Use of IDF Curves Design of a roof drainage system

Similar documents
Learning objectives. Upon successful completion of this lecture, the participants will be able to:

HYDROLOGIC-HYDRAULIC STUDY ISABELLA OCEAN RESIDENCES ISLA VERDE, CAROLINA, PR

DIVISION 5 STORM DRAINAGE CRITERIA

The Islamic University of Gaza- Civil Engineering Department Sanitary Engineering- ECIV 4325 L5. Storm water Management

Appendix I OFFICE OF THE MORGAN COUNTY SURVEYOR STORMWATER DESIGN MANUAL 7/1/2008

ANALYSIS OF HYDRAULIC FLOOD CONTROL STRUCTURE AT PUTAT BORO RIVER

THE RATIONAL METHOD FREQUENTLY USED, OFTEN MISUSED

HYDROLOGIC MODELING CONSISTENCY AND SENSITIVITY TO WATERSHED SIZE

RAIN WATER HARVESTING FOR URBAN FLOOD PEAK REDUCTION

Hydrologic Study Report for Single Lot Detention Basin Analysis

ATTACHMENT C Design Analysis for Erosion Protection Cover for Piñon Ridge Tailing Cells

Overview of NRCS (SCS) TR-20 By Dr. R.M. Ragan

Storm Sewer Design. Bob Pitt University of Alabama and Shirley Clark Penn State Harrisburg

APPENDIX G HYDRAULIC GRADE LINE

Urban Drainage Introduction. A.Ramachandra Rao. C.B. Burke. T.T. Burke, Jr.

DRAINAGE & DESIGN OF DRAINAGE SYSTEM

PRELIMINARY HYDROLOGY STUDY

ROOF AND PROPERTY DRAINAGE

Highway Drainage 1- Storm Frequency and Runoff 1.1- Runoff Determination

Activity Calculating Property Drainage

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN PLANT GREENE COUNTY ASH POND ALABMA POWER COMPANY

Index. Page numbers followed by f indicate figures.

Summary of Detention Pond Calculation Canyon Estates American Canyon, California

Highway Engineering. 3 _ 2/2 Lecture/Laboratory Hours

1. Stream Network. The most common approach to quantitatively describing stream networks was postulated by Strahler (1952).

Updated Rainfall Coefficients for Texas The EBDLKUP-NEW.XLS Tool

IBS Site Drainage: Senior Design Project

PART 3 - STANDARDS FOR SEWERAGE FACILITIES DESIGN OF STORM SEWERS

TECHNICAL BULLETIN. Synthetic Turf Athletic Field Drainage Design Assistance

Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7: Hydraulic Design of Sewers and Storm Water Drains

Appendix J: Storm Conveyance Design Parameters

Software Applications for Runoff Hydrological Assessment

SEWAGE TREATMENT AND DISPOSAL

FLOOD INUNDATION ANALYSIS FOR METRO COLOMBO AREA SRI LANKA

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN PLANT BARRY ASH POND ALABAMA POWER COMPANY

Preliminary Drainage Analysis

APPENDIX IV. APPROVED METHODS FOR QUANTIFYING HYDROLOGIC CONDITIONS OF CONCERN (NORTH ORANGE COUNTY)

Treatment Volume: Curve Numbers. Composite CN or Not? Treatment Volume: Curve Numbers. Treatment Volume: Calculation. Treatment Volume: Calculation

PRELIMINARY DRAINAGE REPORT NEWCASTLE FIRE STATION OLD STATE HIGHWAY

Assessment of the Climate Change Impact on a Dry Detention Pond at Kota Damansara, Malaysia

HYDROLOGIC-HYDRAULIC STUDY BAYAMON SOUTH COMMERCIAL CENTER BAYAMON, PUERTO RICO. Casiano Ancalle, P.E. August, 2006 I.

Hydrology and Water Management. Dr. Mujahid Khan, UET Peshawar

Siphonic. Drain System. Engineered Water Solutions for Today s Building Design Needs

Water supply components

HYDROLOGY STUDY PREPARED FOR: MARKHAM PERRIS LLC 302 WEST FIFTH STREET, SUITE 103 SAN PEDRO, CA (310) FOR THE PROJECT:

ROOF TOP RAIN WATER HARVESTING. Manohar Patil

10.0 Storm Sewer Systems

The SuDS Manual Frequently asked questions

Drop Height For Channel Erosion Control

HYDROLOGIC & HYDRAULIC ASPECTS of the Walnut Street Bridge over the Schuylkill River Philadelphia, PA

Chapter H. Introduction to Surface Water Hydrology and Drainage for Engineering Purposes

Hydrology Study. For Bella Terrazza Portion of Lot 1, Block 39, Subdivision of S Tract, Rancho El Cajon El Cajon, CA 92021

Hydrology Study. Ascension Heights Subdivision Ascension Drive at Bel Aire Road San Mateo, California (Unincorporated)

MODELING AND RELIABILITY OF RAINWATER HARVESTING SYSTEM AT EDUCATIONAL INSTITUTION

Sizing Calculations and Design Considerations for LID Treatment Measures

CHAPTER 3 STORMWATER HYDROLOGY. Table of Contents SECTION 3.1 METHODS FOR ESTIMATING STORMWATER RUNOFF

HYDROLOGICAL INVESTIGATIONS IN SEMI-ARID AREAS CASE STUDY: RAILWAY CULVERT DESIGN IN LIBYA

Rainfall, Runoff and Peak Flows: Calibration of Hydrologic Design Methods for the Kansas City Area

iswm TM Technical Manual Hydrology:

La Riereta Catchment Sant Boi de Llobregat

MISMANAGEMENT OF STORMWATER MANAGEMENT A CASE STUDY

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART PLANT DANIEL ASH POND B MISSISSIPPI POWER COMPANY

CHAPTER 12 BRIDGE DECK DRAINAGE SYSTEMS

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART PLANT YATES ASH POND B (AP-B ) GEORGIA POWER COMPANY

Understanding. Hydraulics. palgrave macmillan. Les Hamill. University of Plymouth THIRD EDITION

Culvert Sizing procedures for the 100-Year Peak Flow

Flood hazard assessment in the Raval District of Barcelona using a 1D/2D coupled model

Facilities Development Manual

Ponds. Pond A water impoundment made by excavating a pit, or constructing a dam or an embankment.

Hydraulic Analysis of Storm Diversion System (SDS) of Hatirjheel Begunbari Lake of Dhaka City

TRENCH FORMER. ABT, INC., 259 Murdock Road, Troutman NC 28166, (800)

ESTABLISHMENT OF AN EMPIRICAL MODEL THAT CORRELATES RAINFALL- INTENSITY- DURATION- FREQUENCY FOR MAKURDI AREA, NIGERIA

The Texas A&M University and U.S. Bureau of Reclamation Hydrologic Modeling Inventory (HMI) Questionnaire

The Effects of Debris on the Flow Rates of Roof Drains and Scuppers

HY-12 STORM DRAIN SOFTWARE COMPARISON STUDY. Merrill M. Taylor. A project submitted to the faculty of. Brigham Young University

Hancor, Inc. Drainage Handbook Hydraulics 3-1

Chapter 6. Hydrology. 6.0 Introduction. 6.1 Design Rainfall

EART 204. Water. Dr. Slawek Tulaczyk. Earth Sciences, UCSC

Contact the Jurisdictional Engineer for materials allowed by each jurisdiction.

STORM WATER MANAGEMENT REPORT

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART PLANT YATES ASH POND 3 (AP-3) GEORGIA POWER COMPANY

Analysis of Runoff Reduction and Hydrologic Cycle Utilizing LID Concepts

Estimating Stormwater Runoff from the 3D-model of an Urban Area in Istanbul

Municipal Stormwater Ordinances Summary Table

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART PLANT BOWEN ASH POND 1 (AP-1) GEORGIA POWER COMPANY

ENGINEERING INFRASTRUCTURE REPORT 32 & 34 TENNYSON AVE, TAKAPUNA ISSUED FOR RESOURCE CONSENT

HYDROLOGIC CONSIDERATIONS. 22 nd Annual Nonpoint Source Pollution Conference Saratoga Springs, NY

What s so hard about Stormwater Modelling?

CIMAHI RIVER BENCHMARKING FLOOD ANALYSIS BASED ON THRESHOLD OF TOTAL RAINFALL

CHAPTER 6 COLLECTION SYSTEM HYDRAULIC MODEL

Appendix C. FSSR 14 Regional Growth Curves with Irish River Data. and. FSSR 16 (Greenfield) Rainfall Runoff Model Estimation

PLAN CHECK CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS 2014 LAPC

Measuring discharge. Climatological and hydrological field work

Overland Flow Time of Concentration on Very Flat Terrains

The role of domestic rainwater harvesting systems in storm water runoff mitigation

Design of Sewerage System for Jaffarpur area in Southwest New Delhi

Appendix B. Storm Drain System Data

ATTACHMENT 4: Design Calculations and Construction Details

Modelling and Analysis of EES Systems Using SWMM

Irrigation Rehabilitation Program Design and Construction Standards

Transcription:

Use of IDF Curves Design of a roof drainage system Your engineering firm is currently planning the construction of a residential apartment building in Davos, Switzerland. Your task is to design the roof drainage system of the building and particularly to estimate the diameter of: (a) the vertical leaders, (b) the vertical drains and (c) the horizontal drainpipes. A general layout of a roof drainage system is provided in Figure 1, whereas Figure 2 shows a schematic diagram of a roof drainage system. Based on the local regulations, the accepted level of risk for single buildings is the 50-year flood (i.e. flood occurring on average once in 50 years) of 10-min duration. The local rainfall intensity-duration-frequency curve (IDF curve) is provided in Figure 3. The roof covers an area, A, of 7440 m 2, the slope of the horizontal pipes leading from the vertical leaders to the wall (type a), S 1, is equal to 0.010 m/m and the slope of the horizontal pipes draining the interior leaders in the interior walls (type b), S 2, is equal to 0.042 m/m. Figure 1: General layout of a roof drainage system Figure 2: Schematic diagram of the roof drainage system 1

Rainfall intensity [mm/h] 120.0 100.0 80.0 60.0 40.0 IDF Curve for the station of Davos R = 2 years R = 5 years R = 10 years R = 25 years R = 50 years Power (R = 2 years) Power (R = 5 years) Power (R = 10 years) Power (R = 25 years) Power (R = 50 years) 20.0 0.0 0 5 10 15 20 25 30 Rainfall duration [h] Figure 3: Rainfall intensity-duration-frequency curve for the station of Davos Literature Chow, V.T., Maidment, D.R. and Mays, L.W. (1988). Applied Hydrology, New York. McGraw- Hill. McCuen, R.H. (2017). Hydrologic analysis and design. Fourth Edition. Department of Civil and Environmental Engineering. University of Maryland. Boston. Pearson. Summary of the solution procedure The first step of the design procedure is to select a layout for the roof drainage system determining the required number of vertical leaders. Next, the design rainfall intensity is to be estimated based on the IDF curve and the drainage regulations (i.e. estimation of the rainfall intensity for a specific hazard frequency and runoff concentration time). Once the roof drainage system layout and the design rainfall intensity have been estimated, the rational method, that will be discussed in detail in a following lecture on Flood Frequency Analysis, can be used to estimate the design discharge entering the horizontal pipes. The horizontal pipes diameter required to carry this discharge can be calculated by the Manning s equation assuming that the pipes are flowing full under gravity but are not pressurized. The diameter of the vertical leaders and drains may be estimated using the provided empirical equation. 2

Additional remarks and assumptions One vertical leader should be used per 930 m 2 of roof area The design rainfall intensity is obtained from the local IDF curve Pipe s flow is gravity driven but is not pressurized, so that the pipe capacity can be calculated by means of the Manning s equation for open channel flow The friction slope is set equal to the bed slope of the pipe The Manning s roughness coefficient n is 0.015 for all horizontal drainpipes The estimated diameter values should be rounded up to the next larger commercially available size The following pipe diameters in [mm] are available for roof drains: 50, 100, 150, 200, 250, 300, 400, and 450 Collection of formulas Rational Method Q = C i A (1) Pipe Capacity based on the Manning s Equation d = 3.21 Q d n 0.375 S 0.5 (2) Vertical leader and drain diameter (empirical equation) d = 0.573 Q d 0.375 (3) where: A is the drainage area [m 2 ] C is the runoff coefficient for the drainage area A d is the pipe diameter [m] d is the diameter of both vertical leaders and drains [m] i is the design rainfall intensity [mm/h] n is the Manning s roughness coefficient Q is the peak discharge rate [m 3 /s] Q d is the design capacity per pipe [m 3 /s] S is the slope of the pipe [m/m] 3

Appendix Table A 1: Runoff coefficients for use in the rational method (Chow et al., 1988) 4

Suggested solution Estimation of the number of vertical leaders Provided that one vertical leader should be used per 930 m 2 of roof area and the rooftop covers an area of 7440 m 2, the number of leaders, n, may be estimated as follows: n = rooftop area 7440 m2 = = 8 vertical leaders 1 leader per 930 m2 930 m2 Estimation of the design rainfall intensity The design rainfall intensity is obtained from the local IDF curve (Figure 3) and the local drainage regulations (i.e. duration and frequency of the rainfall). The local drainage regulations specify the following rainfall requirements: (a) a hazard frequency corresponding to 50-year return period and (b) a runoff concentration time of 10-min. Using the IDF curve provided in Figure 3, the corresponding rainfall intensity is computed as approximately 99.3 mm/h. IDF Curve for the station of Davos Rainfall intensity [mm/h] 120.0 100.0 80.0 60.0 40.0 R = 2 years R = 5 years R = 10 years R = 25 years R = 50 years Power (R = 2 years) Power (R = 5 years) Power (R = 10 years) Power (R = 25 years) Power (R = 50 years) 20.0 0.0 0 5 10 15 20 25 30 Rainfall duration [h] 5

Estimation of the flow capacity per vertical leader The total peak discharge rate, Q, may be specified using the design rainfall intensity, i, and applying the rational method (Equation 1). The value of the runoff coefficient may be determined using Table A 1. For a rooftop area and a hazard frequency corresponding to 50- year return period, the runoff coefficient is equal to 0.92. Q = C i A Q [m 3 s] = 0.92 99.3 [mm h] 7440 [m 2 ] [10 3 m 1 mm] [1 h 3600 s] Q = 0.19 [m 3 s] To determine the design flow capacity per vertical leader, Q d, one has to divide the total peak discharge rate, Q, by the number of vertical leaders, n. It is assumed that the total peak discharge rate is equally distributed to each vertical leader. Q d = Q n Q d [m 3 s] = 0.19 [m 3 s] 8 [leaders] Q d = 0.024 [m 3 s] Design of the roof drainage system The last step of the design procedure is to compute the size of the vertical leaders, the vertical drains, and the horizontal drainpipes. As observed in the layout of the roof drainage system (Figure 1) and estimated above, the system comprises of 8 vertical leaders and 4 vertical drains. Each vertical drain drains out two vertical leaders. Regarding the horizontal drainpipes, three different types exist: (a) 8 horizontal pipes leading from the vertical leaders to the wall, (b) 4 interior horizontal pipes, and (c) 4 horizontal pipes in the sections where the horizontal pipes of the interior leaders connect with the pipes of the exterior leaders. Vertical leaders The diameter of both vertical leaders and drains may be determined applying the empirical equation (3). The diameter of each vertical leader is as follows: d = 0.573 Q 0.375 d d [m] = 0.573 0.024 [m 3 s] 0.375 d = 0.142 [m] Given the available commercial diameters, a 150-mm leader is chosen. Vertical drains The diameter of each vertical drain is as follows: d = 0.573 Q 0.375 d d [m] = 0.573 0.048 [m 3 s] 0.375 d = 0.183 [m] Given the available commercial diameters, a 200-mm drain is chosen. In this case, the flow capacity per vertical drain is twice the flow capacity per vertical leader as calculated above because each vertical drain drains out two vertical leaders. 6

Horizontal drainpipes The diameter of horizontal pipes of any type may be determined applying the equation (2). The diameter of each horizontal pipe leading from the vertical leaders to the wall (type a) is as follows: d = 3.21 Q 0.375 d n 3.21 0.024 [m3 s] 0.015 0.5 d [m] = S 1 0.010 0.5 0.375 d = 0.188 [m] Given the available commercial diameters, a 200-mm horizontal pipe is chosen. The diameter of each interior horizontal pipe (type b) is as follows: d = 3.21 Q 0.375 d n 3.21 0.024 [m3 s] 0.015 0.5 d [m] = S 2 0.042 0.5 0.375 d = 0.143 [m] Given the available commercial diameters, a 150-mm horizontal pipe is chosen. The diameter of each horizontal pipe in the sections where the horizontal pipes of the interior leaders connect with the pipes of the exterior leaders (type c) is as follows: d = 3.21 Q 0.375 d n 3.21 0.048 [m3 s] 0.015 0.5 d [m] = S 2 0.042 0.5 7 0.375 d = 0.186 [m] Given the available commercial diameters, a 200-mm horizontal pipe is chosen.

In this case, the flow capacity is twice the flow capacity per drain as calculated above because each pipe drains out two vertical leaders. A slope of 0.042 m/m is assumed as well. 8