Julie Glover and Kevin Brown KTA-Tator, Inc. Wind-Driven Rain Assessment

Similar documents
Why test a system that has already been tested? Typical Manufacturers information for window to wall interface and basis for reported test results.

ACCELERATED FIELD TEST METHOD FOR WATER PENETRATION OFMASONRV

Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera

2007 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

CRITERIA FOR TESTING IMPACT & NON IMPACT RESISTANT BUILDING ENVELOPE COMPONENTS USING UNIFORM STATIC AIR PRESSURE

Corium Brick Rainscreen System Specifications

SHEET METAL ROOF TEST REPORT

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

Commissioning Under the Influence

Field Testing and Forensic Analysis for Manufacturers

RENEW ELASTOMERIC ACRYLIC COATING (PAINT GRADE) MANUFACTURERS SPECIFICATION / SECTION

Cleaning and Protecting Concrete Surface Preparation, Application, and Inspection. NESMEA October 17, 2017 Kenneth A. Trimber KTA-Tator, Inc.

Architectural Testing, Inc. 849 Western Avenue North Saint Paul, Minnesota Dan Johnson, Director - Regional Operations

Specifications. When specifying metal panel roof systems, roof. system designers and specifiers need to be aware

SECTION ALUMINUM WINDOWS

Product Guide Specification

Ultra-High Performance Wall System Glass Fiber Reinforced Concrete

DIVISION 04 MASONRY. Section Title Number MASONRY Maintenance of Masonry Masonry Mortaring Masonry Accessories

Alply CLASSIC WALL Architectural Insulated Panel Wall System

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

SECTION ALUMINUM STORM WINDOWS

A. Submit product data sheets and literature verifying physical properties of materials.

SECTION INSULATED METAL WALL PANELS. ATAS International, Inc. General Specification for Commercial/Industrial and Architectural Applications

Section COATING RESTORATION

PROJECT LOCATION SECTION COPPER METAL PLATE WALL PANELS

Wall Selection Guide Section 1.1

SECTION COMMON WORK RESULTS FOR CONCRETE SSPECIALTY COATINGS

Home Stretch Liquid Waterproofing Fluid Applied Waterproofing Membrane

(Project Location) (your firm's name)

SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove

ROOFING APPLICATION STANDARD (RAS) No. 109

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

PALLET TAG PROGRAM LABORATORY REPORT

DIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone.

Guideline Specification ACRYMAX ARS-1-C Reinforced Composite Elastomeric Membrane System for Concrete Roofs Fluid-Applied Roofing

Structural Performance Tests of VHB Structural Glazing Tapes

***********************************************************************************

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SPECIFICATIONS SECTION UL LISTED HEAT AND SMOKE VENTS

SECTION BLAST RESISTANT WINDOWS

T700 SERIES(AW50)-Impact (Formerly 8050 series) SINGLE HUNG 3 1/4 FRAME DEPTH (SIDE LOAD)

ZYCOSIL WATER REPELLENT

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

FMA / AAMA / WDMA Installation Committee Update. Jim Katsaros / DuPont Building Innovations FMA Installation Committee April 24, 2012

SECTION SILOXANE WATER REPELLENTS

FL200 13/4 x41/2 GUIDE SPECIFICATION. Non-Thermal Storefront

Building Enclosure Performance for Existing and New Buildings

BACKSTOP TM NT - Texture A high performance, water-resistive membrane and air barrier

Madewell Products Corporation December Industrial Court Alpharetta, GA Office: (770) Fax: (770)

Master Specification WALLTITE Eco v.3 by BASF Canada Inc. Section SPRAY POLYURETHANE FOAM INSULATION Page 1

How Many Times Can You Repaint the Exterior of Your Building? Kevin Brown KTA-Tator, Inc.

TerraClad TM General Specifications

Building Enclosures - Getting Them Built Correctly

SECTION 07530CP EPDM MEMBRANE ROOFING

Building Envelope Commissioning and Building Diagnostic Test: Case Studies Course Number: CXENERGY1506

The Penetrating Damp Solution

E-Wall System 5800, 5800-I

Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS

What is a Rain Screen Sealant Joint System?

PECORA SILICONE SEALANTS

PRODUCT SPECIFICATIONS

Innovating Continuous Exterior Insulation. Theresa A. Weston, PhD. 1

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

A. Section includes extruded aluminum windows with operating sash, operating hardware, and insect screens.

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS PART 1 - GENERAL 1.1 SUMMARY. A. Section Includes:

SECTION MODIFIED BITUMINOUS SHEET WATERPROOFING

SECTION CONCRETE PAVING SLABS SET IN MORTAR

Windows & Deal Trays Maximum security for high-threat locations

STUCCO FAILURES and REMEDIATION Roger G. Morse AIA

Chapter Meeting: Joint Meeting with Boston CSI and ICRI at Granite Links Insulating Load-Bearing Masonry Building January 8, 2014

Henry Blueskin VP160 Air Barrier System Installation Manual

Margaret Batts Tobin Laboratory

Waterproofing and Types of Drains

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013)

Insulating Basements: Part 1 Fundamentals

Rain Penetration Performance Of Mortarless Interlocking Blockwork Walls

Air Barrier Requirements for Low-Slope Roof Assemblies Myths vs. Facts

Repair Maintenance Hangar Phase II August 2010

1 Exam Prep Concrete Masonry Handbook Questions and Answers

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

MS-2A LINER SPECIFICATIONS: for STRUCTURAL REPAIR and SEALING of MANHOLES

SECTION COPPER WALL PANELS. ***This section has been updated to IBC. Verify for specific project conditions.***

SECTION BRICK MASONRY ASSEMBLIES

SECTION CONCRETE ABOVE GROUND FUEL STORAGE

THE BRITE THING TO DO

Building Envelope Systems Exam Learning Objectives

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION

SECTION High Performance Coatings Field Applied Acrylic Urethanes (Solid Color, Pearl and Metallic Finishes)

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION

General Guide to Joint Sealants for Architects

SAMPLE SPECIFICATION

International Fireproof Technology Inc.

Originally Issued: 12/12/2014 Revised: 12/29/2017 Valid Through: 12/29/2018

PROJECT LOCATION SECTION TEXTURED METAL PLATE WALL PANELS

Guide Specifications - Section SL35. NanaWall SL35, Aluminum Framed Folding System PART 1 - GENERAL

A. Section includes surface preparation and the application of high-performance coating systems on the following substrates:

Transcription:

Julie Glover and Kevin Brown KTA-Tator, Inc. Wind-Driven Rain Assessment

Explain the differences between waterproof, weatherproof, and water repellent. Identify a laboratory test method used for determining the winddriven rain resistance of a coating. Explain the use of Rilem Tubes. Identify field methods that can be used to assess the wind-driven rain resistance of new or existing coatings or water repellents on walls.

Water Infiltration is the biggest culprit in building envelope failures. Driving rain is significant source of bulk moisture for above-grade walls. Repairing the building envelope becomes very costly if bulk moisture from rain is not controlled.

Wind-Driven rain is the process by which rainwater is driven or forced through an exterior wall system or assembly due to either existing voids in the wall system itself, or voids created by allowable, in-service deflection of the wall system under applied wind loads. Uncontrolled wind-driven rain causes damage by rain that comes through an opening being propelled by wind.

Adverse Health Effects triggering respiratory problems Biological growth Damage to moisture sensitive materials Masonry spalling from excessive freeze/thaw cycles Corrosion of steel reinforcing and components Coating damage Efflorescence Reduction of the insulating Value (R-value) of thermal insulation

When rain strikes a building, it will run off if unobstructed or infiltrate Water can infiltrate due to kinetic energy, gravity or other forces if there are defects Depending on the wall system type bulk water may be: Stored (Mass walls) Excluded or infiltrate (Barrier walls) Drained (Cavity or Screened walls) The wall or enclosure should protect interior spaces from the environment Must understand differences in wall system types when it comes to wind-driven rain resistance

Exterior coatings are a critical component for barrier type wall assemblies Wind-driven rain resistance of the coating is essential for protection of barrier type walls It is even more critical in coastal environments or areas with high amounts of rainfall

Test results for wind-driven rain resistance can be found on the product data sheet (PDS) in the Performance data, Technical data or Physical properties section of the PDS Test results are typically provided for high-build acrylic coatings such as elastomeric It is not common to see winddriven rain test results for thinfilm acrylics

Good wind-driven rain resistance does not mean a coating is waterproof The term waterproof should not be used interchangeably with wind-driven rain resistance Waterproofing is typically in the form of a sheet applied or liquid applied material defined as resistance to passage of water under hydrostatic pressure Pigmented coatings used above grade on masonry or concrete structures are typically referred to as Weatherproof or Weather Resistant Weatherproof typically refers to the resistance of the passage of water not subjected to hydrostatic pressure

Wind-driven rain resistance testing of coatings in the laboratory evaluates the ability to resist water penetration through a dried film, erosion of the coating or coating degradation on a concrete test panel when exposed to water spray under pressure ASTM D6904 Standard Practice for Resistance to Wind-Driven Rain of Exterior Coatings Applied on Masonry is the most common type of laboratory test ASTM D6904 references Federal Specification TT-C-555B Federal Specification of Coating, Textured (For Interior and Exterior Masonry Surface)

ASTM D6904 and Fed Spec TT-C-555B are used to test above ground masonry and concrete coatings Water is sprayed onto painted 8 x 16 x 2 concrete test panels using a fish-tail nozzle 60 70 gallons per hour of water is sprayed under a 5 unit difference of atmospheric pressure inside the test chamber when compared to the outside pressure This difference in atmospheric pressure is meant to produce an equivalent dynamic pressure at 98 miles per hour wind velocity The ASTM method recommends a water exposure time of 24 hours, while the Federal Specification recommends a 48-hour exposure time, unless water penetration occurs sooner Assessment of test panels is either visual (wet block) or by weight loss/gain

ASTM references testing a specified coating system, consisting of block filler and a second layer of masonry paint May include a water repellent if specified Coating system requirements are recommended by manufacturer or the specifications requiring the wind-driven rain results Parameters for testing including the number of layers, type of material applied, thickness of each layer, the curing time and conditions, and length of exposure (24 hrs or 48 hrs) are documented Testing is performed in either duplicate or triplicate The test panels are clamped into the test chamber and subjected to water exposure Coating system should prevent water from penetrating into the masonry concrete panels under specific testing conditions. Results evaluated visually or by weight of block

There is no pass/fail criteria listed in the test methods Pass/fail criteria is left up to the discretion of the manufacturer and user Acceptance criteria may include: Total weight loss/gain Blistering Softening Other visual changes, i.e. water penetration to the back of the concrete panels, erosion of coating from concrete surface Most coating manufacturers require a maximum limit of weight loss (due to erosion) or gain (due to absorption) of 0.2 pounds

Initial purpose of ASTM D6904 was to evaluate a clear sealer (non-pigmented) or penetrating sealer for water penetration and degradation Test methods have been used frequently to test a wide variety of coatings than originally intended, including pigmented coatings Coating manufacturers commonly use pigmented primers as sealers or other pigmented coatings to resist water penetration

Purposes of field testing the wind-driven rain resistance of exterior coating systems: Evaluate mock ups Analyze moisture intrusion problems Determine if and why leakage has occurred into a building Tests are meant to simulate a blowing rain Common types of field test methods: Sealed test chamber Calibrated nozzle Spray rack Garden hose Rilem tube

ASTM C1601, Standard Test Method for Field Determination of Water Penetration of Masonry Wall Surfaces, measures the amount of water penetration into a wall and designed to test insitu walls ASTM E514, Standard Test Method for Water Penetration and Leakage Through Masonry, is a similar test but is a laboratory test method ASTM E514 measures through-wall penetration whereas ASTM C1601 measures surface water penetration

Uses a pressure/test chamber with a 12 square-foot test area (typically 3 x 4 ) Mechanically anchored and sealed to the wall Water is pumped into the test chamber and through the spray bar at the top of the chamber (3.4 gal/hr. per s.f. of wall) Air pressure is applied to simulate winddriven rain (typically 10 psf) Water is collected and recirculated

Pre-conditioning period Four hour test Water intrusion can occur within a few minutes Volume of water loss, air pressure and water flow recorded in 5 minute intervals Air pressure along with capillary action results in water transport Rate water is absorbed or penetrates indicates wall s resistance to winddriven rain

Apparatus primary intended as a field test on window and fenestration products AAMA 501.2 Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtainwalls and Sloped Glazing Systems Same test and principle can be used to test exterior coatings and water repellents Uses a special nozzle (Type B-25 #6.030)

Attached to ¾ garden hose Directs a cone of water spray at 30-35 PSI Typical rate of 2.2 gal/hr. per s.f. of wall Does not include forced air pressure Water is directed at the test area Move slowly back and forth at a distance of 1 0 Observer on inside will check for leakage

Water spray test using a water rack Similar in principle to ASTM E1105, Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform or Cyclic Static Air Pressure Difference Test uses small nozzles attached to a water rack delivering water uniformly ASTM E1105 primarily intended for field testing of installed fenestrations and uses a sealed test chamber on the inside Spray rack apparatus can be used to evaluate the wind driven rain resistance of the coating or water repellent

EXAMINE WALL SURFACE PRIOR TO WATER SPRAY OBTAIN MOISTURE READINGS PRIOR TO WATER SPRAY

INTERIOR VISUALLY INSPECTED DURING WATER SPRAY INFRARED IS USEFUL IN IDENTIFYING LEAKS

Although not complying with a standard, a garden hose or sprinkler can be used to evaluate resistance to leakage through a coating or water repellent Not Quantitative Garden hose tests can identify if the wind-driven rain resistance created by the coating is poor, but they do not confirm that it is good because the test variables are not adequately controlled

Measures the rate of water absorption through a porous material Developed by a European association headquartered in Paris, France Measures the quantity of water absorbed over a definite period of time Test method 11.4 was developed by a technical committee within Rilem

Test apparatus consists of a clear plastic tube that is graduated from 0 to 5 ml Tube is connected to a small reservoir with a circular brim Brim is attached with putty Area where it joins wall is approximately 1 square inch Water is filled to the 0 graduation mark

When filled, test exerts approximately 0.17 psi of pressure on the wall, which is equivalent to 96.4 mph Check test at least every 5 minutes, up to 20 minutes Record ml absorbed Conduct tests in block and mortar joints Testing can be done on pigmented or clear water repellents Avoid testing during rain or after rain

Water loss of 20% or less during the 20-minute test period is adequate (SWRI) The start time, end time, ml loss and material type is recorded. Testing of an entire wall can take several hours Typically multiple tests are conducted at the same time

Type of Test Wind Pressure Factored into Test Standard Advantages Disadvantages Test Chamber Yes ASTM C1601 Complies with standard. Most quantitative. Most controllable. Long history of use Calibrated Spray Nozzle No AAMA 501.2 (Applies to Fenestrations) Spray Rack No None (ASTM E1105 if used with sealed chamber) Inexpensive, easy to use Large Test area Expensive. Tests fairly small area. Requires specialized equipment and expertise Qualitative only Expensive. Qualitative only (except for moisture readings). Requires specialized equipment and expertise Garden Hose No None Inexpensive, easy to use Qualitative only Rilem Tube Yes Rilem Test Method 11.4 Inexpensive, easy to use, quantitative Small test area

High build elastomeric are common pigmented coating systems used to control wind-driven rain Some water-repellent systems may have 15% solids or more used to control wind-driven rain Better wind-driven rain resistance can link to lower permeance Designer must consider the trade off Delicate balance between breathability and controlling winddriven rain

Coatings and water repellents play a key role in controlling moisture intrusion in a barrier wall type assembly Both laboratory and field tests can be performed to verify a coating system s resistance to wind-driven rain ASTM D6904 is the most common type of laboratory test. Field tests include; test chamber, calibrated spray nozzle, spray rack, garden hose and Rilem Tube Some tests are used for wind-driven rain resistance testing of fenestrations but the same principles apply when testing coatings