CONSTRUCTION SPECIFICATION FOR CHAIN-LINK FENCE

Similar documents
CONSTRUCTION SPECIFICATION FOR CHAIN-LINK FENCE

MATERIAL SPECIFICATION FOR CHAIN-LINK FENCE COMPONENTS

Special Provision No. 540S01 March OPSS 540, Construction Specification for Highway Fence, is deleted and replaced with the following:

SECTION CHAIN LINK FENCES AND GATES (PARK)

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories.

CHAIN LINK FENCES AND GATES

SECTION 1043 FENCE MATERIAL

MERCHANTS METALS. A. ASTM F552 Standard Terminology Relating to Chain Link Fencing

Advisory Circular PAGECONTROLCHART. Remove Pages Dated II Inscr t Pages Dated l/2/ thru 258-l 7/6/ l/2/90

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF POLES

SECTION CHAIN-LINK FENCES AND GATES 02821/1

Houston Community College 3200 Main Parking Garage November 15, 2010 Houston Community College

CONSTRUCTION SPECIFICATION FOR STEEL REINFORCEMENT FOR CONCRETE

A. Product Data shall be provided for each type of product indicated.

SECTION CHAIN LINK FENCES AND GATES

A. ASTM A121 Specification for Metallic-Coated Carbon Steel Barbed Wire. B. ASTM A392 Specification for Zinc-Coated Steel Chain-Link Fence Fabric

SECTION CHAIN LINK FENCES AND GATES

SECTION ORNAMENTAL ALUMINUM FENCING

SECTION WELDED STEEL PICKET FENCE. 1. Fusion welded and rackable ornamental steel picket fence system.

CONSTRUCTION SPECIFICATION FOR FORMWORK AND FALSEWORK

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

MATERIAL SPECIFICATION FOR STEEL REINFORCEMENT FOR CONCRETE

Section 2 Supplemental Specification 2.11 High Tension Cable Barrier

CONSTRUCTION SPECIFICATION FOR TRENCHING, BACKFILLING, AND COMPACTING

CONSTRUCTION SPECIFICATION FOR STRUCTURAL STEEL

CONCRETE STEPS, HANDRAILS, AND SAFETY RAIL

SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 5 REINFORCING STEEL. 5.1 General Certification Fabrication...

SPECIFICATION FOR REINFORCED SOIL WALL

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

CONSTRUCTION SPECIFICATION FOR SEWAGE FORCEMAIN INSTALLATION IN OPEN CUT

MATERIAL SPECIFICATION FOR CIRCULAR AND ELLIPTICAL CONCRETE PIPE

CONSTRUCTION SPECIFICATION FOR CONCRETE CROSSWALK INDEX TS SCOPE...3

Construction Specification for Utility Adjustments

Community Services Dept., City of Mississauga Subdivision Requirements Manual Page 1 of 11 Specifications Revised: January 31, 2003

A. Coordinate chain link fence & gate work with work before and after. See especially: 1. Bollards on worksite that are more than 10 ft from fence.

Amendment to OPSS 493 (Nov 2015) Construction Specification for Temporary Potable Water Supply Services

SECTION HANGERS AND SUPPORTS FOR PLUMBING

AS AS Australian Standard. Chain-link fabric security fences and gates. This is a free 7 page sample. Access the full version online.

MATERIAL SPECIFICATION FOR CIRCULAR AND ELLIPTICAL CONCRETE PIPE

SECTION COLD-FORMED METAL FRAMING

Construction Specification for Concrete Unit Pavers

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

Bi-Directional Static Load Testing of Drilled Shafts

American Metal Specialties, Inc.

GABIONS AND REVET MATTRESSES

A. Pre-engineered, pre-finished extruded aluminum Pavilions.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK

Special Provision No. 405F03 March 2005

METAL HANDRAILS AND RAILINGS. A. Properly identified manufacturer's literature, including shop and erection drawings before starting work.

SECTION REINFORCING STEEL

Daytona Beach Pier Building Renovation Jun 2010

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

TS 805 POLES TTS CONSTRUCTION SPECIFICATION FOR POLE INSTALLATION TTS MATERIAL SPECIFICATION FOR STEEL POLES BASE MOUNTED

Superior Aluminum Guide Specification 10/4/2016 Non-Welded Aluminum Pipe Railing

1. Cast-in-place concrete is specified in Section

SECTION PLATE CONNECTED WOOD TRUSSES

MATERIAL SPECIFICATION FOR BEARINGS - ELASTOMERIC PLAIN AND STEEL LAMINATED

G. Shop drawing of wall with all dimensions, details, and finishes. Drawings must include post foundations.

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Click on image to enlarge.

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

POST FRAME BUILDING STANDARDS

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

Flotation Docking Systems, Inc.

Stainless Steel Aeration Equipment Specification

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Model # 158-P4. 12/12/2013 Page 1 of 11

HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

Model # 238HS-P8. 4/27/2011 Page 1 of 11

SECTION METAL FABRICATIONS

02800 SHADE STRUCTURES

Reliant Holdings Ltd Safety Management System

Model # BT238-U6. 9/30/2014 Page 1 of 12

PIPE AND TUBE RAILINGS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION ACCORDION FOLDING PARTITIONS

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

REVISED SECTION REINFORCING STEEL FOR CONCRETE STRUCTURES. Approved:

SECTION 716 SIGN MATERIALS SCOPE

SECTION EXTERIOR GRILLS AND SCREENS

Construction Specification for Concrete Bus Pad

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.

SECTION DECORATIVE METAL FENCES AND GATES

Special Provision No. 599S22 March 2001

ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL)

Attachment A-Flagpole(s) Specifications

CONSTRUCTION SPECIFICATION FOR UNTREATED SUBBASE, BASE, SURFACE, SHOULDER, SELECTED SUBGRADE, AND STOCKPILING

Table of Contents. List of Drawings

Installation Manual. ArchCast Bridge. 3-Sided Precast Concrete Bridge Structure

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Transcription:

ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 541 NOVEMBER 2005 CONSTRUCTION SPECIFICATION FOR CHAIN-LINK FENCE TABLE OF CONTENTS 541.01 SCOPE 541.02 REFERENCES 541.03 DEFINITIONS 541.04 SUBMISSION AND DESIGN REQUIREMENTS - Not Used 541.05 MATERIALS 541.06 EQUIPMENT - Not Used 541.07 CONSTRUCTION 541.08 QUALITY ASSURANCE 541.09 MEASUREMENT FOR PAYMENT 541.10 BASIS OF PAYMENT APPENDICES 541-A Commentary 541.01 SCOPE This specification covers the requirements for the installation of chain-link fence. 541.01.01 Significance and Use of Appendices Appendices are not a mandatory part of this specification unless invoked by the Owner. Appendix 541-A is a commentary appendix to provide designers with information on the use of this specification in a Contract. Page 1 Rev. Date: 11/2005 OPSS 541

541.02 REFERENCES This specification refers to the following standards, specifications, or publications: Ontario Provincial Standard Specifications, Construction OPSS 904 Concrete Structures Ontario Provincial Standard Specifications, Material OPSS 1541 Chain-Link Fence Components Canadian Standards Association W59-03 Welded Steel Construction (Metal Arc Welding) ASTM International A 780-01 Standard Practice for Repair of Damaged and Uncoated Areas of Hot Dip Galvanized Coatings 541.03 DEFINITIONS For the purpose of this specification, the following definitions shall apply: Barbed Wire means the twisted longitudinal wires, termed line wires, to which the barbs are attached. Barbed Wire Arm means the metal arm to support the barbed wire. Bottom Wire means the wire installed at the bottom of fence and fastened to the bottom of the fence fabric and extending throughout each section of fence between terminal posts. Brace Rail means a tubular or fabricated steel section used for bracing terminal posts. Diagonal Brace Wire means the wire used for bracing terminal posts. End Post means the fence post positioned at the ends of a section of fence. Fence Post means an upright tubular or fabricated steel member for supporting fencing material. Fitting means the mechanical connection of various designs, shapes, and metals to join fence components into an integral structure. Gatepost means a terminal post on each side of a gate forming a gateway. Knuckled means the type of selvage obtained by interlocking adjacent wire ends in pairs and then bending the wire ends back into a closed loop. Line Post means the fence post spaced at regular intervals between terminal posts throughout each section of fence. Page 2 Rev. Date: 11/2005 OPSS 541

Selvage means the edge finish on woven chain-link fabric joining pairs of pickets. The selvage may be knuckled or twisted. Terminal Post means end, gate, corner, and straining posts. Top Rail means a tubular or fabricated steel section continuously joined by means of sleeves or couplings throughout all sections of fence extending between terminal posts. Top Wire means the wire installed at the top of fence and extending continuously throughout all sections of fence between terminal posts. Twisted means the type of selvage obtained by interlocking adjacent wire ends in pairs and then twisting the wire at least two turns with the wire ends above the twist. Wire Ties means the wire used to tie chain-link fence fabric to line posts, bottom wires, and top rails or top wires. 541.05 MATERIALS 541.05.01 Chain-Link Fence Fence fabric, posts and rails, diagonal wire braces, top and bottom wires, gates, fittings and accessories, turnbuckles, and barbed wires shall be according to OPSS 1541. 541.05.02 Fasteners Fasteners for attaching fence fabric to posts, top rails or wires, and bottom wires shall be made with the same material as the fence fabric. However, stainless steel fasteners may be used with any fence fabric. 541.05.03 Concrete Concrete shall have a nominal minimum 28-Day compressive strength of 20 MPa. 541.07 CONSTRUCTION 541.07.01 Site Preparation Prior to the commencement of fencing operations, remove any debris and correct ground undulations to obtain a smooth and uniform gradient. All trees, stumps, and brush along the fence line shall be cut off at ground level and all logs and overhanging branches that would interfere with the erection of the fence shall be removed. 541.07.02 Chain-Link Fence 541.07.02.01 Post Installation 541.07.02.01.01 General All posts shall be placed plumb and set accurately in line and position. Posts shall be cut to the required height above the ground to present a smooth and uniform profile. Page 3 Rev. Date: 11/2005 OPSS 541

Line post spacing shall be in equal horizontal distances with a maximum of 3,000 mm between line posts. All posts shall be fitted with waterproof metal caps designed to fit and fasten securely over the posts. All line post caps shall carry either the top rail or top wire as specified in the Contract Documents. Corner posts shall be installed at horizontal deflections in the fence line of 10 degrees or more. Straining posts shall be installed at equal intervals not exceeding 150 m. Additional straining posts shall be installed where changes in vertical alignment of the fence exceed 30 degrees. 541.07.02.01.02 Posts On Concrete Barrier All posts installed on a concrete barrier shall be fastened to the concrete barrier using 12.7 mm Hilti HIT RE 500 anchors using HAS threaded rods or equivalent installed according to manufacturer s specifications with lock washers. Each post shall be fabricated with a welded steel base plate grade 300 W and according to the Contract Documents. All welds shall be to a low hydrogen classification according to CSA W59-M. Manual electrodes shall be E7015, E7016, or E7018. All welds shall be continuous. 541.07.02.01.03 Concrete Footings All posts set in earth, loose or friable rock, or where overburden on solid rock is 450 mm or greater shall be set in concrete footings that are rough cast in the ground and domed above grade to shed water and to the dimensions shown in the Contract Documents. Where the size of hole exceeds the minimum dimensions of the footings, place the footing against undisturbed ground or backfill the hole with suitable earth material compacted to a density of 95% of maximum dry density and then bore a hole to the required minimum dimensions. Concrete placing, curing, and protection from the elements shall be according to OPSS 904. 541.07.02.02 Bracing A pipe or wire brace shall be placed diagonally across the panel at all end and gateposts. Corner and straining posts shall be supported with diagonal braces placed on both sides of the post. The higher end of the diagonal brace shall be connected at the terminal post. End fittings for pipe braces shall be secured by a 6 mm bolt placed through the fitting and brace at both ends of the brace. 541.07.02.03 Top Rails, Top Wires, and Bottom Wires Top rails or top wires shall be installed as specified in the Contract Documents. Top rails or top wires shall be fastened securely to line post tops using waterproof caps. In sag locations, drill the post and cap and fasten with a self-tapping screw to ensure a secure fit. Top rails shall be fastened to terminal posts with centre bands. Top and bottom wires shall be stretched tight and securely fastened to terminal posts with turnbuckles and centre bands. Page 4 Rev. Date: 11/2005 OPSS 541

One turnbuckle is to be used between terminal posts. 541.07.02.04 Fence Fabric Fence fabric shall not be installed until the concrete footings have cured for a minimum of 5 Days. The fabric shall be stretched tight and securely fastened to terminal posts with steel tension bars and steel or aluminum tension bands. The longitudinal axis of the diamond pattern shall be perpendicular to the slope of the top rail. The fabric shall be placed on the side of the post nearest the roadway with the barbed edge at the top, except that on curves of 50 m or smaller radius, the fabric shall be placed on the side of the post away from the centre of the curve. The fabric shall be securely fastened to the line posts, bottom wire, and top rail or top wire with wire ties. The wire ties on the top and bottom wire shall have a minimum of two twists. The fabric shall not be fastened to any diagonal braces. 541.07.02.05 Barbed Wire Barbed wire shall be installed when specified in the Contract Documents. Barbed wire arms to support the barbed wire shall be installed with the arm pointing away from the roadway. 541.07.03 Gates Gates shall be installed in locations and of the type and size as specified in the Contract Documents. 541.07.03.01 Gate Installation Gates shall be constructed with the fabric on the side furthest from the roadway with the barbed edge at the top. All gates shall have a chain hook to hold gates open and double gates shall have a steel gate centre rest with a drop bolt for the closed position. The surface grade within the required gate sweep area shall be low enough to permit free movement of the gate. 541.07.04 Zinc Coating Repairs Cut ends, field drilled holes, and damaged areas of hot dip galvanized coatings on galvanized components shall be repaired according to ASTM A 780. 541.07.05 Site Restoration After fence erection, the site shall be cleaned and trimmed and the ground restored to a neat and original condition existent prior to fencing operations. 541.07.06 Management of Excess Material Management of excess material shall be according to the Contract Documents. Page 5 Rev. Date: 11/2005 OPSS 541

541.08 QUALITY ASSURANCE 541.08.01 Construction The Contract Administrator may perform a spot visual inspection to determine conformance with the workmanship, design, and dimensional requirements of this specification. Failure to conform to the specifications may result in a partial or complete inspection of the installation and removal and replacement of all defective workmanship or materials. 541.09 MEASUREMENT FOR PAYMENT 541.09.01 Actual Measurement 541.09.01.01 Chain-Link Fence Measurement of chain-link fence is along the contour of the ground for the actual length of fence erected and shall include gate openings. 541.09.01.02 Gates For measurement purposes, a count shall be made of the gates installed, regardless of the size and type. Double gates shall be counted as one gate. 541.09.02 Plan Quantity Measurement When measurement is by Plan Quantity, such measurement shall be based on the units shown in the clauses under Actual Measurement. 541.10 BASIS OF PAYMENT 541.10.01 Chain-Link Fence - Item Gates - Item Payment at the Contract price for the above tender items shall be full compensation for all labour, Equipment, and Material required to do the work. 541.10.02 Removals and Replacements Costs associated with any required removals and replacements of defective workmanship or materials shall be the Contractor s responsibility at no cost to the Owner. Page 6 Rev. Date: 11/2005 OPSS 541

Appendix 541-A, Commentary for OPSS 541, November 2005 Note: This appendix does not form part of the standard specification. It is intended to provide information to the designer on the use of this specification in a Contract. Designer Action/Considerations The designer should specify the following in the Contract Documents: - Locations of top rail or top wire to be used. (541.07.02.01.01) - Barbed wire locations. (541.07.02.05) - Gate locations, type, and size. (541.07.03) The designer should consider the placement of the fence fabric in relation to the post, where the fence is located between two roadways and where snow loading from ploughing operations could separate the fence fabric from the post, e.g., freeway and service road. The designer should ensure that the Ontario Provincial Standards General Conditions of Contract and the 100 Series General Specifications are included in the Contract Documents. Related Ontario Provincial Standard Drawings OPSD 972.101 OPSD 972.102 OPSD 972.130 OPSD 972.131 Fence, Chain-Link, Component - Barbed Wire Fence, Chain-Link, Component - Gate Fence, Chain-Link, Installation - Roadway Fence, Chain-Link, Installation - Concrete Barrier Page 7 Rev. Date: 11/2005 OPSS 541