Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

Similar documents
Thermal Performances Of Three Types Of Ground Heat Exchangers In Short-Time Period Of Operation

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Study on Heat Exchange Characteristics for PHC Energy Piles

APPLICATIONS OF A DYNAMIC THREE-DIMENSIONAL NUMERICAL MODEL FOR BOREHOLE HEAT EXCHANGERS. M. He, S.J. Rees, L. Shao

Parametric Study for Evaluation of Design Parameters of Standing Column Well

Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields

Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers

A quasi-two-dimensional standing column well model for ground source heat pump systems

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing

Optimal Design for a Hybrid Ground-Source Heat Pump

Thermal Efficiency of the Borehole Heat Exchanger Built with Drilling Mud.

STUDY ON THE DESIGN PROCEDURE OF GEOTHERMAL HEAT PUMPS: GEOTHERMAL HEAT PUMP SYSTEM WITH

PREPROCESSOR FOR THE GENERATION OF G-FUNCTIONS USED IN THE SIMULATION OF GEOTHERMAL SYSTEMS

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

TEMPERATURE STRATIFICATION OF CIRCULAR BOREHOLE THERMAL ENERGY STORAGES

Pitfalls of Rules of Thumb in Geothermal Heat Pump Design

EXPERIMENT FOR VERIFICATION OF GROUND SOURCE HEAT PUMP USING THE DIRECT EXPANSION METHOD

Performance Analysis of Slinky Horizontal Ground Heat Exchangers for a Ground Source Heat Pump System

Ground Source Heat Pumps: Testing three mediums surrounding the piping in geothermal field beds to evaluate performance

Working parameters affecting earth-air heat exchanger (EAHE) system performance for passive cooling: A review

ANALYSIS OF VARIOUS DESIGNING PARAMETERS FOR EARTH AIR TUNNEL HEAT EXCHANGER SYSTEM

SIMULATION AND OPTIMIZATION OF GROUND SOURCE HEAT PUMP SYSTEMS

NUMERICAL SIMULATION OF GROUND HEAT AND WATER TRANSFER FOR GROUNDWATER HEAT PUMP SYSTEM

Optimizing Borehole Heat Exchanger Spacing to Maximize Advective Heat Transfer A THESIS SUBMITTED TO THE FACULTY OF UNIVERSITY OF MINNESOTA BY

Modeling of Standing Column Wells in Ground Source Heat Pump Systems

GEOTHERMAL HEAT PUMPS CONFIGURATIONS/INSTALLATION

Finite Volume Based Computer Programs for Ground Source Heat Pump Systems

Ground Coupled Heat Pump Systems a Key for a Sustainable Development of Heating and Cooling Buildings

Modeling of Usage of Air Injection Well in a Geothermal System

Energy and Buildings

NUMERICAL MODELLING OF MULTIPLE STANDING COLUMN WELLS FOR HEATING AND COOLING BUILDINGS

CFD ANALYSIS OF THERMAL INFLUENCE ZONE OF EARTH AIR TUNNEL HEAT EXCHANGER UNDER TRANSIENT CONDITIONS

Calculation and Analysis the Influence on the Cooling Water Velocity and Hot Metal Circulation to the Long Life Blast Furnace

Optimal design of vertical ground heat exchangers by using entropy generation minimization method and genetic algorithms

MODELING THE VIABILITY OF UNDERGROUND COAL FIRES AS A HEAT SOURCE FOR ELECTRICAL POWER GENERATION

Simulation of Hybrid Ground Source Heat Pump Systems and Experimental Validation

Geothermal Heating & Cooling in Health Care Applications

This paper was presented at 12th REHVA World Congress (Clima 2016).

Hafiz M K U Haq 1, Birgitta J. Martinkauppi 1, and Erkki Hiltunen 1 1 Department of Energy Technology

Cooling Ceiling Panel

Geothermal Tunnel Linings. Principles of Geothermal Tunnel Linings

Computational Study of Hybrid Water Heater with Evacuated Glass Tube Solar Collector and Rice Husk Combustion

The correct citation for this paper is:

CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas

Numerical study of the influence of injection/production well perforation location on CO 2 -EGS system

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

White Paper. Geothermal Heating and Cooling

DISTRIBUTION TRANSFORMER COOLING USING THE GEOTHERMAL ENERGY FROM THE UNDERGROUND ELECTRIC PIPELINES

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Heat Integration Across Plants Considering Distance Factor

Numerical Simulation of Critical Factors Controlling Heat Extraction from Geothermal Systems Using a Closed-Loop Heat Exchange Method

Research on Ground Source Heat Pump Design

Horizontal Borehole Study

Thermal Management of Densely-packed EV Battery Set

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE

The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results

Exergy Analysis of a Ground-Source Heat Pump System. University of Cambridge, Department of Engineering, Cambridge, UK, 2

Use of Geothermal Energy in Snow Melting and Deicing of Transportation Infrastructures

GCEP Model. The GCEP (Ground Coupling Ecole Polytechnique) model does hourly simulations of rectangular borfields.

Analysis of Fuel Cell Driven Ground Source Heat Pump Systems in Community Buildings

The potential of earth-air heat exchangers for low energy cooling of buildings in South Algeria

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Impellers of low specific speed centrifugal pump based on the draughting technology

HEAT TRANSFER ANALYSIS OF GEOTHERMAL HEAT EXCHANGERS IN GROUND-COUPLED HEAT PUMP SYSTEMS. Abstract. 1. Introduction

Bore field sizing : Theory and applications

International Journal Of Scientific Research And Education Volume 3 Issue 3 Pages March-2015 ISSN (e): Website:

School of Energy and Environmental Engineering, Hebei University of Technology, Tianjin , China

ScienceDirect. Compact hot water storage systems combining copper tube with high conductivity graphite and phase change materials

Geothermal Praxis in Germany

A Modeling of Biomass Fast Pyrolysis using CFD in a fluidized bed reactor

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

Abstract. Nomenclature. A Porosity function for momentum equations L Latent heat of melting (J/Kg) c Specific heat (J/kg-K) s Liquid fraction

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Energy performance evaluation and optimisation of ground source heat pump systems

Ground Source Heat Pump System Design and Permitting AWWA Pacific Northwest Section Conference, May 6-8, 2009 Salem, Oregon

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

THE GEOTHERMAL ADVANTAGE

Heat Extraction from Deep Single Wells

Effect of alumina nanoparticles in the fluid on heat transfer in double-pipe heat exchanger system

A. This Section includes exterior piping for vertical, direct-buried, ground-loop, heat-pump systems that operate between 23 and 104 deg F.

Overview of Method for Reducing Grounding Resistance of Substation Grounding System

ENERGY SAVING IN BUILDING USING PCM IN WINDOWS

Thermal Analysis of Solar Flat Plate Collector

Snow-Melting on Sidewalks with Ground-Coupled Heat Pumps in a Heavy Snowfall City

CFD ANALYSIS OF CALANDRIA BASED NUCLEAR REACTOR: PART-II. PARAMETRIC ANALYSIS OF MODERATOR

Heat Insulation Analysis of an Aluminium Honeycomb Sandwich Structure

Exergy analysis of a flat plate solar collector

O. Capron *1, A. Samba 1,2, N. Omar 1, H. Gualous 2, P. Van den Bossche 1, J. Van Mierlo 1. Brussel, Brussels, BELGIUM. 1.

Study of water falling film over horizontal drop shaped and inverted drop shaped tubes

CFD Simulation Studies on Integrated Approach of Solar Chimney and Earth Air Tunnel Heat Exchanger for Building Space Conditioning

Performance of an Open Ducted Type Very Low Head Cross- Flow Turbine

A Solar Wall System Utilized in Rural Houses of Northeast China

Electrical/thermal performance of hybrid PV/T system in Sharjah, UAE

Passive Cooldown Performance of Integral Pressurized Water Reactor

PERFORMANCE CHARACTERIZATION OF SHALLOW HELICAL GROUND HEAT EXCHANGERS FOR GROUND SOURCE HEAT PUMP APPLICATIONS. Francisco Javier Alvarez Revenga

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

Transcription:

American Journal of Energy Engineering 14; (5): 13-17 Published online October 1, 14 (http://www.sciencepublishinggroup.com/j/ajee) doi: 1.11648/j.ajee.145.11 Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump Jalaluddin 1, *, Akio Miyara 1 Department of Mechanical Engineering, Hasanuddin University, Makassar, Indonesia Department of Mechanical Engineering, Saga University, Saga-shi, Japan Email address: jalaluddin_had@yahoo.com (Jalaluddin), miyara@me.saga-u.ac.jp (A. Miyara) To cite this article: Jalaluddin, Akio Miyara. Performance Investigation of Multiple-Tube Ground Heat Exchangers for Ground-Source Heat Pump. American Journal of Energy Engineering. Vol., No. 5, 14, pp. 13-17. doi: 1.11648/j.ajee.145.11 Abstract: The present study aims to investigate the performance of multiple-tube ground heat exchangers (GHEs). The multiple-tube GHEs with a number of pipes installed inside the borehole were simulated. Thermal interferences between the pipes and performance of multiple-tube GHEs are discussed. Increasing the number of inlet tube in the borehole increases the contact surface area and then leads to increase of heat exchange with the ground. However, ineffective of heat exchange in the outlet tube caused by thermal interferences from the inlet tube reduces the heat exchange rate for the GHEs. The GHE performances increase of 9.1 % for three-tube, of 13.6 % for four-tube, and of.1 % for multi-tube compared with that of the U-tube. The four-tube and multi-tube GHEs which consist of four pipes as heat exchange pipes where the multi-tube GHE provides better performance than that of the four-tube GHE. This fact indicates that thermal interferences between the pipes affect the performance. Thermal interferences between the pipes should be considered. Keywords: Heat Exchange Rate, Thermal Interferences, Multiple-Tube GHEs 1. Introduction The geothermal energy source is categorized based on ASHRAE [1] for using in high-temperature electric power production; > 15 ο C, intermediate and low temperature direct-use applications; < 15 ο C, and Ground-source heat pump (GSHP) system applications; generally < 3 ο C. The GSHP system has been widely used in engineering application for space heating and cooling. The GHEs used in the GSHP system are installed in either horizontal trenches or vertical boreholes. Short-term and long-term performances are important issues of the GSHP system. Both the short-term and long-term behavior of ground loop heat exchangers is critical to the design and energy analysis of ground-source heat pump systems []. Short-term analysis is required for detailed building energy analysis and the design of hybrid GSHP system [3, 4]. It helps to understand the effects of short duration peak loads on the ground response [5-9] and to establish the running control strategies for alternative operation modes in short time scales of operation such as for cooling, heating, and hot water heating according to different requirements [1]. The GHEs used in the GSHP system are installed in either horizontal trenches or vertical boreholes. Temperature distributions, energy and exergy performances for two different horizontal GHEs [11, 1] and for three different vertical boreholes of 3, 6, and 9 m [13, 14] have been reported. Several factors such as local conditions, ground heat exchanger (GHE) parameters, and operation conditions contribute significantly to the thermal performance of the GHE that used in the GSHP system to exchange heat with the ground. Analyzing the GHE performance in those conditions is needed to provide an accurate prediction of the performance in the GSHP system design. A number of studies have investigated the GHE performance in various backfilled materials, concrete pile foundations, and configuration shapes [15-18]. Heat exchange rate of the GHE was also evaluated by Jun et al. [19] with considering the effect of running time, shank spacing, depth of borehole, velocity in the pipe, thermal conductivity of grout, inlet temperature and soil type. Experimental study of thermal performance of three types of GHEs including U-tube, double-tube, and multi-tube types installed in a steel pile foundation with m of depth has been done []. The heat exchange rates of the GHEs in 4 hours of continuous operation with flow rates of, 4, and 8 l/min and the effect of increasing the flow rate have been discussed. The performance of the GHEs has been also investigated in different operation modes [1]. Operating the GHEs with

14 Jalaluddin and Akio Miyara: Performance Investigation of Multiple-Tube Ground Heat Exchangers for Ground-Source Heat Pump different operation mode shows the different characteristic in their heat exchange rates. This work investigates thermal interference and performance of multiple-tube ground heat exchangers (GHEs). The multiple-tube GHEs with a number of pipes installed inside the borehole were simulated in order to investigate the thermal interferences between the tubes and their performances.. Numerical Method.1. GHE Models Three-dimensional unsteady-state models for multiple tubes of GHEs were built and simulated by using a commercial CFD code, FLUENT. Steel pipes, which are used as foundation pile for houses, were buried in the ground and used as boreholes for the GHEs. Multiple-tube GHEs including U-tube, multi-tube, three-tube, four-tube types where a number of pipes installed inside the boreholes at m depth were simulated in order to investigate the thermal interferences between the tubes and their performances. The multiple tubes were inserted in the steel pile, and the gaps between the steel pile and tubes were grouted with silica-sand. In addition, the multi-tube consists of a central insulated-pipe as the outlet tube and four pipes as the inlet tubes placed around the central pipe. The three-tube and four-tube types were built with installing three and four tubes inside the boreholes which consists of two inlet and one outlet tubes for the three tube type and three inlet and one outlet tubes for the four-tube type, respectively. For all the GHEs, polyethylene is used as a tube material. The ground around the GHEs is modeled of 5 m in radius. Fig. 1 shows the horizontal cross-sections of the multiple tube types of GHE models. Three-dimensional hybrid mesh generation was applied in the GHE models. All the related geometric parameters and material thermal properties for the GHEs are listed in Table 1. Table 1. Related geometric parameters and material thermal properties of the GHEs. Parameters Value Unit U-tube, Tri-tube and Four-tube Inlet and outlet pipes of the multiple-tube GHEs (material: Polyethylene) Outer diameter, d o.33 m Inner diameter, d i.6 m Thermal conductivity, k PE.35 W/(m K) Multi-tube Inlet pipes of the multi-tube (material: Polyethylene) Outer diameter, d o.5 m Inner diameter, d i. m Thermal conductivity, k PVC.35 W/(m K) Outlet pipe of the multi-tube (material: Polyethylene) Outer diameter, d o. m Inner diameter, d i.16 m Thermal conductivity, k PVC.35 W/(m K) Pile foundation of the multiple-tube GHEs (material: Steel) Outer diameter, d o.1398 m Inner diameter, d i.198 m Thermal conductivity, k Steel 54 W/(m K) Grout (material: Silica sand) Thermal conductivity, k grout 1.4 W/(m K) Figure 1. The horizontal cross-sections of the multiple-tube GHEs... Boundary Conditions The ground profiles around the borehole consist of Clay, sand, and Sandy-clay. This ground profiles are typical for Saga city, Japan [1]. The ground properties can be estimated using the values for similar ground profiles in this simulation. The thermal characteristic parameters of the ground are: Clay (ρ = 17 kg/m 3, k = 1. W/m K, c = 18 J/kg K) Sand (ρ = 151 kg/m 3, k = 1.1 W/m K, c = 11 J/kg K) Sandy-clay (ρ = 196 kg/m 3, k =.1 W/m K, c = 1 J/kg K) A constant and uniform temperature was applied to the top and bottom surfaces of the model. Variation of ground temperature near the surface due to ambient climate effect is negligible. Uniform initial ground temperature is assumed to be equal to the undisturbed ground temperature and constant of 17.7 ο C. This value is based on recorded data of local ground temperature at Saga city, Japan []. Inlet temperature and flow rate of circulated water are specified as boundary conditions. The inlet water temperature was set to be constant of 7 ο C. The flow rate of circulated water was set to 16 l/min. For the GHE models that used more than one inlet pipe, this flow rate is the total flow rate of the inlet pipes. k-epsilon two equation turbulence models were applied in the FLUENT simulation set-up. Scaled residuals for turbulence models were monitored.

American Journal of Energy Engineering 14; (5): 13-17 15 3. Heat Transfer Model Three-dimensional unsteady-state model used in simulation is: T k x T + y T T + = c z ρ t where k is thermal conductivity (W/m K), T is temperature (K), ρ is density (kg/m 3 ), c is specific heat (J/kg K), t is time and z is depth. Temperature variation distribution of circulated water is simulated and the thermal performances of the GHEs were investigated by calculating their heat exchange rates through the water flow. The heat exchange rate is calculated by the following equation (1) Q =ɺ mcp T () where mɺ is flow rate, c p is specific heat, and T is the temperature difference between the inlet and outlet tubes of circulated water. The heat exchange rate per unit borehole depth is defined as the following equation and it is used to express the performance of each GHEs. outlet tube is smaller than that of the U-tube. It indicates that effectiveness of the outlet tube decreases due to the thermal interferences from the two inlet tubes. The cross-sectional temperature distributions at 1 m depth after 7 h operation are shown in Fig. 3. The thermal interferences between the inlet and outlet tubes can be seen from these figures. In comparison with the U-tube GHE, the outlet tube of the three-tube GHE is affected by thermal interferences more significant than that of the U-tube GHE as shown in Fig. 3 (b). This fact proves that the water temperature is slightly change caused by thermal interference from the inlet tubes. A similar characteristic of the water temperature distribution is found in the four-tube GHE. In the multi-tube GHE, the water temperature decrease in the inlet tube is largest among those of other GHEs. The thermal interferences from the inlet tubes to the outlet tube are prevented by insulation of the outlet tube and then, the water temperature stays almost constant in the outlet. Q = Q/ L (3) where L is the depth of each GHE. 4. Results and Discussion 4.1. Thermal Interferences Effect Depth (m) - -4-6 -8-1 -1-14 -16 Water temperature distributions after 7 h operation U-tube: inlet outlet Three-tube: inlet A and C outlet B Four-tube (3 inlet pipe): inlet A, B and D outlet Multi-tube: inlet A, B, C, and D outlet E -18 - - 99. 99.5 3. 3.5 31. Temperature (K) (a)u-tube (b)three-tube Figure. Water temperature distributions of multiple- tube GHEs. Figure shows the water temperature distribution of the multiple-tube GHEs after 7 h operation. The temperatures of water are measured at the central point of the tubes. Water temperature distributions decrease in the inlet and outlet tubes of the U-tube GHE. In the three-tube GHE, the water temperature distribution in the inlet tube decreases more than that of the U-tube but the water temperature changes in the (c)four-tube

16 Jalaluddin and Akio Miyara: Performance Investigation of Multiple-Tube Ground Heat Exchangers for Ground-Source Heat Pump 13.6 % for four-tube, and of.1 % for multi-tube compared with that of the U-tube GHE. Table. Heat exchange rates of the multiple-tube GHEs after operating in 7 h. Average heat exchange rate in 7 h, ( Multiple-tube GHEs (W/m) U-tube 7.9 Tri-tube 9.55 Four-tube 3.77 Multi-tube 3.53 Q h / 7 L) (d)multi-tube Figure 3. The cross-sectional temperature distributions at 1 m depth after 7 h continuous operation. Heat exchange rate (W/m) 8 75 7 65 6 55 5 45 4 35 3 5 15 1 Multiple-tube GHEs Four-tube Three-tube Multi-tube U-tube 5 1 3 4 5 6 7 Time (hour) Figure 4. Heat exchange rates of multiple-tube GHEs 4.. Thermal Performances of the Multiple-Tube GHEs Figure 4 shows the heat exchange rates of the GHEs with operating time. In the three-tube and four-tube GHEs, increasing the number of inlet tubes increases the contact surface area and then leads to increase of heat exchange. However, ineffective of heat exchange in the outlet tube caused by thermal interferences from the inlet tubes reduces the heat exchange rates for the both GHEs. In the case of the multi-tube GHE, increasing the contact surface area and protecting thermal interference by insulation of the outlet tube contributes to the heat exchange rate. This result shows that installing a number of pipes inside the borehole does not increase the heat exchange rate of GHE linearly with increasing the contact surface area. Thermal interferences between the pipes should be considered. Effect of thermal interference between the tubes to the GHE thermal performance can be seen from the four-tube and multi-tube GHES which consist of four heat exchange pipes. The multi-tube GHE provides a better performance compared with that of in the four-tube GHE. It is due to insulation of outlet tube in the multi-tube GHE. This fact indicates that thermal interferences between the pipes affect the GHE performance. Average heat exchange rates of the multiple-tube GHEs after operating in 7 h are listed in Table. The GHE performances increase of 9.1 % for three-tube, of 8 75 7 65 6 55 5 45 4 35 3 5 15 1 5 5. Conclusions The geothermal energy sources are locally available and environmentally friendly energy source in the case of reducing CO emission. The well-known application is for space heating and cooling in residential and commercial buildings with using GSHP system. Recently, various types of GHEs are used in the GSHP system to exchange heat with the ground. The heat exchange performance of the GHE is an important subject of GSHP system design. Multiple-tube GHEs are studied to investigate the thermal interference and performance of multiple-tube ground heat exchangers (GHEs). Heat exchange rate of the multiple-tube GHEs are affected significantly by thermal interferences between the inlet and outlet tubes. Increasing the number of inlet tubes increases the contact surface area and then leads to increase of heat exchange with the ground. However, ineffective of heat exchange in the outlet tube caused by thermal interferences from the inlet tubes reduces the heat exchange rates for the GHEs. The GHE performances increase of 9.1 % for three-tube, of 13.6 % for four-tube, and of.1 % for multi-tube compared with that of the U-tube. Thermal interferences between the pipes affect the GHE performance and should be considered in design of GHE. References [1] ASHRAE: 11 ASHRAE Handbook: HVAC Applications, SI Edition, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, GA 339. [] C. Yavuzturk, J.D. Spitler,, S.J. Rees, A Transient Two-dimensional Finite Volume Model for the Simulation of Vertical U-tube Ground Heat Exchangers, ASHRAE Transactions, 1999, vol. 15(), pp. 465-474. [3] C. Yavuzturk, J.D. Spitler, Field Validation of a Short Time-Step Model for Vertical Ground Loop Heat Exchangers, ASHRAE Transactions, 1, vol. 17(1), pp. 617-65. [4] V. Partenay, P. Riederer, T. Salquea, E. Wurtz, The influence of the borehole short-time response on ground source heat pump system efficiency, Energy and Buildings, 11, vol. 43, pp. 18 187. [5] L. Lamarche, B. Beauchamp, New solutions for the short-time analysis of geothermal vertical boreholes, International Journal of Heat and Mass Transfer, 7, vol. 5, pp. 148 1419.

American Journal of Energy Engineering 14; (5): 13-17 17 [6] G. Bandyopadhyay, W. Gosnold, M. Mann, Analytical and semi-analytical solutions for short-time transient response of ground heat exchangers, Energy and Buildings, 8, vol. 4, pp. 1816 184. [7] E.J. Kim, J.J. Roux, G. Rusaouen, F. Kuznik, Numerical modelling of geothermal vertical heat exchangers for the short time analysis using the state model size reduction technique, Applied Thermal Engineering, 1, vol. 3, pp. 76 714. [8] A. Zarrella, M. Scarpa, M. De Carli, Short time step analysis of vertical ground-coupled heat exchangers: The approach of CaRM, Renewable Energy, 11, vol. 36, pp. 357-367. [9] E. Zanchini, S. Lazzari, A. Priarone, Long-term performance of large borehole heat exchanger fields with unbalanced seasonal loads and groundwater flow, Energy, 1, vol. 38, pp. 66-77. [1] P. Cui, H. Yang, Z. Fang, Numerical analysis and experimental validation of heat transfer in ground heat exchangers in alternative operation modes, Energy and Buildings, 8, vol. 4, pp. 16 166. [11] H. Esen, M. Inalli, M. Esen, Numerical and experimental analysis of a horizontal ground-coupled heat pump system, Building and Environment, 7, vol. 4, pp. 116 1134. [1] H. Esen, M. Inalli, M. Esen, K. Pihtili, Energy and exergy analysis of a ground-coupled heat pump system with two horizontal ground heat exchangers, Building and Environment, 7, vol. 4, pp. 366 3615. [13] H. Esen, M. Inalli, Thermal response of ground for different depths on vertical ground source heat pump system in Elazig, Turkey, Journal of the Energy Institute, 9, vol. 8 (), pp. 95-11. [14] H. Esen, M. Inalli, Y. Esen, Temperature distributions in boreholes of a vertical ground-coupled heat pump system, Renewable Energy, 9, vol. 34, pp. 67-679. [15] X. Li, Y. Chen, Z. Chen, J. Zhao, Thermal performances of different types of underground heat exchangers, Energy and Buildings, vol. 38, pp. 543 547. [16] Y. Hamada, H. Saitoh, M. Nakamura, H. Kubota, K. Ochifuji, Field performance of an energy pile system for space heating, Energy and Buildings, 7, vol. 39, pp. 517 54. [17] J. Gao, X. Zhang, J. Liu, K.S. Li, J. Yang, Thermal performance and ground temperature of vertical pile-foundation heat exchangers: A case study, Applied Thermal Engineering, 8, vol. 8, pp. 95 34. [18] C. Lee, M. Park, S. Min, S.H. Kang, B. Sohn, H. Choi, Comparison of effective thermal conductivity in closed-loop vertical ground heat exchangers, Applied Thermal Engineering, 11, vol. 31, pp. 3669-3676. [19] L. Jun, Z. Xu, G. Jun, Y. Jie, Evaluation of heat exchange rate of GHE in geothermal heat pump systems, Renewable Energy, 9, vol. 34, pp. 898 94. [] Jalaluddin, A. Miyara, K. Tsubaki, S. Inoue, K. Yoshida, Experimental study of several types of ground heat exchanger using a steel pile foundation, Renewable Energy, 11, vol. 36, pp. 764-771. [1] Jalaluddin, A. Miyara, Thermal performance investigation of several types of vertical ground heat exchangers with different operation mode, Applied Thermal Engineering, 1, vol. 33-34, pp. 167 174.