s the costs of fuels and consumables to rise, the ability to accurately measure the amount used in a process becomes significant

Similar documents
Selecting the correct device for measurement control

Utility Flow Metering for Steam and Heated/Chilled Water: A Tutorial. Richard Gruskos Flow Products Manager Kessler Ellis Products

February 5, 2013 Roy Ratcliffe, President RM Controls, Inc.

Thermal Mass Flow Meters Help Reduce Energy Costs and Enhance Emissions Monitoring Systems

The Paradigm Case Method of Flowmeter Selection

It can be reliably stated that experience in South African and international

Fluid Flow Conditioning. August 2015

VERIS Accelabar. Superior Flow Measurement Accuracy

Rosemount Annubar Flowmeter Series. The Value of Innovation, Realized

Pro-V Multivariable Flowmeter Model M23 Insertion Vortex

Accutube Averaging Pitot Tubes

Pro-V Multivariable Flowmeter Model M23 Insertion Vortex

Fundamental Overview of an NGL Meter Station Design Tony Lockard Enterprise Products 1100 Louisiana Street, Houston, TX

ORIFICE MTERE BASIC SELECTION & DESIGN CONSIDERATIONS. All rights reserved to thepetrostreet.com

Gilflo flowmeters. for steam, liquids and gases

Engineering Standard. Saudi Aramco DeskTop Standards

Manual of Petroleum Measurement Standards Chapter 5 Metering

TVA Target Variable Area Flowmeter

Proven Flow Measurement Solutions for the Oil and Gas Industry

Flow Test Data Book and Flow Handbook for 405 Compact Orifice Series and 1595 Conditioning Orifice Plate

VENTURI FLOWMETERS. Your First Choice in Intelligent Flow Management...

Target Inline Flowmeter

Like piezoresistive, piezoelectric,

ASME PTC Flow Measurement

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE

COMBIMASS Thermal Gas Flow

DIVA flowmeter. for saturated steam flow measurement

Airflow Measurement for HVAC Systems Comparing Technologies June 11, 2003

Transient and Succession-of-Steady-States Pipeline Flow Models

VENTURI FLOW METER CALIBRATIONS SERIAL NUMBERS: , , , Prepared for. Imperial Flange and Fitting.

Flow Rate Measurement In Emissions Monitoring

Custom Engineered Flow Meters. Differential Pressure Products

DS-4018 English Rev. FA. ProPlate Flowmeter Mass ProPlate Flowmeter Model 1195 Integral Orifice

Setting The Standard

Industrial Flowmeters

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Model 140MX Flowmeter Functional Overview

Thank You for Attending Today s Webinar. Our Featured Speaker

Carbon Dioxide as a Test Fluid for Calibration of Turbine Meters

Steam Meters Selection and Installation

COOLING TECHNOLOGY INSTITUTE

Honda Cars Philippines Ensures Quality Manufacturing With Advanced Gas Measurement Solution Case Study

Handling Fluid Fertilizers Selecting the Right Equipment Components

Mexico Gas Flaring Reduction. EU Flaring Regulatory Measurement Requirements & Best Practice Lynn Hunter

Solar Flat Plate Thermal Collector

Flow Conditioning for Irrigation Propeller Meters

CUSTODY TRANSFER FLOW MEASUREMENT WITH NEW TECHNOLOGIES. Stephen A. Ifft McCrometer Inc. Hemet, California, USA

Rosemount 1152 Alphaline Nuclear Pressure Transmitter

Calculate the Costs of Piping System Elements

Downsizing a Claus Sulfur Recovery Unit

Sentinel LNG. Panametrics Ultrasonic Flowmeter for Cryogenic Liquids. GE Sensing & Inspection Technologies. Benefits. Applications

Flow Meter Calibration

Permanent Pressure Loss Comparison Among Various Flowmeter Technologies

Reducing Maintenance and Saving Fuel with Ellison s Portable Steam Calorimeter

Water flow measurement in the oil and gas industry

Honeywell Thermal Solutions. Engineering Guide

Saudi Aramco Uses Kurz to Help Monitor Flare Emissions

Data Sheet. Measuring System trikon Vortex Flow Meter EDZ 420 in Microprocessor Technology. Vortex meter trikon EDZ 420.

Flare Measurement Advanced Ultrasonics

FLOWRATE MEASURE PROBE DEBIX

Biogas Conference Kolding, DK, 04 April 2017 BINDER. Biogas Monitoring Why and How? Jan Talkenberger, Manager International Sales, Binder GmbH

Gilflo ILVA Flowmeters

Rosemount 405 Compact Orifice Primary Element

Pipe Flow Hydraulics

ASI MODEL DM 100 SERIES DILUTING MODULES

Micro Motion Technical Overview and Specification Summary

How to Develop a Methane Emissions Feasibility and Measurement Study

YARWAY HANCOCK CONTINUOUS BLOWDOWN GLOBE VALVE SERIES 5505

Rosemount 1154 Alphaline Nuclear Pressure Transmitter

Engineered Solutions for Landfill Gas Well Field Management

The Continuing Coriolis Evolution

FPI Mag Flow Meter. Next Generation Mag Meter: Solving WTP s Tight Installation Dilemma. McCrometer, Inc. (800)

The Effects of Increased Pressure on the Reaction Kinetics of Biomass Pyrolysis and Combustion

Verabar APPLICATION DATA. True Performance in Flow Measurement

Water Measurement. Presentation by. L. Niel Allen Extension Irrigation Specialist Utah State University

Controlling NOx and other Engine Emissions

Swirl flowmeter FS4000 Compact, reliable and robust

Feedwater Flow Measurement with Venturi and Comparison to the other Parameters in NPP Krško

TEST REPORT. EVALUATION CENTER Intertek Testing Services NA Inc Murphy Drive Middleton, WI 53562

BINDER. Italian German Conference Verona, Italy, 26 September Biogas Monitoring Why and How?

Products Solutions Services. Vortex. Prowirl

Reflux Samplers for Process Gas Chromatographs Their Use and The Importance of Product Design

introduced before the end of World War II. 2 They are less the focus of new product development than new-technology

Contour K5 Technical Information

Measuring Air Velocity - presented by Lonnie Glen, Kice Industries 2/28/2018. (and why it is important) Applications for Air

Purpose of Today s Presentation

ABSTRACT INTRODUCTION

Vortex EX DELTA lowmeter Technical Specifications

VortexMaster and SwirlMaster Natural gas measurement in power plants, boilers and incinerators

Southwest Clean Air Agency NE 99 th St, Suite 1294, Vancouver, WA 98682

FLOW MEASUREMENT Product Code 316 Instruction manual Contents

Vortex Flowmeter FV4000 (TRIO-WIRL V) Swirl Flowmeter FS4000 (TRIO-WIRL S)

On-Line Diagnostics Techniques in the Oil, Gas, and Chemical Industry

Insertion Flow Meters. The only hot tap Full Profile Insertion Flow Meter.

A REVIEW OF STEAM FLOWMETERING TECHNOLOGY

HYDRAULIC DEMONSTRATION CHANNEL

CHAPTER 6 : GAS SAMPLING SYSTEMS

Energy Advisor. Introduction. Energy Advisor. Product Data Sheet October 2014

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

Chapter 10 VAPOR AND COMBINED POWER CYCLES

Transcription:

FLOW METER SELECTION FOR IMPROVED GAS FLOW MEASUREMENTS A The proper selection of a flow meter for measuring the amount of gas consumed in a process can be challenging. Know the type of technology that can address your process condition before jumping to purchase. Art Womack Fluid Components International LLC San Marcos, Calif. s the costs of fuels and consumables (natural gas, hydrogen, oxygen, etc.) continue to rise, the ability to accurately measure the amount used in a process becomes significant in controlling costs and determining bottom line profits. It may have been acceptable in the past to absorb these expenses as necessary overhead to conduct business, but more companies are beginning to analyze consumables used in heat treating processes to determine the profitability of each particular job. Therefore, it is important to implement a strategy of adding cost effective, accurate gas flow measuring devices to the equipment. General Flow Meter Technologies Once a decision is made to add this level of measurement, it should be relatively easy to select a flow meter that will meet user needs. Currently available technologies include differential pressure with primary flow elements, magnetic, ultrasonic, turbine, venturi, rotameter, coriolis, vortex shedding, and thermal dispersion. We can add the same type of metering being used in other parts of the facility since we are familiar with it, or we can search flow meters on the web and quickly find a couple of meters, something either inexpensive or hi-tech, that will do the job for us. How difficult can it be? Unfortunately, it does require more analysis than this to ensure that we get the correct flow meter solution for the application. All of us should understand by now that there are advantages and disadvantages associated with any type of technology used in process measurement. Just the type of fluid that we are trying to measure can limit the options available. Fluids come in the form of liquids, slurries, gases and steam. There are fewer concerns associated with the flow measurement of a liquid or slurry given that they are considered incompressible and, if homogeneous, have a constant density. Gases require more consideration given that they are compressible, which results in a density that varies with changes Different flow-meter technologies are available to address various process conditions. HEAT TREATING PROGRESS JULY/AUGUST 2008 25

Volumetric flow rate (Q) Q = velocity (avg) area (pipe) V = average velocity of gas (length/time) ft/s Q = V A A = cross-sectional area of pipe (area) ft 2 Q = volumetric flow rate (volume/time) ft 3 /s Mass flow rate (M) M = density volumetric flow rate M = V A = density of gas (mass/volume) lb/ft 3 M = Q M = mass flow rate (mass/time) lb/s Fig. 1 Basic flow-rate formulas. Assume a volumetric air flow rate of 3,000 acfm @ standard conditions of 70 F (21.1 C) and 14.7 psia Actual process temperature = 100 F (37.8 C) Actual process pressure = 50 psig (64.7 psia) To determine an equivalent flow rate at process conditions, we would calculate it as follows: = Qacfm P act /T act T std /P std = 3,000 acfm 64.7 psia/310.8 K 294.1 K/14.7 psia = 12,494.6 scfm Note: Temperatures and pressures must be converted to absolute values; Kelvin (273 + C) and psia (14.7 + psig) Since air is compressible, the mass flow rate can be represented as a volumetric flow rate of 12,494.6 scfm. Fig. 2 Volumetric versus mass flow rate. Non-direct mass flow measurement with DP Gas flow Mass flow measurement with thermal dispersion Gas flow P Fig. 3 Mass flow measurement. P T Mass flow in process pressures and temperatures. Steam presents its own set of complications since not only is it compressible, it has a high moisture content at relatively high temperatures. For the purposes of this article, we are going to look at the differences between liquids and gases. For reasons that will be explained, a proven method for measuring a liquid does not necessarily translate into a good solution for measuring a gas. Consideration should be given, but not necessarily limited, to the following items when selecting a flow meter for gas measurements: accuracy, turndown ratios, pressure drops, process temperatures, additional sensor requirements, and process connections. Standard density Flow computer Mass flow To help develop a method that will allow us to effectively compare technologies, we are going to look specifically at how these factors are addressed by Differential Pressure and Thermal Dispersion technologies. Differential Pressure Technology The most common method of measuring liquid flow is to use a differential pressure (DP) transmitter with a sharp edged orifice plate. The square root extraction of the pressure drop across the orifice is directly proportional to the volumetric flow rate in the pipe (Fig. 1). Other primary flow elements used to make similar measurements using DP transmitters are pitot tubes, averaging pitot tubes (e.g., Annubars), v-wedges, and v-cones (e.g., McCrometer). These same instruments are often selected in gas flow measurement based on maintaining commonality of instrumentation throughout a facility. While this makes sense from a maintenance and inventory standpoint, the real objective is to improve the gas flow measurement of the process. Since we are now trying to measure a compressible gas, it is necessary to recognize that knowing the mass flow rate is more beneficial than the volumetric flow rate (Fig. 2). Without taking into account that the density of a gas will change with variations in process temperature and pressure, a volumetric flow reading will not be an accurate representation of actual gas consumption in a process. This limitation of volumetric flow meters in gas applications can be overcome. The addition of pressure and temperature transmitters can provide the data required to compensate for changes in gas density under process conditions. Sending the flow, temperature, and pressure readings into the PLC or DCS will allow for the calculation of the mass flow rate. However, this adds complexity, extra sensor expense, and extra installation expense to the gas flow measurement (Fig. 3). When working with flow elements like an orifice or averaging pitot tube, the use of a multivariable transmitter would definitely simplify the installation. Several factors come into play when determining the actual accuracy of a DP transmitter being used with a primary flow element. You don t want to work from the incorrect belief that a DP transmitter will provide an accuracy of ±0.1% or greater depending on the manufacturer. If you look closer at the specifications, the accuracy could vary with the span ratio (turndown), percentage of flow rate being measured, long-term drift, temperature effects, and static pressure effects. Bestcase conditions may provide accuracy better than ±1%, but the true accuracy can be ±5% or greater under actual process conditions. We have yet to take into account the additional inaccuracies associated with the additional pressure and temperature transmitters required because we are trying to de- 26 HEAT TREATING PROGRESS JULY/AUGUST 2008

termine the mass flow rate, not volumetric! Accuracy could be further degraded if the gas has particles that can build up around the edges of the orifice or plug the small openings in a pitot tube over time. A v-wedge flow element can be more forgiving in dirty gas applications. When using a DP transmitter with an orifice, the turndown ratio would be more in the line of 10:1, or maybe 20:1, depending on the transmitter. This could become a significant issue when the required gas flow is high for one process and very low for another. Without adequate turndown, it is possible to end up with a meter that is only capable of accurately measuring on the high end of the flow range. It is a common practice to stack meters of varying ranges to take readings from the same primary flow element to increase the measured flow range. This approach further increases the cost and complexity of the system. The use of a sharp-edged orifice or any other type of primary flow element is intended to create a measurable pressure difference. Although pressure drop is not critical in all gas applications, it does impact the efficiency of a process in the form of wasted energy. For an orifice plate, this loss could be significant over the life of the process. Averaging pitot tubes or v-wedges can limit those losses by reducing the size of the obstruction in the flow line. In the case of an orifice, this loss can be in the neighborhood of 50 in. w.c. (water column) in a 4-in. line for a flow rate of 3,000 scfm. Given the same conditions, that value may be less than 20 in. w.c. for an averaging pitot tube and v-wedge. With low process pressures, these losses can limit the ability to maintain the required minimum flow rate of the system. When performing mass flow measurements, the actual process temperatures must be taken into consideration. Although there are many applications in which the gases are delivered at ambient conditions, there are applications in heating and cogeneration systems in which the temperatures can be quite high. Most DP transmitters are rated for temperatures up to 250 F at the point of the measuring cell. In applications that will be significantly higher than this (say 500 F or so), it is necessary to use impulse tubing to dissipate the extra heat from the process. A general rule of thumb is about a foot of stainless steel tubing per 100 F. For even higher temperatures, the use of a process (chemical) seal with a non-expanding fill fluid may be required. The use of impulse tubing or process seal is not a major concern, but it will slow the response time of the meter, add cost and complexity to the installation, and require adequate elevation if there is condensation in the lines. Proper installation of a DP transmitter to a primary flow element adds to the complexity of the installation. To ensure accuracy, DP transmitters require periodic calibration checks. To perform these checks with the system operating, installation of a 5-way manifold between the flow element and transmitter is common. This manifold allows for both isolation from the process and the ability to apply a known pressure source for calibration checks of the zero and span. A 3-way manifold may also be used, but it will only allow for isolation from the process. It would then have to be removed from the manifold to perform calibrations. Either way, it is another item that will add to installed costs. Temperature sensor (Pt1000) plus heater element as active or heated sensor Temperature sensor (Pt1000) as reference sensor or unheated sensor Thermal Dispersion Technology Another technology often used in gas flow applications is the thermal dispersion flow meter, also referred to as thermal differential (Delta-T), or simply thermal. This particular instrument makes use of two high precision resistance temperature detectors (RTDs). A reference RTD measures the process temperature and an active RTD is heated to a known value to create a differential temperature between the two sensors. When there is no flow, the differential will be at its greatest. As the gas begins to flow, the active RTD begins to cool and decreases the differential between the two sensors (Fig. 4). This is an oversimplification of the operating principle, but provides a basic understanding. Thermal technology is advantageous because it also takes into account the density, absolute viscosity, thermal conductivity, and specific heat of the gas being measured. The end result is a very accurate mass flow reading that requires no additional instrumentation or calculations. The accuracy of a thermal mass flow meter is very straightforward. It is commonly broken into two components: a percentage of reading and a percentage of full scale. These instru- Output signal, dc volts 7 6 5 4 3 2 1 Difference in temperature Difference in resistance Difference in voltage Air 0.03 0.3 3 30 150 300 Velocity, m/s Fig. 4 Operating principle of thermal dispersion. HEAT TREATING PROGRESS JULY/AUGUST 2008 27

Common types of flow meters Perforated plate Vane Fig. 5 Solutions for inadequate straight run. More companies are beginning to analyze consumables used in a process to determine the profitability of each job. Fig. 6 ST75V flow meter with built-in flow conditioner. Tab type Tube bundle Thermal flow meter with integral flow conditioner ments are immune to long-term drift, are commonly compensated for broad temperature ranges and the effects of pressure changes are negligible. Therefore, to really understand how technologies compare, it is necessary to look at worse-case process conditions and run the calculations. In most applications, you can expect to achieve a turndown ratio of 100:1 with a thermal meter. This allows maintaining a high level of accuracy over the entire flow range without having to stack multiple instruments. The pressure drop across a sharp edged orifice versus the drop across a single-point thermal flow element can be 5 to 10 times greater. The most significant difference can be observed when operating at 70 to 100% of the maximum flow range. Using the example of a flow rate of 3,000 scfm in a 4 in. line, the pressure drop is in the neighborhood of 15 in. w.c. for a thermal meter versus. 50 in. w.c. for a DP meter and orifice. Thermal meters are inherently suited for use in high-temperature applications.because this is literally dealing with RTDs in thermowells, standard temperature capabilities of these meters run to about 350 F. With modifications to the design of the flow element, some manufacturers offer variations suited to process temperatures in a range as high as 500 to 850 F, which require no added installation considerations. The installation of a thermal flow element is simple. In the case of an inline meter, the elements can be provided with either threads or flanges. With insertion type elements, it is common to install the units with a threaded compression fitting. Unlike a DP transmitter, periodic calibration of a thermal meter is not required. Manufacturers may recommend that a calibration check be performed every 12 to 18 months. In the case of processes that run continually or involve dirty gases, the use of a packing gland and ball-valve assembly is recommended with an insertion meter for extraction of the flow element for either calibration or inspection and cleaning. Like any other instrument, thermal dispersion technology does have limitations and is not ideal in certain applications. First and foremost is that these instruments are not suitable for measuring the flow of liquids, slurries or saturated steam. Thermal technology is best suited for the measurement of dry gases, gases with limited moisture, or superheated steam (no water vapor). It also is necessary to keep in mind that thermal meters are normally calibrated for a specific gas composition. For instance, this can be a single gas such as air, hydrogen, oxygen, etc. or a composition like natural gas (methane and ethane). If the composition changes, the mass flow reading will remain repeatable, but it will no longer be as accurate. The use of a correction factor may improve the accuracy to acceptable limits for some processes. If a process has condensation in the lines, a thermal meter may provide false readings due to the cooling of the active RTD that is not directly related to the flow rate. In some cases, appropriate positioning of the flow element in the pipe can reduce or eliminate this effect. Other cases might require the use of condensation (knock-out) pots or filters to reduce the moisture content to acceptable levels. Ideal vs. Actual Flow Conditions Another factor that impacts accurate gas flow measurement is the upstream and downstream (straight-run) piping conditions. For line sizes up to 6 in. diameter, it is normally accepted that a straight run of 20 pipe diameters (i.e., 20D) upstream and 10 pipe diameters (10D) downstream from the metering point is required for a fully developed flow profile. The acceptable requirements for lines over 6 in. are 15D upstream and 7.5D downstream. Although it is realistic to be able to find a 7.5 ft straight run of 3 in. pipe, it is more difficult to locate an appropriate 22.5 ft run for a 12 in. pipe. When straight-run conditions are inadequate, obstructions (e.g., elbows, valves, etc.) can disrupt the flow profile and reduce 28 HEAT TREATING PROGRESS JULY/AUGUST 2008

the accuracy of any flow meter technology being used. Since our objective is to improve the flow measurement, additional errors should not be accepted. The next step is to understand the flow disturbance created by actual piping conditions. Many in-line obstructions can generate distorted velocity profiles. This will affect the readings of meters that are based on the average or maximum velocity of a fully developed flow profile. In the case of elbows out of plane, a swirling effect occurs. Knowing this will help selecting a conditioning device that will properly address user needs. Common types of flow conditioners are perforated plates, screens, vanes, tube bundles, and tabs (Fig. 5). These are all simple, mechanical devices that are installed in the process piping before the metering point. Perforated plates and screens do an adequate job of generating a measurable velocity profile, but have limitations when it comes to swirl. Tube bundles and vanes provide better conditioning for swirl, but allow a good portion of a distorted velocity profile to move on to the metering point. Only the tab design has been shown to eliminate the effects of both a distorted velocity profile and swirl by generating a very repeatable and measurable velocity profile. Like primary flow elements, the design of the flow conditioner can introduce pressure losses that equate to wasted energy. The greatest losses are observed with perforated plates and the least amount is associated with the tab design. In the case of thermal flow meters, some manufacturers have integrated flow conditioning devices into their flow element (Fig. 6). This is a great benefit because it not only reduces the amount of straight-run required for an installation, but also it provides an instrument that has been fully calibrated to the process conditions and provides a very high level of measurement accuracy. Conclusion The proper selection of a flow meter for measuring the amount of gas consumed in a process can be challenging. Until you determine what types of technology will properly address your actual process conditions, you should not jump ahead to evaluating costs associated with purchase price and installation. Getting one or two experienced gas flow meter manufacturers involved in the initial evaluation stage can add value by allowing them to make recommendations up front with regard to improving flow measurements. This can provide peace of mind that the flow meters selected are right for the application and will provide accurate measurements to optimize the process and achieve cost-reduction goals. HTP For more information: Art Womack Sr. Applications Engineer Fluid Components International LLC 1755 La Costa Meadows Dr. San Marcos, CA 92078 tel: 800/854-1993 e-mail: awomack@fluidcomponents.com Web site: www.fluidcomponents.com HEAT TREATING PROGRESS JULY/AUGUST 2008 29