Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Similar documents
Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Pins Insulator. Composite/Polymers Insulators

Performance of Thermoplastic Elastomeric and Thermoset Insulators under Accelerated Acid Rain Multistress Conditions

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Comparative study on field collected samples of aged silicon rubber composite coatings for high voltage insulators

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators

Energy Division Insulators

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE

Data Sheet 110kV TD123II dry type outdoor termination

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Polymer Suspension Insulators 69kV to 765kV

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.

INSULATORS NEW. See page J-4 for more information.

Mapping HV Insulators Pollution in the Mediterranean Island of Crete

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines

Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments

Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution

General Requirements. Technical Specifications for Insulators of Transmission Lines

Polymer Station Post Insulators for 69 to 345 kv Applications

Resin impregnated paper bushings. Product information

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

Polymer Post Insulators for 46 to 500kV Applications

PRY-MOULD. High Voltage Accessories for Extruded Cables

Polymer Cutout Testing Recommendations

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units

Advanced Materials. Semiflexible hydrophobic epoxy for composite insulators

SURGE ARRESTERS kv in silicone shield

Volcanic Ash Contamination of High Voltage Insulators

Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions

Evaluation of Coating Materials. 2 Evaluation Items for Coating Materials. 3 Evaluation Test with 5 Coating Materials

THERMAL IMAGE, PARTIAL DISCHARGE AND LEAKAGE CURRENT CORRELATION OF CERAMIC INSULATOR UNDER DIFFERENT CONTAMINATION LEVEL

REDUCTION OF REFLECTION LOSSES IN SOLAR CELL BY USING TIAL2 AND ZR ANTI REFLECTIVE COATING

Insulating Covers. Insulators: EPBI: Light Weight Polymeric Post Insulator. EPBI: Light Weight Polymeric Stand Off Insulator

UNS 5kA Arrester. Certified Test Report IEC

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

Porcelain Insulator Performance under Different Condition of Installation around Aligarh

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications.

Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network

* 1 Engr. Muhammad Junaid, 2 Engr. Mehran Tahir, 3 Engr. Kamal Haider, * 4 Engr. Muhammad Aamir

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators

Understanding New IEC Mechanical Test Requirements of Arresters

LINDSEY EMERGENCY RESTORATION SYSTEM

Electric Field and Potential Distribution in a 420 kv Novel Unibody Composite Cross-Arm

Chemical analysis of insulator contaminants and Reliability improvement of T&D line for smart operation of grid under chemically polluted environment

Feb12 Rev D

Insulator pollution in transmission lines

SUMMARY. More information on:

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

Cooperation of Conventional Electric Power Grids and Smart Power Grids

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013

The Role of Inorganic Fillers in Silicone Rubber for Outdoor Insulation Alumina Tri-Hydrate or Silica

The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions

Simulation of Steel and Composite Leaf Spring by Varying Thickness

MEASUREMENTS AND BENCHMARK OF PV-T COLLECTORS ACCORDING TO EN12975 AND DEVELOPMENT OF A STANDARDIZED MEASUREMENT PROCEDURE

MILESTONES OVERHEAD LINES SILCOSIL SILICONE INSULATORS. Leading Innovations in Silicone Rubber Technology

Heat Transfer Analysis of Advanced ic Engine Cylinder

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36

PV module durability testing under high voltage biased damp heat conditions

Assessment of Exposure Level to Background Radiationin South Valley University, Egypt

Chapter 2 Power Package Electrical Isolation Design

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use

Study of the Strength Geopolymer Concrete with Alkaline Solution of Varying Molarity

The COMPOSITE INSULATORS

Industrial Coatings: HIGHLY DURABLE, SUPERHYDROPHOBIC AND OLEOPHOBIC. (White Paper) NeverWet LLC

High Quality Porcelain Insulators for Transmission Lines

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May 2010

DSM Advanced Layers for Bi-facial Modules

Solar Cooker Lab Instructor s Guide Motivation:

Mar11 Rev D

MODULE MANUFACTURING AND TESTING ANUPAM SHARMA

SECTION N EQUIPMENT FOR SUBSTATION MAINTENANCE

Silver and Sulfur: Case Studies, Physics, and Possible Solutions. C. Hillman, S. Binfield, J. Seppi, and J. Arnold DfR Solutions April 15, 2009

Polymer Cutout Evaluation NEETRAC

CONTROL OF GRID CONNECTED PV INVERTER USING LMF ADAPTIVE METHOD

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Thermal Analysis of Solar Flat Plate Collector

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Effects of Ambient Temperature on the Performance of a Photovoltaic Solar System in a Tropical Area.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

STUDY ON MECHANICAL PROPERTIES OF LIGHT TRANSMITTING CONCRETE

VpCI PROTECTION SYSTEM FOR ELECTRICAL/ ELECTRONIC ENCLOSURES

Light and current induced degradation in p-type multi-crystalline cells and development of an inspection method and a stabilisation method

Low Stress Silicone Encapsulant Enables Distributed Power Generation

BS 6206 KM BS EN KM 51961

Design of Grid Connected PV System Using Pvsyst

Solar Radiation Potential as Energy Source of Photovoltaic Powered Uninterrupted Power Supply in Perlis, Northern Malaysia

Effect of Contaminant Flow-rate and Applied Voltage on the Current Density and Electric Field of Polymer Tracking Test

Technical specification for Rubber Injection Moulding Machine

ABchimie 526UV LED DS140 Dec Conformal Coating (UV LED-Dual cure)

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS

Transcription:

IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators N.Sumathi 1,V.S.N.K.Chaitanya 2,T.S.Gowtham 3 1 Assistant Professor Department of Electrical and Electronics Engineering, UCEK, JNT University, Kakinada, Andhra Pradesh, INDIA 2 Assistant Professor (C) Department of Electrical and Electronics Engineering, UCEK,JNT University, Kakinada, Andhra Pradesh, INDIA 3 P.G.Student, EEE Department, UCEK, JNT University, Kakinada, Andhra Pradesh, INDIA Abstract: Outdoor polymer insulators are exposing to different contaminated conditions and environmental factors like UV rays for a long time. These will degrade the insulator performance and decrease the life span. However, the surface of insulating material, such as silicone (Si) rubber will lost its hydrophobic nature due to these severe environmental conditions. Long term performance analysis of polymer insulators is essential to estimate the life expectancy. In this paper, experimental investigation is carried out on 33kV silicone composite insulators under salt contamination and UV ray s exposure. Insulator performance is analyzed by measuring leakage current and breakdown voltage for a certain interval of time up to 185days. Test results are compared between virgin insulators and contaminated insulators. Compared to virgin sample average leakage current is increased up to 77.19% for sample 1 and 71.79% for sample 2. Average breakdown voltage decreased to 45.61% for sample 1 and 41.66% for sample 2. These results help to estimate the life span of polymer insulator for long run. Keywords: Polymer composite Insulator, UltraViolet(UV)rays, Salt pollution, Leakage Current(LC), Breakdown Voltage (BDV) I. Introduction Outdoor polymer insulators are exposed to different electrical and mechanical stresses. In addition to these stresses, insulators will be operated in highly inconstant atmospheric conditions. Due to these environmental factors like UV irradiation and different pollution contaminations like salt, fog, urea and cement etc., degradation and aging of insulator takes place and results to flashover. Now a day s polymer material like silicone (Si) rubber is commonly used due to its hydrophobic nature [1]. This nature helps to increase breakdown strength of the insulator. Severe atmospheric conditions and several pollution contaminations result to loss of hydrophobicity. Transmission lines near seashore will have severe salt pollution in the atmosphere. This pollution shows severe impact on insulator performance. To analyze this performance, laboratory tests like artificial salt fog test is standardized for porcelain insulators but for polymer insulators it is under considerations as per IEC 62217-2012 recent publication [5]. In addition to salt pollution, UV rays from sun will also degrade the insulator. Due to these severe atmospheric conditions life span of polymer insulators is becoming low. Hence, long term performance analysis is must to determine the life expectancy of polymer insulators. Reference [1] has compared field exposure test results and laboratory test results. By using these comparisons, polymer insulator performance under salt contamination is evaluated. Xingliang Jiang [2] have studied and evaluated artificial contaminated flashover performance of glass and porcelain insulators. Artificial salt fog test was carried out [3] on both RTV coated ceramic insulator and HTV silicone rubber insulator. Test results are compared for both type of insulators and proved silicone rubber insulators are better than RTV coated ceramic insulator In this paper, experimental investigation is carried out on 33kV silicone composite insulators under salt contamination and UV ray s exposure. Insulator performance is analyzed by measuring leakage current and breakdown voltage for a certain interval of time up to 185days. Test results are compared between virgin insulators and contaminated insulators. II. Sample Preparation And Experimental Setup A. Test Sample Polymer insulators consist of three components. They are core, weather sheds and metal fittings [4]. Core is made of FRP rod sheathed with weather sheds and housing made of silicone (Si) rubber. End fittings are attached to core by crimping polymer (Si) composite insulator components are shown in fig1.two insulators are used for experimental evaluation. DOI: 10.9790/1676-1106024555 www.iosrjournals.org 45 Page

Fig.1 Polymer insulator [4] Table-I Test Samples Dimensions Polymer(Si) Composite Insulator Insulator type Sectional Length (mm) 510 + 18.75 Dry Arcing Distance (mm) 380 + 15.50 Creepage Distance (mm) 910 + 28.75 Specific Creepage Distance(mm/kV) 25 + 2.50 Core Diameter(mm) 21 + 2.34 Pitch (mm) 45+ 3.30 Pollution Range Medium IEC 61109[4] is a standard for polymer suspension and tension insulator. Before the test arrangement, all virgin sample dimensions are measured to confirm with IEC 61109 standards. Dimensions are tabulated in table. I. Sample dimensions and their tolerance values are confirmed with IEC 61109. After measuring dimensions, all insulators are cleaned with de-mineralized water to remove dust. B. Experimental Setup After cleaning, test sample is arranged in suspension mode and energized as per the circuit diagram shown in fig.2. Fig.2 Experimental Setup After making connections, power frequency voltage are applied to the sample in steps up to BDV is reached. At each step leakage current is measured and tabulated.test results are given in table II. Table-II Virgin Sample Test Results S.No Applied Voltage (kv) Sample1 Sample2 Leakage Current (µa) Leakage Current (µa) 1 20 16.3 17.3 2 40 32.9 33.6 3 60 55.2 52.2 4 80 86.6 80.9 5 100 123.6 108.6 BDV (kv) 166 170 III. Samples Under Salt Contamination And UV Rays To determine the long term performance of insulator under salt contamination and UV rays, virgin samples are continuously exposed to artificial salt pollution and artificial UV rays. Salt water is taken from sea and pollution is applied on insulator by spaying method as shown in fig.3. DOI: 10.9790/1676-1106024555 www.iosrjournals.org 46 Page

Fig.3 Artificial Salt Contamination by spaying method After spraying salt water, insulators are exposed to artificial UV rays by using UV lamps as shown in fig.4. Fig.4 Insulators under UV Irradiation The above procedure is repeated for everyday 24 hours. Leakage current and breakdown voltages are measured for certain intervals of time up to 185 days. IV. Measurement of LC and BDV ON contaminated test samples C. Sample1 After 15 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 5.14% and BDV decreased to 1.84%. LC results are shown in fig.5. Fig.5 Sample-1 LC measurement after 15Days DOI: 10.9790/1676-1106024555 www.iosrjournals.org 47 Page

After 30 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 7.97% and BDV decreased to 3.10%. LC results are shown in fig.6. Fig.6 Sample-1 LC measurement after 30Days After 45 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 10.95% and BDV decreased to 7.10%. LC results are shown in fig.7. Fig.7 Sample-1 LC measurement after 45Days After 60 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 16.41% and BDV decreased to 18.57%. LC results are shown in fig.8. Fig.8 Sample-1 LC measurement after 60Days DOI: 10.9790/1676-1106024555 www.iosrjournals.org 48 Page

After 75 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 23.39% and BDV decreased to 22.96%. LC results are shown in fig.9. Fig.9 Sample-1 LC measurement after 75Days After 105 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 48.27% and BDV decreased to 32.80%. LC results are shown in fig.10. Fig.10 Sample-1 LC measurement after 105Days After 135 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 72.65% and BDV decreased to 38.33%. LC results are shown in fig.11. Fig.11 Sample-1 LC measurement after 135Days DOI: 10.9790/1676-1106024555 www.iosrjournals.org 49 Page

After 150 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 73.99% and BDV decreased to 39.50%. LC results are shown in fig.12. Fig.12 Sample-1 LC measurement after 150Days After 165 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 74.67% and BDV decreased to 44.35%. LC results are shown in fig.13. Fig.13 Sample-1 LC measurement after 165Days After 185 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 77.19% and BDV decreased to 45.61%. LC results are shown in fig.14. Fig.14 Sample-1 LC measurement after 185Days DOI: 10.9790/1676-1106024555 www.iosrjournals.org 50 Page

Fig.15 Sample-1 Number of Days Vs BDV When the degree of pollution increases, breakdown strength of the test sample decreased as shown in fig.15. D. Sample2: After 15 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 5.67% and BDV decreased to 6.25%. LC results are shown in fig.16. Fig.16 Sample-2 LC measurements after 15Days After 30 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 7.97% and BDV decreased to 3.10%. LC results are shown in fig.17.. Fig.17 Sample-2 LC measurements after 30Days DOI: 10.9790/1676-1106024555 www.iosrjournals.org 51 Page

Fig.18 Sample-2 LC measurements after 45Days After 45 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 16.94% and BDV decreased to 7.59%. LC results are shown in fig.18. Again after 60 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 38.44% and BDV decreased to 17.24%. LC results are shown in fig.19. Fig.19 Sample-2 LC measurements after 60Days After 75 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 53.69% and BDV decreased to 30.77%. LC results are shown in fig.20. Fig.20 Sample-2 LC measurements after 75Days DOI: 10.9790/1676-1106024555 www.iosrjournals.org 52 Page

After 105 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 62.53% and BDV decreased to 32.81%. LC results are shown in fig.21. Fig.21 Sample-2 LC measurements after 105 Days After 135 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 65.85% and BDV decreased to 36%. LC results are shown in fig.22. Fig.22 Sample-2 LC measurements after 135 Days After 150 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 67.19% and BDV decreased to 39.34%. LC results are shown in fig.23. Fig.23 Sample-2 LC measurements after 150 Days DOI: 10.9790/1676-1106024555 www.iosrjournals.org 53 Page

After 165 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 67.69% and BDV decreased to 40.49%. LC results are shown in fig.24. Fig.24 Sample-2 LC measurements after 165 Days After 185 days of contamination, LC and BDV are measured. When compared to virgin sample results, average LC is increased to 71.79% and BDV decreased to 41.66%. LC results are shown in fig.25. Fig.25 Sample-2 LC measurements after 185 Days Fig.26 Sample-2 Number of days Vs BDV When the degree of pollution increases, breakdown strength of the test sample decreased as shown in fig.26 DOI: 10.9790/1676-1106024555 www.iosrjournals.org 54 Page

V. Conclusion Polymer insulator will expose to different variable atmospheric conditions. Due to these severe conditions degradation of insulator takes place and results to flashover. Polymer insulators will give better results under contaminated conditions but ageing occurs after a long period. Hence, long term performance analysis is must. In this paper long term performance analysis is carried out on 33kV polymer insulator under salt contamination and UV rays.lc and BDV are measured for regular intervals up to 185 days. Results proved that as the degree of contamination is high more will be the UV rays effect. Test results are compared between virgin insulators and contaminated insulators. Compared to virgin sample average leakage current is increased up to 77.19% for sample 1 and 71.79% for sample 2. Average breakdown voltage decreased to 45.61% for sample 1 and 41.66% for sample 2. Acknowledgment We acknowledge our gratitude to University college of Engineering, JNTU, Kakinada for completion of this work. References [1] H.Homma, Determination of long-term performance of polymeric insulators for distribution lines by salt fog method, Conference on electrical insulation and die electric phenomenon, pp. 401-404, 2006. [2] Xingliang Jiang, Study on AC artificial contaminated flash over performance of various types of insulators, IEEE transactions on power delivery, vol. 22 october 2007, pp. 2567-2574. [3] Isaias Ramirez, Salt fog testing of RTv coated ceramic insulators and comparision with HTV silicon rubber insulators, IEEE transactions, 2012, pp. 794-797. [4] IEC 61109, Composite suspension and tension insulators for AC over head lines, 2008. IEC 62217, Polymeric insulators for indoor and outdoor use, 2012. DOI: 10.9790/1676-1106024555 www.iosrjournals.org 55 Page