A COMPARISON OF GAS ANALYSIS TECHNOLOGIES AVAILABLE FOR EFFICIENT AND SAFE COMBUSTION IN CONTROL FIRED HEATERS

Similar documents
Combustion Control and Safety A comparison between Zirconium Oxide/Catalytic and Tunable Diode (TDL) Technologies Dr Stephen Firth / Rhys Jenkins

FGA 300 Panametrics Flue Gas Oxygen Analyzer. GE Sensing. Features. Applications

Improving Steel Reheat Furnace Performance with the ZoloSCAN-RHT Combustion Monitoring System

About AMETEK/Thermox Worldwide Availability and Support Fuel Savings Calculator

Next Generation Reheat Furnace Control: ZoloSCAN Laser Combustion Diagnostics

TruePeak TDLS200. NH 3 Slip Measurement. <Document Number> Copyright Yokogawa Electric Corporation <date/time>

Power-Cost Alternative De-NOx Solutions for Coal-Fired Power Plants

Flue Gas Analysis as a Diagnostic Tool for Fired Process Heater Furnaces

ETHYLENE PLANT DRY CRACKED GAS Product Code 54801

EuroFID Total Hydrocarbon Analyzer

Diode laser analyser LS4000 Ammonia slip measurement for DeNOx process

CH88 In Situ Flue Gas Oxygen Transmitter

The Proper Mechanism for Field Validating Moisture Analyzers. GE Measurement & Sensing GE Oil & Gas

Fpollutant-free zero air for analytical

Improving H 2 O Measurement in Catalytic Reformer Hydrogen Recycle Streams

Continous Emission Monitoring: Methods, Regulations and QA/QC. Anders Arvidsson, Opsis AB, Sweden

metals temperature limits.

Compact flue gas analyser: testo 300 M-I

TVOC Heated FID VE 7

Portable Gas Detectors for Landfill Gases

POLLUTION FROM MOTOR VEHICLES

Safer, More Efficient Combustion Control for Fired Heaters

Controlling NOx and other Engine Emissions

Accutube Averaging Pitot Tubes

COMTEC O 2. InSitu analyzer systems. / CO e DEVELOPED AND MANUFACTURED IN GERMANY

Downsizing a Claus Sulfur Recovery Unit

Chapter 10. Applications for Chemiluminescence in Combustion Diagnostics

ABB Measurement & Analytics Monitoring cement plant stack emissions using FTIR

DETECTION AND DETERMINATION OF H 2 S AND TOTAL SULFUR IN NATURAL GAS Marshall T. Schreve Del Mar Scientific, LTD.

Carbon / Hydrogen / Sulfur Analyzers

Two Great Technologies Together At Last. The 700 Series NanoTrace Moisture And Oxygen Analyzers

CEMS for Measurement of Ammonia, SO 3, and Low Level NOx

Methane concentrations are measured using portable gas detection instruments, usually a methane meter or explosimeter which has a readout in either

CEM500-L. Online Gas Analyser. Specialist Of UV Spectroscopy

Reverse Technology Transfer, a Case Study: Use of Automotive OF sensors in Rocket Applications

ICAC MARAMA Portable Emission Analyzers


Thermal Mass Flow Meters Help Reduce Energy Costs and Enhance Emissions Monitoring Systems

TABLE OF CONTENT

COMBUSTION OPTIMIZATION OF A 150 MW (NET) BOILER UTILIZING AIR AND FUEL FLOW MEASUREMENT AND CONTROL

Laser measurement of KCl vapor in 4 MW CFB boiler during straw combustion and ferric sulfate injection

Aurora TDLAS analyzers for Hydrogen Recycle Applications

View from the Penthouse

Oxygen Measurement and Analysis

Simulation of Flameless Combustion of Natural Gas in a Laboratory Scale Furnace

Oxygen Sensor QGO20...

Greenhouse Gas Measurement Technology

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

THE COMBUSTION OF HYDROCARBONS. I love the smell of napalm in the morning smells like victory!

MRU Instruments, Inc. Houston, Texas Tel.: (844) (Toll Free)

METHOD 3 - GAS ANALYSIS FOR THE DETERMINATION OF DRY MOLECULAR WEIGHT. NOTE: This method does not include all of the

On-line corrosion mapping of industrial plant using advanced electrical resistance techniques

Duke Energy Seminar September 3 5, 2008 Concord, NC

Heated FID 109A. Rack Mount/Table Top NMGOC Analyzer

Prima PRO process mass spectrometer

CECEBE Technologies Inc.

testo 340 Speed, power & precision in industrial combustion analysis.

Chapter 11. Direct Reduced Iron (DRI)

PTAC PROCESS TECHNOLOGY II - SYSTEMS. Last Reviewed: Page 1 of 10

A BASIC IMMERSION FIRETUBE FLOWNEX MODEL

Results are presented in Table 1. The tube was fabricated from a Type 347 and no unusual conditions were noted.

Process Analytical Technology How much oxygen is inside?

Carbon / Sulfur Analyzers

Lab 6 Measurement of Ozone

Errors associated with excess air multipoint

Identify three common gaseous pollutants in air and state how each of these pollutants are produced.

COMBIMASS Thermal Gas Flow

Measuring trace impurities in HyCO, regeneration hydrogen and inert gases Los Gatos Research (LGR)

Saudi Aramco Uses Kurz to Help Monitor Flare Emissions

Understand boiler performance characteristics. Use these suggestions when buying, designing or optimizing steam generators

Measurement of H 2 O in Catalytic Reformer Hydrogen Recycle Streams Using Tunable Diode Laser Absorption Spectroscopy (TDLAS)

testo 320. Combustion analysis in HD High Def & Heavy Duty For Residential & Commercial Applications 1

State one factor that makes a good fuel. (1) (b) Bioethanol is a fuel that can be obtained from the plant, sugar beet.

Synthesis Gas Processes for Synfuels Production

COLow COHigh COLow/H comp NO NOx NO2 CO2 H2S SO2 CXHY LANCOM 4. Portable Flue Gas Monitoring.

July Table 1. General influencing trends of carbon and sulfur on the physical properties ofmetals.

BURNER FLAME TEMPERATURE DURING WARM UP AND HOT STANDBY. Alan D. Mosher KPS Technology & Engineering LLC

Continuous Emissions Monitoring Systems. Engineering & Design. For PetroChem Processes

Gaseous and Noise Pollutants

COLow COHigh COLow/H 2 NO 2 CO 2 H 2 S SO 2 C X H Y LANCOM 4. Portable Flue Gas Monitoring. comp NO NOx

ADECOS II. Advanced Development of the Coal-Fired Oxyfuel Process with CO 2 Separation

Fully Extractive Vs. Dilution Extractive CEMS

Potentials and Limitations with respect to NO x -Reduction of Coke Plants

Minimize the Risk of Fire During Distillation Column Maintenance

Zonal* Combustion Optimization for Coal-Fired Boilers

Coal-Fired Boiler Optimization

REFERENCE MEASURING INSTRUMENT

Biogas analysers. Product overview. MRU over 30 years of innovative gas analysis! Biogas, landfill gas, biomethane, coal mine gas, CHP exhaust gas

deltafit deltafit made by systec Air-flow regulation for sewage treatment plants - Precise - Compact - Maintenance-free

General Air Monitoring/ SCHMT Monitoring Equip. Working to meet established Hazmat Team Goals:

6515 Series Measurement of CO2 in Flue Gases. A simple Katharometer-type measuring system for CO2 in flue gases as a guide to combustion efficiency

Advances in NOx Compliance Testing with Portable Electrochemical Analyzers

PROCESS INSTRUMENTS THERMOX.

195LiquidsCatalog.

PRODUCT CONFORMITY CERTIFICATE

Proven Flow Measurement Solutions for the Oil and Gas Industry

Hydrazine, sodium and dissolved oxygen measurement The power of boiler chemistry

Laird Thermal Systems Application Note. X-ray Cooling in Industrial Scanners

Sorbents Evaluation Testing Facilities. 95% removal efficiency or an emission standard of lbs/gw h by 2012, while

Catalytic Oxidation of Hydrogen in Air Streams

Transcription:

EXPERTS IN COMBUSTION CONTROL EXPERT PAPER A COMPARISON OF GAS ANALYSIS TECHNOLOGIES AVAILABLE FOR EFFICIENT AND SAFE COMBUSTION IN CONTROL FIRED HEATERS By Rhys Jenkins, Product Business Manager, Servomex Fired heaters are integral to hydrocarbon processing (HP). Specifically designed for the reaction of fuel and air to produce extremely high gas temperatures, heaters transfer this energy to potentially highly flammable process fluids via heat exchangers. They consume large quantities of fuel, produce large quantities of emissions and are a potential safety hazard to personnel and plant. However, they are currently irreplaceable within many HP processes so they warrant the highest levels of understanding and care in their operation and control. Recent improvements in burner technology to reduce NOx emissions require closer monitoring of the process, as newer burners often operate under narrower process control conditions than older, larger nozzle diameter gas burners. Demands have also grown on plant operators to improve safety practices, increase plant efficiency and reduce environmental emissions. As a consequence, more accurate and reliable instrumentation is required to support the control of the process. New and improved technologies are available to control fired heater combustion with ever greater accuracy and reliability, but the correct selection and effective use of these technologies requires understanding of a complex and delicate process. THE PRINCIPLES OF EFFECTIVE COMBUSTION CONTROL IN FIRED HEATERS The cornerstones of a well controlled combustion process are optimized air to flue ratio and efficient fuel consumption. Before analyzer technologies were developed to measure excess air in the products of combustion, fired heaters were run in conditions of high excess air. Although this meant inefficient and costly fuel consumption, it was the only way to avoid the creation of low oxygen, fuel rich conditions that could lead to a potentially dangerous explosion. The introduction of Zirconium Oxide technologies in the late 1960s allowed engineers to obtain reliable and continuous measurements of excess air, enabling them to reduce the air-to-fuel ratio closer to that of the theoretical stoichiometric combustion mix. Unfortunately, the reduction of excess air poses a new problem: the nearer the process moves to the tipping point at which incomplete combustion takes place, the potential to move from safe to unsafe operating conditions increases, as well as the speed at which these transitions can happen (fig.1).

The control and safety systems that run fired heaters must therefore perform an extremely complicated balancing act. It is often not enough to just increase excess air levels when incomplete combustion is detected, as the complex interactions of oxygen and unburned fuel can lead to flammable mixtures igniting further down from the burners. Such conditions can lead to a number of negative process control conditions, including excess heat at the process tubes, which causes damage and leaks; carbon deposits on the process tubes, which decreases efficiency and heat transfer; and, in extreme cases, potentially dangerous combustion events can occur. However, if a process problem is detected either by analytical instruments or other safety devices, it is inadvisable to simply switch off the fuel supply to the burners. Abrupt stops, restarts and light off conditions are the most common time for furnace incidents to occur. It is safer to bring the process carefully and correctly under control than to fully shutdown and restart the process and, as such, good quality and comprehensive analysis of the products of combustion, or lack of, is vital. Despite the risks, there are measureable rewards for operating fired heaters at Low Excess Air (LEA) levels. In LEA combustion control the lowest level of fuel is consumed and the products of combustion are cooled the least by unused excess air. The cost benefits of these efficiencies are considerable, with just a single percentage saving in fuel enabling savings of many tens or even hundreds of thousands of dollars per year. Controlling air levels just above the point at which incomplete combustion starts also enables the cleanest burn, helping plants meet environmental emissions requirements. This in particular reduces the emission of NOx, created when unused oxygen reacts with nitrogen from the combustion air, which will be produced even by low NOx burners if they are not run as lean as possible (fig.2). A competent LEA combustion process running at approximately 2.5-5% excess air or 0.5-1% oxygen above the point at which unburned fuel in the form of carbon monoxide starts to breakthrough can be maintained and controlled at the most efficient running point. If the process is run with too little air, the products of combustion will contain unburned fuel which is wasted and passed into the atmosphere. As soon as there is not enough air to allow full combustion of the fuel, the process will quickly degenerate into an unsafe condition. Pockets of carbon monoxide, and possibly hydrogen and methane, can travel through the process, causing localized hot spots as they ignite and produce higher emissions of gases such as carbon monoxide. These effects begin to manifest at less than 10-15% excess air or 2-3% oxygen in the flue gas, with burner inefficiencies preventing stoichiometric combustion levels being reached. Excluding extractive techniques used for portable gas analyzers and some highly specialist fixed gas analyzer applications, there are currently two very different technologies available to measure the level of unused oxygen in the fired heater combustion process. Zirconium oxide cell technologies commonly known as Zirconia have been established for more than 50 years, but have recently been challenged by the introduction of Tunable Diode Laser (TDL) analyzers. Both offer distinct advantages and disadvantages in their usage, so it is extremely important to understand their respective qualities to deduce which is most suitable for an application. Neither offers a one-sizefits-all solution, but there are notable advantages to be gained by using them as complementary techniques. ZIRCONIUM OXIDE: OPTIMUM TECHNIQUES FOR OPTIMUM OXYGEN CONTROL Zirconia is a proven technology that measures oxygen on a wet basis, enabling the sampling and direct analysis from the hot, wet and often corrosive products of combustion. This avoids added complexities and reliability issues associated with a sample conditioning system, while readings do not have to be converted from dry basis to wet basis, which can be a cause of inaccurate readings. Furthermore, Zirconia technology is an inherent partial pressure measurement, which allows the percentage oxygen measurement to be made independent of temperature and pressure. Zirconia analyzers are broadly split into two types: close coupled extractive analyzers and in situ analyzers. The most effective and reliable method for using Zirconia technology in process control is within a close-coupled extractive analyzer system, where a sensor enclosure is installed to the side of the process. This enclosure is heated above the gas dew point and contains the zirconia sensor connected to the process via a sample probe. The enclosure also normally contains an aspirator driven by compressed air, or occasionally nitrogen, which is used to extract the sample from the process.

The enables the sampling and direct analysis from hot, wet and corrosive combustion products. As this type of system can be installed close to the burners, the lag time for oxygen analysis the measurement delay due to sensor response is minimized, giving operators a comparatively short response time. Detailed burner performance can be also monitored by installing multiple analyzers across banks of burners; this is especially important in fired heaters where low NOx burners are fitted, as the burners are notoriously difficult to evaluate through visual inspection as the flame is non luminous. The outputs of these analyzers can then be averaged to give oxygen trim control. Many systems also offer the option of fitting an additional carbon monoxide or combustibles catalytic sensor. This offers additional diagnostic benefits for process and burner optimization, including providing early indications that excess air levels are too low, or that a bank of burners is incorrectly set up, adversely affected by other burners or suffering from nozzle blockage. Flame traps should always be specified when choosing this type of analyzer system to prevent the sensors from becoming a source of ignition back to the process. Care should then be taken to ensure that the flame traps have little effect on measurement lag times. High flow close-coupled extractive analyzers analyzers that aspirate over 1l/min of sample from the process can suffer from considerable sample lag times, as the pressure drops across flame traps at high flow rates causes reductions in sample flow. For added measurement certainty, it is recommended that analyzers are specified where the calibration gases supplied to the instrument can verify the whole of the system s performance, inclusive of the probe inlet to the analyzer, sensors and the aspirator outlet. With in-situ analyzers, the zirconia sensor is situated at the end of a probe that is inserted into the hot products of combustion. While relatively simple and cost-effective to install, the sensor is directly affected by the process temperature variations and limited in absolute operational temperature. The mechanical requirements of higher-temperature operation effectively making the analyzer operate like a diffusion-based, semi-close couple extractive analyzer are complex, with bulky assemblies that incur high installation overheads. Critically, when flame traps are fitted to an in-situ technique, the lag time can be up to several minutes or more, which many engineers will consider too risky for safe control. Problems can be compounded by probe installation points: if placed too far from the burners to limit process temperature effects on the sensors, then both air ingress into the flue and delays caused by the distance from the burners can weaken the ability to control the process efficiently and safely. The longer the analysis lag time and greater the air ingress, the further the process excess oxygen levels have to be controlled away from the ideal LEA point, as a high safety margin is then required to prevent incomplete combustion. As a consequence, engineers must have a clear understanding that their processes will be compromised by the potential shortcomings of in-situ techniques, regardless of the initial installation cost benefits they offer. TDL TECHNOLOGIES: A COMPLEMENTARY TECHNOLOGY TO OPTIMIZE PROCESS A major development in gas analysis techniques has been the introduction of Tuneable Diode Laser (TDL) technologies. Enthusiastically received by engineers and plant operators, a range of different technology integrations are now available from multiple manufacturers. Yet while TDL offers distinct advantages in the measurement of multiple gas types, it also has operational limitations which make its use in fired heaters a complementary technique rather than a complete replacement for other technologies. TDL consists of a tunable diode laser light source, transmitting optics, an optically accessible absorbing medium, receiving optics and detector. TDL technologies are particularly suitable for in situ cross stack measurements, with a typical cross stack system consisting of the laser emitter module and receiver mounted across the process pipe line or flue stack. The gas concentration information is held in the gas absorption line shape, which is obtained by scanning the laser wavelength over the specific absorption line. This causes a reduction of the measured signal intensity, which is detected by a photodiode and then used to determine the gas concentration. Being a spectroscopic absorption measurement technique, TDL effectively counts molecules (or number density of molecules) that fall within the beam. Within a certain gas mix, the number density for a fixed percentage composition is strongly pressure and temperature dependent according to the universal gas laws. Therefore external temperature inputs are required to enable the analyzer to derive an accurate percentage oxygen measurement. Laser 3 Plus Combustion Compact TDL combustion series measures O 2, CO and CH 4 offering unique features and low cost of ownership. There are primarily two cross stack TDL technologies in use: Direct Absorption Spectroscopy (DAS) and Wavelength Modulated Spectroscopy (WMS). DAS is the first generation technique of TDL absorption spectroscopy, providing measurements from a relatively crude approximation of the area under the absorption curve generated by the laser scan.

Today, few analyzer manufacturers use this approach to measurement analysis, as DAS yields a relatively noisy signal which compromises measurement accuracy. DAS is also limited due to the broad absorption line shape, with measurement data contained within the wings of the absorption curve, hence a proportion of the absorption data is not scanned and cross interferences from background gases, molecular interactions and environmental fluctuations can be difficult to correct. While the disadvantage of the DAS technique is generally not significant in relation to oxygen analysis, for all other gases it is a limitation to measurement accuracy. WMS is a sophisticated evolution of the DAS technique, which takes a measurement of the second harmonic of the absorption curve. This yields a very sharp absorption curve with all measurement data contained within the laser scan width and very defined turning points which are easily computed, allowing an accurate evaluation of the area under the absorption curve. By delivering excellent cross interference rejection, precise temperature and pressure correction and low noise measurements, the greater accuracy and stability given by the WMS measurement means it is consequently the most commonly used TDL measurement technique. TDL based systems appear an ideal choice for in situ cross stack measurements in process and combustion control applications. As there is no physical or mechanical interaction with the process other than molecular absorption they offer a highly stable base line measurement, with a long interval between calibrations and a fast response measurement in hot, wet, corrosive and dusty process conditions. TDL technologies therefore appear highly attractive on both maintenance and performance grounds, but the technology has potential disadvantages when compared to zirconia for a process control measurement. For oxygen analysis, TDL offers an average path measurement across all burners, while zirconia analyzers can be used to measure a particular section of burners by their ability to sample a single point. As TDL purchase and installation costs are between three to five times that of a zirconia installation, multiple zirconia analyzers can be purchased for an equivalent amount that can be used to both gain an average measurement and the single point measurements for burner diagnostics. TDL is also susceptible to a range of environmental factors which must be compensated for, including path length variation, window purge gas effects, optical interferences and temperature and pressure changes. For a WMS instrument an error of approximately +/ 5% of reading is normal, while for a DAS measurement the error can be considerably higher. Problems can also arise in the fitting of optical windows between both the source and the process and between the detector and the process. These windows must remain clean at all times, which can only be achieved by purging the dead space with a gas that will not interfere with the measurement. For an oxygen measurement this precludes the use of compressed air, so nitrogen is used as the purge gas. As this is normally consumed at a rate of 20l/min to 50l/min for each side of the TDL, depending on process gas velocity, it makes operation and maintenance prohibitively expensive when compared with zirconia techniques, unless the process is too corrosive or dust laden for a zirconia analyzer to operate reliably. There is also no way of calibrating a measurement without removing both the TDL source and detector and fitting a fixed length calibration cell. Even with the calibration cell fitted, which is usually one meter in length, a true calibration is difficult to achieve accurately as process path lengths typically vary from 5m to 20m long. The instrument must apply correction factors to compensate for the calibration cell path length and process path length differences. TYPICAL FURNACE LAYOUT Ideal analyzer layout for control fired heaters, utilizing Zirconia and TDL technologies across the process for maximum safety, efficiency and control. Laser 3 Plus Laser 3 Plus

TDL delivers greater advantages in the measurement of carbon monoxide, with the fast response and specificity of TDL enabling carbon monoxide breakthrough to be monitored accurately. While it is not generally advisable to use carbon monoxide breakthrough as part of the process control loop, it can act as a secondary and complementary measurement to the oxygen measurement, assisting LEA optimization and introducing a further level of process safety related diagnostics. Carbon monoxide measurement using TDL also avoids the problem of high sulfur levels inhibiting catalytic sensors, while the ability to use compressed air as a purge gas removes the prohibitive costs associated with using TDL for an oxygen measurement. But as TDL offers an average path measurement, rather than a point measurement, a catalytic measurement of carbon monoxide combined within the same analyzer as the zirconia oxygen measurement gives a enhanced, cost-effective diagnostic capabilities for burner efficiency. Possibly the most significant application for TDL in fired heater processes lies in the ability to integrate the technology into flameout protection, specifically the measurement of methane in natural gas burners. If TDL is installed so that a burner flameout can be detected quickly, it enables greater flexibility and response to control and shut down processes. A further advantage of a methane optimized measurement is that a single TDL monitor can obtain further data to monitor carbon monoxide and moisture levels. In normal operating conditions no carbon monoxide or methane should be present in the process, so moisture analysis is particularly useful as it serves as a reference peak in the same laser scan cycle to prevent laser drift and loss of laser line lock. CONCLUSION In a typical fired heater, the optimum analytical techniques for process control, efficiency, safety and emissions reduction are a mix of Zirconia and TDL technologies applied to specific locations. A minimum of two zirconia analyzers placed at the top of the radiant section, or at the very least bottom of the convective section, is essential: analyzers at these locations will minimize lag times and air ingress, enabling an average measurement and providing back-up when one analyzer requires maintenance. For LEA operation, a combustibles sensor combined with the zirconia analyzer is a very cost effective choice, the installation of which will support process safety procedures and site safety regulations. The addition of an integrated flow alarm also enables preventative maintenance. Levels of carbon monoxide and water within the radiant section can be effectively measured by TDL in conjunction with Zirconia for oxygen. For flameout protection and diagnostics, and for added combustibles breakthrough analysis, an additional combined CO/methane TDL can be used. This TDL should be located as close to the burners as physically possible. While TDL will continue to improve, it is not yet ready to completely displace the older technologies of Zirconia and catalytic sensors within combustion control. Within the short to medium term, it seems more likely that its introduction will trigger a new generation of zirconia and catalytic sensor improvements and analyzer developments. This competition between technologies will ultimately benefit process engineers and operators, as it will help generate new, cost effective and reliable instrument solutions. visit: servomex.com GET YOUR EXPERT SOLUTIONS NOW Contact your local business center TEL: +1 281 295 5800 TEL: +971 6552 8073 TEL: +91 22 3934 2700 TEL: +86 (0)21 6489 7570 TEL: +44 (0)1892 652 181