Installation Guide and Safety Manual Resilmount A237R (Resilient Sound Isolation Clips)

Similar documents
Installation Guide and Safety Manual

RSIC-1 SOUND ISOLATION SYSTEMS RSIC-1 INSTALLATION GUIDE

RSIC-1. RSIC-1, the Low Cost, High Performance, Noise control Solution. RSIC-1 specifications:

RESILIENT SOUND ISOLATION CLIPS

RSIC-1 RSIC-1 INSTALLATION GUIDE RSIC-1 SOUND ISOLATION CLIP CONCRETE CMU

SECTION SOUND ISOLATION

RSIC-1EXT04 SOUND ISOLATION CLIP RSIC-1EXT04 INSTALLATION GUIDE

Product Guide Specification

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD ASSEMBLIES

UL Design System HW-D-1012 continued

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19

Backer Box INSTALLATION

PinkWood Ltd. Revised September 29, 2017

Container Installation Guide

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications.

I-STUD Shaftwall System

BENEFITS OF GREEN GLUE IN STANDARD WALL CONSTRUCTION

1. The subfloor must be structurally sound and able to withstand live and dead loads with a deflection limitation of L/360.

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division

SECTION NON-STRUCTURAL METAL FRAMING

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

Shaftwall and Area Separation Wall Systems.

AND ACCESSORIES FOR DRYWALL CONSTRUCTION

I-STUD Shaftwall System

2012 & 2015 International Building Code. Section Section Section Section Section Section 713.4

It s not magic, it s engineering. Impact and Airborne Sound Control. GenieClip. US Patent No. 7,895,803

SECTION GYPSUM WALLBOARD SYSTEMS. A. Gypsum board at new wall partitions or where indicated on drawings. B. ASTM C442 - Gypsum Backing Board

Container Installation Guide

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

PLYWOOD FLOATING FLOOR

TYPICAL BEARING WALL FRAMING

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer)

R Code and Commentary for 2012 NC Residential Code final 03/06/13

SECTION B Steel Frame Wall Systems. Contents. Steel Stud Selection Tables. Introduction. Design Considerations. Installation.

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

Cavity ShAftwall System

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: HOMASOTE COMPANY

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

Shaftwall & Stairwell Systems Fire protection & sound isolation for shafts & stairwells

City of Republic Community Development Girder and Header Spans for Exterior Walls

PS 3000 Installation Manual Step-By-Step Procedures C.9. DOOR AND WINDOW OPENINGS C.9.1 PREPARE IN ADVANCE. C.9.2 VBUCK CONSTRUCTION.

The GlasRoc Shaftliner Type X advantage...

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000?

Rev. 07 8/15 Please Read Disclaimers:

INSTALLATION MANUAL. ZIP System R12 Sheathing. Contents. 07 ZIP System R12 Sheathing Window Installation 08 ZIP System R12 Sheathing Siding Guidelines

Document number CURTAIN FIRE DAMPERS

SECTION GYPSUM WALLBOARD. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

QuietRock 530 RF Application Notes

STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

SLOTTED STUD WIND-LOAD & NON-LOAD BEARING DEFLECTION WALL SYSTEM. U.L. FIRE RATED Head-of-Wall Joint Systems

Residential Building Inspections

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing

1. Interior gypsum wallboard. 2. Exterior gypsum board panels for ceilings and soffits. 3. Tile backing panels.

PATENTS ARE PENDING. Building Dimensions. Exterior Dimensions Roof Edge to Roof Edge

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

GLASS WALL SPECIFICATIONS

CEILING & WALL SYSTEMS

Light-Metal Roof Edge, Raised

SECTION COPPER WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.***

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Floors Walls Ceilings

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code

2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

Siding and Soffit Installation Guidelines

Gypframe profiles. Dimensional specifications

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

Section HIGH-TENSION Stretched-Fabric Wall Systems SoftWalls, Inc.

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER

INSTALLING MrPEX TUBING

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

GypLyner (walls) Metal framed wall lining system. GypLyner.

LISTING INFORMATION OF Weyerhaeuser - TJI Joists SPEC ID: 26948

Drywall and Plastering

Temporary Construction Loads Over I-Joist Roofs And Floors

BEARING METAL STUD FRAMING

SECTION ROOF SPECIALTIES

138 H-STUD AREA SEPARATION WALL SYSTEM

STEP UP SHOWER BASE INSTALLATION GUIDE FOR TIMBER AND CONCRETE FLOORS

GLASS WALL SPECIFICATIONS

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.

The System Slotted Deflection Track (pat# 5,913,788)

Fire Barrier Duct Wrap 615+

FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION

Smarter. Safer. Leaner.

General. Moisture. Secondary Water-Resistive Barrier. Storage. Gaps & Sealants. Stud Spacing. Flashing, Windows, Doors & Openings

Transcription:

Installation Guide and Safety Manual Resilmount A237R (Resilient Sound Isolation Clips) 3" RESILMOUNT A237R SPECIFICATIONS 1d " f" Width...1.375 inch Height...3.25 inch Depth...1.125 inch Weight....025 lbs Max Spacing...48 on center Max Load...36 lbs 1 ¼" 2 ½" Max Where to find hat channel? Call Dietrich Metal Framing to find a dealer near you 877-474-4052 x1 Ask for 25 gauge 7/8 Drywall Furring Channel (other names can be Hat Channel or HI Hat Channel). NOT Resilient Channel. " HAT (FURRING) CHANNEL SPECIFICATIONS Gauge:...25 gauge with hemmed edge Depth:... f" Width Top:...1 ¼" Width Bottom:...2 ½" max When splicing hat channel, overlap 6 inches in between two Resilmount Clips. Secure the channel with two 7/16 framing screws or 18 gauge tie-wire can be used. * Available at your local building supply stores FASTENERS A B C 2 ½" 1 " 2 ¼" (A) Wood: #8 x 2 ½ Coarse Threads (B) Steel: #8, 10 or 12 x 1 5 8 Self-tapping Type S (C) Concrete: 3 16 dia. x 2 ¼ Anchor screws DO NOT fasten Resilmount clips to framing members with nails. Use only approved screws. SOUNDPROOFING ACCESSORIES Solutions for living life quietly 98 12TH STREET SAN FRANCISCO, CA 94103 888 / 927 / 7496 PH 415 / 864 / 4447 FX WWW.WESTCOASTSOUNDSOLUTIONS.COM Sealtight Outlet Pads Silenseal Acoustic Sealant

WALL INSTALLATION GUIDE NOTES Resilmount A237R shall not exceed 48 inches on center. Spacing between hat channels shall not exceed 24 inches. Fasten the Resilmount A237R to the substrate with a fastener approved for a minimum pull-out and shear of 120 lbs. Locate the bottom row of Resilmount A237R within 3 inches of the floor. (May be adjusted lower to accommodate installation of baseboard.) Hat Channels are installed horizontal to the floor. Use a 4 foot level to ensure that Resilmount A237R and hat channels are installed horizontal and level. Install the drywall vertically from the bottom up leaving a 1/4 thick gap around perimeter of wall to be filled with acoustical caulk. Caulk around the entire perimeter of the gypsum board. STEP 1 Review Sound Isolation Company s layout guidelines before starting installation of walls or ceilings. (See page 7 ) We suggest installing the ceiling first, before installing the walls. STEP 2 Space Resilmount A237R so not to exceed 48 on center. Secure clips with a single fastener through the middle screw hole in clip. (Fig 2.1) Wood: Steel: Use #8 x 2-1/2 coarse thread screws Use #8, 10 or 12 x 1-5/8 Type S self-tapping screws Concrete: Use 3/16 dia x 2-1/4 Tapcon or equal anchor Figure 2.1: Screw clips into stud wall STEP 3 Snap hat channel onto Resilmount A237R. (Fig 2.2) Optional Method for Steps 2 & 3 (When using 25 Guage Furring Channel) Figure 2.2: Snap hat channel into clip Snap clips onto furring channel. Hand slide clips to proper location on the furring channel before installing it on the wall. Once located on the wall use a 4 foot level to ensure you are installing the clips and channel horizontal and level. Fasten both ends of the clip to secure the channel. 2 of 5

STEP 4 The floor shims are critical to ensure best results. Place 1/4 shims on the floor in front of sole plate (Fig 3.1). Install the first row of drywall vertically against the wall (Fig 3.2). Attach drywall to channel following local building codes. Note: Only remove the shims after all the gypsum board is completely screwed to all the hat channels. STEP 5 Figure 3.1: Place shims on floor in front of base plate Use acoustical caulk around the entire perimeter of each wall. (See Figure 3.3) LOAD SPECIFICATION FOR RESILMOUNT CLIP A237R Clips are designed to carry hat channel with one or more layers of gypsum wallboard attached. The load capacity of the clip depends on the number and spacing of clips used. The maximum design load capacity for the A237R Clips in shear (wall application) or in tension (ceiling application) is as follows. Design load calculations are based on tested loading to failure where the furring channel deforms. Figure 3.2: Install drywall vertically to hat channels Standard Clip Spacing Load Capacity 2:1 safety factor 2.5:1 safety factor* A237R with 25 gauge steel Hat Channel 45 lbs 36 lbs * Suggested safety factor of 2.5:1 for more critical life safety applications Note: 5/8 thick gypsum wallboard weighs 2.3 lbs/sq ft. 1/2 thick gypsum wallboard weighs 1.85 lbs/sq ft. Where to find hat channel? Call Dietrich Metal Framing to find a dealer near you 877-474-4052 x1 Ask for 25 gauge 7/8 Drywall Furring Channel (other names can be Hat Channel or HI Hat Channel). NOT Resilient Channel. Figure 3.3: Use Acoustical Caulk around the perimeter and edges GENERAL INFORMATION All potential sound leaks such as gaps around outlets, windows, door frames, pipe penetrations, etc should be sealed with a non-hardening acoustical sealant or resilient putty. See Sound Isolation Company s Sealtight Putty Pads, for even better results. Wall and ceiling assemblies and the specific construction requirements are listed at: www.soundisolationcompany.com/sealtight Figure 3.4: Tape and mud drywall 3 of 5

CEILING INSTALLATION GUIDE NOTES Resilmount Clip shall not exceed 48 on center Spacing between hat channels shall not exceed 24 Fasten the Resilmount to the substrate with a fastener approved for a minimum pull-out and shear of 120lbs. Locate the first row of Relimount Clips with 6" of the wall and within 6" of the opposite wall. Hat Channels are installed perpendicular to the joists Install the gypsum board leaving a 1/4 thick gap around perimeter to be filled with acoustical caulk. Caulk around the entire perimeter of the gypsum board. STEP 1 Review Sound Isolation Company s Resilmount Clip layout guidelines before starting installation of walls or ceilings. (See page 8 ) We suggest installing the ceiling first before installing the walls. STEP 2 Space Resilmount Clips so not to exceed 48 on center. Secure Resilmount Clips with a single fastener through the top screw hole in clip. Wood: Steel: Use #8 x 2-1/2 coarse thread screws Use #8, 10 or 12 x 1-5/8 Type S self-tapping screws Concrete: Use 3/16 dia x 2-1/4 Tapcon or equal anchor Figure 5.1: Screw A237R into joists STEP 3 Secure with screw/anchor into floor joists. (See Figure 5.1) Snap Hat Channel into Resilmount Clips. (See Figure 5.2) Figure 5.2: Snap Hat Channel into Clip Optional Method for Steps 2 & 3 (When using 25 Guage Furring Channel) Snap clips onto furring channel. Hand slide clips to proper location on the furring channel before installing it on the ceiling. Once located on the ceiling use a 4 foot level to ensure you are installing the clips and channel horizontal and level. Fasten both ends of the clip to secure the channel. 4 of 5

Walls & Ceilings Usage (7/8 hat channel, 24 o.c.) 1-4 5-8 9-12 13-16 17-20 21-24 25-28 29-32 33-36 37-40 1-3 4 6 8 10 12 14 16 18 20 22 3-5 6 9 12 15 18 21 24 27 30 33 5-7 8 12 16 20 24 28 32 36 40 44 7-9 10 15 20 25 30 35 40 45 50 55 9-11 12 18 24 30 36 42 48 54 60 66 11-13 14 21 28 35 42 49 56 63 70 77 13-15 16 24 32 40 48 56 64 72 80 88 15-17 18 27 36 45 54 63 72 81 90 99 17-19 20 30 40 50 60 70 80 90 100 110 19-21 22 33 44 55 66 77 88 99 110 121 21-23 24 36 48 60 72 84 96 108 120 132 23-25 26 39 52 65 78 91 104 117 130 143 25-27 28 42 56 70 84 98 112 126 140 154 27-29 30 45 60 75 90 105 120 135 150 165 29-31 32 48 64 80 96 112 128 144 160 176 31-33 34 51 68 85 102 119 136 153 170 187 33-35 36 54 72 90 108 126 144 162 180 198 35-37 38 57 76 95 114 133 152 171 190 209 37-39 40 60 80 100 120 140 160 180 200 220 39-41 42 63 84 105 126 147 168 189 210 231 Walls & Ceilings Usage (7/8 hat channel, 16 o.c.) 1-4 5-8 9-12 13-16 17-20 21-24 25-28 29-32 33-36 37-40 1-2 4 4 6 8 10 12 14 16 18 20 22 2 4-4 8 12 16 20 24 28 32 36 40 44 4-5 4 10 15 20 25 30 35 40 45 50 55 5 4-6 7 12 18 24 30 36 42 48 54 60 66 6 7-8 14 21 28 35 42 49 56 63 70 77 8-9 4 16 24 32 40 48 56 64 72 80 88 9 4-10 7 18 27 36 45 54 63 72 81 90 99 10 7-12 20 30 40 50 60 70 80 90 100 110 12-13 4 22 33 44 55 66 77 88 99 110 121 13 4-14 7 24 36 48 60 72 84 96 108 120 132 14 7-16 26 39 52 65 78 91 104 117 130 143 16-17 4 28 42 56 70 84 98 112 126 140 154 17 4-18 7 30 45 60 75 90 105 120 135 150 165 18 7-20 32 48 64 80 96 112 128 144 160 176 20-21 4 34 51 68 85 102 119 136 153 170 187 21 4-22 7 36 54 72 90 108 126 144 162 180 198 22 7-24 38 57 76 95 114 133 152 171 190 209 24-25 4 40 60 80 100 120 140 160 180 200 220 25 4-26 7 42 63 84 105 126 147 168 189 210 231 26 7-28 44 66 88 110 132 154 176 198 220 242 28-29 4 46 69 92 115 138 161 184 207 230 253 29 4-30 7 48 72 96 120 144 168 192 216 240 264 30 7-32 50 75 100 125 150 175 200 225 250 275 32-33 4 52 78 104 130 156 182 208 234 260 286 33 4 34 7 54 81 108 135 162 189 216 243 270 297 34 7-36 56 84 112 140 168 196 224 252 280 308 36-37 4 58 87 116 145 174 203 232 261 290 319 38 4-40 60 90 120 150 180 210 240 270 300 330 Disclaimer: These application notes represent the accepted procedures for successful installation. These suggestions may be followed, modified, or rejected by the owner, engineer, contractor, and/or their respective representative(s) since they, not Sound Isolation Company, are responsible for planning and executing procedures appropriate to a specific application. Sound Isolation Company reserves the right to alter these suggestions and encourages contact with the factory or its representatives to review any possible modification to these application notes prior to commencing installation. It is the responsibility of the owner, engineer, contractor, and/or their respective representative(s) to ensure that installation meets all applicable Building Codes. There is no performance warranty expressed or implied for any particular project or installation. 5 of 5