MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Steet, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Floida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315-2599 NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy Entega Roof, LLC 1289 NE 9 th Ave Okeechobee, FL 34972 SCOPE: This NOA is being issued unde the applicable ules and egulations govening the use of constuction mateials. The documentation submitted has been eviewed and accepted by Miami-Dade County RER -Poduct Contol Section to be used in Miami-Dade County and othe aeas whee allowed by the Authoity Having Juisdiction (AHJ). This NOA shall not be valid afte the expiation date stated below. The Miami-Dade County Poduct Contol Section (in Miami-Dade County) and/o the AHJ (in aeas othe than Miami-Dade County) eseve the ight to have this poduct o mateial tested fo quality assuance puposes. If this poduct o mateial fails to pefom in the accepted manne, the manufactue will incu the expense of such testing and the AHJ may immediately evoke, modify, o suspend the use of such poduct o mateial within thei juisdiction. RER eseves the ight to evoke this acceptance, if it is detemined by Miami-Dade County Poduct Contol Section that this poduct o mateial fails to meet the equiements of the applicable building code. This poduct is appoved as descibed heein, and has been designed to comply with the Floida Building Code including the High Velocity Huicane Zone of the Floida Building Code. DESCRIPTION: Bella High S LABELING: Each unit shall bea a pemanent label with the manufactue's name o logo, city, state and following statement: "Miami-Dade County Poduct Contol Appoved", unless othewise noted heein. RENEWAL of this NOA shall be consideed afte a enewal application has been filed and thee has been no change in the applicable building code negatively affecting the pefomance of this poduct. TERMINATION of this NOA will occu afte the expiation date o if thee has been a evision o change in the mateials, use, and/o manufactue of the poduct o pocess. Misuse of this NOA as an endosement of any poduct, fo sales, advetising o any othe puposes shall automatically teminate this NOA. Failue to comply with any section of this NOA shall be cause fo temination and emoval of NOA. ADVERTISEMENT: The NOA numbe peceded by the wods Miami-Dade County, Floida, and followed by the expiation date may be displayed in advetising liteatue. If any potion of the NOA is displayed, then it shall be done in its entiety. INSPECTION: A copy of this entie NOA shall be povided to the use by the manufactue o its distibutos and shall be available fo inspection at the job site at the equest of the Building Official. This NOA enews NOA No. 14-1120.05 and consists of pages 1 though 5. The submitted documentation was eviewed by Gaspa J Rodiguez. Page 1 of 5
ROOFING ASSEMBLY APPROVAL Categoy: Sub-Categoy: Mateial: Type: Roofing Roofing s Concete Wood 1. SCOPE This appoves a oofing system using Entega Bella High S concete oof tile as manufactued in Okeechobee, FL and descibed in Section 2 of this Notice of Acceptance. Fo use in locations whee the pessue equiements, as detemined by applicable Building Code, do not exceed the design pessue values obtained by calculations in compliance with RAS 127 using the values listed in section 4 heein. The attachment calculations shall be pepaed as a moment based system. 2. PRODUCT DESCRIPTION Manufactued by Applicant Dimensions Bella High S Length = 16 ½" Width = 13-1 / 4" Thickness = ½" Test Specifications TAS 112 Type 2 Class II Poduct Desciption High pofile, intelocking, extuded concete oof tile equipped with two nail holes. Fo mechanical, mota o adhesive set applications. Tim Pieces l = vaies w = vaies vaying thickness TAS 112 Accessoy tim, concete oof pieces fo use at hips, akes, idges and valley teminations. 2.1 MANUFACTURING LOCATION 1. Okeechobee, FL 2.2 EVIDENCE SUBMITTED Test Agency Test Identifie Test Name/Repot Date Celotex Copoation Testing Sevices Celotex Copoation Testing Sevices 25-7094-(3, 6 & 9) Static Uplift Testing 25-7120-(1 & 2) Static Uplift Testing 25-7183-(3 & 4) Static Uplift Testing 25-7214-(3, 4, &7) Static Uplift Testing 25-7804-4 Static Uplift Testing 520111-3 Static Uplift Testing TAS 101 520191-2-1 Static Uplift Testing TAS 101 Oct. 1994 Nov. 1994 Feb. 1995 Mach, 1995 Sep. 1996 Dec. 1998 Mach 1999 Walke Engineeing, Calculations Aeodynamic Multiplie Mach 1999 Page 2 of 5
2.2 EVIDENCE SUBMITTED Test Agency Test Identifie Test Name/Repot Date Walke Engineeing, Calculations Restoing Moment June 2007 IBA Consultants, 2421-94 ASTM C 1167 June 2006 Ameican Test Lab of South Floida RT1210.03-15 TAS 112-95 Dec 2015 3. LIMITATIONS: 3.1 Fie classification is not pat of this acceptance. 3.2 Fo mota o adhesive set tile applications, a static field uplift test in accodance with TAS 106 may be equied, efe to applicable building code. 3.3 Applicant shall etain the sevices of a Miami-Dade County Cetified Laboatoy to pefom quately test in accodance with TAS 112, appendix A. Such testing shall be submitted to the Miami-Dade Poduct Contol Section fo eview. 3.4 Minimum undelayment shall be in compliance with the applicable Roofing Applications Standads listed section 4.1 heein. 3.5 30/90 hot mopped undelayment applications may be installed pependicula to the oof slope unless stated othewise by the undelayment mateial manufactues published liteatue. 3.6 This acceptance is fo wood deck applications. Minimum deck equiements shall be in compliance with applicable building code. 4. INSTALLATION 4.1 Entega Sales, s Bella High S concete oof tile and its components shall be installed in stict compliance with Roofing Application Standad RAS 118, RAS 119 and RAS 120. 4.2 Data Fo Attachment Calculations Table 1: Aveage Weight (W) and Dimensions (l x w ) Weight-W (lbf) Length-l (ft) Width-w (ft) Bella High S 10.5 1.375 1.08 Table 2: Aeodynamic Multiplies - λ (ft 3 ) λ (ft 3 ) Batten Application λ (ft 3 ) Diect Application Bella High S 0.349 0.378 Bella High S Table 3: Restoing Moments due to Gavity - M g (ft-lbf) 2":12" 3":12" 4":12" 5":12" 6":12" Geate than 7":12 Battens Diect Battens Diect Battens Diect Battens Diect Battens Diect Battens Diect 6.19 6.89 6.11 6.80 5.99 6.67 5.85 6.51 5.68 6.33 5.50 6.13 Page 3 of 5
Bella High S Table 4: Attachment Resistance Expessed as a Moment - M f (ft-lbf) fo Nail-On Systems Fastene Type Diect (min 15/32 plywood) Diect (min. 19/32 plywood) Battens 2-10d Ring Shank Nails 28.6 41.2 19.4 1-10d Smooth o Scew 5.1 6.8 2.8 Shank Nail 2-10d Smooth o Scew 6.9 9.2 7.3 Shank Nails 1 #8 Scew 20.7 20.7 18.1 2 #8 Scew 43.2 43.2 29.8 1-10d Smooth o Scew 23.1 23.1 19.0 Shank Nail (Field Clip) 1-10d Smooth o Scew 29.3 29.3 24.0 Shank Nail (Eave Clip) 2-10d Smooth o Scew 27.6 27.6 38.6 Shank Nails (Field Clip) 2-10d Smooth o Scew Shank Nails (Eave Clip) 38.1 38.1 41.8 2-10d Ring Shank Nails 1 33.1 48.1 50.9 1. Installation with a 4" tile headlap and fastenes ae located a min. of 2½ fom head of tile. Table 5: Attachment Resistance Expessed as a Moment M f (ft-lbf) fo Two Patty Adhesive Set Systems Application Minimum Attachment Resistance Bella High S Adhesive 29.3 2 1 See manufactues component appoval fo installation equiements. 2 Flexible Poducts Company Bond Aveage weight pe patty 10.7 gams. 3M 2-Component Foam Roof Adhesive AH-160 Aveage weight pe patty 8 gams. Table 6: Attachment Resistance Expessed as a Moment - M f (ft-lbf) fo Single Patty Adhesive Set Systems Application Minimum Attachment Resistance Bella High S 3M 2-Component Foam Roof Adhesive AH-160 66.5 3 3M 2-Component Foam Roof Adhesive AH-160 38.7 4 3 Lage patty placement of 63gams of 3M 2-Component Foam Roof Adhesive AH-160. 4 Medium patty placement of 24gams of 3M 2-Component Foam Roof Adhesive AH-160. Table 7: Attachment Resistance Expessed as a Moment - M f (ft-lbf) fo Mota Set Systems Application Attachment Resistance Bella High S Mota Set 5 24.5 5 -Tite Roof Mota. Page 4 of 5
5. LABELING 5.1 All tiles shall bea the impint o identifiable making of the manufactue's name o logo as seen in detail below, o following statement: "Miami-Dade County Poduct Contol Appoved". OR ENTEGRA SALES BELLA HIGH S CONCRETE TILE LABEL (LOCATED UNDERNEATH TILE) BUILDING PERMIT REQUIREMENTS: As equied by the Building Official o the applicable Building Code in ode to popely evaluate the installation of this system. This Notice of Acceptance on its own cannot be used to obtain a building pemit. PROFILE DRAWING 16-1 2" 13-1 4" END OF THIS ACCEPTANCE Page 5 of 5