LOW-ENERGY BUILDING HEATING SYSTEM MODELLING

Similar documents
125 BEPM. Lecture handouts

125BEPM - Building energy performance modeling. Lecture handouts

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

External Environment and Indoor Microclimate

Proceedings: Building Simulation 2007

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

The optimization of the mechanical night cooling system in the office building

ESP-r: INTEGRATED SIMULATION TOOL FOR DESIGN OF BUILDINGS AND SYSTEMS

Figure 1: Uncovered and covered PVT collectors

Solar Energy Technologies

Passive Houses Worlswide: International Developments

Modelling Approaches for Displacement Ventilation in Offices

Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Non-Residential Passive House Buildings

AN APPLICATION OF BUILDING SIMULATION TECHNIQUES TO THE ASSESSMENT OF NATURAL VENTILATION IN OFFICE WITH DOUBLE SKIN FACADE

EARLY AND DETAILED DESIGN STAGE MODELLING USING PASSIVHAUS DESIGN; WHAT IS THE DIFFERENCE IN PREDICTED BUILDING PERFORMANCE?

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

Solar Home Design and Thermal Mass

Assignment 3 Integrated Energy Design

Passive House Object Documentation

Apartment building Sodastraße 40 in Ludwigshafen, DE

Renewable Energy for Indoor Agriculture

Passive house optimization for Southern Italy based on the New Passivhaus Standard

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

PERFORMANCE EVALUATION OF PV VENTILATED GLAZING

Optimization of Thermosiphon Solar Water Heating systems working in a Mediterranean Environment of Cyprus

Thermal insulation of buildings and cooling demand

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad

Hermann Lebherz and Annelie Stumpp present: Double Green Building a German Passiv Haus case study together with electricity-generation solar panels

An Investigation of Energy Efficient and Sustainable Heating Systems for Buildings: Combining Photovoltaics with Heat Pump

Geothermal Praxis in Germany

In general, passive-solar components can be described by the U-value (heat loss coefficient) and

EDEM detail description part 1: inputs and outputs

EnerPHit. Criteria for Residential-Use Refurbished Buildings

Oregon High Performance Home Requirements

Solar Flat Plate Thermal Collector

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

OKO House by YOUMEHESHE architects

MSc Thesis. Integration of Building Performance Simulation in Product Development Processes

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

nzeb Germany - Strategy to improve energy efficiency in the German building sector and the leading role of public buildings Dr.-Ing.

Fraunhofer Gesellschaft Hansastrasse 27c, München,

INFLUENCES OF LIGHTING CONTROL AND NATURAL VENTILATION ON ENERGY USE AND OVERHEATING FOR A DAY-LIT INDUSTRIAL BUILDING

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

Passivhaus Project Documentation Wrexham Passivhaus

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Passive Houses in South West Europe

Great Ocean Rd Ice Creamery

Performance Study of Solar Air Heater with Baffled Duct

Feasibility study of a roof top Solar room heater

BUILDING ENERGY SYSTEMS

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Heating, Cooling, Lighting: Sustainable Design Methods for Architects

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund

Asset Energy Calculator Guidance

White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS

SOLAR ENGINEERING OF THERMAL PROCESSES

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

Local project in Dublin - IRELAND

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

Student Modeling Competition

INTEGRAL BUILDING AND ENERGY DESIGN OF AN OFFICE BUILDING COMPARISON OF INITIAL DESIGN IDEAS WITH MONITORED RESULTS

Deep energy retrofit An Analysis of Energy Efficient Retrofit Strategies for Office Buildings in China

Passivhus Norden 2013

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Unit 7 Overview of Solar Thermal Applications

Modeling Energy Consumption Effects of Glazing

DESIGN AND RECOMMANDATIONS FOR DECENTRALIZED SOLAR DISTRICT HEATING SYSTEMS IN FRANCE

Compliance Certificate

Glazed photovoltaic-thermal component for building envelope structures

Building Sustainability Why Passive House?

APT building on Makartstrase, Linz AT

Glaciers are melting, sea levels are rising, cloud forests are drying, and wildlife is scrambling to keep pace.

Application possibilities of solar air systems in context with growing importance of geo tourism

BUILDING REGULATIONS PART L 2011 PROVISIONS & COSTS (STANDARD 3-BED SEMI-D, CIRCA 120 SQM)

Exergy analysis of a flat plate solar collector

Energy Efficiency Best Practices

F. Flourentzou Lefkosia new townhall passive bioclimatic Minergie design. Flourentzos Flourentzou: Innovation park EPFL Lausanne, Switzerland

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods

Single family house in Herselt BE

Regenerative heat exchanger with ceramic core; high thermal efficiency (up to 90%). Telescopic pipe adaptable to the wall thickness.

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

Property Condition Assessment

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

2000 Antwerp, terraced house

PREFABRICATED LOAD BEARING WALL PANELS EFFECTIVE TECHNOLOGIES FOR EARTH STRUCTURES

SorTech package solution description

Energy Efficient Museum Buildings

STUDY ON SIMULATION MODELLING STRATEGY FOR PREDICTING THERMAL ENERGY DEMAND PROFILES OF RESIDENTIAL COMPLEX

The Centre for Sustainable Building (ZUB) * A Case Study

Evaluation of Underfloor Air Distribution

Reducing The Carbon Output Of A Modern Commercial Building

Exterior Perspective, East End

Evaluation of efficiency and collector time constant of a solar flat plate collector

The use of Simulation Software to Evaluate the Thermal Performance of Buildings in Brazil

Building Concepts for a mid-century energy-neutral society

Steel-Tinplate as a solar wall panel and its effectiveness

Modeling and analyzing solar cooling systems in Polysun

Marjana Šijanec Zavrl, Erik Potočar,

Transcription:

Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 LOW-ENERGY BUILDING HEATING SYSTEM MODELLING Karel Kabele,Michal Kabrhel Czech Technical University in Prague, Faculty of Civil Engineering Department of Environmental and Building Services Engineering Thákurova 7, 166 29 Praha 6, CZ e-mail : kabele@fsv.cvut.cz voice/fax: +420 2 24354570 ABSTRACT The paper is discussing problems of modelling of those elements in low-energy building design process. There is preview of the mathematical approaches and tools, which could be used to evaluate and predict energy-environmental aspects of the low-energy building systems design process. Discussion is supported by evaluation of case study of energy system in low energy building using ESP-r. The evaluation is focused on energy consumption in the conditions of the Czech Republic. INTRODUCTION Low-energy building heating design concept in climate conditions of Central Europe is based on minimising of heating energy consumption as one of the critical criterions in building design aiming to decrease total energy consumption and environmental pollution. Problematic of low energy buildings is not only in perfect thermal insulation of the building Roof air solar collector envelope, but also in design and control of heating systems, which are distributors of energy in the building and main producers of the operational pollution (Kabele,K.,2002). Heating system must cover transmission and ventilation heat loss. Comparing with traditional buildings, where the main part of heat loss was in transmission, the low-energy buildings are typical with reverse ratio of transmission and ventilation heat loss. There are several building elements, which are used to minimize energy consumption (Kabele K., Kadlecová M., Matoušovic T., Centnerová L.,1999). Besides well insulated building envelope there are elements like heat recovery, controlled air exchange rate, earth pre-heater, accumulation, solar energy utilisation (PV and water systems), wind energy utilisation and systems like warm-air heating. Development of requirements on thermal properties of new buildings in them Czech Republic is now at this stage, that each new building, built from public finances or private finances with annual energy consumption over 700 GJ, could be considered as low-energy building with Waste air outlet Roof collector loading air duct Warm-air heating Greenhouse collector loading air duct Greenhouse Gravel heat accumulator Air heater with heat recovery Tube heat exchanger Fresh air supply Figure 1.Scheme of the low energy building energy system - 591 599 -

Exterior V 5,e Exterior Zone 5 Roof collector Exterior V 1,e V 2,5 V 3,e Zone 1 Greenhouse collector V 1,2 Zone 2 Loading air circumscribed by storage mass Q 2,3 Zone 3 Fresh air supply duct V 3,4 Zone 4 Air heater Interior Figure.2 Operational scheme of active solar system with long-term heat accumulation specific energy consumption from 80 up to 140 kwh/m 2 a 1. That is approximately 1/3 comparing to existing buildings, where specific heat consumption is in range 210-300 kwh/m 2 a. Within the new buildings it is necessary to calculate with specific heating output 30 up 60 W/m 2 of heated floor area. This property has impact to the heating system, which should enable to operate in much lower outputs than in existing buildings (Kabele,K., Centnerová L.,Krtková,Z.,2001). PROBLEM ANALYSIS Presented study is example, how to use modelling and simulation of building energy performance during conceptual stage of building design process. At the beginning of this case study was architect s idea to use green house and part of the roof like a air solar collector and top store energy in underground gravel storage in the space below the building. The questions were will this system work; what will be contribution of this system to total energy balance? At this design stage, there was only coarse idea about shape of the building, size of the zones and therefor it was not possible to go to deep into the details in input and, of course, not to expect exact results. Accurancy of the results is adequate to the accurancy of the inputs and therefor we tried to find optimal level of detail in the zones description. The section of the building is on the figure 1, operational scheme of the analysed system is on the figure 2. The building is equipped with two sets of air solar collectors. One is created by south-faced glazed cavity in the roof space, second one is in front of the building, created by green-house space. Accumulator is created by free strewn gravel in thermal insulated 1 kwh/m 2 /a kilowatt-hours per square meter per year (a is abbreviation from Latin annum = year) space below the house. Accumulator loading is solved by uniform air exchange of entire volume of the gravel by loading air, which is heated up in above mentioned air solar collectors. If the loading air temperature is higher than gravel accumulator temperature, load fans are switched on and circulation of the air between accumulator and collectors is running. This circulation is terminated by balanced temperature between the collector and accumulator. Accumulator unload is solved by air-tight tube heat exchanger, represented by plastic pipes register. Through this heat-exchanger is supplied all fresh air, used for controlled ventilation and heating of the building. Fresh air, pre-heated in this accumulator, is further heated to the required temperature in traditional air-conditioning heater unit and than transported into the flats. MODEL To analyse thermal behaviour of system elements, we used ESP-r (ESRU,1996) modelling and simulation environment (Clarke, J.A.,1985). We divided entire system into five thermal zones according to the scheme (figure 2). Zones of the roof collector and greenhouse (zones 1 and 5) were modelled like standard thermal zones in the building, with given thermo-physical properties of surrounding constructions (Kabele,K. 1998). These two zones are loaded with fixed infiltration rate 0.3 ACH (V 1,0 ), which represents untightness of the zone envelope construction. At the decision phase of the model design we discussed also possibility of setting-up flow network, but at this level of design of the system components there were no more details about construction and we decided to use fixed infiltration rate. - 592 600 -

Zone 2 gravel heat accumulator was modelled by transformation of the mass and surface of the gravel into the concave rectangular paralellelepipedwith similar thermo-physical properties. Mass of the gravel was concentrated into the walls of the rectangular paralellelepipedwith and on the outside surface of the walls was set fixed temperature +14 C according to preliminary simulation calculation of the average long-term gravel stones core temperature. Transformation is based on equal physical parameters in terms of heated surface, thermal capacity and heat transfer coefficient. Validation by real physical measurements of such model is problematic (no of existing gravel accumulators is available for measurements)and therefor we compared the results with results of specialized model for underground heat exchangers used for air pre-heating or precooling(passiv Haus Institut,1999, Kabele, 2002). Zone 2 is loaded only by loading air exchange with collectors (V 1,2, V 2,5 ) and heat transfer through the walls of tube heat exchanger for fresh air supply (Q 2,3 ).Zone 3 represents inside of pipe heat exchanger for fresh air supply into the building. Common wall of the zones 2 and 3 surface is equal to the surface of the tube heat exchanger bank of pipes, the wall material has equal properties like the pipe. Zone 3 is loaded only by infiltration equal to fresh air supply (V 3,0 ) and same volume of air delivered into the air heater, represented by zone 4. There is only air exchange between zones 3 and 4. Air heater is modelled by zone 5, where is set ideal control of heater output to keep fixed air temperature on the system exit into the building air distribution network. Graphical representation of the model in the ESP-r is on the figure 3. SIMULATION For the simulation were specified problem ranges, which are difficult to solve by traditional design approach. It was above all two design questions: What is the sensitivity of the system to loading air volume set-up? What is the sensitivity of the system to the gravel mass in the heat accumulator? Those parameters were analyzed in the relation to the annual heat consumption (Kabele,K.,Kadlecová,M.,Krtková,Z., 2000). Respecting the complexity of the solved problem and in general small experience with realisation of such building energy system, we decided to use method of virtual experiments on the computer model with oneyear simulation loop (Hensen, J.L.M.,1991). Climate data To define climate conditions we used database of test reference year (TRY) for Praha, which is possible to use for most of the Czech Republic regions. Ambient dry-bulb temperature in this TRY is in the range <-17.7 C to 27,3 C>. System parameters preview Greenhouse infiltration (V 1,0 ) constant air exchange between the greenhouse and outside environment, representing greenhouse envelope untightness. Set at the value 0.3 ACH. Greenhouse loading air (V 1,2 ) - forced air exchange between greenhouse and gravel heat accumulator, which transports collected solar energy into the accumulator. This air exchange is activated, when the temperature in the accumulator is lower than temperature in the greenhouse. The air exchange rate is in particular experiments variable in the range from 100 to 6000 m 3.h -1. Figure 3 ESP-r model - 593 601 -

U < = = > - * +, ) ('& %$ 9 : ; 6 7 8 3 4 5 0 1 2. / =? @ A B C D E F G H I J K J J L M N O P Q R O S T V W X Y X Z [ \ ] ^ Z _ ` a V [ b ^! " # c d e f g d h i j d g k l m m n o n p q r s t u q v w Figure 4 Annual energy consumption Roof collector infiltration (V 5,0 ) constant air exchange between the roof solar air collector and outside environment, representing collector envelope un-tightness. Set at the value 0.3 ACH. Roof collector loading air (V 5,2 ) - forced air exchange between collector and gravel heat accumulator, which transports collected solar energy into the accumulator. This air exchange is activated, when the temperature in the accumulator is lower than temperature in the collector. The air exchange rate is in particular experiments variable in the range from 1000 to 3000 m 3.h -1. Fresh air supply ventilation rate of the fresh air, which is delivered into the building. The ventilation rate was set according to the entire volume of the building on the level 0.5 ACH. Accumulation mass of the heat accumulator mass of the gravel in the accumulator. This parameter was calculated from the accumulator volume with fixed ground plan and variable height from 0.5 m to 1.8 m. From this volume was calculated mass of the gravel Table 3 Annual energy consumption Experiment kwh/a Savings 0 11838 0% 1 6601 44% 2 6200 48% 3 6234 47% 4 5084 57% 5 5065 57% 6 6200 48% 7 6268 47% 8 6266 47% 9 5606 53% 10 5590 53% 11 5239 56% Average 5850.3 50.2% Figure 5 Coverage of energy requirements by particular hat sources fraction 45 mm, which was in the range 50250 kg to 180900 kg (Kabele,K., Kabrhel M., 2001). Virtual experiments preview (table 1) Experiment 0 - reference, when was not included any solar energy utilisation. All fresh air was transported directly into the air heater, where was heated up to required supply temperature. Energy used for this is equal to infiltration energy consumption in traditional house. In all other experiments was fresh air transported into the air heater through the tube heat exchanger in the gravel accumulator. Experiments 1 to 3 variation of the greenhouse loading air rate Experiments 4 to 8 collector and greenhouse loading air variation and combination Experiment 9 to 11 variation of the gravel accumulation mass Figure 6 Annual temperature history profile of the gravel accumulator mass - 594 602 -

SIMULATION RESULTS Selected results of the simulation, which were used for the conclusion are presented in following tables and graphs. Table 2 summarises raw simulation results, on the figure 4 are results related to the ground plan area of the solved building. The energy required for fresh air heating in the solved building will be covered by heat recovery from waste air and from auxiliary heat source (i.e.gas boiler). Energy consumption of particular heat sources is in the table 5, comparison of the energy requirements coverage is on the figure 5. CONCLUSION Virtual experiments confirmed that use of preheating of fresh air supply in gravel accumulator, located below the building contributes positively into the energy balance. Use of simple preheating of fresh air supply in gravel accumulator decreases annual energy consumption for ventilation air to approx. 50%. Use of heat recovery unit decreases annual energy consumption for ventilation air to approx. 25%. Serial connection of the accumulator and heat recovery unit decreases the heat recovery unit efficiency due to the relative small temperature difference between supply and waste air. Virtual experiments did not confirm significant influence of design parameters to the collecting and accumulating of solar energy in simulated configuration of collectors and accumulator size. The solar energy contribution is in this case very small and most of the accumulator energy gain is given by relative constant earth temperature below the building. In all of simulated virtual experiments was the accumulator mass temperature during the year in the range 12 C to 16 C (see figure 6) (Kabele K., 2002). ACKNOWLEDGMENTS This paper is integrated in the framework of CTU Research Aim CEZ J04/98: 210000005 and 21000011. REFERENCES Clarke, J.A.,1985. Energy simulation in building design, Adam Hilger Ltd, Bristol ESRU,1996."ESP-r A Building Energy Simulation Environment; User Guide Version 9 Series, "ESRU Manual U96/1, University of Strathclyde, Energy Systems Research Unit, Glasgow. Hensen, J.L.M.,1991. "On the thermal interaction of building structure and heating and ventilating system, "Doctoral dissertation Eindhoven University of Technology (FAGO). (ISBN 90-386-0081-X) Kabele,K. 1998 Modelování a analýza pasivních x y z { } ~ x x ƒ ˆ Š Œ Ž simulace,obnovitelné zdroje energie, 3, s 39- š œ ž Ÿ -8.7.1998 (in Czech) Kabele K., Kadlecová M., Matoušovic T., Centnerová L.,1999.,, Application of complex energy simulation in competition design of Czech embassy in Ottawa,Proc. Building Simulation 99, vol II pp 249-255, International Building Performance Association IBPSA,Kyoto 1999,ISBN 4-931416-01-2 Kabele,K.,Kadlecová,M.,Krtková,Z.,2000. Application of the computer simulation in warmair heating system design in low-energy buildings, Proceedings of the 4th international conference Energy for Buildings, 21.9-22.9.2000, pp 271-287, Vilnjus,Lithuania, ISBN 9955-401-54-0 Kabele,K., Kabrhel M., 2001. Study of the Earth Heat exchanger in Low Energy Building Ventilating System, Proceedings of the International conference Sustainable Building and Solar Energy 2001, pp 154- ª «15.-16.11.2001 Kabele,K.,2002. Modelování a simulace energetického chování budov. Modelling and simulation of building energy performance. ± ² ² ³ ² µ ¹ º» ¼ ½ ¾ À Á Â Ã Ä µ Å Passiv Haus Institut, 1999. PHLUFT. Programmteil zur Berechnung von Erdreichwärmetauschern. Darmstad - 595 603 -

Greenhouse infiltration Greenhouse loading air Table 1 Virtual experiments preview Collector infiltration Collector loading air Fresh air supply Accumulating mass of the gravel Experiment [ ACH] [m 3 /hod] [ACH] [m 3 /hod] [m 3 /hod] [kg] 0-refer. 0.3 0 0.3 0 273 0 1 0.3 100 0.3 0 273 180900 2 0.3 2000 0.3 0 273 180900 3 0.3 6000 0.3 0 273 180900 4 0.3 2000 0.3 100 273 180900 5 0.3 6000 0.3 3000 273 180900 6 0.3 100 0.3 3000 273 180900 7 0.3 100 0.3 2000 273 180900 8 0.3 100 0.3 1000 273 180900 9 0.3 2000 0.3 2000 273 180900 10 0.3 2000 0.3 2000 273 50250 11 0.3 2000 0.3 2000 273 100500 Experiment Energy gain from the gravel accumulator Table 2 Virtual experiments evaluation Heat recovery Æ Ç È É Ê Auxiliary heat source Total energy savings kwh/m 2 /a kwh/m 2 /a kwh/m 2 /a kwh/m 2 /a % 0 0 0 50 0 0% 0r 2 0 25 25 25 50% 1 22 14 14 36 72% 2 24 13 13 37 74% 3 24 13 13 37 74% 4 28 11 11 39 79% 5 29 11 11 39 79% 6 24 13 13 37 74% 7 24 13 13 37 74% 8 24 13 13 37 74% 9 26 12 12 38 76% 10 26 12 12 38 76% 11 28 11 11 39 78% Average (exp 1-11) 25 12 12 38 75% Std. deviation (exp 1-11) 2.21 1.1 1.1 1.1 2% 2 Experiment 0r is direct fresh air supply from outside with heat recovery unit. - 596 604 -