Note to Specifier: Use this product for coated glass-mat faced polyisocyanurate insulation boards such as Rboard.

Similar documents
SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

Master Specification WALLTITE Eco v.3 by BASF Canada Inc. Section SPRAY POLYURETHANE FOAM INSULATION Page 1

A. Source Limitations: Obtain each type of building insulation through one source.

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

(Project Location) (your firm's name)

ROCKWOOL Board Insulation Section Master Guide Specification (ROCKBOARD 80) Page 1 January 2017

Sept 30, 2004 Page 1

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

Short Form Guide Specification. STYROFOAM CAVITYMATE Ultra Air Barrier Wall System

SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

Magnum Board Section Digicon Information Inc. Page 1

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Thermasheath-XP. Insulation for Exposed Use

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

Acceptable Floor Substrates: Concrete, cured mortar bed, plywood, and backer board.

Section Pre-Applied Sheet Membrane Waterproofing

SECTION 07530CP EPDM MEMBRANE ROOFING

September 24, 2011 Page 1 PRODUCT DESCRIPTION PRODUCT FEATURES

ROCKWOOL Blanket (and Batt) Insulation Section Master Guide Specification Page 1 Jan 2017

C. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each product.

ROXUL Roof and Deck Insulation Section Master Guide Specification (MONOBOARD ) Page 1 April 2016

Firestone Polyiso Boards

Gold Bond BRAND Gypsum Sheathing

Acrytec NC 25 & NC 25 Insulated Glass-Fiber Reinforced Cementitious (GFRC) Rainscreen Panel System

ROXUL Roof and Deck Insulation Section Master Guide Specification Page 1 April 2016

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

ROXUL Blanket (and Batt) Insulation Section Master Guide Specification (AFB) Page 1 April 2015

.1 Provide submittals in accordance with Section Submittal Procedures.

(Specifier Note: Aristech Surfaces LLC is the manufacturer of the Avonite brand

A. National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

EcoTouch Insulation with PureFiber Technology

TSX Insulation for Exposed Use ROOF WALL SPECIALTY

SPECIFICATION GUIDELINE

OptiLiner Banded Liner System, Thermal, Metal Building

Closed cell expanded polystyrene (EPS) insulation with graphite.

Alply CLASSIC WALL Architectural Insulated Panel Wall System

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013)

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

THERMAL INSULATION

SECTION SUPERGREEN LAM (LIQUID-APPLIED MEMBRANE AIR/VAPOR BARRIER SYSTEM)

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

Wall Insulation: Selection, Application and Specification

SECTION MANUFACTURED ROOF EXPANSION JOINTS

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

SECTION ELASTOMERIC MEMBRANE ROOFING

Thermal Insulation

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION #05-221C 2012

WALL APPLICATIONS IN BUILDINGS EXCEPTIONAL R-VALUE. OUTSTANDING RESISTANCE TO MOISTURE. LONG TERM DURABILITY.

PERM-FLEX (JC) ASSEMBLY DIRECT APPLICATION TO CEMENT BOARD SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

PRODUCT SPECIFICATIONS

SECTION EXPANSION CONTROL

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

MASTERFORMAT SPECIFICATION

SECTION VAPOR PERMEABLE FLUID-APPLIED AIR BARRIER MEMBRANE

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

Air and Vapor Barrier 3015

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL

SECTION PREPARATION FOR RE-ROOFING

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Magnum Board Section Digicon Information Inc. Page 1

Amvic Insulated Radiant PEX Panel Specification

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

BEARING METAL STUD FRAMING

Trusted ICC ES DIVISION: ATLANTA, CGF PRO, ENERGYS. Look. Conformity! Evaluation. ICC-ES Evaluation

SPECIFICATION GUIDELINE

COMMERCIAL BUILDING APPLICATIONS

GUIDE SPECIFICATION: DUCT LINER

Guideline Specifications

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

RAY-CORE Structural Insulated Roof and Wall Panels

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1.

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

Metal Roof Panels

SECTION PRE-ENGINEERED BUILDING INSULATION


ACFoam-II HCFC Free "Green" Polyiso Specification

1.1 SECTION INCLUDES A. Insulated Metal and FRP Wall and Ceiling Panels and Related Accessories.

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

A. Meet at Project site <insert number> days before starting installation.

Corium Brick Rainscreen System Specifications

SECTION ROOF SPECIALTIES

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS

A. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

Application Instructions for Dryvit Backstop NT For Use Beneath Claddings Other Than Dryvit EIFS

CENTRIA FORMABOND II Metal Composite Wall System

SECTION SHEET MEMBRANE SOUND REDUCTION, CRACK ISOLATION / JOINT BRIDGING, AND WATERPROOFING

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Insulation Board. Knauf Data Sheet PE-DS

National Gypsum Company. Drop In Specification Language. Gold Bond BRAND exp Interior Extreme AR Gypsum Panel

Transcription:

Note to Specifier: Use this product for coated glass-mat faced polyisocyanurate insulation boards such as Rboard. Note to Specifier: Make selections, such as board thickness and sizes, etc. Where selection is indicated with an [OR] statement, select the appropriate paragraph and delete the inappropriate statement. Delete all Note to Specifier paragraphs and [AND] [OR] options before final print. Disclaimer: The manufacturer has reviewed the product information contained in this guide specification. The information is organized and presented to assist the specification writer working on a construction project to select the appropriate products and to save time in writing the project specification Section. The specification writer is responsible for product selection as well as the use and application of this information, and should contact the manufacturer to ensure that all options are available and that the associated specification information is valid and correct. SECTION 072115 COATED GLASS-MAT FACED POLYISOCYANURATE FOAM BOARD INSULATION PART 1 - GENERAL 1.1 SECTION INCLUDES A. Rigid polyisocyanurate foam insulation with coated glass-mat facers. B. Fasteners, adhesives, and sealants necessary for a complete installation. Note to Specifier: Carefully and completely edit "WORK SPECIFIED IN OTHER SECTIONS" below to coordinate with other sections being included in the project manual. 1.2 WORK SPECIFIED IN OTHER SECTIONS A. Division 01 Section 017419, Construction Waste Management, for proper separation, handling, and disposal of waste materials. B. Division 01 Section 018100, Facility Performance Requirements, for thermal and air infiltration characteristics for assemblies utilizing rigid polyisocyanurate foam board insulation. C. Division 01 Section 018113.13, Sustainable Design Requirements LEED for New Construction and Major Renovations, for commissioning requirements. D. Division 01 Section 018113.19, Sustainable Design Requirements LEED for Core and Shell Development, for commissioning requirements. E. Division 01 Section 019113, General Commissioning, for commissioning requirements. COATED GLASS-MAT FACED POLYISOCYANURATE FOAM BOARD INSULATION 072115-1

F. Division 03 Section [insert section number] for [Cast-in-Place] [Architectural Precast] Concrete assemblies utilizing rigid polyisocyanurate foam board insulation. G. Division 04 Section 042000, Unit Masonry, for masonry assemblies utilizing rigid polyisocyanurate foam board insulation. H. Division 05 Section 054000, Cold Formed Metal Framing, for cold formed metal framing supported wall assemblies utilizing rigid polyisocyanurate foam board insulation. I. Division 06 Section 061060, Sheathing, for substrate materials for rigid polyisocyanurate board foam insulation. J. Division 07 Section 072500, Weather Barriers for requirements of weather barriers in conjunction with rigid polyisocyanurate foam board insulation. K. Division 07 Section 079200, Joint Sealants for requirements of joint sealants in conjunction with rigid polyisocyanurate foam board insulation. L. [Continue as appropriate for the project]. 1.3 SUBMITTALS A. Make submittals in accordance with requirements specified in Division 01 Section 013300 Submittal Procedures. B. Product Test Reports: Submit evaluation reports published by independent authority indicating evidence of compliance with specified criteria. C. Product Data: Submit product data for each type of product indicated. D. Samples: Submit three samples, minimum size 101 mm x 203 mm (4 in X 8 in). Note to Specifier: DELETE the following Paragraph and subparagraphs if project requirements do not include LEED. If LEED is included, coordinate selections made below with the LEED requirements for the project. E. LEED Submittals: 1. Product Certificates for Credit MR 5.1 and Credit MR 5.2: For products and materials required to comply with requirements for regional materials indicating location and distance from Project of material manufacturer and point of extraction, harvest, or recovery for each raw material. a. Include statement indicating cost for each regional material and the fraction by weight that is considered regional. 1.4 QUALITY ASSURANCE COATED GLASS-MAT FACED POLYISOCYANURATE FOAM BOARD INSULATION 072115-2

A. Surface Burning Characteristics: Mark products with readily identifiable mark from recognizable testing agency indicating compliance with CAN/ULC S102. 1. Flame spread less than 500. B. CCMC Evaluation Report No. 12423-L: Meets CAN/ULC S704-03, Type 2, Class 3 1.5 STORAGE AND HANDLING A. Comply with Manufacturer s recommendations for the proper storage and handling of insulation materials. B. Store materials off of ground, protected from physical damage, and covered or otherwise shielded from sunlight. C. Protect insulation so that insulation does not come in direct contact with rain, snow, or other moisture sources. D. Cover installation within 60 calendar days of initial installation. Note to Specifier: Delete the following if a Construction Waste Management Plan is not required for the project. 1.6 WASTE MANAGEMENT AND DISPOSAL A. Separate and recycle waste materials in accordance with Section 017419, "Construction Waste Management." PART 2 - PRODUCTS 2.1 POLYISOCYANURATE RIGID FOAM BOARDWALL INSULATION A. Coated Glass-Mat Faced Polyisocyanurate Foam Board Wall Insulation: High performance rigid insulation board consisting of CAN/ULC S704-03, Type 2, Class 3 closed-cell polyisocyanurate foam core laminated between two coated glass-mat facers with a minimum weight of 360 grams/m2. 1219 mm x 2438 mm (4 ft x 8 ft) or factory cut to 406 mm x 2438 mm (16 in x 8 ft) Energy Shield CGF formerly Rboard manufactured by Atlas Roofing Corporation. Note to Specifier: Select the appropriate thickness/rsi Value/R-value for project requirements. Delete those not used. Coordinate with details shown on drawings 1. Provide coated glass faced insulation with the following thickness, RSI Value, and R- values: Thickness Thickness "RSI" "R" Value inches Value 13 mm 1/2 0.53 3.0 19 mm 3/4 0.79 4.5 COATED GLASS-MAT FACED POLYISOCYANURATE FOAM BOARD INSULATION 072115-3

25 mm 1.0 1.06 6.0 38 mm 1.5 1.58 9.0 51 mm 2.0 2.13 12.1 64 mm 2.5 2.69 15.3 76 mm 3.0 3.26 18.5 89 mm 3.5 3.82 21.7 102 mm 4.0 4.40 25 2. Facer Materials: Coated glass-mat facer on each face of insulation. Note to Specifier: Indicate preference for size of board. If not critical, delete reference and let Contractor choose. Bold text indicates a selection is required, please choose accordingly and delete unused data. 3. Size: [1219 mm x 2438 mm] (4 ft x 8 ft) or/ and [1219 mm x 2743 mm](4 ft x 9 ft). 4. Size: 2438 mm (8 ft) x [406 mm] (16 in) [or] [610 mm] (24 in) to fit between wall ties. 5. Flame Spread and Smoke Developed: Less than 500 when tested in accordance with CAN/ULC S102. 6. Water Vapour Permeance: Greater than 60 ng/(pa s m 2 ) at 25.4 mm (1 perm per inch) when tested in accordance with ASTM E 96, Desiccant Method. 7. Compressive Strength: Greater than 140 kpa when tested in accordance with ASTM D 1621. 8. Tensile Strength: Greater than 35 kpa when tested in accordance with ASTM D 1623. 9. Flexural Strength: Greater than 275 kpa when tested in accordance with ASTM C 203. 10. Water Absorption: Less than 3.5% by volume when tested in accordance with ASTM D 2842. 11. Dimensional Stability: Less than 1% linear change in length or width when tested in accordance with ASTM D 2126. 12. Service Temperatures: -73ºC to +122ºC. 13. Produced without using HCFC, CFC, HFC blowing agents. 2.2 ACCESSORIES Note to Specifier: Retain adhesive or mechanical fastener installation as appropriate for the intended supporting materials. Generally retain the adhesive installation when insulation is intended to be installed to a flat surface such as CMU or continuous sheathing. If unsure of the best installation method, consult with Manufacturer's representative. A. Insulation Adhesive and Joint Treatment: High strength, heavy-bodied, adhesive formulated to bond insulation to metal, concrete, air/ vapour membranes or masonry surfaces. 1. Product: Subject to compliance with the requirements, provide one of the following: a. Bakor/Henry Air Block 21 b. Other products approved in writing by the insulation board manufacturer. Note to Specifier: Generally retain mechanical fastener when insulation is intended to be installed to a stud wall. Consult with fastener manufacturer's representative for the appropriate fastener for each situation. B. Mechanical Fasteners: Select type, size and length compatible with the substrate, wall system and exposure. COATED GLASS-MAT FACED POLYISOCYANURATE FOAM BOARD INSULATION 072115-4

C. Joint Sealant: Single component, non-shrink joint sealants, backings that are compatible with each other and with other materials in the assembly. D. Expanding Foam Sealant: Single component, non-shrink, complying with CAN/ULC S710 that is compatible with insulation board. Note to Specifier: Always retain tape insulation if insulation is to function as sheathing membrane. E. Joint Tape: Joint tape suitable for use with coated glass-mat facers. Ensure compatibility prior to use by field testing. PART 3 - EXECUTION 3.1 EXAMINATION A. Inspect areas to receive insulation. Ensure that substrates intended for adhesive fastening are clean and free from moisture or other materials that may have a deleterious effect on adhesion. Prepare report identifying conditions that may be detrimental to the performance of the insulation and proceed with installation only after the conditions noted have been properly addressed. 3.2 INSTALLATION A. General: 1. Comply with Manufacturer's instructions for installation of polyisocyanurate rigid foam board wall insulation. 2. Do not install polyisocyanurate rigid foam board wall insulation that has become soiled, wet, or has not been properly protected from sunlight. 3. Dry fit polyisocyanurate rigid foam board wall insulation prior to final installation. Neatly trim around conduits, pipes, and other items that will penetrate insulation board. Note to Specifier: Retain Adhesive attachment, Mechanical attachment, or both depending on the proposed substrates(s). B. Adhesive Attachment: 1. Apply adhesive in accordance with the manufacturers written instructions. Ensure insulation is well bonded to the substrate at all joints between boards and at all penetrations. C. Mechanical Attachment: 1. Select a mechanical fastener appropriate for the intended substrate. Fasten insulation board to substrate with mechanical anchors spaced no greater than 9.5 mm (3/8 in) from edge of board or opening, 305 mm (12 in) on center at perimeter edges and openings and no greater than 406 mm (16 in) on center in both directions within the field of the perimeter. The washer of a single 44.5 mm (1 ¾ in) washer style fastener may be used to bridge adjoining boards. COATED GLASS-MAT FACED POLYISOCYANURATE FOAM BOARD INSULATION 072115-5

3.3 ACCESSORIES Note to Specifier: Generally retain both joint sealant and expanding foam sealants. A. Joint Treatment: For joints, gaps, and openings less that 13 mm wide, install continuous bead of joint treatment to form a seal at all board joints and openings. B. Expanding Foam Sealant: For joints, gaps, and openings greater than 13 mm wide, install sealant in a continuous ribbon between adjacent board edges, working sealant in to joint for a full depth bead of sealant. Note to Specifier: Always retain tape installation if insulation is to function as sheathing membrane. C. Tape: Install tape to form a continuous seal between adjacent boards. Ensure compatibility and maintain adequate overlaps. 3.4 PROTECTION A. Protect polyisocyanurate rigid foam board wall insulation from excess moisture, mechanical damage, and exposure to open flame. B. Promptly repair damage caused to insulation in a manner that retains integrity and continuity of insulation and facer materials. C. Cover insulation with cladding promptly, but no later than 60 days after installation of insulation. END OF SECTION COATED GLASS-MAT FACED POLYISOCYANURATE FOAM BOARD INSULATION 072115-6