A comparison of numerically and experimentally obtained in-plane responses of a full-scale unreinforced masonry building frame

Similar documents
Non-linear equivalent frame modelling:- Assessment of a two storey perforated unreinforced masonry wall

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

MODAL PUSHOVER ANALYSIS OF RC FRAME BUILDING WITH STAIRCASE AND ELEVATOR CORE

SEISMIC REHABILITATION OF A COMMON TYPE OF URM BUILDING IN IRAN

Modelling of RC moment resisting frames with precast-prestressed flooring system

Performance Based Seismic Design of Reinforced Concrete Building

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

Nonlinear Pushover Analysis of Steel Frame Structure Dahal, Purna P., Graduate Student Southern Illinois University, Carbondale

In-plane testing of precast concrete wall panels with grouted sleeve

Static Analysis of Multistoreyed RC Buildings By Using Pushover Methodology

Seismic Vulnerability of Old Masonry Gaioleiro

A SIMPLIFIED METHOD FOR THE ESTIMATION OF THE SEISMIC RESISTANCE OF RC FRAMES WITH WEAK INFILL PANELS

Evaluation of Earthquake Risk Buildings with Masonry Infill Panels

A Comparison of Basic Pushover Methods

ANALYSIS PROCEDURES FOR PERFORMANCED BASED DESIGN

PUSHOVER ANALYSIS FOR THE RC STRUCTURES WITH DIFFERENT ECCENTRICITY

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

BEHAVIOR OF INFILL MASONRY WALLS STRENGTHENED WITH FRP MATERIALS

Nonlinear seismic assessment of eight-storey reinforced concrete building according to Eurocode EN

Proposed Update to Masonry Provisions of ASCE/SEI 41: Seismic Evaluation and Retrofit of Existing Buildings

EARTHQUAKE HAZARD REDUCTION IN EXISTING CONCRETE BUILDINGS AND CONCRETE WITH MASONRY INFILL BUILDINGS

optimal design of frp retrofitting for seismic resistant rc frames C. Chisari 1, C. Bedon 2 1

EXPERIMENTAL STUDY OF THE DEFORMATION CAPACITY OF STRUCTURAL MASONRY

NONLINEAR PERFORMANCE OF A TEN-STORY REINFORCED CONCRETE SPECIAL MOMENT RESISTING FRAME (SMRF)

Comparative Study on Concentric Steel Braced Frame Structure due to Effect of Aspect Ratio using Pushover Analysis

SEISMIC TEST OF CONCRETE BLOCK INFILLED REINFORCED CONCRETE FRAMES

DEFORMATION CAPACITY OF STRUCTURAL MASONRY: A REVIEW OF THEORETICAL RESEARCH

PUSHOVER ANALYSIS OF A MODERN AGGREGATE OF MASONRY BUILDINGS THROUGH MACRO-ELEMENT MODELLING

PUSHOVER ANALYSIS OF A 19 STORY CONCRETE SHEAR WALL BUILDING

COST C26. Urban Habitat Constructions under Catastrophic Events EARTHQUAKE RESISTANCE WG 2 Session, March 30th

Practical Nonlinear Analysis for Limit Design of Reinforced Masonry Walls

Nonlinear Finite Element Modeling & Simulation

Finite Element Modelling of Unreinforced Masonry (URM) Wall with Openings: Studies in Australia

Out-of-Plane testing of an unreinforced masonry wall subjected to one-way bending

Experimental Study on Wall-Frame Connection of Confined Masonry Wall

Seismic Performance Evaluation of Torsionally Asymmetric Buildings

Non-Linear Pushover Analysis of Flatslab Building by using Sap2000

Behaviour and design of innovative hybrid coupled shear walls for steel buildings in seismic areas

Index terms Diagrid, Nonlinear Static Analysis, SAP 2000.

ON DRIFT LIMITS ASSOCIATED WITH DIFFERENT DAMAGE LEVELS. Ahmed GHOBARAH 1 ABSTRACT

SEISMIC STRENGTHENING OF PARTIALLY INFILL RC BUILDINGS USING BRICK INSERTS - EXPERIMENTAL INVESTIGATION ON 3D MODEL STRUCTURE

Seismic Retrofit Of RC Columns With Inadequate Lap-Splice Length By External Post-Tensioned High-Strength Strips

BEHAVIOR OF REINFORCED CONCRETE BEAM WITH OPENING

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

ctbuh.org/papers CTBUH Recommendations for the Seismic Design of High-Rise Buildings

DESIGN OF HIGH-RISE CORE-WALL BUILDINGS: A CANADIAN PERSPECTIVE

Interaction between ductile RC perimeter frames and floor slabs containing precast units

EVALUATION OF THE NEED FOR WEAK BEAM-STRONG COLUMN DESIGN IN DUAL FRAME-WALL STRUCTURES

SEISMIC EVALUATION OF BUILDINGS WITH POSTTENSIONED BEAMS BY NON-LINEAR STATIC ANALYSIS

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress

Effect of soft storey on multistoried reinforced concrete building frame

In-situ Out-of-Plane Airbag Testing of Infill Masonry Cavity Walls

Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower

PUSHOVER ANALYSIS FOR PERFORMANCE BASED-SEISMIC DESIGN OF RC FRAMES WITH SHEAR WALLS

EFFECT OF INFILL STIFFNESS ON SEISMIC PERFORMANCE OF MOMENT RESISTING RC STRUCTURE

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

CYCLIC BEHAVIOUR OF TRUSS TYPE REINFORCED CONCRETE MASONRY WALLS

NON-LINEAR STRUCTURAL INTEGRITY ANALYSIS

SEAU 5 th Annual Education Conference 1. ASCE Concrete Provisions. Concrete Provisions. Concrete Strengths. Robert Pekelnicky, PE, SE

Nonlinear Static Pushover Analysis of a Shear Wall Building in Madinah

Seismic Performance and Design of Linked Column Frame System (LCF)

Strengthening of infilled RC frames by CFRP

INFLUENCE OF BNWF SOIL MODELLING ON DYNAMIC BEHAVIOUR OF PILE FOUNDATION FOR RC FRAME WITH STRUCTURAL WALL

Behaviour of Reinforced Concrete Dual Structural System: Strength, Deformation Characteristics, and Failure Mechanism

RESPONSE STUDY OF MULTI-STORIED BUILDINGS WITH PLAN IRREGULARITY SUBJECTED TO EARTHQUAKE AND WIND LOADS USING LINEAR STATIC ANALYSIS

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

GFRP REINFORCING OF CONCRETE MASONRY INFILL WALLS. Abstract

SEISMIC ASSESSMENT AND REHABILITATION OF UNREINFORCED MASONRY BUILDINGS IN THE USA

DISPLACEMENT-BASED SEISMIC DESIGN OF CONCRETE BRIDGES

Evaluation of Seismic Behavior for Low-Rise RC Moment Resisting Frame with Masonry Infill Walls

COMPARATIVE STUDY OF REINFORCED CONCRETE SHEAR WALL ANALYSIS IN MULTI- STOREYED BUILDING WITH OPENINGS BY NONLINEAR METHODS

22. DESIGN OF STEEL BRACED FRAMES Eccentrically Braced Steel Frames

Updating the ASCE 41 Provisions for Infilled RC Frames

BASE SHEAR REDISTRIBUTION BETWEEN THE R/C DUAL SYSTEM STRUCTURAL COMPONENTS

TESTING OF AN EARTHQUAKE-DAMAGED UNREINFORCED MASONRY BUILDING

Earthquake Design of Flexible Soil Retaining Structures

We are IntechOpen, the first native scientific publisher of Open Access books. International authors and editors. Our authors are among the TOP 1%

Inelastic Versus Elastic Displacement-Based Intensity Measures for Seismic Analysis

SEISMIC EFFECTS ON COUPLED SHEAR WALL STRUCTURE BY COUPLING BEAMS WITH SIDE BOLTED STEEL PLATES

Effect of Standard No Rules for Moment Resisting Frames on the Elastic and Inelastic Behavior of Dual Steel Systems

NON-LINEAR FINITE ELEMENT MODELING OF RC FRAME-MASONRY WALL INTERACTION UNDER CYCLIC LOADINGS

Non Linear Analysis of Composite Beam Slab Junction with Shear Connectors using Ansys.16

Study on Nonlinear Static Analysis of R/C Frames Retrofitted With Steel Plate Shear Wall

Contents. 1.1 Introduction 1

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Analytical Investigation of Seismic Performance of Exterior RC Beam-Column Joints Rehabilitated with New Scheme

Shaking Table Test of Controlled Rocking Reinforced Concrete Frames

DETERMINATION OF MOMENT RESISTING RC FRAMES OF RESPONSE REDUCTION FACTORS

MIDAS Training Series

Modeling of Coupled Nonlinear Shear and Flexural Responses in Medium-Rise RC Walls

COMPARISON BETWEEN THE DIRECT DISPLACEMENT BASED DESIGN AND THE FORCE BASED DESIGN METHODS IN REINFORCED CONCRETE FRAMED STRUCTURES

PSEUDO-DYNAMIC TESTING OF UNREINFORCED MASONRY BUILDING WITH FLEXIBLE DIAPHRAGM. Jocelyn Paquette 1 and Michel Bruneau 2 ABSTRACT

Behaviour of Concrete Filled Rectangular Steel Tube Column

Finite Element Simulation of Low Concrete Strength Beam-Column Joint Strengthened with CFRP

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

EXPERIMENTAL AND NUMERICAL SIMULATIONS OF COLLAPSE OF MASONRY ARCHES

Seismic performance assessment of reinforced concrete buildings using pushover analysis

Transcription:

Proceedings of the Tenth Pacific Conference on Earthquake Engineering Building an Earthquake-Resilient Pacific 6-8 November 2015, Sydney, Australia A comparison of numerically and experimentally obtained in-plane responses of a full-scale unreinforced masonry building frame A. Pir, L.S. Hogan, D.Y. Dizhur, K.Q. Walsh, & J.M. Ingham Department of Civil and Environmental Engineering, University of Auckland, New Zealand. ABSTRACT: Pushover analysis is a popular technique to determine the displacement capacity and failure mechanisms of assemblies of building components or global building behaviour. As pushover analysis is often used for the assessment of unreinforced masonry (URM) buildings, there is a need to benchmark existing modelling frameworks against large scale testing in order to assist in the development of best practice guidelines. Hence, a study was performed to assess the suitability of existing pushover analysis techniques to represent the in-plane response of a clay brick URM building frame. Utilising material and geometrical properties determined from in-situ measurements and laboratory testing, a blind pushover analysis of a three-storey frame from an early 1900s URM building located in central Auckland, New Zealand was performed using the SAP2000 TM (2011) software package and following national and international assessment guidelines. The results obtained from the simulated pushover analysis were compared to those obtained from experimental in-situ pushover testing of the building frame, and recommendations regarding the in-plane pushover analysis of URM frames were made based on the results. Keywords: pushover analysis, URM, rocking wall, seismic response, clay brick, earthquakes, heritage buildings 1 INTRODUCTION Pushover analysis is a nonlinear assessment method used to evaluate the predicted response of buildings and building components when subjected to lateral earthquake loading. The method is based on nonlinear force-deformation relationships of substructures and can be used to assess building strength capacity and post-yielding behaviours. The brittleness of the masonry material potentially results in the formation of nonlinear behaviour at low displacement demands. An equivalent frame approach for assessing unreinforced masonry (URM) piers and spandrels was introduced by Dolce (1989) which was adopted by Knox (2012) and Sarkar et al. (2015). This approach is widely utilised by practicing engineers in place of costly finite element methods using shell and solid elements. The case study building modelled in this research programme was an early 1900s URM building experimentally tested for in-plane response. The west wall of the building was subjected to quasi-static and impulse loads at the roof level, and the tested URM wall was pushed to the initiation of cracking and rocking in the URM piers. More information on the building and experimental studies are presented in Hogan et al. (2015a, 2015b). As reported herein, a blind pushover numerical simulation was carried out to predict the lateral response of the URM wall, and the predictions were compared to the experimental results. The URM wall in-plane assessment methods as presented in NZSEE (2015) and ASCE 41-13 (2014) include linear and nonlinear analytical guidelines used to predict the seismic performance of URM walls in-plane. Paper Number 67

2 ANALYTICAL MODEL AND VALIDATION 2.1 URM equivalent frame Based on the Dolce (1989) equivalent frame model, a URM wall loaded in-plane can be discretised into frame elements (i.e. piers, spandrels, and rigid connection zones). The effective heights of the URM piers based on the proposed criteria of the Dolce (1989) method are shown in Figure 1. Knox (2012) carried out experimental and numerical research on URM walls and employed the equivalent frame concept to predict the nonlinear in-plane response of laboratory-built URM walls. According to Knox (2012), the numerical modelling of URM walls using the equivalent frame approach was found to be generally compatible with experimental results. Figure 1. Piers effective heights as proposed by Dolce (1989) In the considered wall of the subject building, a reinforced concrete (RC) bond beam existed at each floor level. Hence, the spandrel beams at the first and second levels of the equivalent frame model were modelled as composite elements (i.e., URM and RC). The schematic drawings of the tested URM wall and its equivalent frame are illustrated in Figure 2. RC Beam AP3 DP3 IP3 URM RC Beam AP2 URM RC Beam DP2 HP1 AP1 DP1 IP1 a) Components of the tested wall b) Equivalent frame of the tested wall Figure 2. Schematic drawings of the tested wall 2.2 Material properties In the study reported herein, material properties were experimentally determined and subsequently employed in the model of the case study building in order to accurately simulate the nonlinear behaviour of each component. The experimentally measured mechanical characteristics of the masonry prisms included the mean compressive strength (f m ), modulus of elasticity (E m ), and the 2

mean masonry bed joint shear strength f jv which were equal to 6.3 MPa, 5632 MPa, and 0.44 MPa respectively. The mean compressive strength and Young s modulus of URM prisms were obtained using the procedures reported in ASTM C1314 (2011) which represents the un-crack characteristics of URM material. The horizontal compressive strength (f mh ) and the shear modulus of masonry material (G m ) were assumed equal to 0.5f m and 0.4f m respectively, in accordance with NZSEE (2015) and ASCE 41-13 (2014) guidelines. The mean measured concrete compressive strength and modulus of elasticity were 18.5 MPa and 18,190 MPa, respectively. 2.3 Strength-deformation relation of URM components 2.3.1 URM pier in-plane capacity URM pier failure is potentially governed by four fundamental mechanisms. According to NZSEE (2015), the lateral load capacity corresponding to each of the four mechanisms can be calculated by the following formulae: V r = 0.9(αP+0.5P W )L w H eff (1) V tc = (αp+0.5p W )L w h eff (1 f a 0.7f m ) (2) V dt = f dt A n β (1 + f a f dt ) (3) V s = 0.7(A n c + μ s (P+P W )) (4) Where V r, V tc, V dt, and V s are the maximum predicted capacities for rocking, toe crushing, diagonal tensile cracking, and bed joint sliding failure mechanisms, respectively. In these formulae, P and P w represent the overburden load applied at the top of the effective height of the pier plus the pier self weight. L w and h eff represent the length and effective height, respectively, of the pier, and f a and f m represent the axial stress at the bottom of pier and masonry prism compressive strength, respectively. The masonry diagonal tensile stress and net area are denoted by f dt and A n, and parameters c and μ represent masonry cohesion and friction respectively. The maximum capacity of each pier is governed by the minimum of the calculated in-plane strengths of the four failure mechanisms. When discounting the presence of flanges, the predicted shear strengths for each pier of the case study wall are listed in Table 1 with the minimum capacity included in bold, indicating that the dominant failure mode for all piers was predicted to be rocking. The generalised strength-deformation diagram for the rocking mechanism as prescribed by NZSEE (2015) and ASCE 41-13 (2014) is shown in Figure 3. Pier ID* Axial Load ** Table 1. Predicted pier capacity V r V tc V dt V s Axial Load *** V r,flanged AP1 131 33 34 164 195 156 42 AP2 79 21 23 129 174 93 28 AP3 33 10 11 80 121 36 15 DP1 240 66 68 194 264 236 72 DP2 156 45 47 157 229 153 49 DP3 87 29 31 125 199 85 31 HP1 87 42 45 205 297 104 49 IP1 150 30 30 177 204 183 38 IP3 33 9 10 81 122 36 11 * Pier IDs are illustrated in Figure 2-(a) ** Axial load at the top of the simplified piers ***Axial load at the top of the flanged piers 3

Figure 3. Generalised strength-deformation relation for URM piers (NZSEE 2015) The displacement corresponding to maximum rocking strength is symbolised by Δ y. The toe crushing limit capacity and its corresponding deformation, Δ tc,r, were defined by utilising the moment-curvature approach prescribed by NZSEE (2015). The toe crushing deformation limit can be determined from the following formula (Moon 2004): tc,r =h eff 2 (0.8)(0.0035) 1 ( ) Pb ( 0.8f ' ) 3 m bw Where P b represents the axial load at the bottom of the pier, b w is the pier width, and the other parameters are as defined previously. 2.3.2 Effect of flanges on the URM pier rocking capacity According to NZSEE (2015), the in-plane response of URM piers is significantly influenced by the presence of flanges. Yi et al. (2008) developed a set of formulae to predict the capacity of flanged walls based on internal stress distribution in the URM walls. In the current study, the primary shear capacities of the piers were calculated according to NZSEE (2015) while neglecting the flanges, and the effects of flanges on rocking capacity (the assumed dominant mechanism) were evaluated by considering the flange self-weight acting on the flange geometrical centroid, with updated values for rocking capacity provided in the far right columns of Table 1. The pier details are illustrated in Figure 4. (5) Figure 4. Pier cross-sections (The flange area is indicated by A f ) 4

2.3.3 Spandrel flexural and shear capacity The URM and RC spandrel compressive models were based on the Park-Kent model (Kaushik et al. 2007), and it was assumed that the URM material behaved as weak concrete (compared to the concrete compressive strength of RC beams) with a mean compressive strength of 6.3 MPa. Each spandrel was modelled as a composite component by using asymmetrical moment-rotation relationships based on flexural equilibrium as shown in Figure 5. The shear capacity of the URM spandrel material was calculated according to NZSEE (2015). Compared to the shear strength of the RC beam, the URM spandrel shear strength was relatively insignificant. Hence, the shear capacity of the RC beam by itself was assumed to represent the spandrel shear strength. Figure 5. Schematic of the flexural equilibrium of a composite spandrel for positive and negative flexure 2.4 Numerical modelling SAP2000 TM was employed as the platform for predicting the nonlinear response of the case study URM building wall. SAP2000 TM allows the user to define the shear and flexural hinge properties for asymmetrical and composite sections. Equivalent frame components were defined according to the measured geometries of the in situ building wall. To assess the in-plane shear capacity of the tested URM wall, two sets of pier cross-sections, the simplified and as-built flanged piers, were defined by using the section designer in SAP2000 TM. The first pier set included simplified pier sections for which the effects of the flanges on the URM wall were neglected. The second pier set consisted of modelled piers with as-built cross-sections. The strength-deformation relationship for each URM pier was defined by assigning a nonlinear shear hinge at midheight based on NZSEE (2015) and ASCE 41-13 (2014) recommendations. The shear hinge was the preferred simulation option for modelling of the rocking mechanism (the dominant mechanism) since the shear strength corresponding to the relative displacement of piers could be modelled directly in accordance with NZSEE guideline (shown in Figure 3). In order to calibrate the shear hinge responses to lateral deformation, each pier was initially subjected to an isolated pushover analysis. The spandrels were modelled according to measured geometries with three plastic hinges assigned to represent the flexural and shear behaviour of the composite RC beam. Flexural plastic hinges were assigned to each end of every spandrel, and shear hinges were assigned to the midlength of every spandrel. The connections between piers and spandrels were modelled as rigid zones by considering offset lengths at the ends of each element based on the recommendations of Dolce (1989). 3 IN-PLANE PUSHOVER PREDICTED RESPONSE To compare the numerical pushover curves with the experimental results, a single point load was applied at the roof level in place of typical pushover load distribution which is a linearly increasing load at each floor. The base shear force corresponding to the roof displacement was recorded in 1000 analytical steps by imposing an incremental displacement at the roof level of the wall up to 0.4 mm in each step. With increasing lateral deformation, rocking mechanisms formed at the top piers, at the shear hinges which were defined in order to simulate a rocking mechanism, also developed at the top piers after an insignificant deformation of 1.5 mm. Subsequently, the shear capacity degraded due to toe crushing mechanism in piers AP3, DP3, and IP3. The final collapse stage of the modelled URM 5

Base shear wall as shown in Figure 6 was governed by toe crushing in the top floor piers. The maximum shear capacities of the simulated wall were predicted to occur at 1.75 mm and 2 mm of roof level displacement in the simplified and flanged models, respectively. Figure 6. Deformed equivalent frame The simulated pushover capacity curves for the URM wall models with the simplified and flanged cross-section configurations, respectively, are illustrated in Figure 7. Each drop in the numerical pushover curve represents the complete loss of lateral load carrying capacity of a pier at the roof level which was defined according to the pier deformation limits as shown in Figure 3. The model with asbuilt flanged piers resulted in an 18% increase in predicted maximum lateral capacity compared to the simplified model, due to predicted increases in the rocking capacity and toe crushing strength. The predicted pushover curve of the modelled wall with flanged piers had a lower lateral drift capacity compared to the simplified model due to differences in the toe crushing limit capacity, consistent with the results reported by Yi et al. (2008), explaining the earlier lateral strength loss of the IP3 pier in the flanged model. At the roof level, the IP3 pier was the sole pier with a flange located at the toe. Furthermore, the deformation capacity corresponding to toe crushing would be reduced by any increase in the axial load (Equation 5). 60 50 40 30 20 DP3 Loss DP3 Loss simplified piers model flanged piers model IP3 Loss AP3 Loss 10 AP3 Loss IP3 Loss 0 0 50 100 150 200 250 300 350 Displacement at roof level (mm) Figure 7.Base shear-displacement curves of the tested wall 6

Base-shear Base-shear 4 COMPARISON OF PREDICTEDAND EXPERIMENTAL RESULTS The URM wall shown in Figure 8 (as modelled in Figure 2) was subjected to in-situ quasi-static and impulse loading, and the load-deformation measurements were recorded over eight loading cycles. Due to limitations in the loading capacity of the test equipment relative to the measured strength of the wall, the building wall was likely not loaded to its ultimate strength. The maximum applied load to the in situ wall was measured as 55 kn (Figure 9). Figure 8. The URM wall subjected to in-plane load Comparison between numerical and experimentally measured pushover results (Figure 9-a) indicated that the simplified numerical model underestimated the minimum possible strength of the tested wall and the flanged model predicted the pier strength closer to the minimum possible strength of the tested wall. The displacements corresponding to the maximum numerically measured shear strength, 55 kn, were 1.9 mm for the flanged pier model and 3.75 mm for the experimental results, respectively (Figure 9-b). The initial stiffnesses of the tested and the simulated walls were approximately identical, and the difference between the in-plane stiffness of the experimentally tested wall and simulated wall could be explained by the rocking mechanism of a pier which is simulated as rigid-body rotation and independent from the member stiffness in the model. In the experimental study, approximately, 46% of the total 0.3 mm deformation at the middle pier was due to rocking (Hogan et al. 2015b) which could explain the 51% difference in the simulated and experimentally measured displacements corresponding to 55 kn. The initial and secant stiffnesses referred to the base shear-deformation ratios corresponding to the initial linear and the maximum experimentally measured shear strength, respectively. Experimental load-displacement hysteresis Experimental load-displacement hysteresis Experimental load-displacement envelope Experimental load-displacement envelope 60 Predicted load-displacement envelope 60 Predicted load-displacement envelope 50 50 40 40 30 30 20 20 10 10 0 0 1 2 3 4 0 0 1 2 3 4 Displacement at the roof level (mm) Displacement at the roof level (mm) a) Simplified piers b) Flanged piers Figure 9. Load-displacement curves 7

5 CONCLUSION An analytical model for the in-plane assessment of a case study URM wall was presented based on an equivalent frame approach as well as NZSEE (2015) and ASCE 41-13 (2014) guideline recommendations. The maximum in-plane load capacity of the URM wall was predicted by performing a blind pushover analysis. The maximum predicted in-plane shear capacities corresponding to the simplified and flanged pier cross-sections were 47 and 56 kn respectively, which indicated that by taking the flanges into account, an 18% increase in the shear capacity of the case study URM wall was predicted. Hence, it was concluded that considering the flanged cross-section in the pushover model would likely result in more realistic in-plane strengths. Compared to the experimentally measured pushover result, the predictive model underestimated the actual in-plane wall capacity. Compared to the tested wall, the initial stiffness of the simulated wall was 6% higher. Furthermore, the higher measured displacements of the tested wall at the roof level corresponding to 55 kn demonstrated that the numerical model overestimated the secant wall stiffness by 51%. 6 REFERENCES: ASCE/SEI 41-13. 2014. Seismic evaluation and retrofit of existing buildings. American Society of Civil Engineers, Washington D.C, United States. ASTM C1314. 2011. Standard test method for compressive strength of masonry prisms. American Society for Testing and Materials, Pennsylvania, United States. Dolce M. 1989. Models for in-plane loading of masonry walls. Corso sul consolidamento degli edifici in muratura in zona sismica. Ordine degli Ingegneri,Potenza. (Italian) Hogan L.S., Walsh K.Q., Beskhyroun S., Ingham J.M., and Dizhur D.Y. 2015a. Contribution of timber-framed partition walls to the dynamic characteristics of an unreinforced masonry building. New Zealand Society of Earthquake Engineering Technical Conference. 10-12 April 2015. Wellington. Hogan L.S., Walsh K.Q., Ingham J.M., and Dizhur D.Y. 2015b. Experimental pushover testing of a full-scale existing unreinforced clay brick masonry building. 10th Pacific Conference on Earthquake Engineering. 6-8 November 2015. Sydney, Australia. Knox L.C. 2012. Assessment of perforated unreinforced masonry walls responding in-plane. University of Auckland. PhD Thesis. Auckland. Kaushik H.B., Rai D.C., and Jain S.K. 2007. Stress-strain characteristics of clay brick masonry under uniaxial compression. Journal of Materials in Civil Engineering, 19(9).728-738. Moon F.L. 2004. Seismic strengthening of low-rise unreinforced masonry structures with flexible diaphragms. Georgia Institute of Technology. PhD Thesis. Georgia. NZSEE 2015. Assessment and improvement of the structural performance of buildings and earthquakes - recommendations of a NZSEE study group on earthquake risk buildings. New Zealand Society for Earthquake Engineering. Wellington. Sarkar A., Halder L., and Sharma R. 2015. Seismic damage evaluation of unreinforced masonry buildings in high seismic zone using the nonlinear static method. Advances in Structural Engineering.1039-1053. Springer India. SAP2000 Ultimate. 2011. Structural analysis program. V-15.1. Computers and Structures Inc, Berkeley, CA, USA. Yi T., Moon F.L., Leon R.T., and Kahn L.F. 2008. Flange effects on the nonlinear behaviour of URM piers. The Masonry Society Journal. 26(2).31-42. 8