AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

Similar documents
AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: GAMCO CORPORATION

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: SPECIALTY WHOLESALE SUPPLY

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: THE NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS Glen Ellyn, Illinois

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

MARLIN WINDOWS, INC 3500 HC SERIES 3 3 8" SLIDING WINDOW PAGE 1

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION

System WV410 Storefront Window System

U-Factor, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance Calculation Report

Series 510-I Thermal Heavy Commercial Projected Window

Architectural Testing

TMS 114 XT TECHNICAL MANUAL

Series Heavy Commercial Projected Window

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

T14000 Series storefront

TMS 152 / 152T / 152XT TECHNICAL MANUAL

FL200 13/4 x41/2 GUIDE SPECIFICATION. Non-Thermal Storefront

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES

SERIES 8520 AW-PG80-AP PROJECT-OUT AWNING WINDOW

SECTION VINYL WINDOWS AND DOORS. 2.2 Slider Windows Classic Series (Standard sizes) and Thermo-Fit Series (Custom sizes)


HomeMaker3 Windows and Doors

A. Section includes extruded aluminum windows with operating sash, operating hardware, and insect screens.

MikronWood Thermal Advantage Composite Window System Ideal for new construction and replacement applications in colder temperature climates

Vinyl Windows and Doors

VINYL SINGLE HUNG WINDOW

Vinyl Window Designs Ltd. 550 Oakdale Road Toronto, ON M3N 1W6 SPECIFICATIONS

Veka Evolutions Commercial Window Program

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS. A. This Section includes fixed and operable aluminum-framed windows.

DOUBLE HUNG SERIES 860 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: C.R.F. 50. Thermal U Value:.61. Main Frame Depth: 4

SINGLE HUNG SERIES 810 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.61. Main Frame Depth: 4

2000/2100/2200 Series Heavy Commercial Sliding Patio Doors

PW251 21/2 x7 GUIDE SPECIFICATION. Curtain Wall

TEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System

Series 660 Single Hung * Series 670 Double Hung Series 6600 Fixed ** Heavy Commercial Hung Thermal Window

Awning Windows Montecito New Construction Window

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E Rendered to REGUPOL AMERICA

PRODUCT SPECIFICATION SERIES 9000 WINDOW WALL THERMALLY BROKEN ALUMINUM CASEMENT / AWNING / FIXED WINDOW

Casement Windows Montecito New Construction Window

Condensation on Indoor Glass Surface

7520 Casement Windows

HORIZONTAL SLIDER SERIES 910 ANSI/AAMA/NWWDA 101/I.S Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.66. Main Frame Depth: 4

HORIZONTAL SLIDER SERIES 900 ANSI/AAMA/NWWDA 101/I.S Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.66. Main Frame Depth: 4

The Aluminum Framed Monumental Folding/Paired Panel System

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

HORIZONTAL SLIDER SERIES 600 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: C.R.F.: 50. Thermal U Value:.

WESTECK WINDOWS and DOORS

E-Wall System 5800, 5800-I

SuperWallTM. Curtainwall - Window Wall

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

3. Reinforcement: Reinforce and/or modify framing system as required to accept door hardware, accessories, operators, security, etc.

Architectural Specification Manual

T700 SERIES(AW50)-Impact (Formerly 8050 series) SINGLE HUNG 3 1/4 FRAME DEPTH (SIDE LOAD)

YES SSG TU Vent Window System

Engineered Specifically for New Construction Applications

System Thermal Clip Storefront System

Structural Performance Tests of VHB Structural Glazing Tapes

4-5/8" Offset Projected Architectural Thermal Aluminum Windows. Project In TR-740 (AW-PG80-AP) or Project Out TR-750 (AW-PG80-AP)

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N

SWING DOOR SPECIFICATION

Series x Thermal Triple Set Storefront Framing

New Construction Windows and Doors

SL70 The Monumental Thermally Broken Aluminum Framed Folding System

MARCH, 2017 Trifab 451UT Framing 1 EC ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS Guide Specs

Exceed Your Expectations Today And Well Into the Future.

Why test a system that has already been tested? Typical Manufacturers information for window to wall interface and basis for reported test results.

SERIES 5500 H-HC60 DOUBLE-HUNG TILT WINDOW

ASTM C 1363 Thermal Performance Test Report

DIVISION 8 OPENINGS SECTION ALUMINUM WINDOWS

BUT THEN AGAIN, SO DO WE.

CASEMENT PROJECT OUT SERIES 6400 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: Main Frame Depth: 3 1/4

Vinyl Replacement Windows and Doors

PERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System

S Page 2 of 14 E0A0 2

Architectural Manual. Thermally Improved Aluminum Series Windows & Patio Doors

SECTION ALUMINUM STORM WINDOWS

THERMALLY BROKEN STEEL WINDOWS STEEL WINDOW INSTITUTE A STANDARD OF EXCELLENCE

Architectural Manual. Thermally Improved Aluminum Series Windows & Patio Doors

NanaWall HSW60 - Thermally Broken Aluminum Framed Single Track Sliding System

FLOOR CEILING ASSEMBLY

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

General Specifications COMPLETE PRODUCT LINE

NORTH TONAWANDA CSD Capital Projects 2015

CASEMENT PROJECT OUT SERIES 4400 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: Main Frame Depth: 4

AUGUST, 2017 IR 500/501 Framing 1 EC ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS Guide Specs

Alply CLASSIC WALL Architectural Insulated Panel Wall System

Section Sliding Aluminum Framed Glass Doors (2500 Model Specifications)

FRENCH DOOR VINYL SERIES 455 / 555

Transcription:

AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) Summary of Results Thermal Transmittance (U-Factor) 0.48 Condensation Resistance Factor - Frame (CRF f ) Condensation Resistance Factor - Glass (CRF g ) 63 Unit Size: 59" x 23-5/8" Layer 1: Gap 1: 1/4" 0.53" Clear A1-D: Aluminum Spacer 90% Argon* Layer 2: 1/4" PPG Solarban 60 (e=0.035*, #3) Reference must be made to Report No. E5507.01-116-46, dated 04/23/15 for complete test specimen description and data.

AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION 131-10 Maple Avenue Flushing, New York 11355 Report Number: Test Date: Report Date: E5507.01-116-46 04/21/15 04/23/15 Test Sample Identification: Series/Model: W250C Awning Type: Projecting (Awning) Test Sample Submitted by: Client Test Procedure: The condensation resistance factor (CRF) and thermal transmittance (U) were determined in accordance with AAMA 1503-09, Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections 1. Average warm side ambient temperature 2. Average cold side ambient temperature 3. 15 mph dynamic wind applied to test specimen exterior. 4. 0.0" +0.04" static pressure drop across specimen. Test Results Summary: 69.80-0.42 F F 1. 2. Condensation resistance factor - Frame (CRF f ) Condensation resistance factor - Glass (CRF g ) 63 Thermal transmittance due to conduction (U) 0.48 (U-factors expressed in Btu/hr ft 2 F)

Page 2 of 9 Test Sample Description: Frame: Material: AU (0.18"): Aluminum with Thermal Improvement - All Members Size: 59" x 23-5/8" Daylight Opening: N/A Glazing Method: N/A Exterior Color: Clear Exterior Finish: Anodized Interior Color: Clear Interior Finish: Anodized Corner Joinery: Mitered / Keys & Stakes / Sealed Vent: Material: Size: Daylight Opening: Exterior Color: Interior Color: Corner Joinery: AU (0.18"): Aluminum with Thermal Improvement - All Members 57-1/4" x 21-7/8" 52-1/4" x 16-7/8" Glazing Method: Interior Clear Exterior Finish: Anodized Clear Interior Finish: Anodized Mitered / Keys & Stakes / Sealed Glazing Information: Layer 1: 1/4" Clear Gap 1: 0.53" A1-D: Aluminum Spacer Layer 2: 1/4" PPG Solarban 60 (e=0.035*, #3) Gas Fill Method: Single-Probe Method* Desiccant: Yes 90% Argon* *Stated per Client/Manufacturer N/A Non-Applicable

Page 3 of 9 Test Sample Description: (Continued) Weatherstripping: Description Flexible hollow bulb gasket Quantity 1 row Location Frame and vent perimeter EPDM wedge gasket 1 row Interior glazing perimeter Hardware: Description 1/4 Turn lever lock handle Quantity 2 Location Bottom rail Metal keeper 2 Sill Multi-arm hinge 2 Jambs/stiles Metal snubber set 1 set Head/top rail Drainage: Drainage Method Weep notch Size 0.88" x 0.13" Quantity 2 Location Sill

Page 4 of 9 Test Duration: 1. The environmental systems were started at 15:29 hours, 04/20/15. 2. The thermal performance test results were derived from 02:05 hours, 04/21/15 to 06:05 hours, 04/21/15. Condensation Resistance Factor (CRF): The following information, condensed from the test data, was used to determine the condensation resistance factor: T h T c FT p FT r W FT GT CRF g CRF f = Warm side ambient air temperature 69.80 F = Cold side ambient air temperature -0.42 F = Average of pre-specified frame temperatures (14) 39.05 F = Average of roving thermocouples (4) 35.78 F = = [(FT p - FT r ) / (FT p - (T c + 10))] x 0.40 FT p (1-W) + W (FT r ) = Frame Temperature 0.044 38.91 F = Glass Temperature 43.98 F = Condensation resistance factor Glass CRF g = (GT - T c ) / (T h - T c ) x 100 63 = Condensation resistance factor Frame CRF f = (FT - T c ) / (T h - T c ) x 100 The CRF number was determined to be (on the size as reported). When reviewing this test data, it should be noted that the frame temperature (FT) was colder than the glass temperature (GT) therefore controlling the CRF number. Refer to the 'CRF Report' page and the 'Thermocouple Location Diagram' page of this report.

Page 5 of 9 Thermal Transmittance (U c ): T h = Average warm side ambient temperature 69.80 F T c = Average cold side ambient temperature -0.42 F P = Static pressure difference across test specimen 0.00 psf 15 mph dynamic perpendicular wind at exterior Nominal sample area 9.68 ft 2 Total measured input to calorimeter 507.33 Btu/hr Calorimeter correction 181.08 Btu/hr Net specimen heat loss 326.25 Btu/hr U = Thermal Transmittance 0.48 Btu/hr ft 2 F Glazing Deflection: Vent Edge Gap Width Estimated center gap width upon receipt of specimen in laboratory (after stabilization) Center gap width at laboratory ambient conditions on day of testing Center gap width at test conditions 0.53" 0.53" 0.53" 0.47" The sample was inspected for the formation of frost or condensation, which may influence the surface temperature measurements. The sample showed no evidence of condensation/frost at the conclusion of the test. Prior to testing the specimen was sealed with silicone on the interior side and checked for air infiltration per Section 9.3.4. Required annual calibrations for the Architectural Testing Inc. 'thermal test chamber' (ICN 000001) in York, Pennsylvania were last conducted in May 2014 in accordance with Architectural Testing Inc. calibration procedure. A CTS Calibration verification was performed December 2014. A Metering Box Wall Transducer and Surround Panel Flanking Loss Characterization was performed December 2014.

Page 6 of 9 CRF Report Time: 04:04 04:34 05:04 05:34 06:05 AVERAGE Pre-specified Thermocouples - Frame 1 36.42 36.41 36.36 36.36 36.35 36.38 2 36.65 36.68 36.65 36.61 36.57 36.63 3 38.12 38.10 38.09 38.03 38.05 38.08 4 42.81 42.84 42.82 42.78 42.81 42.81 5 36.53 36.52 36.50 36.50 36.49 36.51 6 7 39.38 38.52 39.32 38.53 39.40 38.54 39.38 38.45 39.38 38.42 39.37 38.49 8 38.00 37.99 38.03 37.95 37.91 37.98 9 39.93 39.94 39.97 39.92 39.97 39.95 10 42.80 42.80 42.81 42.79 42.84 42.81 11 40.45 40.43 40.44 40.39 40.43 40.43 12 37.62 37.64 37.66 37.60 37.61 37.63 13 38.48 38.47 38.42 38.40 38.39 38.43 14 41.24 41.26 41.27 41.20 41.21 41.24 FT P 39.07 39.07 39.07 39.03 39.03 39.05 Pre-specified Thermocouples - Glass 15 30.46 30.50 30.47 30.43 30.43 30.46 16 55.60 55.60 55.53 55.44 55.55 55.55 17 43.27 43.27 43.28 43.25 43.21 43.26 18 37.05 37.04 37.01 36.99 37.02 37.02 19 58.29 58.32 58.35 58.29 58.21 58.29 20 39.28 39.27 39.33 39.33 39.32 39.31 GT 43.99 44.00 44.00 43.96 43.96 43.98 Cold Point (Roving) Thermocouples 21 34.70 34.70 34.70 34.70 34.70 34.70 22 35.90 35.90 35.90 35.90 35.90 35.90 23 36.10 36.10 36.10 36.10 36.10 36.10 24 36.40 36.40 36.40 36.40 36.40 36.40 FT R 35.78 35.78 35.78 35.78 35.78 35.78 W 0.04 0.04 0.04 0.04 0.04 0.04 FT 38.92 38.92 38.92 38.88 38.89 38.91 Warm Side - Room Ambient Air Temperature 69.80 69.81 69.80 69.81 69.80 69.80 Cold Side - Room Ambient Air Temperature -0.42-0.41-0.42-0.39-0.40-0.41 CRF f CRF g 63 63 63 63 63 63

Page 7 of 9 Thermocouple Location Diagram SELECT DRAWING, DRAG HERE, AND IDENTIFY COLD POINTS 23 22 21 24 Cold Point Locations 21 21. 34.70 22 22. 35.90 23 23. 36.10 24 24. 36.40

Page 8 of 9 Architectural Testing, Inc. will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. The test record retention end date for this report is April 21, 2019. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Ryan P. Moser Senior Technician Shon W. Einsig Senior Technician Individual-In-Responsible-Charge RPM:klb E5507.01-116-46 Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Drawings (6) Architectural Testing, Inc. is accredited by the International Accreditation Service (IAS) under the specific test methods listed under lab code TL-144, in accordance with the recognized International Standard ISO/IEC 17025:2005. The laboratory s accreditation or test report in no way constitutes or implies product certification, approval, or endorsement by IAS.

Page 9 of 9 Revision Log Rev. # Date Page(s) Revision(s).01R0 04/23/15 All Original Report Issue. Work requested by Howard Nguyen of Gamco Corporation This report produced from controlled document template ATI 00025(c), revised 03/14/2013.