DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY

Similar documents
DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BASF CORPORATION (RIGID PU SYSTEMS)

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: NATURAL POLYMERS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

Trusted DIVISION: 07 SYSTEM. Conformity! ICC-ES Evaluation. not specifically. Copyright 2014

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE SPRAY MARKET, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: LAPOLLA INDUSTRIES, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: TERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

ESR-1655 Reissued April 2014 This report is subject to renewal April 1, 2016.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: JOHNS MANVILLE

ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: SES FOAM

Trusted ICC ES DIVISION: ATLANTA, CGF PRO, ENERGYS. Look. Conformity! Evaluation. ICC-ES Evaluation

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

REPORT HOLDER: JOHNS MANVILLE TH STREET DENVER, COLORADO EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: REFLECTIX INCORPORATED

REPORT HOLDER: ATLAS EPS, A DIVISION OF ATLAS ROOFING CORPORATION 8240 BYRON CENTER SOUTHWEST BYRON CENTER, MICHIGAN EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

REPORT HOLDER: GEORGIA PACIFIC GYPSUM LLC 2861 MILLER ROAD DECATUR, GEORGIA EVALUATION SUBJECT: DENSELEMENT BARRIER SYSTEM

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

DIVISION: FINISHES SECTION: FIRE RETARDANT COATINGS REPORT HOLDER: FIRE RETARDANT COATINGS OF TEXAS, LLC

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

Originally Issued: 07/06/2009 Revised: 04/07/2017 Valid Through: 07/31/2017

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

Originally Issued: 07/31/2015 Revised: 07/31/2017 Valid Through: 07/31/ General

REPORT HOLDER: INSULFOAM, A DIVISION OF CARLISLE CONSTRUCTION MATERIALS, INC TH AVENUE EAST PUYALLUP, WASHINGTON EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC.

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BASF CORPORATION

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

DIVISION: MASONRY SECTION: MANUFACTURED BRICK MASONRY SECTION: MANUFACTURED STONE MASONRY REPORT HOLDER:

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: BASF CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: GENTEK BUILDING PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

REPORT HOLDER: LOUISIANA-PACIFIC CORPORATION 414 UNION STREET, SUITE 2000 NASHVILLE, TENNESSEE EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: EQUITONE

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC.

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: AMVIC INCORPORATED

REPORT HOLDER: RARE MANUFACTURING INC A AVENUE SURREY, BRITISH COLUMBIA V4N 4P2 CANADA EVALUATION SUBJECT: IRONWOOD SHAKE

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS DIVISION: SIDING REPORT HOLDER: VM ZINC

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

REPORT HOLDER: CALIFORNIA EXPANDED METAL PRODUCTS COMPANY (CEMCO) CROSSROADS PARKWAY NORTH, SUITE 325 CITY OF INDUSTRY, CALIFORNIA 91746

REPORT HOLDER: GREENMAKER INDUSTRIES, LLC 697 OAKWOOD AVENUE WEST HARTFORD, CONNECTICUT EVALUATION SUBJECT: DECOPLAST DDARS NOTCHED

REPORT HOLDER: GYPSUM ASSOCIATION 962 WAYNE AVENUE, SUITE 620 SILVER SPRING, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: 3A COMPOSITES USA INC.

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: PROWALL BUILDING PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: CERAMICA LA ESCANDELLA, S.A.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: ROOF PANELS REPORT HOLDER: ROSER CO., LTD.

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: FIRE ROCK PRODUCTS LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: ASSOCIATED MATERIALS, INC.

Joint Evaluation Report

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: DERBY BUILDING PRODUCTS INCORPORATED

Transcription:

0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2670 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY 200 LARKIN CENTER 1605 JOSEF DRIVE MIDLAND, MICHIGAN 48674 EVALUATION SUBJECT: STYROFOAM SPRAY POLYURETHANE FOAM RS2030, RS2045, CM2030, CM2045, MX2030 AND MX2045 Look for the trusted marks of Conformity! 2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2017 ICC Evaluation Service, LLC. All rights reserved.

ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2670 Reissued July 2017 Revised October 2017 This report is subject to renewal July 2019. A Subsidiary of the International Code Council DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 21 00 Thermal Insulation REPORT HOLDER: THE DOW CHEMICAL COMPANY 200 LARKIN CENTER 1605 JOSEF DRIVE MIDLAND, MICHIGAN 48674 (866) 583-2583 www.dowbuildingmaterials.com EVALUATION SUBJECT: STYROFOAM SPRAY POLYURETHANE FOAM RS2030, RS2045, CM2030, CM2045, MX2030 AND MX2045 1.0 EVALUATION SCOPE Compliance with the following codes: 2012 and 2009 International Building Code (IBC) 2012 and 2009 International Residential Code (IRC) 2012 and 2009 International Energy Conservation Code (IECC) Other Codes (see Section 8.0) Properties evaluated: Physical properties Surface-burning characteristics Water vapor transmission Air permeability Attic and crawl space installation Fire-resistance-rated construction Thermal resistance Exterior walls in Types I through IV construction 2.0 USES STYROFOAM Spray Polyurethane Foam RS2030, RS2045, CM2030, CM2045, MX2030 and MX2045 are used as nonstructural thermal insulating materials. STYROFOAM Spray Polyurethane Foam RS2030 and RS2045 are used in Type V construction under the IBC and dwellings under the IRC. The insulations are for use in wall cavities, sprayed onto the surface of walls, floor/ceiling assemblies, attics, crawl spaces, sill plates and/or headers when installed in accordance with Section 4.0. Under the IRC, the insulations may be used as air-impermeable insulation when installed in accordance with Section 3.5. STYROFOAM Spray Polyurethane Foam CM2030, CM2045, MX2030 and MX2045 may be used in Types I, II, III and IV construction under the IBC (see Section 4.7 for use in Types I, II, III and IV construction). The insulations may also be used in Type V construction under the IBC and dwellings under the IRC. The insulations are for use in wall cavities, sprayed onto the surface of walls, floor/ceiling assemblies, attics, crawl spaces, sill plates and headers when installed in accordance with Section 4.0. Under the IRC, the insulations may be used as air-impermeable insulation when installed in accordance with Section 3.5. STYROFOAM Spray Polyurethane Foam CM2030 and CM2045 may be used in fire-resistance-rated wall assemblies when construction is in accordance with Section 4.6. 3.0 DESCRIPTION 3.1 General: The insulations are two-component, closed-cell, sprayapplied, semirigid, medium-density, polyurethane foam plastics having a nominal density of 2 pcf (32 kg/m 3 ). The insulations are produced in the field by combining a polymeric isocyanate component A with a resin-based component B. The Part A component is packaged in 55 gallon (208 L) drums, labeled as Dow 3019 Isocyanate. The insulation components have a shelf life of six months when stored between 60 F (15 C) and 90 F (32 C) in unopened containers. 3.2 Surface-burning Characteristics: The insulations have a flame-spread index of 25 or less and a smoke-developed index of 450 or less when tested in accordance with ASTM E84 (UL 723) at a maximum thickness of 4 inches (102 mm). Thicknesses of up to 12 inches (305 mm) for wall and ceiling cavities are recognized based on testing in accordance with NFPA 286, when the insulation is covered with a minimum 1 / 2 -inch-thick (12.7 mm) gypsum wallboard or an equivalent thermal barrier complying with, and installed in accordance with, the applicable code. 3.3 Thermal Resistance, R-values: The insulations have thermal resistance (R-values) at a mean temperature of 75 F (24 C) as shown in Table 1. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2017 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 5

ESR-2670 Most Widely Accepted and Trusted Page 2 of 5 3.4 Vapor Retarder: The insulations have a vapor permeance of less than 1 perm [5.7x10-11 kg/(pa-s-m 2 )], in accordance with ASTM E96, when applied at minimum thicknesses of 2.2 inches (56 mm), and qualify as Class II vapor retarders. 3.5 Air Permeability: The insulations at a minimum thickness of 1 / 2 inch (12.7 mm) are considered air-impermeable insulations in accordance with 2012 IRC Section R806.5 (2009 IRC Section R806.4), based on testing in accordance with ASTM E283. 4.0 INSTALLATION 4.1 General: The insulations must be installed in accordance with the manufacturer s published installation instructions, the applicable code and this report. The manufacturer s published installation instructions must be available on the jobsite at all times during installation. 4.2 Application: The insulation is spray-applied on the jobsite using a volumetric displacement pump combining Part A and Part B components at a one-to-one ratio, as specified in the manufacturer s published installation instructions. The insulation is applied in passes having thicknesses of no less than 1 / 2 inch (12.7 mm) and no more than 2 1 / 2 inches (64 mm) to achieve the total thicknesses specified in this report. The maximum service temperature must be no greater than that specified in The Dow Chemical Company installation instructions. The insulation must not be used in electrical outlet or junction boxes or in direct contact with water. The substrates to which the insulation is applied must be free of moisture (dew or frost), grease, oil, solvents and other materials that would adversely affect the adhesion of the spray polyurethane foam. 4.3 Thermal Barrier: The spray-applied insulations must be separated from the interior of the building by an approved thermal barrier of 1 / 2 -inch-thick (12.7 mm) gypsum wallboard or an equivalent 15-minute thermal barrier complying with IBC Section 2603.4 or IRC Section R316.4, as applicable, except where installation is in attics, crawl spaces, sill plates, band joists, rim joists or headers as described in Sections 4.4 and 4.5. 4.4 Attics and Crawl Spaces: 4.4.1 Application with a Prescriptive Ignition Barrier: When the spray-applied insulations are installed within attics or crawl spaces, where entry is made only to service utilities, an ignition barrier must be installed in accordance with IBC Section 2603.4.1.6 or IRC Sections R316.5.3 and R316.5.4, as applicable. The ignition barrier must be consistent with the requirements for the type of construction required by the applicable code, and must be installed in a manner so that the foam plastic insulation is not exposed. 4.4.2 Application without a Prescriptive Ignition Barrier: STYROFOAM Spray Polyurethane Foam insulations may be installed in attics and crawl spaces as described in this section without the ignition barriers described in IBC Section 2603.4.1.6 and IRC Sections R316.5.3 and R316.5.4, subject to the following conditions: a. Entry to the attic or crawl space is only to service utilities, and no storage is permitted. b. There are no interconnected attic or crawl space areas. c. Air in the attic or crawl space is not circulated to other parts of the building. d. Attic ventilation is provided when required by IBC Section 1203.2 or IRC Section R806, or as required, except when air-impermeable insulation is permitted in unvented attics in accordance with Section R806.4 of the IRC. e. Under-floor (crawl space) ventilation is provided when required by IBC Section 1203.3 or IRC Section R408.1, as applicable. f. Combustion air is provided in accordance with IMC (International Mechanical Code ) Section 701. In attics, the insulation may be spray-applied with no covering (no ignition barrier) to the underside of roof sheathing or roof rafters, and/or vertical surfaces. In crawl spaces, the insulation may be spray-applied with no covering (no ignition barrier) to the underside of floors and/or vertical surfaces. The thickness of the foam plastic, applied to the underside of the top of the space and/or vertical surfaces, must not exceed 10 inches (254 mm). The insulations may be installed in unvented attics as described in this section in accordance with 2012 IRC Section R806.5 (2009 IRC Section R806.4). 4.4.3 Use on Attic Floors: The STYROFOAM Spray Polyurethane Foam insulations may be installed at a maximum thickness of 10 inches (254 mm) between and over the joists in attic floors. The insulation must be separated from the interior of the building by an approved thermal barrier. The ignition barrier required in IBC Section 2603.4.1.6 and IRC Section R316.5.3 may be omitted. 4.5 Use on Sill Plates, Band Joists and Headers: The STYROFOAM Spray Polyurethane Foam insulations with a maximum thickness of 8 inches (203 mm) may be applied to sill plates and headers without a thermal barrier or ignition barrier, based on testing in accordance with NFPA 286. 4.6 One-hour Nonload-bearing Fire-resistance-rated Wall Assemblies: The STYROFOAM Spray Polyurethane Foam CM2030 and CM2045 may be installed in the stud cavities of nonload-bearing one-hour fire-resistance-rated walls (see Figure 1 for all components in the assembly), provided the system is installed in accordance with the following: 4.6.1 Steel Framing: The framing consists of channelshaped steel studs, 3 5 / 8 inches wide (79 mm) with 1 1 / 2 -inch (38 mm) legs, formed from minimum No.18 MSG galvanized steel spaced 16 inches on center; and channelshaped runners, 3 3 / 4 inches wide (95 mm) with 1 1 / 4 -inch (31 mm) legs, formed from minimum No.18 MSG galvanized steel, attached to the floor at 24 inches (610 mm) on center. 4.6.2 Wall Finish: The interior side of the wall must be finished with one layer of 5 / 8 -inch-thick (15.9 mm), Type X gypsum wallboard applied vertically with joints centered over studs and fastened to steel studs with 1 1 / 4 -inch-long (31 mm), No.8, Type S, self-drilling, self-tapping steel screws spaced 8 inches (203 mm) on center along edges and 12 inches (305 mm) on center in the field of the board. All joints and screw heads must be covered with joint tape

ESR-2670 Most Widely Accepted and Trusted Page 3 of 5 and two coats of joint compound in accordance with GA-216 or ASTM C840. The exterior of the wall must be covered with Dow Thermax (ESR-1659) board, 1 / 2 inch to 3 inches thick (12.7 to 76 mm), attached to the studs with No.8, Type S steel screws in each corner of each piece of the board. The screws must be a minimum of 1 / 2 inch (12.7 mm) longer than the thickness of the board. 4.6.3 Insulation: STYROFOAM Spray Polyurethane Foam CM2030 or CM2045 insulations are applied in the stud cavities against the Dow Thermax at a maximum thickness of 1 1 / 2 inches (38 mm). 4.6.4 Exterior Wall Covering: The exterior wall covering must be 4-inch-wide (102 mm) common brick, with a minimum of a 1-inch (25.4 mm) air space provided between the brick and the foam plastic insulation. 4.7 Exterior Walls of Types I, II, III, and IV Construction: When used on exterior walls of Type I, II, III and IV construction, the STYROFOAM Spray Polyurethane Foam CM2030, CM2045, MX2030 and MX2045 insulations must comply with Section 2603.5 of the IBC at a maximum thickness of 1 1 / 2 inches (38 mm). The potential heat of the foam plastic in any portion of the wall or panels must not exceed the potential heat, expressed in Btu/ft 2 (MJ/m 2 ), of the Spray Polyurethane Foam insulation contained in the wall assembly tested in accordance with NFPA 285. The potential heat of STYROFOAM Spray Polyurethane Foam CM2030, CM2045, MX2030 and MX2045 insulations is 2458 Btu/ft 2 (28 MJ/m 2 ) per inch of thickness. 5.0 CONDITIONS OF USE The STYROFOAM Spray Polyurethane Foam RS2030, RS2045, CM2030, CM2045, MX2030 and MX2045 insulations described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The insulations must be installed in accordance with the manufacturer s published installation instructions, this evaluation report and the applicable code. The instructions within this report govern if there are any conflicts between the manufacturer s published installation instructions and this report. 5.2 The insulations must be separated from the interior of the building by an approved 15-minute thermal barrier as described in Section 4.3, except when installation is in attics and crawl spaces as described in Section 4.4, or when application is on sill plates or headers as described in Section 4.5. 5.3 The insulations must be protected from the weather during and after application. 5.4 The insulations must be applied by installers certified by The Dow Chemical Company or by the Spray Polyurethane Foam Alliance (SPFA) for the installation of spray polyurethane foam insulation. 5.5 Use of the insulations in areas where the probability of termite infestation is very heavy must be in accordance with 2012 IBC Section 2603.9 (2009 IBC Section 2603.8) or IRC Section R318.4, as applicable. 5.6 Jobsite certification and labeling of the insulation must comply with 2012 IRC Sections N1101.16 (2009 IRC Sections N1101.4 and N1101.4.1) and 2012 IECC Sections C303.1.1, C303.1.2 and R401.3 (2009 IECC Sections 303.1.1. and 303.1.2), as applicable. 5.7 When use is on buildings of Type I, II, III or IV construction, documentation must be submitted to the code official verifying that the insulation has been qualified as a component of an assembly tested in accordance with IBC Sections 2603.5.1 (unless constructed in accordance with Section 4.6), 2603.5.5 and 2603.5.7. The maximum potential heat of the spray polyurethane foam plastic used in the assembly must be no greater than that noted in Section 4.7. 5.8 The insulation components (Parts A and B) are produced by The Dow Chemical Company, under a quality control program with inspections by ICC-ES. 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Spray-applied Foam Plastic Insulation (AC377), dated April 2016), including reports of tests in accordance with Appendix X of AC377. 6.2 Reports on air leakage tests in accordance with ASTM E283. 6.3 Reports on water vapor transmission tests in accordance with ASTM E96. 6.4 Data in accordance with ASTM E119. 6.5 Reports of potential heat tests in accordance with NFPA 259. 6.6 Reports of room corner fire tests in accordance with NFPA 286. 7.0 IDENTIFICATION Components of STYROFOAM Spray Polyurethane Foam insulations are identified with the manufacturer s name (The Dow Chemical Company) and address; the product name (A Component is labeled Dow 3019 isocyanate; B Component is labeled with one of the product names listed in this report); lot number; use and application instructions; the flame-spread and smoke-development indices; the evaluation report number (ESR-2670). 8.0 OTHER CODES 8.1 Evaluation Scope: In addition to the codes referenced in Section 1.0, the products in this report were evaluated for compliance with the requirements of the following codes: 2006 International Building Code (2006 IBC) 2006 International Residential Code (2006 IRC) 2006 International Energy Conservation Code (2006 IECC) 2003 International Building Code (2003 IBC) 2003 International Residential Code (2003 IRC) 2003 International Energy Conservation Code (2003 IECC) 8.2 Uses: The products comply with the above-mentioned codes as described in Sections 2.0 to 7.0 of this report, except as noted below: Application with a Prescriptive Ignition Barrier: See Section 4.4.1, except attics must be vented in accordance with Section 1203.2 of the 2006 and 2003 IBC or Section R806 of the 2006 and 2003 IRC; and crawl space ventilation must be in accordance with

ESR-2670 Most Widely Accepted and Trusted Page 4 of 5 Section 1203.3 of the 2006 and 2003 IBC or Section R408 of the 2006 and 2003 IRC, as applicable. Application without a Prescriptive Ignition Barrier: See Section 4.4.2, except attics must be vented in accordance with Section 1203.2 of the 2006 and 2003 IBC or Section R806 of the 2006 and 2003 IRC; and crawl space ventilation must be in accordance with Section 1203.3 of the 2006 and 2003 IBC or Section R408 of the 2006 and 2003 IRC, as applicable. THICKNESS (inches) TABLE 1 THERMAL RESISTANCE (R-VALUES) PRODUCT R-VALUES 1,2 ( F.ft 2.h/Btu) 2030 (RS, CM, MX) 2045 (RS, CM, MX) 1 6.0 6.5 1.5 9.0 9.6 2 12 13 3 18 19 3.5 21 22 4 25 25 5 31 32 5.5 34 35 6 37 38 7 43 44 8 49 50 9 55 57 10 62 63 11 68 69 12 74 76 For SI: 1 inch = 25.5 mm; 1 F.ft 2.h/Btu = 0.176 110 K.m 2 /W. 1 R-values are calculated based on test values at 1- and 4-inch thicknesses. 2 R-values are calculated based on test values at 1- and 3.5-inch thicknesses.

ESR-2670 Most Widely Accepted and Trusted Page 5 of 5 Legend: (1) Floor and ceiling runners; (2) steel studs; (3) lateral support members (not shown); (4) gypsum board; (5) Dow CM Series spray polyurethane foam plastic; (6) Dow Thermax ; ( 7) self-adhered flashing tape or sealant (optional); (8) mortar drop protection (optional); (9) wall anchor ties; (10) vapor retarder or water-resistive barrier (optional); (11) brick veneer FIGURE 1