CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING

Similar documents
DIVISION 1100 TRAFFIC

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy.

CONSTRUCTION STANDARDS SECTION CS 3 TRENCH FOUNDATION, BEDDING AND BACKFILL

(Condensed from National Electric Code)

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

CHAPTER 11 CONDUITS AND FITTINGS

A. Product Data shall be provided for each type of product indicated.

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

CONDUITS AND FITTINGS

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

Section 2: Underground

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

Electric Service Standards

SECTION LUMINAIRES AND ACCESSORIES

Engineering Department. Street and Safety Lighting Standards and Guidelines

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

TEMPORARY METER POLE INSTALLATION

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

SECTION OUTLET, PULL, AND JUNCTION BOXES

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

SERVICE LINES, METERS AND APPURTENANCES

SECTION GROUNDING AND BONDING

Welcome to Douglas County PUD

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables

Specifications for Residential Underground Electric Service Installation

Douglas County Traffic Signal Installation Guidelines (January 2013)

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

1.1 Related Work.1 Electrical Pathway Lighting Design Spec.: Section 16010

SECTION INSULATED WIRE AND CABLE

Project: Type: Qty: Optics. Series. Reflector Mounting Lamping Finish Voltage Options BLC - S BLC-L 21 1 /4" 36 1 /4" 3 1 /2" O.D.

OPERATING PROCEDURE NO. 310

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

HANDHOLES, PULLING VAULTS AND JUNCTION BOXES

SECTION SPORTS FIELD LIGHTING

UNIFORM STANDARD DRAWINGS CLARK COUNTY AREA, NEVADA YEAR 2015 REVISIONS

SECTION HIGHWAY GRADE CROSSING WARNING SYSTEMS

Basic Service. This Section provides information regarding a. Introduction

Public Works Division Lighting District Supplemental Specifications For Solar School Flashing Beacon Installation March 2007

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

ITEM 460 REINFORCED CONCRETE PIPE Description. This Item shall govern for the furnishing of reinforced concrete pipe.

RICHFIELD CITY CONSTRUCTION STANDARDS

PRIMARY LINE EXTENSION

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL)

Underground Piping for Private Hydrants & Sprinkler Supply Line

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

All service lines shall conform to the following requirements:

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

CONSULTANT PROCEDURES & DESIGN GUIDELINES Electrical Manholes and Handholes UNIVERSITY OF MISSOURI

Gainesville Technical Center 5399 Wellington Branch Drive Gainesville VA Phone (703)

This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems.

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS

Solar Powered TS1000 Installation Pictures. (Trench and Fill Method) City of Vallejo, CA

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION STORM DRAIN

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

Specifications for Residential Overhead Electric Service Installation

Basic Requirements for Residential Electrical Installations

UNDERGROUND SERVICES SECONDARY

GV 001 Equipment Bases and Enclosures General Information

Underground Service Requirements and Instructions

UNITED NATIONS DEVELOPMENT PROGRAMME ITB

WOOD POLE SPAN WIRE SIGNAL SYSTEMS

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

Modular CABANA Kit 16 x 16 (6x6) Lumber: Western Red CEDAR #1 (Cabinet) Shingles: 5X / 16" long / 1/2" thick or 16 oz. copper

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Series - 1

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year

Large Basic Service. This Section applies to members requiring new. Introduction. Service Types

SECTION STORM DRAINAGE UTILITIES. B. Section : Site Restoration and Rehabilitation

SECTION 716 SIGN MATERIALS SCOPE

DISCONTINUED CFL. Specifications. Compact Floodlights revision 11/13/14 kl_cfl_spec.pdf. Fixture Options: Approvals: Job: Fixture Catalog number:

Electric Service Handbook

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISIONS FOR BUY AMERICA

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

SECTION HEAT TRACING FOR PLUMBING PIPING

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

SECTION SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS. Display hidden notes to specifier. (Don't know how?

The following is a summary of parameters for preparation of a traffic impact analysis when such analysis is required by the City of Highland:

SECTION A1 EXCAVATION AND BACKFILL GENERAL

Electric Service Standards

SECTION CHAIN LINK FENCES AND GATES

Transcription:

CONSTRUCTION STANDARDS SECTION CS 15 STREET LIGHTING CS 15-0l SCOPE: Street Lighting improvements shall be constructed in conformance with Section 86, Signals, Lighting and Electrical Systems, of the CALTRANS Standard Specifications and the requirements of the National Electric Code (NEC) except as modified by the City Standard Specifications and Standard Drawings. The stricter requirement shall apply in the case of conflicting information between the CATRANS Standard Specifications, the NEC, and the City Standard Specifications and Standard Drawings. The work shall consist of furnishing and installing luminaires containing an integral ballast system, with high pressure sodium lamps, photoelectric cells; electrolier standards, electrolier arms and foundations, conduit and conductor wiring and all other materials and appurtenances in accordance with the Project Plans and these specifications. CS 15-02 MATERIALS AND CONSTRUCTION: All materials and construction shall be in compliance with this section of these specifications. A. All materials delivered to the job shall be new, best quality of their respective grades, in accordance with the following specifications and packed in their original sealed containers. All materials to be installed shall bear the Underwriters Laboratories., Inc. (U.L.) label. B. The Contractor shall use materials mentioned in these specifications as standard, and in no case will a substitute be allowed without written approval of the City Engineer/Director of Public Works. C. All work and material shall be protected at all times. Conduit openings shall be closed with protective caps during installation and all materials shall be covered and protected against dirt, water and mechanical or other injury. All materials damaged during course of construction shall be replaced or repaired to original condition by the Contractor. D. The Contractor shall not allow or cause any of his work to be covered up or enclosed until it has been inspected, and approved by the Director of Public Works. Should any of the work be enclosed or covered up before such inspection, the Contractor shall, at his own expense, uncover the work and, after it has been inspected and approved, make all repairs with such material as may be necessary to restore all work to its original and proper condition. E. The Contractor shall furnish and install the street lighting equipment in accordance with the criteria shown in Table CS 7-1 Approved Street Light Equipment and all other requirements specified within these City Street Lighting CS-15-1 CS-SEC15 REV 11 March 2008

Standard Specifications. The Luminaire and Mounting type shall conform to the Project Plans and these specifications. TABLE CS 15-1 APPROVED STREET LIGHT EQUIPMENT Luminaire and Mounting Type Cobra Head on single electrolier arm Cobra Head on single electrolier arm Decorative Post Top Type Mount Decorative Post Top Type Mount Decorative Tear Drop Mount on single electrolier arm Where allowed by street classification Cul-de-sac, Residential and Collector Arterial Cul-de-sac and Residential Approved fixture 1 Pole Height Mounting Height GE M-250R2 or 31 32 6 equal 2 GE M-250R2 or 31 32 6 equal 2 Lumec AT 30-70HPS-SHA3M- ACDR-QTA/120- PH8-HS- GN8TX/RAL6012 Collector Lumec AT 30-100HPS-SHA3M- ACDR-QTA/120- PH8-HS- GN8TX/RAL6012 Arterial Lumec RN20-200HPS-THA3- ACDR-QTA/120- SMA-PH8-HS- GN8TX/RAL6012 15 17 15 17 27 6 30 1 The luminaire fixture shall be classified as Type III Distribution unless otherwise noted on the Project Plans. The Luminaire fixture and mounting height for Industrial Streets are designed on a case by case basis and shall conform to the requirements shown on the Project Plans. 2. Each fixture shall include a regulator ballast, a photo-electric receptacle for a twist lock photo cell, and not include a power door option. The 70 and 100 watt fixtures shall include a glass or acrylic drop lens and 200 watt fixtures shall include a glass drop lens except that lighting installed on traffic signal installations shall include a flat glass lens. CS 15-03 FOUNDATIONS: Foundations shall be cast-in-place and in conformance with Section 86-2.01 Excavating and Backfilling, and Section 86-2.03, Street Lighting CS-15-2 CS-SEC15 REV 11 March 2008

Foundations, of the CALTRANS Standard Specifications except as amended herein and the Standard Drawings. CS 15-04 ELECTROLIER STANDARDS: Electrolier standards shall be defined for the purpose of these Standard Specifications to include the pole, base, and base cover. Electrolier Standards shall conform to the Standard Drawings and the following requirements: A. Each standard shall have an identification Street Light number sticker in black, installed in accordance with the Standard Drawings. The Street Light numbers will be shown on the plans. B. The hand hole shall be oriented on the pole so that a technician while facing the hand hole is also facing oncoming traffic. C. All electrolier standards shall be furnished with a grounding lug or nut installed opposite the hand hole/removable access door and inside the standard. D. Cobra Head Electrolier Standards: Electrolier standards for Cobra head fixtures shall conform to the Standard Drawings and the following criteria: 1. The poles shall consist of galvanized steel material with a minimum thickness of 11 gauge. 2. The poles shall be single-arm poles unless the Project Plans specify otherwise. D. Decorative Post Top Type Mount Electrolier Standards: Electrolier standards for Decorative Post Type fixture shall conform to the Standard Drawings and the following: 1. The electrolier standard shall consist of an aluminum one piece unit which includes the pole with an aluminum structural base and a removable base cover and shall conform to the Standard Drawings. 2. The electrolier standard pole shall be tapered and fluted. 3. The electrolier standard shall be powder coated color Lumec GN8TX/RAL#6012 (dark green). E. Decorative Tear Drop Type Mount Electrolier Standards: Electrolier standards for Decorative Tear Drop Type fixtures shall conform to Standard Drawings and the following: 1. The electrolier standard shall consist of a steel pole and a cast iron split decorative base. 2. The electrolier standard (pole and base) shall be tapered and fluted. 3. The electrolier standard shall be powder coated color Lumec GN8TX/RAL# 6012 (dark green). Street Lighting CS-15-3 CS-SEC15 REV 11 March 2008

CS 15-05 ELECTROLIER ARMS: Electrolier Arms shall conform to the Standard Drawings and the following requirements: A. Cobra Head Electrolier Arms: The electrolier arms for Cobra Head Luminaires shall be six (6) long unless otherwise specified and shall consist of 11 gauge galvanized steel. B. Decorative Tear Drop Mount on single electrolier arms: The electrolier arms for Decorative Tear Drop Mount on single electrolier arms shall be six (6) feet long unless otherwise specified and shall consist of aluminum material powder coated color RAL6012 (dark green). CS 15-06 CONDUIT: Conduit shall be furnished and installed, conforming to the Standard Drawings, the requirements of Underwriters Laboratories Publication UL 543, and the following: A. Conduit shall be 1½ PVC, Schedule 40 conduit. B. Cutting and machining of conduit shall be in accordance with manufacturer s recommendations. Pre-assembly of sections of conduit shall not be permitted except where jacking is required. C. Pulling bells shall be installed on the ends of conduit terminating in pull boxes and electrolier standards. D. The installation of conduit shall conform to the following: 1. Excavation and Backfill for conduit installation shall conform to Sections CS 2, Trench Excavation, and CS 3, Trench Foundation, Bedding and Backfill, of the City Standard Specifications except as amended by this Section CS 15, Street Lighting, of the City Standard Specifications and the Standard Drawings. a. The conduit shall be laid over two inches of uniformly spread sand, and shall be covered by a minimum of 6 inches of sand. b. See section CS 3-07, Rockwheel Trench, for requirements when conduit is installed within existing street pavement (asphalt concrete paved) areas. However, the conduit may be installed with 18 inches of cover provided that the trench is excavated and backfilled in accordance with Section CS 3-07, Rockwheel Trench, of these City Standard Specifications. CS 15-07 PULL BOXES: Pull boxes shall conform to the provisions of Section 2.06, Pull Boxes, of the CALTRANS Standard Specifications as amended herein by this Section CS 15, Street Lighting, of the City Standard Specifications and Standard Drawings. A. Pull boxes shall be precast reinforced concrete, CALTRANS #3 1/2 Box with brass hold down bolts. Street Lighting CS-15-4 CS-SEC15 REV 11 March 2008

B. The cover shall be marked Street Lighting. C. Grout shall not be placed in the bottom of the pull box. CS 15-08 CONDUCTORS AND WIRING: Conductors and wiring shall conform to the provisions of Section 86-2.08, Conductors, and Section 86-2.09, Wiring, of the CALTRANS Standard Specifications as amended herein by this Section CS 15, Street Lighting, of the City Standard Specifications and Standard Drawings. A. Conductors shall be AWG and THWN copper stranded conductor Underwriters Laboratory Approved. B. The size of the conductors shall be as designated on the Project Plans. C. Any NEC approved splice excluding wire nuts connections may be used for splice connections. C. Splices shall be insulated in accordance with Section 86-2.09E, Splice Insulation, type B method of the CALTRANS Standard Specifications. D. A fused disconnect splice connector shall be installed in each conductor between the line and ballast and shall be located and readily accessible within the hand hole of the electrolier standard. The fused disconnect splice shall consist of a Class CC (NEC) midget fuse holder with a 5 amp 250 volt non time delay midget fuse. CS 15-09 LUMINAIRES: Luminaires shall conform to the Standard Drawings and the following requirements: A. Luminaires shall consist of the approved fixture type included in table CS 15-1 shaped aluminum housing, photoelectric control, reflector, and integral regulator type ballast. Luminaires, complete with lamps, shall be installed in the proper orientation to produce the desired light pattern and shall be completely assembled and connected to the conductor. The operating voltage shall be 120 volts unless otherwise specified. B. Ingress Protection (IP) rating for the Luminaire fixture shall conform to the following: 1. Cobra head lighting fixture shall have a minimum IP rating of 55. 2. Decorative Lighting (Post Top and Tear Drop) fixture shall have a minimum IP rating of 66. CS 15-10 LAMPS: Unless otherwise specified, high pressure sodium lamps shall be installed in the luminaires. The wattage of the lamps shall be specified on the plans. Street Lighting CS-15-5 CS-SEC15 REV 11 March 2008

CS 15-11 PHOTOELECTRIC CONTROL: Photoelectric control shall be multi voltage photoelectric relay on a twist lock receptacle. A photoelectric cell shall be installed with each street light and shall be located as follows: A. Cobra Head luminaire on traffic signal standards: Locate photo cell on the top of the traffic signal standard closest to the electrical service pedestal. B. Cobra Head luminaire on electrolier standards: Locate photo cell on the top of the luminaire fixture. C. Decorative Post Top luminaire: Locate photo cell inside the top of fixture. D. Decorative Tear Drop luminaire: Locate photo cell on the top of the luminaire fixture. CS 15-l2 SERVICE CONNECTION: Service connections for street lights served by underground electrical systems will be made at the Service Point Location designated on the Project Plans which is normally a PG&E secondary box. Service Connections shall conform to the following requirements: A. The Contractor shall provide conduit and wire from the PG&E secondary box to and throughout the new street light system. B. Wires shall be tagged at secondary box in accordance with the latest applicable PG& E detail. C. Service connections for electroliers served by overhead electrical systems will be made at a junction box located at the base of the service riser pole. The Contractor shall provide the junction box, conduit and wire from the junction box to the pull box adjacent to the nearest street light. D. All service connections will be made by PG& E. The Contractor shall bear all costs by PG&E for service connection(s). Street Lighting CS-15-6 CS-SEC15 REV 11 March 2008