PUSHOVER ANALYSIS (NON-LINEAR STATIC ANALYSIS) OF RC BUILDINGS USING SAP SOFTWARE

Similar documents
Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

PUSHOVER ANALYSIS FOR THE RC STRUCTURES WITH DIFFERENT ECCENTRICITY

Seismic performance assessment of reinforced concrete buildings using pushover analysis

COMPARATIVE STUDY OF REINFORCED CONCRETE SHEAR WALL ANALYSIS IN MULTI- STOREYED BUILDING WITH OPENINGS BY NONLINEAR METHODS

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

MODAL PUSHOVER ANALYSIS OF RC FRAME BUILDING WITH STAIRCASE AND ELEVATOR CORE

A COMPARATIVE STUDY ON SEISMIC PERFORMANCE EVALUATION OF IRREGULAR BUILDINGS WITH MOMENT RESISTING FRAMES AND DUAL SYSTEMS

Static Analysis of Multistoreyed RC Buildings By Using Pushover Methodology

NONLINEAR STATIC ANALYSIS OF R.C.C. FRAMES (Software Implementation ETABS 9.7)

Non-Linear Pushover Analysis of Flatslab Building by using Sap2000

Performance Based Seismic Design of Reinforced Concrete Building

NONLINEAR PERFORMANCE OF A TEN-STORY REINFORCED CONCRETE SPECIAL MOMENT RESISTING FRAME (SMRF)

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

Nonlinear Pushover Analysis of Steel Frame Structure Dahal, Purna P., Graduate Student Southern Illinois University, Carbondale

ON DRIFT LIMITS ASSOCIATED WITH DIFFERENT DAMAGE LEVELS. Ahmed GHOBARAH 1 ABSTRACT

Seismic Assessment of an RC Building Using Pushover Analysis

Pushover analysis of RC frame structure using ETABS 9.7.1

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

Seismic Performance Evaluation of Torsionally Asymmetric Buildings

Application of Pushover Analysis for Evaluating Seismic Performance of RC Building

SEISMIC STRENGTHENING OF PARTIALLY INFILL RC BUILDINGS USING BRICK INSERTS - EXPERIMENTAL INVESTIGATION ON 3D MODEL STRUCTURE

Nonlinear Static Pushover Analysis of a Shear Wall Building in Madinah

OPTIMUM POSITION OF OUTRIGGER SYSTEM FOR HIGH RAISED RC BUILDINGS USING ETABS (PUSH OVER ANALYSIS)

Non-Linear Static Analysis of RCC Frames

Comparative Study on Concentric Steel Braced Frame Structure due to Effect of Aspect Ratio using Pushover Analysis

Effect of soft storey on multistoried reinforced concrete building frame

EARTHQUAKE ANALYSIS OF A G+12 STOREY BUILDING WITH AND WITHOUT INFILL FOR BHUJ AND KOYNA EARTHQUAKE FUNCTIONS

Seismic Performance Assessment of RCS Building By Pushover Analysis

[Mohammed* et al., 5(8): August, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

BEHAVIOR OF REINFORCED CONCRETE BEAM WITH OPENING

Analytical Study on Seismic Performance of Hybrid (DUAL) Structural System Subjected To Earthquake

PERFORMANCE- BASED SEISMIC DESIGN OF A BUILDING

Interaction between ductile RC perimeter frames and floor slabs containing precast units

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

PERFORMANCE BASED SEISMIC EVALUATION OF MULTI-STOREYED REINFORCED CONCRETE BUILDINGS USING PUSHOVER ANALYSIS

In-plane testing of precast concrete wall panels with grouted sleeve

A Comparison of Basic Pushover Methods

ctbuh.org/papers CTBUH Recommendations for the Seismic Design of High-Rise Buildings

Parametric Study of Dual Structural System using NLTH Analysis Ismaeel Mohammed 1 S. M. Hashmi 2

SEISMIC EVALUATION OF BUILDINGS WITH POSTTENSIONED BEAMS BY NON-LINEAR STATIC ANALYSIS

Effect of Standard No Rules for Moment Resisting Frames on the Elastic and Inelastic Behavior of Dual Steel Systems

TO STUDY THE PERFORMANCE OF HIGH-RISE BUILDING UNDER LATERAL LOAD WITH BARE FRAME AND SHEAR WALL WITH OPENINGS

Nonlinear seismic assessment of eight-storey reinforced concrete building according to Eurocode EN

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure

PUSHOVER ANALYSIS FOR PERFORMANCE BASED-SEISMIC DESIGN OF RC FRAMES WITH SHEAR WALLS

Assessment of P-Delta Effect on High Rise Buildings

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 10, 2016 ISSN (online):

COMPARISON BETWEEN THE DIRECT DISPLACEMENT BASED DESIGN AND THE FORCE BASED DESIGN METHODS IN REINFORCED CONCRETE FRAMED STRUCTURES

Design check of BRBF system according to Eurocode 8 Use of pushover analysis

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

SEISMIC EFFECTS ON COUPLED SHEAR WALL STRUCTURE BY COUPLING BEAMS WITH SIDE BOLTED STEEL PLATES

Seismic Base Isolation of RC Frame Structures With and Without Infill

Prediction of Initial Column Size for Reinforced Concrete Frame Buildings with Intermediate Drift

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

PUSHOVER ANALYSIS OF A 19 STORY CONCRETE SHEAR WALL BUILDING

Seismic Performance and Design of Linked Column Frame System (LCF)

SEISMIC EVALUATION OF RC MULTISTOREY BUILDING OF ASYMMETRIC PLAN WITH VISCO-ELASTIC DAMPER

Behaviour of Reinforced Concrete Dual Structural System: Strength, Deformation Characteristics, and Failure Mechanism

Seismic Retrofit Of RC Columns With Inadequate Lap-Splice Length By External Post-Tensioned High-Strength Strips

optimal design of frp retrofitting for seismic resistant rc frames C. Chisari 1, C. Bedon 2 1

Modelling of RC moment resisting frames with precast-prestressed flooring system

COST C26. Urban Habitat Constructions under Catastrophic Events EARTHQUAKE RESISTANCE WG 2 Session, March 30th

High Performance and Efficiency of Joints in Precast Members

International Journal of Engineering Research And Management (IJERM) ISSN: , Volume-03, Issue-11, November 2016

Effect of Cracked Section on Lateral Response of Reinforced Concrete Flanged Beams

SEISMIC CAPACITY EVALUATION OF POST-TENSIONED CONCRETE SLAB-COLUMN FRAME BUILDINGS BY PUSHOVER ANALYSIS

Application of Buckling Restrained Braces in a 50-Storey Building

Journal of Asian Scientific Research EVALUATION OF RECTANGULAR CONCRETE-FILLED STEEL-HOLLOW SECTION BEAM-COLUMNS

Index terms Diagrid, Nonlinear Static Analysis, SAP 2000.

Seismic resistance of a reinforced concrete building before and after retrofitting Part I: The existing building

Parasiya et al., International Journal of Advanced Engineering Research and Studies E-ISSN

Pushover Analysis of Steel Frame Structures with Different Types of Bracing System

Evaluation of Earthquake Risk Buildings with Masonry Infill Panels

Nonlinear Finite Element Modeling & Simulation

EARTHQUAKE HAZARD REDUCTION IN EXISTING CONCRETE BUILDINGS AND CONCRETE WITH MASONRY INFILL BUILDINGS

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress

We are IntechOpen, the first native scientific publisher of Open Access books. International authors and editors. Our authors are among the TOP 1%

Comparative study of Performance of RCC Multi-Storey Building for Koyna and Bhuj Earthquakes

Seismic Behavior of Soft First Storey

[Jagadeesh B N* et al., 5(9): September, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

Damage-control Seismic Design of Moment-resisting RC Frame Buildings

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 09, 2014 ISSN (online):

THE EXTENDED N2 METHOD IN SEISMIC DESIGN OF STEEL FRAMES CONSIDERING SEMI-RIGID JOINTS

Static and Dynamic Behavior of Reinforced Concrete Framed Building: A Comparative Study

Sabah Shawkat Cabinet of Structural Engineering 2017

Volume 1. HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents

PERFORMANCE OF LATERAL SYSTEMS ON TALL BUILDINGS

Gravity Load Collapse of Reinforced Concrete Columns with Brittle Failure Modes

ANALYSIS PROCEDURES FOR PERFORMANCED BASED DESIGN

EVALUATION OF MODAL PUSHOVER ANALYSIS USING VERTICALLY IRREGULAR FRAMES

Available at ISSN

DESIGN AND COMPARISON OF A RESIDENTIAL BUILDING (G+10) FOR SEISMIC FORCES USING THE CODES: IS1893, EURO CODE8, ASCE 7-10 AND BRITISH CODE

BASE SHEAR REDISTRIBUTION BETWEEN THE R/C DUAL SYSTEM STRUCTURAL COMPONENTS

Extreme Loading for Structures Version 3.1

NONLINEAR DYNAMIC RESPONSE OF DISSIPATIVE DEVICES FOR SEISMIC RESISTANT STEEL FRAMES: EXPERIMENTAL BEHAVIOUR AND NUMERICAL SIMULATION

EFFECT OF FLUID VISCOUS DAMPERS IN MULTI-STOREYED BUILDINGS

Research on the Influence of Infill Walls on Seismic Performance of Masonry Buildings with Bottom Frame-Shear Walls

Transcription:

PUSHOVER ANALYSIS (NON-LINEAR STATIC ANALYSIS) OF RC BUILDINGS USING SAP SOFTWARE PROJECT REFERENCE NO. : 37S0221 COLLEGE : DAYANANDA SAGAR COLLEGE OF ENGINEERING, BANGALORE BRANCH : CIVIL ENGINEERING GUIDE : MOHAMMED ISMAIL STUDENTS : MOHAMMED MAJID ALI HITESH KUMAR MAYURA.V SYED SAID AHMED Introduction: Pushover analysis is an approximate analysis method in which the structure is subjected to monotonically increasing lateral forces with an invariant height-wise distribution until a target displacement is reached. Pushover analysis consists of a series of sequential elastic analysis, superimposed to approximate a force-displacement curve of the overall structure. A two or three dimensional model which includes bilinear or tri-linear load-deformation diagrams of all lateral force resisting elements is first created and gravity loads are applied initially. A pre-defined lateral load pattern which is distributed along the building height is then applied. The lateral forces are increased until some members yield. The structural model is modified to account for the reduced stiffness of yielded members and lateral forces are again increased until additional members yield. The process is continued until a control displacement at the top of building reaches a certain level of deformation or structure becomes unstable. The roof displacement is plotted with base shear to get the global capacity curve. Pushover analysis can be performed as force-controlled or displacement-controlled. In forcecontrolled pushover procedure, full load combination is applied as specified, i.e., force- Controlled procedure should be used when the load is known (such as gravity loading). Also, in force-controlled pushover procedure some numerical problems that affect the accuracy of 1

results occur since target displacement may be associated with a very small positive or even a negative lateral stiffness because of the development of mechanisms and P-delta effects. Pushover analysis has been the preferred method for seismic performance evaluation of structures by the major rehabilitation guidelines and codes because it is conceptually and computationally simple. Pushover analysis allows tracing the sequence of yielding and failure on member and structural level as well as the progress of overall capacity curve of the structure. (girgin. et., 2007) Objectives of the project: The various aspects of pushover analysis and the accuracy of pushover analysis in predicting seismic demands are investigated by several researchers. However, most of these researches made use of specifically designed structures in the context of the study or specific forms of pushover procedure. Firstly, the superiority of pushover analysis over elastic procedures in evaluating the seismic performance of a structure is discussed by identifying the advantages and limitations of the procedure. Then, pushover analyses are performed on case study frames using SAP2000. Also, the effects and the accuracy of various invariant lateral load patterns 'Uniform', 'Elastic First Mode', 'Code', 'FEMA-273' and 'Multi-Modal utilized in traditional pushover analysis to predict the behavior imposed on the structure due to randomly selected individual ground motions causing elastic and various levels of nonlinear response are evaluated. For this purpose, six deformation levels represented a speak roof displacements the capacity curve of the frames are firstly predetermined and the response parameters such as story displacements, inter-story drift ratios, story shears and plastic hinge locations are then estimated from the results of pushover analyses for any lateral load pattern at the considered deformation level. Story displacements, inter-story drift ratios and plastic hinge locations are also estimated by performing an improved pushover procedure named Modal Pushover Analysis (MPA) on case study frames. Pushover predictions are compared with the exact values of response parameters obtained from the experimental results to assess the accuracy of software. 2

Methodology: Modeling In SAP2000 GENERAL DESCRIPTION OF STRUCTURE One of the major objectives of this work was to test a real- life structure under pushover loads. In order to keep the structure as close to reality as possible, no special design for the structure as such was performed and instead a portion of a real life existing office building was selected. Thus the structure tested in this work was a replica of a part of an existing office building. The portion was deliberately selected so that it had certain eccentricities and was un-symmetric in plan (Fig. 4.1). Also the column sizes and sections were varied along the storey as in the case of original real life structure. (Reddy. et., 2010) Although the geometry of the structure tested in this work was kept same as the portion of the original structure, there were few major differences in the reinforcement detailing as mentioned below: Although the original structure was detailed according to new conforming seismic detailing practice as per IS 13920 (BIS, 1993), the structure for the experiment followed the non-seismic detailing practice as per IS 456 (BIS 2000). The reason for this is the fact that pushover analysis is mostly used for retrofit of old structures, which have not followed the seismic detailing practice. Consequently, special confining reinforcement as recommended by IS 13920(BIS, 1993) was not provided. Also no shear reinforcement in the beam- column joints was provided. Since the structure tested is replica of a small portion of the large original structure, the continuous reinforcement in the slab and beams were suitably modified to fit as per the requirement. Another major difference is in the foundation system. In order to avoid any nonlinear behavior of the foundation, a raft foundation with a number of rock anchors were provided. 3

Material Properties The material used for construction is Reinforced concrete with M-20 grade concrete and Fe- 415 grade reinforcing steel. The Stress-Strain relationship used is as per I.S.456:2000. The basic material properties used are as follows: Modulus of Elasticity of steel, Es = 210,000 MP Modulus of Elasticity of concrete, EC = 22,360.68 MPa Characteristic strength of concrete, fck = 20 MPa Yield stress for steel, fy = 415 MPa Ultimate strain in bending, cu =0.0035 Model Geometry The structure analyzed is a four-storied, one bay along X-direction and two bays along Y- direction moment-resisting frame of reinforced concrete with properties as specified above. The concrete floors are modeled as rigid. The details of the model are given as: Number of stories = 4 Number of bays along X-direction =1 Number of bays along Y-direction = 1 Storey height = 4.0 meters Bay width along X-direction = 5.0 meters Bay width along Y-direction = 5.0 meters 4

Results: Deformed 3d View (X Direction) Fig.5.1 Deformed 3D view in x-direction 5

Deformed 3d View (Y Direction) Fig.5.2 Deformed 3D view in Y Direction 6

Pushover curves in x-direction Resultant base shear vs monitored displacement FEMA 356 Method 7

PUSHOVER CURVES IN Y-DIRECTION RESULTANT BASE SHEAR VS MONITORED DISPLACEMENT FEMA 356 Method 8

Conclusions: Up to the value of base shear around 390 KN, the frame has been observed to be linear whereas in case of experiment it was around 300 KN. At this point the flexural tension cracks at the base of the columns depicting reduction in stiffness have been observed. At 430 KN, the cracks at the base of the columns have been found to open wider and failures at other location like beam column joints started. Whereas in case of experiment at a base shear value of approximately 500 KN. After reaching the base shear values of 600 KN, displacements increases at fast rate whereas in case of experiment at the base shear values of 700 KN, the joints of the frame have found to be displaying rapid degradation and the inter storey drift increasing rapidly. Maximum deflection has been found to be more than 300mm at 970 KN. Maximum deflection is more than 770mm at 880KN experimentally. The main conclusions drawn are summarized below: The frame behaved linearly elastic up to a base shear value of around 390 KN. At the value of base-shear 600KN, it depicted non-linearity in its behavior. Increase in deflection has been observed to be more with load increments at base-shear of 600 KN showing the elastic plastic behavior. The joints of the structure have displayed rapid degradation and the inter storey deflections have increased rapidly in non- linear zone. Severe damages have occurred at joints at lower floors whereas moderate damages have been observed in the first and second floors. Minor damage has been observed at roof level. The frame has shown variety of failures like beam-column joint failure, flexural failures and shear failures. Prominent failures are joint failures. Flexural failures have been seen in beams due to X-directional loading. It has been observed that the top storey experienced major damages in this case opposite to the case of frame. Micro cracks have been observed to appear even when the frame is in its elastic zone. The cracks have been found increasing with the increase in deflections. 9

Scope for Future Work: In the present study frame has been studied under monotonic loads. The frame can be studied under cyclic-loading to monitor the variation in load-deflection curves at given time history. The various other parameters as listed below can also be analyzed: with Infill s, Shear wall, Base isolators. 10