 1 (4) Where h f is enthalpy of fusion for water (143.5 Btu/lb). For hot water (hydronic) systems, the above reduces to: q m = 746 s (5) The heat of evaporation q e (mass transfer) is (for hydronic): q e = h fg (0.0201 V + 0.055) (0.188 p av ) (6) where h fg, V, p av are heat of evaporation at the film temperature (Btu/lb), wind speed (mph), and vapor pressure of moist air (inches of mercury), respectively. The heat transfer q h (convection and radiation) is (for hydronic): q h = 11.4 (0.0201 V + 0.055) (t f t a ) (7) where t f is water film temperature ( o F), usually taken as 33 o F. The solution of the general equation for q o for the required road heat output, requires the simultaneous consideration of all four climatic factors: wind speed, air temperature, relative humidity, and rate of snowfall (ASHRAE HANDBOOK, 2011 and John W. L,2000). Annual averages or maximums for the climatic factors should not be used because they are most likely not to occur simultaneously. It is thus necessary to investigate the various combinations that might occur at a site, based on several year s worth of data, to determine the critical combination that is most likely to be experienced (ASHRAE Handbook, 1995). Design climatic conditions and required weather data are collected as follows: 3. CLIMATIC CONDITIONS The climate in the area is relatively dry, especially during the summer months. The site is exposed to severe winter weather, including very high wind speeds of up to 180 km/h. Winter temperature has been measured as low as -30 C. The barometric pressure is 0.75 bar in site E. Table 1 shows some climate data on well site. 2

Table 1: Summary of weather data Annual Average Annual average Annual average Temperatur e ( C) Relative Humidity(% Precipitatio n Wind velocity(km 3.6 52 306-29 - - 50-30 - - - 3.1 Temperature The temperature fluctuations in the project area are large oscillating from -30 C in January to +35 C in June and July. The average monthly temperature in the project area is shown in Figure 20. Figure 2.Temperature variation in the project area 3.2 Humidity Figure 3.Monthly average relative humidity in the project area The humidity in the area is not very high due to high elevation and cold climate. The annual mean relative humidity in the study area is 59.5%. The monthly average relative humidity in the project area is shown in 03. 4. DESIGNING THE SNOW MELTING SYSTEM On the power plant plan (figure 4) the layout of the plant is shown. The area which is supposed to be designed for snow melting system is hatched. Figure 4: Power Plant Layout Hydronic system design includes selection of the following components: (1) heat transfer fluid, (2) piping, (3) fluid heater, (4) pump(s) to circulate the fluid, and (5) controls. With concrete slabs, thermal stress is also a design consideration. The Advanced Snow Melt Control is typically used in medium to large size residential, commercial and industrial areas, building entrances, parking ramps and lots, emergency entrances. Use this control when accurate ice and snow detection is required. Ensures energy savings of up to 80% compared to thermostatically controlled systems 3

In the first step of the designing our system we should choose the level of the system. We should consider the customer s intention and expectation of the snow melting system to select the correct design criteria level. There are 3 levels: Level 1 Residential Designed to keep the surface completely free of snow 95% of the time Occasional snow or ice buildup may occur Typically 5/8 Pextron tubing with 9 spacing (1/2 for small areas) Common applications: Residential applications Driveways Sidewalks Hot tub areas Level 2 Residential/Commercial Designed to keep the surface completely free of snow 98% of the time Typical level selection for most cases Typically 5/8 Pextron tubing with 6 or 9 spacing (3/4 for large areas) Common applications: Commercial and light commercial applications Public access areas to buildings Handicapped ramps Commercial stairways Level 3 Industrial/Critical Designed to keep the surface completely free of snow 99% of the time Advanced Snow Melt Control for sensitivity System must melt snow with no accumulation Typically 5/8 Pextron tubing with 6 spacing (3/4 for large areas) System idling often needed for quick response Common applications: Critical applications Hospital emergency ramps Helipads Access areas for emergency vehicles (fire stations, etc.) Areas deemed critical for public safety In summary Chapman (1957) classifies snow melting installation according to type as Class I, II or III. These types are described as follows: Class I (minimum): residential walks or driveways, interplant ways or paths Class II (moderate): commercial sidewalks and driveways; steps of hospitals Class III (maximum): toll plazas of highways and ridges; aprons and loading area of airports; hospital emergency entrances. 4

Considering the Client s expectation our system will be assumed as level 3(Class III). In the second step of the designing we should calculate the Snow melting load. 5. CALCULATING THE SNOW MELTING LOAD We use the equation which is mentioned in DESIGN CRITERIA section. Our data for this project due to the plans and climatic conditions are s= 0.24, C p = 0.5, ρ= 62.4, t a = - 23.8, c 1 = 12 So from (2) we have: q s = 0.24 0.5 62.4 (32-(-23.8) ) /12 q s = 34.81 Or for hydronic (hot water) (equation (3)) we have: Then we have h f = 143.5 therefore from (4) we have : or for hydronic (hot water) (equation (5)) we have: q s =2.6 0.24 (32-(-23.8) ) q s = 34.81 q m = 0.24 143.5 62.4 /12 q m = 179.08 q m = 746 0.24 q m = 179.04 Also we have values of V and H fg which are V=111.84, H fg = 1075.8 Btu/Ibm and for p av we know that Ø=p v /p g We have Ø=59.5% and p g =0.0062 psia at t=-22 o F from the thermodynamic tables therefore we have (1psi=2.036 in Hg): Therefore from (6) we have: And we have t f = 33 so from equation (7): P av =p v =0.595 0.0062 2.036 P av = 0.0075 in Hg q e =1075.8 (0.201 111.84 + 0.055) (0.188 P av ) q e =4375.85 q h =11.4(0.0201 111.84 + 0.055 (33- (-23.8) ) q h = 61.24 We assume that don t have any snow-free area therefore A r = 0 so finally from (1) we have: q o = 34.81 + 179.04 q o = 213.85 Btu/h.ft2 q o is our the heat output requirement. These values do not include back and edge heat losses; they must be added to get final heat output requirement 6. BACK AND EDGE HEAT LOSS Back and edge heat loss is the percentage of heat lost through the back and edge of the snow melt area. Back and edge heat losses may add up to 40% to the snow melting load, depending on: 1- Construction, 2- Insulation, 3- Exposure, 4- Operating temperature, 5- Ground temperature 5

By Multiplying the snow melting load (q o ) by the adjusting multiplier we can calculate the actual snow melting load. Most of designer companies suggest a multiplier with a value of 1.05 for projects Full Below but No Edge Insulation which is our case. Therefore the actual snow melting load will be: q o actual = 213.85 In the third step of the designing we should calculate the Tube Spacing. 7. TUBE SPACING Decreasing the tube spacing will allow the snow melting system to operate at lower fluid temperatures while meeting the heat output requirements. We choose the following values for spacing: 8. HEAT TRANSFER FLUID Circuit spacing 9 " Circuit offset from the wall 3" Circuit entry spacing 5" Not only because Glycols (ethylene glycol and propylene glycol) are the most popular in snow-melting systems but also because of their moderate cost, high specific heat, and low viscosity; ease of corrosion control we choose them as our Heat Transfer Fluid Automotive glycols containing silicates are not recommended because they can cause fouling, pump seal wear, fluid gelation, and reduced heat transfer. The piping should be designed for periodic addition of an inhibitor. Glycols should be tested annually to determine any change in reserve alkalinity and freeze protection. Only inhibitors obtained from the manufacturer of the glycol should be added. Heat exchanger surfaces should be kept below 140 C, which corresponds to about 280 kpa (gage) steam. Temperatures above 150 C accelerate deterioration of the inhibitors (ASHRAE Handbook,2009). We used the 50% Glycol Fluid type due to it s freezing point (about Freezing Point ( F) and our climatic conditions. Figure 5.Snow Melting Implementation in Iceland 9. DESIGNING THE SNOW MELTING SYSTEM WITH LOOP CAD 2013 We will use the Loop cad 2013 with to design snow melting system and to draw in needed drawings. Loop cad is an industry standard software for the creation of professional circuit layout drawings. The Professional Edition includes Residential Heat Loss Calculations (ASHRAE and CSA options), Hydronic Calculations (temperatures, flows, head losses), Snow Melt Design and Load Calculations, 3D CAD Views and OEM Software Add-ons for fully integrated design and quotations features. Here are the results of the designing with aforementioned software. The remaining of the results are in the appendix due to the longsome of the results. 6

CONCLUSION As it is shown in the results for each case, the required flow rate and source temperature to be supplied is calculated and based on our brine it is possible to provide the needed temperature and flow rate for the system. It should be mentioned that the equipment for implementation limit our design. For example the maximum temperature that can be used in pex al pex tubes is 150 (or 160) or the maximum flow rate of a manifold which can be used is 18 US GPM(or according to some manufacturer 22). Also total length of tubes should be lower than 150 ft. These recommendations are suggested by some of the snow melting equipment manufacturers and it is tried that the design complied with these suggestions. 7

ACKNOWLEDGEMENTS We would like to thank Mr. I. Ghaderi and Dr. S. Porkhial one for their assistance most sincerely. REFERENCES John W. L: PAVEMENT SNOW MELTING (2000) ASHRAE Handbook,. Heating, Ventilating, and Air-Conditioning Applications, Chapter 46 Snow Melting, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA(1995) ASHRAE Handbook, Fundamentals (2009) ASHRAE HANDBOOK, HVAC Applications (2011) APPENDIX 8

9 Najafabadi, Sarikhani and Radmehr

10

11 Najafabadi, Sarikhani and Radmehr

12

13 Najafabadi, Sarikhani and Radmehr

14

15 Najafabadi, Sarikhani and Radmehr